Prior to starting any work, read the operating instructions!
Keep for later use!
Vor Beginn aller Arbeiten Betriebsanleitung lesen!
Zum späteren Gebrauch aufbewahren!
Lire le mode d‘emploi avant de commencer toute opération !
A conserver pour une utilisation ultérieure !
¡Leer el manual de instrucciones antes de comenzar cualquier trabajo!
¡Guardar el manual para una eventual consulta!
2
WIKA operating instructions models PGS10, PGS11 and PGS21
Page3-18
Seite19-34
Page35-50
Página 51-57
11581752.02 09/2013 GB/D/F/E
Contents
Contents
GB
1. General information
2. Safety
3. Specications
4. Design and function
5. Electrical switch contacts
6. Transport, packaging and storage
7. Commissioning, operation
8. Maintenance and cleaning
9. Dismounting and disposal
Appendix 1: Declaration of performance model PGS11.040
Appendix 2: Declaration of performance model PGS21.050
11581752.02 09/2013 GB/D/F/E
WIKA operating instructions models PGS10, PGS11 and PGS21
4
5
8
9
9
12
13
15
16
17
18
3
1. General information
1. General information
■
The pressure gauge described in the operating instructions has been
GB
designed and manufactured using state-of-the-art technology.
All components are subject to stringent quality and environmental
criteria during production. Our management systems are certied to
ISO 9001 and ISO 14001.
■
These operating instructions contain important information on handling
the instrument. Working safely requires that all safety instructions and
work instructions are observed.
■
Observe the relevant local accident prevention regulations and general
safety regulations for the instrument's range of use.
■
The operating instructions are part of the product and must be kept in
the immediate vicinity of the instrument and readily accessible to skilled
personnel at any time.
■
Skilled personnel must have carefully read and understood the
operating instructions prior to beginning any work.
■
The manufacturer's liability is void in the case of any damage caused
by using the product contrary to its intended use, non-compliance with
these operating instructions, assignment of insuciently qualied skilled
personnel or unauthorised modications to the instrument.
■
The general terms and conditions, contained in the sales
documentation, shall apply.
■
Subject to technical modications.
■
Further information:
- Internet address:www.wika.de / www.wika.com
- Relevant data sheet:PV 20.01, PV 21.01, PV 21.02,
4
WIKA operating instructions models PGS10, PGS11 and PGS21
SP 21.01 and SP 21.03
11581752.02 09/2013 GB/D/F/E
1. General information / 2. Safety
Explanation of symbols
WARNING!
... indicates a potentially dangerous situation that can result
in serious injury or death, if not avoided.
Information
… points out useful tips, recommendations and information
for ecient and trouble-free operation.
2. Safety
WARNING!
Before installation, commissioning and operation, ensure
that the appropriate pressure gauge has been selected in
terms of measuring range, design and specic measuring
conditions.
In order to guarantee the measuring accuracy and long-term
stability specied, the corresponding load limits must be
observed.
Only work on the gauge with the voltage disconnected.
Non-observance can result in serious injury and/or damage
to equipment.
Further important safety instructions can be found in the
individual chapters of these operating instructions.
2.1 Intended use
The pressure gauges with switch contacts, switchGAUGE models PGS10,
PGS11 and PGS21, are used for controlling industrial processes for plant
monitoring and for the switching of circuits.
11581752.02 09/2013 GB/D/F/E
WIKA operating instructions models PGS10, PGS11 and PGS21
GB
5
2. Safety
The instrument has been designed and built solely for the intended use
described here, and may only be used accordingly.
GB
The manufacturer shall not be liable for claims of any type based on
operation contrary to the intended use.
2.2 Personnel qualication
WARNING!
Risk of injury should qualication be insucient!
Improper handling can result in considerable injury to
personnel and damage to equipment.
■ The activities described in these operating instructions
may only be carried out by skilled personnel who have the
qualications described below.
Skilled personnel
Skilled personnel are understood to be personnel who, based on their
technical training, knowledge of measurement and control technology and
on their experience and knowledge of country-specic regulations, current
standards and directives, are capable of carrying out the work described
and independently recognising potential hazards.
2.3 Special hazards
WARNING!
Dangerous pressure media such as oxygen, acetylene,
ammable gases or liquids, toxic gases or liquids as well
as for refrigeration plants or compressors require attention
above the standard regulations. Here the specic safety
codes or regulations must be considered.
WARNING!
Residual media in dismounted pressure gauges may result
in a risk to people, the environment and the system. Take
sucient precautionary measures.
6
WIKA operating instructions models PGS10, PGS11 and PGS21
11581752.02 09/2013 GB/D/F/E
2. Safety
2.4 Labelling / safety marks
Product label
Prange ... scale range
Model
Pin
assignment
Explanation of symbols
CE, Communauté Européenne
Instruments bearing this mark comply with the relevant
European directives.
Instruments bearing this mark are recognised by the VdS.
Instruments bearing this mark are recognised by the LPCB.
11581752.02 09/2013 GB/D/F/E
WIKA operating instructions models PGS10, PGS11 and PGS21
P
switch ... switch point
Reference number of the
declaration of performance
Identication number
of the product
certication body
including year of the
rst CE marking
GB
7
3. Specications
3. Specications
Models PGS10, PGS11 and PGS21
GB
Pressure limitation
- Steady3/4 x full scale value
- Fluctuating2/3 x full scale value
- Short timeFull scale value
Temperature eectWhen the temperature of the measuring system
Ingress protection
- Enclosing caseper EN 60529 / IEC 529
Operating temperature
- Ambient-20 ... +60 °C
- MediumMaximum +60 °C
For further specications see data sheet PV 20.01, PV 21.01, PV 21.02,
SP 21.01, SP 21.03 and the order documentation.
8
deviates from the reference temperature (+20 °C):
max. ±0.4 %/10 K of the span
Model PGS10 and PGS11: IP 41
(for PGS11.040 with VdS: IP 54)
Model PGS21: IP 65
WIKA operating instructions models PGS10, PGS11 and PGS21
11581752.02 09/2013 GB/D/F/E
4. Design and function / 5. Electrical switch contacts
4. Design and function
Description
Bourdon tube measuring elements are widely used in technical pressure
measurement due to their robustness and ease-of-use. Under the inuence
of pressure, these measuring elements deform within their elastic limits.
This motion is converted, via a mechanical movement (toothed gear), into
a rotational motion. To this, an electrical limit switch is connected - the
magnetic snap-action contact. The contact closes or opens the connected
electrical circuits when the settable limit values are exceeded.
Scope of delivery
Cross-check scope of delivery with delivery note.
5. Electrical switch contacts
Electrical connection
■
The electrical connection must only be made by qualied skilled
personnel
■
Connection of the switches via cable or via screw terminals in the
terminal box (L-connector)
■
The terminal assignment is stated on the product label of the pressure
gauge
■
The gauges must be connected to the equipotential bonding of the plant
Electromagnetic compatibility
EMC per EN 60947-5-2.
The instruments are to be protected against strong electromagnetic elds.
11581752.02 09/2013 GB/D/F/E
WIKA operating instructions models PGS10, PGS11 and PGS21
GB
9
5. Electrical switch contacts
Flying leads
Single contactDouble contact
GB
red:U
black:SP 1orange:SP 1
Electrical connection via connector (NS 50, 63)
If the IP ingress protection of the connector is lower than that of the
pressure gauge, then this determines the overall ingress protection of the
instrument.
10
+red: UB+ (common)
B
black:SP 2
Angular connector EN 175301-803-C
Single contactDouble contact
1: U
+1: UB+ (common)
B
2: SP 12: SP 1
3: SP 2
Circular connector M12 x 1
Single contactDouble contact
1: U
+1: UB+ (common)
B
4: SP 14: SP 1
2: SP 2
Circular connector M8 x 1
Single contactDouble contact
1: U
+1: UB+ (common)
B
4: SP 14: SP 1
WIKA operating instructions models PGS10, PGS11 and PGS21
3: SP 2
11581752.02 09/2013 GB/D/F/E
5. Electrical switch contacts
Magnetic snap-action contact (normally closed or normally open)
The instruments are delivered with a single or double contact (normally
closed or normally open).
With 'normally closed', the contact ag is engaged with the limit switch and,
on rising pressure, disengages from the contact via the actuator attached to
the pointer. The circuit will be interrupted.
With 'normally open' the contact ag follows the pointer until the limit value
is reached. Once the limit value has been exceeded, the contact ag
engages and the circuit is closed.
The switching function of the switch is indicated by the index 1, 2, 12, 11
or 22.
Index Designa-
1Normally
2Normally
12Normally
11Normally
22Normally
11581752.02 09/2013 GB/D/F/E
WIKA operating instructions models PGS10, PGS11 and PGS21
SymbolSwitching function / setting
tion
open
(NO)
closed
(NC)
open /
closed
(NO-NC)
open /
open
(NO-NO)
closed /
closed
(NC-NC)
direction
Contact makes with rising pressure or
clockwise pointer motion (standard)
Contact breaks with falling pressure or
anticlockwise pointer motion
Contact breaks with rising pressure or
clockwise pointer motion (standard)
Contact makes with falling pressure or
anticlockwise pointer motion
See switching function or setting
direction for single contact
See switching function or setting
direction for single contact
See switching function or setting
direction for single contact
To adjust the switch point, carefully loosen the window using a screwdriver.
The contact (red mark pointer) can then be set to the desired position by
GB
hand. It can be set between 10 % and 90 % of the full scale value.
Afterwards, lightly push the window back into the case.
If the switch point of the instruments approved by VdS is changed
by the customer, the customer will lose the VdS approval.
Adjustability of
contacts
15 % FSV
10 % FSV
6. Transport, packaging and storage
6.1 Transport
Check pressure gauge for any damage that may have been caused by
transport.
Obvious damage must be reported immediately.
6.2 Packaging
Do not remove packaging until just before mounting.
Keep the packaging as it will provide optimum protection during transport
(e.g. change in installation site, sending for repair).
12
WIKA operating instructions models PGS10, PGS11 and PGS21
6.3 Storage
Permissible conditions at the place of storage:
Storage temperature: -20 ... +70 °C
7. Commissioning, operation
Mechanical connection
In accordance with the general technical regulations for pressure gauges
(e.g. EN 837-2 "Selection and installation recommendations for pressure
gauges").
If the pressure gauge is mounted lower than the pressure tapping, the
capillary must be ushed thoroughly before connection in order to clear out
any foreign matter.
When screwing gauges in, the force required for this must not be applied
through the case, but rather through the spanner ats (using a suitable tool)
provided for this purpose on the square shaft of standard connections.
Installation with
spanner
Correct sealing of pressure gauge connections with parallel threads must
be made using suitable sealing rings, sealing washers or WIKA prole seals.
The sealing of tapered threads (e.g. NPT threads) is made by providing the
thread
, with additional sealing material such as, for example, PTFE tape
(EN 837-2).
GB
Wrench surface
Sealing face
The torque depends on the seal used. Connecting the gauge using a clamp
socket or a union nut is recommended, so that it is easier to orientate the
11581752.02 09/2013 GB/D/F/E
gauge correctly.
WIKA operating instructions models PGS10, PGS11 and PGS21
Sealing in the
thread
13
7. Commissioning, operation
Requirements for the installation point
If the measuring point is not adequately stable a measuring instrument
support such as a bracket or ange should be used for fastening (and
GB
possibly via a exible capillary line). If the pressure gauge is exposed to
vibration or pulsating pressure or both, then a liquid lled pressure gauge
may provide considerably better performance and readability. Instruments
should be protected against coarse dirt and wide uctuations in ambient
temperature.
Installation
■
Nominal position per EN 837-1 / 9.6.7 Figure 9: 90° ( ⊥ )
■
Process connection bottom or rear!
■
In order to avoid any additional heating, the instruments must not be
exposed to direct solar irradiation while in operation!
Measuring assemblies
Proven measuring assemblies for various types of media.
liquid mediagaseous media
Filling of the
capillary
Examples
Pressure
gauge above
the tapping
point
Pressure
gauge below
the tapping
point
Admissible ambient and working temperatures
When mounting the pressure gauge it must be ensured that, taking into
consideration the inuence of convection and heat radiation, no deviation
above or below the permissible ambient and medium temperatures can
occur. The inuence of temperature on the display accuracy must be
observed.
14
liquid with
liquid
condensate boiling liquid
vapour only gaseous wet gas
vapour
"liqueed
gases"
dry air
moist air, ue
gases
WIKA operating instructions models PGS10, PGS11 and PGS21
liquid gas
condensate
Steam
11581752.02 09/2013 GB/D/F/E
7. Commissioning, operation / 8. Maintenance and cleaning
Permissible vibration load at the installation site
■
The instruments should always be installed in locations free from
vibration.
■
If the pipe to the gauge is not rigid enough for a vibration-free
installation, the gauge should be mounted by means of mounting
devices for surface or pipe mounting, and, if necessary, with a capillary.
■
If necessary, it is possible to isolate the instrument from the mounting
point by installing a exible connection line between the measuring
point and the pressure gauge and mounting the instrument on a suitable
bracket.
■
If this is not possible, the following limit values must not be exceeded:
Frequency range < 150 Hz
Acceleration < 0.5 g (5 m/s
2
)
Commissioning
During the commissioning process pressure surges must be avoided at all
costs. Open the shut-o valves slowly.
8. Maintenance and cleaning
8.1 Maintenance
■
The instruments are maintenance-free.
■
The indicator and switching function should be checked once or twice
every year. The gauge must be disconnected from the process to check
with a pressure testing device.
■
Repairs are only to be carried out by the manufacturer or appropriately
trained skilled personnel.
11581752.02 09/2013 GB/D/F/E
WIKA operating instructions models PGS10, PGS11 and PGS21
GB
15
8. Maintenance and cleaning / 9. Dismounting and disposal
8.2 Cleaning
CAUTION!
GB
■
Before cleaning, correctly disconnect the pressure gauge
from the pressure supply, switch it o and disconnect it
from the mains.
■
Clean the instrument with a moist cloth.
■
Electrical connections must not come into contact with
moisture.
■
Wash or clean the dismounted instrument before
returning it, in order to protect persons and the
environment from exposure to residual media.
9. Dismounting and disposal
WARNING!
Residual media in dismounted pressure gauges may result
in a risk to people, the environment and the system. Take
sucient precautionary measures.
9.1 Dismounting
Only disconnect the pressure gauge once the system has been depressurised!
9.2 Disposal
Incorrect disposal may endanger the environment.
Dispose of instrument components and packaging materials in an environ-
mentally compatible way and in accordance with the country-specic waste
disposal regulations.
16
WIKA operating instructions models PGS10, PGS11 and PGS21
11581752.02 09/2013 GB/D/F/E
WIKA Alexander Wiegand SE & Co. KG
Germany
PeterKoll
DanielKotlewski
Appendix 1: Declaration of performance model PGS11.040
DECLARATION OF PERFORMANCE
according Construction Performance Regulation EU Nr. 305/2011
Kommanditgesellschaft: Sitz Klingenberg –
Amtsgericht Aschaffenburg HRA 1819
Komplementärin: WIKA Verwaltungs SE & Co. KG –
Sitz Klingenberg –Amtsgericht Aschaffenburg
HRA 4685
as part of e complete operating system.
ued following certificate of certificate of
pass
pass
pass
pass
1. Identification: pressure gauge with switch
2. Model: PGS11.040 according to data sheet SP 21.01
3. Intended use according EN 12094-10: 2003
Components for use in gas extinguishing systems in buildings
4. Manufacturer:
WIKA Alexander Wiegand SE & Co.KG
Alexander-Wiegand-Str. 30, DE 63911 Klingenberg
5. Representative: Not applicable
6. Assessment: System 1
7. Notified body:
VdS Schadenverhütung GmbH, 0786 has performed type testing of the product, initial inspection of the
manufacturing plant and of factory production control with continuous surveillance, assessment and
evaluation of factory production control under system 1 and iss
conformity 0786-CPD-30089.
- accuracy class and nominal sizepass4.1.2
Durability of operational reliability against - corrosionpass4.1.3
Nominal activation conditions/sensitivity
- accuracy class and nominal sizepass4.2.1
Operational reliability
- Design
- Internal pressure
- Operational reliability
- Temperature
Durability of operational reliability against - corrosionpass4.2.6
10. The performance of the product identified in points 1 and 2 is in conformity with the declared performance in point
9. This declaration of performance is issued under the sole responsibility of the manufacturer identified in point 4.
Signed for and on behalf of
WIKA Alexander Wiegand SE & Co. KG
Klingenberg, 2013-08-02
Companydevision:MP-IGQualitymanagement:MP-IG
Signature authorized by the company
Alexander-Wiegand-Straße 30
63911 Klingenberg
11581752.02 09/2013 GB/D/F/E
WIKA operating instructions models PGS10, PGS11 and PGS21
4.2.2
4.2.3
4.2.4
4.2.5
Komplementärin:
WIKA International SE -Sitz Klingenberg Amtsgericht Aschaffenburg HRB 10505
Vorstand: Alexander Wiegand
Vorsitzender des Aufsichtsrats: Dr. Max Egli
GB
17
Tel. +49 9372 132-0
www.wika.de
Vorsitzender des Aufsichtsrats: Dr. Max Egli
Appendix 2: Declaration of performance model PGS21.050
GB
1. Identification: pressure gauge with switch
2. Model: PGS21.050 according to data sheet SP 21.03
3. Intended use according EN 12094-10: 2003
Components for use in gas extinguishing systems in buildings as part of e complete operating system.
4. Manufacturer:
WIKA Alexander Wiegand SE & Co.KG
Alexander-Wiegand-Str. 30, DE 63911 Klingenberg
5. Representative: N
6. Assessment: System 1
7. Notified body:
VdS Schadenverhütung GmbH, 0786 has performed type testing of the product, initial inspection of the
manufacturing plant and of factory production control with continuous surveillance, assessment and
evaluation of factory production control under system 1 and issued following certificate of certificate of
conformity 0786-CPD-30095.
- accuracy class and nominal sizepass4.1.2
Durability of operational reliability against - corrosionpass4.1.3
Nominal activation conditions/sensitivity
- accuracy class and nominal sizepass4.2.1
Operational reliability
- Design
- Internal pressure
- Operational reliability
- Temperature
Durability of operational reliability against - corrosionpass4.2.6
10. The performance of the product identified in points 1 and 2 is in conformity with the declared performance in point
9. This declaration of performance is issued under the sole responsibility of the manufacturer identified in point 4.
Signed for and on behalf of
WIKA Alexander Wiegand SE & Co. KG
Klingenberg, 2013-08-02
Companydevision:MP-IGQualitymanagement:MP-IG
PeterKollDanielKotlewski
Signature authorized by the company
WIKA Alexander Wiegand SE & Co. KG
Alexander-Wiegand-Straße 30
63911 Klingenberg
Germany
18
DECLARATION OF PERFORMANCE
according Construction Performance Regulation EU Nr. 305/2011
Document No.: 14059919.02
ot applicable
acteristicsPerformance EN 12094-10:2003
pass
pass
pass
pass
Kommanditgesellschaft: Sitz Klingenberg –
Amtsgericht Aschaffenburg HRA 1819
Fax +49 9372 132-406
Komplementärin: WIKA Verwaltungs SE & Co. KG –
E-Mail info@wika.de
Sitz Klingenberg –Amtsgericht Aschaffenburg
HRA 4685
WIKA operating instructions models PGS10, PGS11 and PGS21
4.2.2
4.2.3
4.2.4
4.2.5
Komplementärin:
WIKA International SE -Sitz Klingenberg Amtsgericht Aschaffenburg HRB 10505
Vorstand: Alexander Wiegand
11581752.02 09/2013 GB/D/F/E
Inhalt
Inhalt
1. Allgemeines
2. Sicherheit
3. Technische Daten
4. Aufbau und Funktion
5. Elektrische Schaltkontakte
6. Transport, Verpackung und Lagerung
7. Inbetriebnahme, Betrieb
8. Wartung und Reinigung
9. Demontage und Entsorgung
Anlage 1: Leistungserklärung Typ PGS11.040
Anlage 2: Leistungserklärung Typ PGS21.050
11581752.02 09/2013 GB/D/F/E
WIKA Betriebsanleitung Typen PGS10, PGS11 und PGS21
20
D
21
24
25
25
28
29
31
32
33
34
19
1. Allgemeines
1. Allgemeines
■
Das in der Betriebsanleitung beschriebene Druckmessgerät wird nach
dem aktuellen Stand der Technik konstruiert und gefertigt.
Alle Komponenten unterliegen während der Fertigung strengen
Qualitäts- und Umweltkriterien. Unsere Managementsysteme sind nach
D
ISO 9001 und ISO 14001 zertiziert.
■
Diese Betriebsanleitung gibt wichtige Hinweise zum Umgang mit dem
Gerät. Voraussetzung für sicheres Arbeiten ist die Einhaltung aller
angegebenen Sicherheitshinweise und Handlungsanweisungen.
■
Die für den Einsatzbereich des Gerätes geltenden örtlichen Unfallverhütungsvorschriften und allgemeinen Sicherheitsbestimmungen
einhalten.
■
Die Betriebsanleitung ist Produktbestandteil und muss in unmittelbarer
Nähe des Gerätes für das Fachpersonal jederzeit zugänglich
aufbewahrt werden.
■
Das Fachpersonal muss die Betriebsanleitung vor Beginn aller Arbeiten
sorgfältig durchgelesen und verstanden haben.
■
Die Haftung des Herstellers erlischt bei Schäden durch bestimmungswidrige Verwendung, Nichtbeachten dieser Betriebsanleitung, Einsatz
ungenügend qualizierten Fachpersonals sowie eigenmächtiger
Veränderung am Gerät.
■
Es gelten die allgemeinen Geschäftsbedingungen in den
Verkaufsunterlagen.
WIKA Betriebsanleitung Typen PGS10, PGS11 und PGS21
SP 21.01 und SP 21.03
11581752.02 09/2013 GB/D/F/E
1. Allgemeines / 2. Sicherheit
Symbolerklärung
WARNUNG!
… weist auf eine möglicherweise gefährliche Situation hin,
die zum Tod oder zu schweren Verletzungen führen kann,
wenn sie nicht gemieden wird.
Information
… hebt nützliche Tipps und Empfehlungen sowie
Informationen für einen ezienten und störungsfreien Betrieb
hervor.
2. Sicherheit
WARNUNG!
Vor Montage, Inbetriebnahme und Betrieb sicherstellen,
dass das richtige Druckmessgerät hinsichtlich Messbereich,
Ausführung und spezischen Messbedingungen ausgewählt
wurde.
Die Belastungsgrenzen sind einzuhalten, um die
Messgenauigkeit und die Lebensdauer zu gewährleisten.
Alle Arbeiten dürfen nur im spannungslosen Zustand
erfolgen.
Bei Nichtbeachten können schwere Körperverletzungen und/
oder Sachschäden auftreten.
Weitere wichtige Sicherheitshinweise benden sich in den
einzelnen Kapiteln dieser Betriebsanleitung.
2.1 Bestimmungsgemäße Verwendung
Die Druckmessgeräte mit Schaltkontakten switchGAUGE Typen
PGS10, PGS11 und PGS21 dienen zum Steuern und Regeln von
Industrieprozessen, zur Anlagenüberwachung und zum Schalten von
Stromkreisen.
Das Gerät ist ausschließlich für den hier beschriebenen bestimmungs-
11581752.02 09/2013 GB/D/F/E
WIKA Betriebsanleitung Typen PGS10, PGS11 und PGS21
D
21
Loading...
+ 47 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.