White Rodgers 47D43-811 User Manual

Operator: Save these instructions for future use!
FAILURE TO READ AND FOLLOW ALL INSTRUCTIONS CAREFULLY BEFORE INSTALLING OR OPERATING THIS CONTROL COULD CAUSE PERSONAL INJURY AND/OR PROPERTY DAMAGE.
DESCRIPTION
The 47D43-811 is a microprocessor-based demand defrost controller intended for Rheem heat pump systems. This controller uses basic differential temperature means to detect degradation of system performance due to ice build-up on the outdoor coil. The controller uses “self-calibrating” principles to calibrate itself to the heat pump system. The defrosting is performed by reversing the direction of flow of refrigerant.
The 47D43-811 is meant to replace the following controllers in Rheem heat pump systems:
47D43-811 Replaces
47D43-111 47D43-111 47D43-111 02 47D43-101
47-102685-04 47-102685-84 47-102685-05 47-102685-02 47-21517-22
47-21517-92 47-102684-02 47-102684-04 47-102684-07 47-102684-08
DDL-122131-2RH DDL-122131-2RH
47D43-811
Deluxe Defrost Control
INSTALLATION INSTRUCTIONS
47D43-811
PRECAUTIONS
CAUTION
!
• This control is intended only for Rheem heat pump systems.
• Replace 47D43-811 control as a unit - no user serviceable parts.
If in doubt about whether your wiring is millivolt, line or low voltage, have it inspected by a qualified heating and air conditioning contractor or licensed electrician.
Do not exceed the specification ratings.
All wiring must conform to local and national electrical codes and ordinances.
This control is a precision instrument, and should be handled carefully. Rough handling or distorting components could cause the control to malfunction.
CONTENTS
Description ................................................................ 1
Precautions ............................................................... 1
Specifications ............................................................ 2
Operation ................................................................... 2
Installation ................................................................. 3
WARNING
!
• To prevent electrical shock and/or equipment damage, disconnect electric power to system at main fuse or circuit breaker box until installation is complete.
• This control is not intended for use in locations where it may come in direct contact with water. Suitable protections must be provided to shield the control from exposure to water (dripping, spraying, rain, etc.)
• Label all wires prior to disconnection when servicing controls. Wiring errors can cause improper or loss of heat pump operation and/or shock hazard.
• Following installation or replacement, follow appliance manufacturer’s recommended installation/service
instructions to insure proper operation.
• Do not use on circuits exceeding specied voltage. Higher voltage will damage control and could cause shock or re hazard.
www.white-rodgers.com
www.emersonclimate.com
PART NO. 37-7199A
1047
SPECIFICATIONS
Electrical Ratings [@ 77oF (25oC)]:
Rated Voltage ........................ 24 VAC
Rated Voltage Range .................. 18-30 VAC
Max. Power Consumption @ 24 VAC ..... 4.08 VA
Nominal Frequency.................... 50/60 Hz
Relay Load Ratings:
Compressor Contactor Relay ...... 0 VA in rush, 6 VA holding
Fan Relay ...................... 1/2 HP @ 240, 1/4 HP
@ 120 VAC
Reversing Valve Relay (RV) ........ 24 VA
Auxiliary Heat Relay (D)........... 1 Amp. 0.6 P.F.
Operating Temperature Range ........... -40o to 150o F (-40o to 65o C)
Humidity Range ...................... 5% to 95% relative humidity
(non-condensing)
High Pressure Cutout Switch (HPC)....... 18 VAC
Low Pressure Cutout Switch (LPC) ....... 18 VAC
OPERATION
Each controller has 24 VAC input and B, Y, and D terminals for connection to a standard thermostat. The controller has pins for connection of two temperature sensors to measure ambient and coil temperature, as well as connections for high- and low-pressure switch monitoring. Controlled outputs are outdoor fan, reversing valve, and compressor contactor.
The 47D43 provides two LEDs for status and fault indication.
Option Switch
Switch labeled SW1 is used to select the defrost mode termination temperature of outdoor coil. Defrost mode is terminated when the coil temperature exceeds the selected termination temperature. Temperature options for SW1 switch settings are:
B A
On Off 50o F
B A
Off On 60o F
B A
On On 70o F (default)
B A
Off Off 80o F
B A
Test Pins
The pins labeled TEST can be used to change operation mode in the field. Momentarily short the test pins to force the system into the defrost mode. Momentarily short the test pins again to terminate the defrost mode. To avoid unnecessary system mode transition, do not use the test pins frequently.
Diagnostic Features
The control continuously monitors system operation. If a fault occurs, the two LEDs on the control will indicate a diagnostic code, if more than one fault occurs, only the code with the higher priority will be shown.
The table shows the diagnostic codes.
LED #1 LED #2
Off Off No power 0
On On Coil sensor failure 4
Off On
Flash* Flash* Normal 1
Off Flash*
Flash* Off
On Flash*
Flash* On
On Off Defrost mode 1
Alternating Flash 5-minute delay 2
Timing Specications @ 60Hz*
Nom Units
Defrost Lockout Time 34 Mins.
Maximum Defrost Time 14 Mins.
Transient Delay (Normal) 2 Mins.
Back to Back Transient Delay 4 Mins.
Maximum Frosting Time 6 Hrs.
Short Cycle Lockout Time 5 Mins.
Noise Abatement Time (Normal 30 Sec.
Noise Abatement Time (Forced Defrost) 5 Sec.
*50Hz Timings are 20% longer.
Fault
Indication
Ambient sensor failure 3
Low pressure lockout 7
High pressure lockout 8
Low pressure switch open 5
High pressure switch open 6
Display Priority
* The flash time is to be 0.5 seconds on and 0.5 seconds off followed by 2 seconds off.
2
Loading...
+ 2 hidden pages