White Rodgers 3L09 User Manual

3L09
WHITE-RODGERS
Operator: Save these instructions for future use!
FAILURE TO READ AND FOLLOW ALL INSTRUCTIONS CAREFULLY BEFORE INSTALLING OR OPERATING THIS CONTROL COULD CAUSE PERSONAL INJURY AND/OR PROPERTY DAMAGE.
This series of limit controls has a normally closed SPST switch that opens on temperature rise to limit the maxi­mum allowable temperature in forced air heating sys-
THIS CONTROL MUST BE INSTALLED BY A QUALI­FIED INSTALLER.
All wiring must conform to local and national electrical codes and ordinances.
This control is a precision instrument, and should be handled carefully. Rough handling or distorting compo­nents could cause the control to malfunction.
This control has been accurately calibrated at the factory. Any attempt to re-calibrate this control will void the White­Rodgers warranty.
WARNING
!
Do not use on circuits exceeding specified volt­ages. Higher voltages will damage control and could cause shock or fire hazard.
If in doubt about whether your wiring is millivolt, low or line voltage, have it inspected by a quali­fied heating and air conditioning contractor or a licensed electrician.
Limit Controls
INSTALLATION INSTRUCTIONS
DESCRIPTION
tems. A small bimetal sensing element is located in the air stream for quick response. These controls have a fixed temperature setting and fixed differential.
PRECAUTIONS
CAUTION
!
To prevent electrical shock and/or equipment damage, disconnect electric power to system at main fuse or circuit breaker box until installation is complete.
Label all wires prior to disconnection when ser­vicing controls. Wiring errors can cause improper and dangerous operation.
Following installation or replacement, follow appliance manufacturers’ recommended instal­lation/service instructions to insure proper op­eration.
ELECTRICAL RATING:
Resistive: 15 amps @ 120 VAC
13 amps @ 240 VAC
9.3 amps @ 277 VAC
Inductive: 5.8 FLA, 34.8 LRA @ 120 VAC
2.9 FLA, 13.0 LRA @ 240 VAC
Pilot Duty: 278 VA
This control must be mounted in the air stream of the appliance. Follow the original equipment manufacturers’ recommendations for proper location and wiring.
WHITE-RODGERS DIVISION
EMERSON ELECTRIC CO. 9797 REAVIS ROAD ST. LOUIS, MISSOURI 63123-5398
Printed in U.S.A.
SPECIFICATIONS
Temperature Setting:
Fixed setting stamped on control
INSTALLATION
Wiring
All wiring must conform to local and national
electrical codes and ordinances.
PART NO. 37-6133A