White Rodgers 37-6334a User Manual

Operator: Save these instructions for future use!
CAUTION
FAILURE TO READ AND FOLLOW ALL INSTRUCTIONS CAREFULLY BEFORE IN­STALLING OR OPERATING THIS CONTROL COULD CAUSE PERSONAL INJURY AND/OR PROPERTY DAMAGE.
The compact zone valves are 2-way straight through, available as a normally open or normally closed valve. The zone valves come with or without a SPST normally open auxiliary switch and feature a swing-type ball valve, which is designed to rotate which causes the ball plug to seat on a different section of its surface on each closing. They are available in several piping options, sweat, NPT, inverted flare and flare fitting end connections for standard copper tubing, for use with 2-wire thermostats. These zone valves provide a low cost system of zoned temperature control wherever hot water is the heating medium. In new construction, the piping system can be laid out to produce any number of independent temperature controlled zones by use of these valves. In existing buildings, a variety of zone combina­tions can be obtained, depending on the particular piping layout. Each zone requires one zone valve and one thermostat, but only one circulator is normally required for the entire system.
This compact zone valve is intended for use with a low voltage system; do not use this zone valve with a millivolt or line voltage system. If in doubt about whether your wiring is millivolt, line or low voltage, have it inspected by a qualified heating contractor or electrician.
Do not exceed the specification ratings. All wiring must conform to local and national electrical codes and
ordinances.
COMPACT ZONE VALVES
2-WIRE, 2-WAY
For use on systems up to 142 PSI
INST ALLA TION INSTRUCTIONS
DESCRIPTION
Flare Fittings
Available Separately
PRECAUTIONS
To prevent electrical shock and/or equipment damage, disconnect electric power to system at main fuse or circuit breaker box, until installation is complete.
CAUTION
To prevent injuries from scalding always drain system before installing or removing valve. To avoid gear damage operate lever slowly.
All guarantees are void if these specifications are exceeded.
Maximum System Pressure: 142 PSI Differential Across Valve: 20 PSI Maximum Water Temperature: 230°F Minimum Water Temperature: 41°F Maximum Ambiant Temperature: 140°F Approx. Time Cycle: 10 seconds from full close to full open;
4 seconds from full open to full close.
Electrical Rating:
Valve motor – 0.35A @ 25VAC, 50/60 Hz., 6 W nominal Auxiliary switch: 3.0A Max. @ 25VAC
Thermostat: Use two-wire heating thermostat, .35A heat
anticipation is required.
Flow Coefficient - Cv Rating:
1/2" valves – 3.5 Cv (3.0 Kv) 3/4" valves – 3.5 Cv (3.0 Kv) 1" valves – 3.5 Cv (3.0 Kv)
WHITE-RODGERS
EMERSON ELECTRIC CO. 9797 Reavis Road St. Louis, MO 63123-5398 www.white-rodgers.com
WARNING
Do not use on circuits exceeding specified voltages. Higher voltages will damage control and could cause shock or fire hazard.
SPECIFICATIONS
MOUNTING POSITIONS:
Upright or 0° to 90° from upright
UPRIGHT
Fig. 1 Zone valve mounting positions
LEFT OR RIGHT
INLET
UP OR DOWN
360°
MAN
AUTO
PART NO. 37-6334A
0142
OPERATION
The schematic drawing Fig. 2 is for a normally closed valve. As shown, the valve is closed and the thermostat is satisfied.
When the thermostat closes its contacts, the valve begins to open as a circuit is made from the transformer to the motor and thermostat, back to the transformer.
Shortly after the valve begins to open, the auxiliary switch closes (providing a low voltage auxiliary circuit for starting burner and/or circulator). After an elapsed time of about 10 seconds, the valve reaches the full open position. The valve motor now remains energized to keep the valve in the open position.
When the thermostat is satisfied, the circuit through the valve motor is broken and a return spring begins to close the valve. Just before the valve reaches the closed position, the auxiliary switch opens to stop burner and/or circulator.
TYPE 'Z' ZONE VALVE
N.O. CONTACT
AUX. SWITCH
MOTOR
INTERNAL WIRING EXTERNAL WIRING
A B
BLACK
BLACK
BROWN
BLUE GREEN
2-WIRE HEATING
THERMOSTAT
Fig. 2
A
HOT
LINE
N
TRANSFORMER
B
VALVE CLOSED
VALVE OPEN
Fig. 3 Operation for normally close (N.C.) valve
PIPING
The two most commonly used piping systems are shown below. Plan 1 is popular for new installations, while plan 2 is frequently used when converting two­pipe systems.
PLAN 2
A common main supplies all zones, with a water valve installed on the riser to each zone.
Fig. 4
PLAN 1
Water valves installed at the boiler header to provide a separate supply to each zone.
INSTALLATION
ALL GUARANTEES ARE VOID IF THE VALVE IS NOT ASSEMBLED ACCORDING TO THESE INSTRUCTIONS.
1. Disconnect electric power before connecting wiring to prevent electrical shock or equipment damage.
2. Select suitable valve location. Valve may be installed in any position, except upside down. The arrow on the side of the body indicates direction of flow throught the valve. (“A” is inlet, “B” is outlet)
3. Mount valve directly in the tube or pipe, as follows:
NOTE
For normally closed (N.C.) models, with sweat fittings, set the manual lever to the "MAN" position before applying heat to the fittings. This will protect the plug ball inside the valve by removing it from the seat. After installation, place manual lever in the "AUTO" position.
Flare fitting models
Use new, properly reamed pipe, free from chips. The valve body is threaded for standard 5/8 in. OD copper, 45° SAE flare-fitting nuts. These nuts are not furnished with the valve and must be obtained separately.
Sweat copper models
Use new, properly reamed pipe, free from dents or corrosion. Sweat the joints, keeping the outer surface free from solder.
DO NOT use silver solder because of the high melting temperatures required.
NPT pipe models
Use new pipe that is properly chamfered, reamed and free of burrs and chips. If using old pipe, be sure it is clean and free of rust, scale, burrs, chips and old pipe joint compound.
Apply pipe joint compound or teflon tape, only to the male threads of the pipe joint. DO NOT apply compound or teflon tape to the first two threads. If using a vise or open-end wrench to hold the valve while installing piping, do not tighten excessively, as this may damage the valve.
4. Support piping with a pipe hanger on each side of valve.
Fig. 5
729
WIRING
All wiring should be done according to local and national electrical codes
Follow any specific wiring instructions provided by the boiler manufacturer. If none are supplied, the following diagrams offer typical wiring installations using 2-wire heating thermostats (.35A Heat-Anticipation) and other related controls.
A 40VA Transformer will handle up to 4 zone valves. A 20VA will handle up to 2 zone valves.
2
WIRING CONT.
24 VAC
GAS VALVE
HIGH LIMIT
COMMON
G (BLK)
MUST BE N.E.C. CLASS 1 WIRING
Fig. 7a Diagram for Gas-Fired System, eliminate Oil Burner for Gas-Fired system
All wiring should be done according to local and national electrical codes
DIAGRAMS FOR SYSTEMS WHERE BURNER AND CIRCULATOR OPERATION IS INDEPENDENT OF THERMOSTATS
TRANSFORMER
Fig. 6 Zone Valve (N.C.)
N LINE HOT
24 VAC
DIAGRAM FOR SYSTEMS WHERE INTERNAL TRANSFORMER OF RELAY CONTROL SUPPLIES POWER FOR ZONE VALVES
TYPE 668
OIL BURNER CONTROL
IGNITION
TRANS.
BURNER MOTOR
N LINE HOT
ORANGE
WHITE
WHITE
BLACK
F
F
T
T
BLACK
HIGH LIMIT
TYPE 956
FLAME
DETECTOR
RELAY/TRANSFORMER
TRANSFORMER
COM
W-R 2-WIRE HEATING THERMOSTATS
W
Y
STAT
R
BLUE
G
BLACK
BLACK
BLACK
BLUE
BROWN
ZONE VALVES (N.C.)
W-R 2-WIRE HEATING THERMOSTATS
BLUE
BROWN
ZONE VALVES (N.C.)
N.C.
RED
N.O.
CIRCULATOR
MOTOR
BROWN
RELAY COIL
TAPE OFF
Fig. 7 Diagram for Oil-Fired system using Relay/
Transformer with Zone Valves (N.C.)
DIAGRAMS FOR SYSTEMS WHERE EXTERNAL TRANSFORMER REQUIRED FOR POWERING FOR ZONE VALVES
W-R 2-WIRE HEATING THERMOSTATS
ADDITIONAL
ZONES
STAT
BLUE
BLACK
BLACK
LINE
HOT
N
TRANSFORMER
BLACK
BLACK
BLUE
BROWN
ZONE VALVES (N.C.)
LINE HOT
N
BLUE
TRANSFORMER
BLACK
BROWN
BLACK
RELAY/TRANSFORMER
T1
CIRCULATOR
MOTOR
1
2 C1 C2 B1T2
B2
IGN.
TRANS.
BURNER
MOTOR
HOT LINE N
Fig. 8 Diagram for for System using Relay/transformer
with Zone Valves (N.C.)
3
WIRING (Continued)
THERM
163
452
DIAGRAMS FOR SYSTEMS WHERE EXTERNAL TRANSFORMER REQUIRED FOR POWERING FOR ZONE VALVES
TO ZONE
VALVES
N
LINE HOT
BLACK
BLACK
RELAY/TRANSFORMER
TYPE 8B42A OR 8B43A
1 C1 C2 B1
TYPE 829A RELAY
TYPE 809A RELAY
T1T2
2
B2
IGN.
TRANS.
BLACK
BLACK
1 2 L L
HOT LINE
N
BLACK
BLACK
HOT LINE
N
TO GAS VALVE
CIRCULATOR
MOTOR
BURNER
MOTOR
Alternate Connections For Relay/Transformer
AND TRANSFORMER OR OIL BURNER CONTROL
Alternate Connections For Type 809A Relay
OPERATION
Automatic (AUTO) (N.C. valve) (Fig. 9)
On a call for by the thermostat, the valve opens and its auxiliary contacts close, providing a low voltage auxiliary circuit for starting the burner and/or circulator. After an elapsed time of about 10 seconds, the valve reaches the full open position. The valve motor now remains energized to keep the valve in the open position. When the thermostat is satisfied, the valve closes by its integral return spring. The auxiliary contacts open, de-energizing the auxiliary circuit.
Manual (MAN)
Use manual lever in case of power failure or for servicing the system. If power fails while valve is open, valve will return to the closed position. To manually open the valve, move the manual lever to the "MAN" position and lock in place. The valve will return to the "AUTO" position when the valve is electrically energized. The auxiliary contacts close in the "MAN" position. The manual lever is not operational on normally open (N.O.) valve models.
Normally open models (N.O.) (Fig. 11) A normally open valve operates opposite to a normally closed
valve. It is open in the de-energized position and closes when the valve is energized. A reverse-acting (close-on-rise) thermostat is required to control a normally open (N.O.)valve.
CHECKING THE SYSTEM
Turn on the electricity. If gas fired, be sure pilot is lit. Then check each zone separately as follows:
1. Turn thermostat to highest setting. Zone valve for that zone will open and furnace burner will come on as auxiliary circuit is made on valve motor.
2. Turn thermostat to lowest setting. Zone valve for that zone will close and furnace burner will shut off as auxiliary circuit is broken on zone valve.
(Fig. 10)
CIRCULATOR
MOTOR
OIL BURNER
CONTROL
CIRCULATOR
MOTOR
TO GAS VALVE AND TRANSFORMER OR
Alternate Connections For Type 829A Relay
AUXILIARY
SWITCH
N.O.
A B
VALVE CLOSED
POWER 'OFF'
AUXILIARY
SWITCH CLOSED
A
VALVE OPEN
POWER 'ON'
B
Fig. 9 Normally close (N.C.) zone valve
AUTO MAN
AUXILIARY
SWITCH CLOSED
A B
VALVE OPEN, MANUAL POSITION
POWER 'OFF'
Fig. 10 Manual operation of normally close (N.C.) valve
AUXILIARY
SWITCH
N.O.
A
VALVE OPEN POWER 'OFF'
B
AUXILIARY
SWITCH CLOSED
A B
VALVE CLOSED
POWER 'ON'
Fig. 11 Normally open (N.O.) zone valve
4
Loading...