FAILURE TO READ AND FOLLOW ALL INSTRUCTIONSFAILURE TO READ AND FOLLOW ALL INSTRUCTIONS
FAILURE TO READ AND FOLLOW ALL INSTRUCTIONS
FAILURE TO READ AND FOLLOW ALL INSTRUCTIONSFAILURE TO READ AND FOLLOW ALL INSTRUCTIONS
CAREFULLY BEFORE INSTALLING OR OPERATING THISCAREFULLY BEFORE INSTALLING OR OPERATING THIS
CAREFULLY BEFORE INSTALLING OR OPERATING THIS
CAREFULLY BEFORE INSTALLING OR OPERATING THISCAREFULLY BEFORE INSTALLING OR OPERATING THIS
CONTROL COULD CAUSE PERSONAL INJURY AND/ORCONTROL COULD CAUSE PERSONAL INJURY AND/OR
CONTROL COULD CAUSE PERSONAL INJURY AND/OR
CONTROL COULD CAUSE PERSONAL INJURY AND/ORCONTROL COULD CAUSE PERSONAL INJURY AND/OR
PROPERTY DAMAGE.PROPERTY DAMAGE.
DescriptionDescription
Heat Pump (No Auxiliary or Emergency Heat)Yes
Heat Pump (with Auxiliary or Emergency Heat)Yes
Standard Heat & Cooling SystemsYes
Multi-Stage Systems requiring more thanYes
One Call for Heat or Cool
Standard Heat Only SystemsYes
Millivolt Heat Only Systems – Floor or Wall FurnacesNo
Standard Central Air ConditioningYes
Gas or Oil HeatYes
Electric FurnaceYes
Hydronic (Hot Water) Zone Heat – 2 Wires* Yes
Hydronic (Hot Water) Zone Heat – 3 WiresNo
* Common Connection Required
1F85RF-275 Thermostat and
Wireless Remote Sensor Kit
Automatic Heat/Cool Changeover Thermostat for Single Stage/
Multi-Stage/Heat Pump Systems with Wireless Remote Sensor
Installation and Operating Instructions for Model:Installation and Operating Instructions for Model:
Installation and Operating Instructions for Model:
Installation and Operating Instructions for Model:Installation and Operating Instructions for Model:
ModelProgramming Choices
1F85RF-270Non-Programmable5/1/1 Day
F145RF-1328Wireless Remote Sensor
1F85RF-270
Wireless Remote Sensor
SPECIFICATIONSSPECIFICATIONS
SPECIFICATIONS
SPECIFICATIONSSPECIFICATIONS
ThermostatThermostat
Thermostat:
ThermostatThermostat
Electrical Ratings .......................... 20 to 30 VAC 50/60 Hz
Setpoint Range.............................. 45 to 90°F (7 to 32°C)
To prevent electrical shock and/or equipment dam-To prevent electrical shock and/or equipment damage, disconnect electric power to system at main fuseage, disconnect electric power to system at main fuse
age, disconnect electric power to system at main fuse
age, disconnect electric power to system at main fuseage, disconnect electric power to system at main fuse
or circuit breaker box until installation is complete.or circuit breaker box until installation is complete.
or circuit breaker box until installation is complete.
or circuit breaker box until installation is complete.or circuit breaker box until installation is complete.
IndexPage
Installation2
Wiring Connections3
Thermostat/Sensor Quick Reference4
Installer Configuration Menus6
Operating Your Thermostat and Sensor9
Programming13
Troubleshooting14
0.2 to 0.6 Amps per Load
(Y1, E/W1, G)
1.5 Amps (Y2, W2, O, B
Load per terminal)
1.5 Amps Max
(All terminals combined)
CAUTION
Remote Sensor:Remote Sensor:
Remote Sensor:
Remote Sensor:Remote Sensor:
This device complies with Part 15 of the FCC Rules, OperationThis device complies with Part 15 of the FCC Rules, Operation
This device complies with Part 15 of the FCC Rules, Operation
This device complies with Part 15 of the FCC Rules, OperationThis device complies with Part 15 of the FCC Rules, Operation
is subject to the following two conditions: (1) this device mayis subject to the following two conditions: (1) this device may
is subject to the following two conditions: (1) this device may
is subject to the following two conditions: (1) this device mayis subject to the following two conditions: (1) this device may
not cause harmful interference, and (2) this device must acceptnot cause harmful interference, and (2) this device must accept
not cause harmful interference, and (2) this device must accept
not cause harmful interference, and (2) this device must acceptnot cause harmful interference, and (2) this device must accept
any interference received, including interference that may causeany interference received, including interference that may cause
any interference received, including interference that may cause
any interference received, including interference that may causeany interference received, including interference that may cause
undesired operation.undesired operation.
undesired operation.
undesired operation.undesired operation.
Maximum Wireless Remote Sensors.....1 indoor, 1 outdoor
Operating Range .................................... 45 to 90°F (7 to 32°C)
Operating Humidity Range .....................0 to 90% RH
(non-condensing)
Dimensions .............................................2-5/8"H x 4-1/4"W x 7/8"D
* Max. Distance from Thermostat .......... 200 feet
* Distance shown is for a typical application. Distances may vary in
some applications because obstacles that block the signal path
may affect the strength of the signal.
ATTENTION: MERCURY NOTICEATTENTION: MERCURY NOTICE
This product does not contain mercury. However, this product may replace a product which contains mercury.
Mercury and products containing mercury must not be discarded in household trash. Do not touch any spilled mercury.
Wearing non-absorbent gloves, clean up any spilled mercury
and place in a sealed container. For proper disposal of a
product containing mercury or a sealed container of spilled
mercury, place it in a suitable shipping container and send it
to:
White-RodgersWhite-Rodgers
White-Rodgers
White-RodgersWhite-Rodgers
2895 Harrison Street2895 Harrison Street
2895 Harrison Street
2895 Harrison Street2895 Harrison Street
Batesville, AR 72501Batesville, AR 72501
Batesville, AR 72501
Batesville, AR 72501Batesville, AR 72501
www.white-rodgers.com
PART NO. 37-6841BPART NO. 37-6841B
PART NO. 37-6841B
PART NO. 37-6841BPART NO. 37-6841B
Replaces 37-6841A
0745
Page 2
ANTENNA
MOUNTING HOLE
MOUNTING HOLE
INSTALLATIONINSTALLATION
INSTALLATION
INSTALLATIONINSTALLATION
WARNING
!
Thermostat installation and all components of theThermostat installation and all components of the
Thermostat installation and all components of the
Thermostat installation and all components of theThermostat installation and all components of the
control system shall conform to Class II circuits per thecontrol system shall conform to Class II circuits per the
control system shall conform to Class II circuits per the
control system shall conform to Class II circuits per thecontrol system shall conform to Class II circuits per the
NEC code.NEC code.
NEC code.
NEC code.NEC code.
Remove Old ThermostatRemove Old Thermostat
Remove Old Thermostat
Remove Old ThermostatRemove Old Thermostat
A standard heat/cool thermostat consists of three basic parts:
1. The cover, which may be either a snap-on or hinge type.
2. The base, which is removed by loosening all captive
screws.
3. The switching subbase, which is removed by unscrewing
the mounting screws that hold it on the wall or adapter
Before removing wires from old thermostat,Before removing wires from old thermostat,
plate.
Before removing wires from old thermostat,
Before removing wires from old thermostat,Before removing wires from old thermostat,
label each wire with the terminal designation fromlabel each wire with the terminal designation from
label each wire with the terminal designation from
label each wire with the terminal designation fromlabel each wire with the terminal designation from
which it was attachedwhich it was attached
which it was attached. Disconnect the wires from the old
which it was attachedwhich it was attached
thermostat one at a time.
the wallthe wall
the wall.
the wallthe wall
Guidelines for Thermostat/Sensor LocationsGuidelines for Thermostat/Sensor Locations
Guidelines for Thermostat/Sensor Locations
Guidelines for Thermostat/Sensor LocationsGuidelines for Thermostat/Sensor Locations
Do not let wires fall back intoDo not let wires fall back into
Do not let wires fall back into
Do not let wires fall back intoDo not let wires fall back into
Locate the thermostat/sensor about 5 ft. above floor level on
an interior wall in an area that represents the average room
temperature.
Do not mount directly on or near HVAC equipment or other
sources of electrical noise.
Avoid locations close to windows or near adjoining outside
walls, doors leading outside, areas close to air registers or
their direct air flow or areas with poor circulation like alcoves.
Avoid locating the sensor on a concrete wall, junction box or
metal plate. Make sure there are no electrical wires, metal,
pipes or duct work in the part of the wall chosen for the
sensor location.
Thermostat and indoor sensor are not approved forThermostat and indoor sensor are not approved for
Thermostat and indoor sensor are not approved for
Thermostat and indoor sensor are not approved forThermostat and indoor sensor are not approved for
installation in unconditioned space.installation in unconditioned space.
installation in unconditioned space.
installation in unconditioned space.installation in unconditioned space.
Mounting Thermostat and SensorMounting Thermostat and Sensor
Mounting Thermostat and Sensor
Mounting Thermostat and SensorMounting Thermostat and Sensor
1. Remove the packing material from the thermostat and
sensor.
2. Pull the front covers of the thermostat and sensor straight
off the bases. Forcing or prying will cause damage to the
controls.
3. Using the thermostat and sensor bases as templates,
place them on the selected wall locations and mark the
location of all mounting holes (Figure 1 and 3), and the
hole for the thermostat antenna wire illustrated in Figure 2.
4. Move bases out of the way and drill the holes. If mounting
holes drilled are too large and do not allow you to tighten
base snugly, use the plastic screw anchors (provided) for
secure mounting.
5. Make sure the remote communication receiver is plugged
in properly to the thermostat and that the antenna wire is
routed through the thermostat subbase as shown in
Figure 2.
6. Fasten bases loosely to wall, using two mounting screws
for each. Place a level against bottom of base (leveling is
for appearance only and will not affect sensor operation)
and then tighten screws.
7. In the thermostat location, push excess wire into wall and
plug hole with a fire resistant material (such as fiberglass
insulation) to prevent drafts from affecting the thermostat
operation.
2
8. Remove the battery tags in both the thermostat and
sensor and replace the covers by lining them up with the
base and pressing until they snap into place.
ELEC/GASSWITCH
RC/PSSWITCH
ANTENNA
MOUNTING
HOLE
Figure 1 – Thermostat baseFigure 1 – Thermostat base
Figure 1 – Thermostat base
Figure 1 – Thermostat baseFigure 1 – Thermostat base
ANTENNA
WIRE
Figure 2 – Back of thermostat baseFigure 2 – Back of thermostat base
Figure 2 – Back of thermostat base
Figure 2 – Back of thermostat baseFigure 2 – Back of thermostat base
The thermostat requires 2 "AA" alkaline batteries and the
sensor requires 2 "AAA" alkaline batteries. Batteries are
included at the factory with a battery tag to prevent power
drainage. The battery tag must be removed to engage the
batteries. For best results, replace batteries once a year with
new premium brand alkaline batteries such as Duracell
The ELEC/GAS switch is factory set to the ELEC position. In
this position, the thermostat will power the circulator fan on a
call for heat. Electric heat systems may require the switch to
be in the ELEC position.
If your system does not require that the thermostat power the
circulator fan, this switch should be set to the GAS position.
Typically, gas and oil heating systems do not require the
thermostat to power the circulator fan during a call for heat. If
your heat is gas or oil, the switch should be set to the GAS
position.
When the thermostat is configured for Heat Pump, the
thermostat will always power the circulator fan on a call for
heat in the HEAT mode. The ELEC/GAS switch must be set
to match the type of Auxiliary heat your system uses for
proper operation in the EMERgency mode.
RC/PS Switch (Thermostat Power Option)RC/PS Switch (Thermostat Power Option)
RC/PS Switch (Thermostat Power Option)
RC/PS Switch (Thermostat Power Option)RC/PS Switch (Thermostat Power Option)
RC/PSRC/PS
RC/PS
RC/PSRC/PS
SwitchSwitch
Switch
SwitchSwitch
PositionPosition
Position
PositionPosition
RCFor Hardwire Applications. Requires Common Wire
from System Transformer to "C" Terminal on Thermostat
PSFor Power Stealing Applications. Use When Common
from the System Transformer is not Available for
Connection to the "C" Terminal on the Thermostat
NOTE: If set to PS (Power Stealing), the thermostat "C" terminal
must notmust not
must not
must notmust not
have a wire connected.
DescriptionDescription
Description
DescriptionDescription
Page 3
WIRING CONNECTIONSWIRING CONNECTIONS
WIRING CONNECTIONS
WIRING CONNECTIONSWIRING CONNECTIONS
Typical wiring diagrams are provided below for the following systems:
Single Stage Heat/Cool systems
Multi-Stage Heat/Cool systems (No Heat Pump)
Heat Pump system, one compressor or one speed compressor with Aux. Heat
Heat Pump systems, two compressors or two speed compressor with Aux. Heat
Refer to the equipment manufacturers instructions for specific wiring information. After completing the connections configure
the thermostat in the Installer Configuration Menu to match your system type.
Figure 4 – Single Stage (No Heat Pump) Terminal OutputsFigure 4 – Single Stage (No Heat Pump) Terminal Outputs
Figure 4 – Single Stage (No Heat Pump) Terminal Outputs
Figure 4 – Single Stage (No Heat Pump) Terminal OutputsFigure 4 – Single Stage (No Heat Pump) Terminal Outputs
W2
No Output
E/W1
Heat
Mode
1st Stage
(Heater)
G
Blower/
Circulator
Fan Energized
on Call for
Cool or Fan,
Energized on
Call for Heat if
Elect/Gas
Switch Set to
Electric
Energized
in Cool
Mode
(Changeover Valve
or Damper)
*C
Y1
Cool Mode
1st Stage
(Compressor)
Y2
No Output
R
System
24 Volt
24 Volt
Single Stage
(SS1)
**
The RC/PS switch shown in Figure 1 configures the thermostat for Hardwire or Power Stealing.The RC/PS switch shown in Figure 1 configures the thermostat for Hardwire or Power Stealing.
*
The RC/PS switch shown in Figure 1 configures the thermostat for Hardwire or Power Stealing.
**
The RC/PS switch shown in Figure 1 configures the thermostat for Hardwire or Power Stealing.The RC/PS switch shown in Figure 1 configures the thermostat for Hardwire or Power Stealing.
(Hot)
(Common)
Optional
Connection
B
O
Energized
in Heat, Off
Mode
(Changeover Valve
or Damper)
L
Fault
Indicator
for Heat
Pump
Systems
with
Malfunction
Switch
NEUTRAL
24VAC
HOT
CLASS II
TRANSFORMER
120VAC
The factory setting is RC (Hardwire) and requires a Common connection from the system transformer to the "C" terminal on
the thermostat. If no common wire is available for the thermostat "C" terminal, move the RC/PS switch to PS (Power Steal-
G
Blower/
Circulator
Fan Energized
on Call for
Cool or Fan,
Energized on
Call for Heat if
Elect/Gas
Switch Set to
Electric
must notmust not
must not
must notmust not
O
Energized
Energized
in Heat, Off
in Cool
Mode
Mode
(Change-
(Change-
over Valve
over Valve
or Damper)
or Damper)
have a wire connected.
B
L
Fault
Indicator
for Heat
Pump
Systems
with
Malfunction
Switch
NOTENOTE
ing).
NOTE: If set to PS (Power Stealing), the thermostat "C" terminal
NOTENOTE
Figure 5 – Multi-Stage (No Heat Pump) Terminal OutputsFigure 5 – Multi-Stage (No Heat Pump) Terminal Outputs
Figure 5 – Multi-Stage (No Heat Pump) Terminal Outputs
Figure 5 – Multi-Stage (No Heat Pump) Terminal OutputsFigure 5 – Multi-Stage (No Heat Pump) Terminal Outputs
W2
Y2
Heat
Heat
Mode
Mode
1st Stage
2nd Stage
System
Multi-Stage
(MS2)
R
24 Volt
(Hot)
*C
24 Volt
(Common)
Optional
Connection
Y1
Cool Mode
1st Stage
(Compressor 1)
Cool Mode
2nd Stage
(Compressor 2)
E/W1
NEUTRAL
24VAC
HOT
CLASS II
TRANSFORMER
**
The RC/PS switch shown in Figure 1 configures the thermostat for Hardwire or Power Stealing.The RC/PS switch shown in Figure 1 configures the thermostat for Hardwire or Power Stealing.
*
The RC/PS switch shown in Figure 1 configures the thermostat for Hardwire or Power Stealing.
**
The RC/PS switch shown in Figure 1 configures the thermostat for Hardwire or Power Stealing.The RC/PS switch shown in Figure 1 configures the thermostat for Hardwire or Power Stealing.
120VAC
The factory setting is RC (Hardwire) and requires a Common connection from the system transformer to the "C" terminal on
the thermostat. If no common wire is available for the thermostat "C" terminal, move the RC/PS switch to PS (Power Steal-
G
Blower/
Circulator
Fan Energized
on Call for
Heat/Cool
or Fan,
Note: Set
Elect/Gas
switch for
Emergency
Mode Heat Type
must notmust not
must not
must notmust not
O
Energized
Energized
in Heat, Off,
in Cool
Emergency
Mode
Mode
(Change-
(Change-
over Valve)
over Valve)
have a wire connected.
B
L
Fault
Indicator
for Heat
Pump
Systems
with
Malfunction
Switch
NEUTRAL
24VAC
HOT
CLASS II
TRANSFORMER
120VAC
NOTENOTE
ing).
NOTE: If set to PS (Power Stealing), the thermostat "C" terminal
The RC/PS switch shown in Figure 1 configures the thermostat for Hardwire or Power Stealing.The RC/PS switch shown in Figure 1 configures the thermostat for Hardwire or Power Stealing.
*
The RC/PS switch shown in Figure 1 configures the thermostat for Hardwire or Power Stealing.
**
The RC/PS switch shown in Figure 1 configures the thermostat for Hardwire or Power Stealing.The RC/PS switch shown in Figure 1 configures the thermostat for Hardwire or Power Stealing.
24 Volt
(Hot)
24 Volt
(Common)
Optional
Connection
Heat Mode-
1st Stage
Cool Mode-
1st Stage
(Compressor 1)
Y2
No Output
Heat Mode-
2nd Stage
Cool Mode-
2nd Stage
(Compressor 2)
The factory setting is RC (Hardwire) and requires a Common connection from the system transformer to the "C" terminal on
the thermostat. If no common wire is available for the thermostat "C" terminal, move the RC/PS switch to PS (Power Steal-
NOTENOTE
ing).
NOTE: If set to PS (Power Stealing), the thermostat "C" terminal
Before operating the thermostat, familiarize yourself with the
display and button functions. Both thermostat and remote
sensor consist of two parts: the cover and the base. To remove
a cover, pull it straight out from the base. To replace a cover, line
it up with the base and press until the cover snaps into place on
the base.
The Thermostat Buttons and Switches and DisplayThe Thermostat Buttons and Switches and Display
The Thermostat Buttons and Switches and Display
The Thermostat Buttons and Switches and DisplayThe Thermostat Buttons and Switches and Display
Raises and lowers the temperature setting.
1
Light flashes every 20 seconds indicating acceptable
2
signal reception from indoor or outdoor remote sensor.
Buttons for setting time (Time), programming (Prgm),
3
running program (Run) and bypassing program to
hold a constant temperature (Hold).
6
2
5
4
7
ONON
ON,
ONON
COOLCOOL
COOL,
COOLCOOL
AUTOAUTO
AUTO).
AUTOAUTO
SYSTEM button (
4
heat pump systems only).
FAN switch (
5
Displays the active temperature sensor (outside,
6
remote, local) and its sensed temperature.
Displays ( ) when in keypad lockout mode.
7
Indicates day of the week.
8
Indicates the thermostat mode information:
9
HOLDHOLD
"
HOLD" alternates with the system mode (see item 12)
HOLDHOLD
if the HOLD button is pressed to bypass the program
and maintain a constant temperature.
Displays currently programmed set temperature (blank
10
SYSTEM SYSTEM
when
SYSTEM is
SYSTEM SYSTEM
Alternately displays the current time and the tempera-
11
ture average of sensors (thermostat [local] and/or
indoor remote) turned on.
HEATHEAT
"
HEAT" is displayed when set to heating,
HEATHEAT
12
COOLCOOL
"
COOL" is displayed when set to cooling,
COOLCOOL
AUTOAUTO
"
AUTO" is displayed when set for automatic change-
AUTOAUTO
over between heating and cooling.
AUTOAUTO
When "
AUTO" is displayed, the currently active mode
AUTOAUTO
(Heat or Cool) will also display.
EMEREMER
"
EMER" is displayed flashing (heat pump systems
EMEREMER
only) when the thermostat is set to the Emergency
Mode. Emergency is used to bypass the heat pump
and use only the back-up heating system.
FLTRFLTR
"
FLTR" is displayed as a reminder to change or clean
FLTRFLTR
the air filter after system has run for the programmed
filter time period.
OFFOFF
OFF).
OFFOFF
AUTOAUTO
AUTO,
AUTOAUTO
HEATHEAT
HEAT,
HEATHEAT
OFF, EMEROFF, EMER
OFF, EMER
OFF, EMEROFF, EMER
12
14
15
16
17
Figure 7 – Thermostat display, buttons and switchesFigure 7 – Thermostat display, buttons and switches
Figure 7 – Thermostat display, buttons and switches
Figure 7 – Thermostat display, buttons and switchesFigure 7 – Thermostat display, buttons and switches
Displays "
14
activated. Limited range limits the temperature the
thermostat can be set to.
Indicates the system is sending a fault signal to the
15
thermostat "L" terminal. This does not indicate a fault
in the thermostat.
Antenna will display for a few seconds when the remote
16
or outdoor transmitted signal is received.
LRLR
LR" when the limited range feature is
LRLR
18
1311
8
9
10
Stage 1 & 2 indicator.
13
STG 1STG 1
"
STG 1" indicates when the first stage heat or cool is
STG 1STG 1
energized. "
heat or cool is energized. "+2" blinking indicates
Auxiliary Heat stages are energized on Heat Pump
Systems.
STG + 2STG + 2
STG + 2" indicates when the second stage
STG + 2STG + 2
4
Displays "LOW BATT" when the 2 "AA" batteries are
17
low and should be replaced.
Indicates the current signal strength level of the remote
18
temperature system. Signal strength level is low (one
bar on), medium (two bars on) or high (three bars on).
The remote will operate with 1 bar showing.
The Sensor Buttons and DisplayThe Sensor Buttons and Display
The Sensor Buttons and Display
The Sensor Buttons and DisplayThe Sensor Buttons and Display
Raises the setting.
1
Lowers the setting.
2
Sensed temperature from –40 to 140°F with °F and °C
3
indicator
Channel identification A B C O indicator
4
9 bar comfort adjust graph with H (hotter) and C (cooler)
5
Transmission occurrence indicator
6
Keypad lockout indicator
7
Calibrate temperature offset indicator
8
Learn mode activated indicator
9
Low battery indicator
10
Temperature offset used when hold time is active
11
Figure 8 – Remote Sensor display and buttonsFigure 8 – Remote Sensor display and buttons
Figure 8 – Remote Sensor display and buttons
Figure 8 – Remote Sensor display and buttonsFigure 8 – Remote Sensor display and buttons
Normal OperationNormal Operation
Normal Operation
Normal OperationNormal Operation
3
o
6
A
Configuration ItemsConfiguration Items
Configuration Items
Configuration ItemsConfiguration Items
1
2
4
5
Alternates PWR and on to indicate normal operation
12
with display turned OFF
6
PWR HLD
12
11
3
BATT
10
o
LOCK
ABCO
CALIB
LEARN
9
H
C
5
7
4
8
5
5
5
Page 6
THERMOSTTHERMOST
THERMOST
THERMOSTTHERMOST
Press the System button until
PressPress
Press
PressPress
StepStep
Step
StepStep
Button(s)Button(s)
Button(s)
Button(s)Button(s)
AA
T CONFIGURAT CONFIGURA
A
T CONFIGURA
AA
T CONFIGURAT CONFIGURA
INSTALLER/CONFIGURATION MENUINSTALLER/CONFIGURATION MENU
INSTALLER/CONFIGURATION MENU
INSTALLER/CONFIGURATION MENUINSTALLER/CONFIGURATION MENU
DisplayedDisplayed
Displayed
DisplayedDisplayed
(Factory Default)(Factory Default)
(Factory Default)
(Factory Default)(Factory Default)
TION MENUTION MENU
TION MENU
TION MENUTION MENU
OFF OFF
OFF is displayed, then press the and simultaneously
OFF OFF
Press Press
Press
Press Press
or or
or
or or
to selectto select
to select
to selectto select
CommentsComments
Comments
CommentsComments
10
11
12
13
14
15
16
17
18
19
20
21
1
2
3
4
5
6
7
8
9
SystemSystem
System
SystemSystem
SystemSystem
System
SystemSystem
SystemSystem
System
SystemSystem
SystemSystem
System
SystemSystem
SystemSystem
System
SystemSystem
SystemSystem
System
SystemSystem
SystemSystem
System
SystemSystem
SystemSystem
System
SystemSystem
SystemSystem
System
SystemSystem
SystemSystem
System
SystemSystem
SystemSystem
System
SystemSystem
SystemSystem
System
SystemSystem
SystemSystem
System
SystemSystem
SystemSystem
System
SystemSystem
SystemSystem
System
SystemSystem
SystemSystem
System
SystemSystem
SystemSystem
System
SystemSystem
SystemSystem
System
SystemSystem
SystemSystem
System
SystemSystem
SystemSystem
System
SystemSystem
RunRun
RunReturns to the OFF mode
RunRun
CR HEAT COOL CR HEAT COOL
CR HEAT COOL
CR HEAT COOL CR HEAT COOL
FA HEAT COOL FA HEAT COOL
FA HEAT COOL
FA HEAT COOL FA HEAT COOL
(Room Temperature)(Room Temperature)
(Room Temperature)
(Room Temperature)(Room Temperature)
MS2MS2
MS2
MS2MS2
LER (OFF)LER (OFF)
LER (OFF)
LER (OFF)LER (OFF)
OUTSIDE OUTSIDE
OUTSIDE
OUTSIDE OUTSIDE
REMOTE REMOTE
REMOTE
REMOTE REMOTE
LOCAL LOCAL
LOCAL
LOCAL LOCAL
CH CH
CH
CH CH
PRG 4PRG 4
PRG 4
PRG 4PRG 4
EMR EMR
(ON)(ON)
EMR
(ON)
EMR EMR
(ON)(ON)
CL CL
(OFF)(OFF)
CL
(OFF)
CL CL
(OFF)(OFF)
CdL CdL
(ON)(ON)
CdL
(ON)
CdL CdL
(ON)(ON)
0 FLTR0 FLTR
0 FLTR
0 FLTR0 FLTR
0 F0 F
0 F
0 F0 F
4:00 HOLD4:00 HOLD
4:00 HOLD
4:00 HOLD4:00 HOLD
FF
F
FF
LR HEAT LR HEAT
LR HEAT
LR HEAT LR HEAT
LR COOL LR COOL
LR COOL
LR COOL LR COOL
CA CA
(OFF)(OFF)
CA
(OFF)
CA CA
(OFF)(OFF)
OFF LOCKOFF LOCK
OFF LOCK
OFF LOCKOFF LOCK
0 00 LOCK0 00 LOCK
0 00 LOCK
0 00 LOCK0 00 LOCK
(OFF)(OFF)
(OFF)
(OFF)(OFF)
(OFF)(OFF)
(OFF)
(OFF)(OFF)
(ON)(ON)
(ON)
(ON)(ON)
(0)(0)
(0)
(0)(0)
(90)(90)
(90)
(90)(90)
(45)(45)
(45)
(45)(45)
SS1, HP2, HP1SS1, HP2, HP1
SS1, HP2, HP1Selects Single stage, Multi-stage, or Heat Pump
SS1, HP2, HP1SS1, HP2, HP1
LER (ON)LER (ON)
LER (ON)Selects learn mode OFF or ON
LER (ON)LER (ON)
OUTSIDE OUTSIDE
OUTSIDE
OUTSIDE OUTSIDE
REMOTE REMOTE
REMOTE
REMOTE REMOTE
LOCAL LOCAL
LOCAL
LOCAL LOCAL
PRG 0, PRG 2PRG 0, PRG 2
PRG 0, PRG 2Selects Programmable Periods
PRG 0, PRG 2PRG 0, PRG 2
EMR EMR
EMR
EMR EMR
(FA)(FA)
(FA)
(FA)(FA)
(ON)(ON)
(ON)
(ON)(ON)
FA HEAT COOL FA HEAT COOL
FA HEAT COOL
FA HEAT COOL FA HEAT COOL
0–19500–1950
0–1950
0–19500–1950
4 LO to 4 HI4 LO to 4 HI
4 LO to 4 HISelects Temperature Display Adjustment 4 LO 4 HI
4 LO to 4 HI4 LO to 4 HI
0:00 to 8:000:00 to 8:00
0:00 to 8:00Selects Temporary Program Override Time
0:00 to 8:000:00 to 8:00
(Increments of 15 minutes)(Increments of 15 minutes)
(Increments of 15 minutes)0:00 =Disabled
(Increments of 15 minutes)(Increments of 15 minutes)
LR 62 to LR 89LR 62 to LR 89
LR 62 to LR 89Selects Limited HEAT range
LR 62 to LR 89LR 62 to LR 89
LR 46 to LR 82LR 46 to LR 82
LR 46 to LR 82Selects Limited COOL range
LR 46 to LR 82LR 46 to LR 82
(ON)(ON)
(ON)Selects OUTSIDE sensor OFF or ON
(ON)(ON)
(ON)(ON)
(ON)Selects REMOTE (indoor) sensor OFF or ON
(ON)(ON)
(OFF)(OFF)
(OF F)Selects LOCAL sensor ON or OFF
(OFF)(OFF)
1 to 91 to 9
1 to 9Select Receiver frequency offset
1 to 91 to 9
(OFF)(OFF)
(OFF)Selects Energy Management Recovery OFF or ON
(OFF)(OFF)
SLSL
SLSelects Fast or Slow cycle selection
SLSL
CL CL
(ON)(ON)
CL
(ON)Selects Compressor Lockout CL OFF or ON
CL CL
(ON)(ON)
CdL CdL
(OFF)(OFF)
CdL
(OF F )Selects Backlight Display ON or OFF
CdL CdL
(OFF)(OFF)
(OFF)(OFF)
(OF F )Selects Fast Second Stage ON or OFF
(OFF)(OFF)
(increments of 50)(increments of 50)
(increments of 50)Selects filter replacement run time.0 =Disabled
(increments of 50)(increments of 50)
CC
CFor C selection
CC
CA CA
(ON)(ON)
CA
(ON)Selects Comfort Alert Lock
CA CA
(ON)(ON)
ON LOCKON LOCK
ON LOCKSelects Buttonpad Lockout
ON LOCKON LOCK
001 to 999001 to 999
001 to 999Selects Buttonpad lockout combination number
001 to 999001 to 999
(Single stage or 2-stage) system configuration
Selects temperature display as F° or C°
Press System to set code
The configuration menu allows you to set certain thermostat
operating characteristics to your system or personal requirements.
Set SYSTEM button to
OFFOFF
OFF, then simultaneously press
OFFOFF
and to enter configuration menu. The display will
show the first item in the configuration menu.
The configuration menu table summarizes the configuration
options. An explanation of each option follows.
Press SYSTEM to change to the next menu item. To exit the
menu and return to the program operation, press RUN. If no
keys are pressed within fifteen minutes, the thermostat will
revert to normal operation.
Single Stage, Multi-stage or Heat Pump ConfigurationSingle Stage, Multi-stage or Heat Pump Configuration
1)
Single Stage, Multi-stage or Heat Pump Configuration
Single Stage, Multi-stage or Heat Pump ConfigurationSingle Stage, Multi-stage or Heat Pump Configuration
This menu item requires you configure the thermostat to
match your system. Choose your system option from the
table below:
System TypeSystem Type
System Type
System TypeSystem Type
Single Stage Heat/Cool systemsSS1
Multi-Stage Heat/Cool systems (No Heat Pump)MS2
Heat Pump system, 1 compressor or 1 speed compressorHP1
Heat Pump systems, 2 compressors or 2 speed compressorHP2
Select OptionSelect Option
Select Option
Select OptionSelect Option
The thermostat is factory defaulted to MS2. To select a
different option, press the or key to scroll through
the choices.
6
Select Learn Mode On or OffSelect Learn Mode On or Off
2)
Select Learn Mode On or Off – Selecting
Select Learn Mode On or OffSelect Learn Mode On or Off
LER OnLER On
LER On
LER OnLER On
enables the learn mode of the thermostat receiver. Your
thermostat is configured at the factory to recognize the
remote sensor shipped with it. The Learn Mode Option is
used only when required as described in
OptionOption
Option.
OptionOption
Selects OUTSIDE sensor OFF or ONSelects OUTSIDE sensor OFF or ON
3)
Selects OUTSIDE sensor OFF or ON – Selec ting
Selects OUTSIDE sensor OFF or ONSelects OUTSIDE sensor OFF or ON
Learn ModeLearn Mode
Learn Mode
Learn ModeLearn Mode
OUTSIDE ON enables the thermostat to read a wireless
outdoor temperature sensor that has been configured for
Sensor O in the Learn Mode. This allows the thermostat
to display the outdoor temperature reading.
Selects REMOTE sensor OFF or ON Selects REMOTE sensor OFF or ON
4)
Selects REMOTE sensor OFF or ON – Selecting
Selects REMOTE sensor OFF or ON Selects REMOTE sensor OFF or ON
REMOTE ON allows the thermostat to sense an indoor
remote sensor that has been set-up the Learn mode. The
maximum number of Indoor Remote Sensors is 1
configured to sensor A, B or C.
Selects LOCAL sensor ON or OFF Selects LOCAL sensor ON or OFF
5)
Selects LOCAL sensor ON or OFF – Selecting LOCAL
Selects LOCAL sensor ON or OFF Selects LOCAL sensor ON or OFF
ON allows the thermostat to use the onboard temperature
sensor exclusively or for averaging with the remote
sensor readings. To control temperature using only the
indoor remote sensor temperature(s), use the
buttons to select
Select Receiver frequency offsetSelect Receiver frequency offset
6)
Select Receiver frequency offset – This option allows
Select Receiver frequency offsetSelect Receiver frequency offset
LOCAL OFFLOCAL OFF
LOCAL OFF.
LOCAL OFFLOCAL OFF
or
you to select a different channel than the factory default
for communication between the thermostat and remote
sensor. Note: If a different channel is selected on the
thermostat it must also be changed to the same
Page 7
THERMOSTTHERMOST
THERMOST
THERMOSTTHERMOST
setting on the remote. This is only used in areas where
there are other wireless devices or electronic equipment
that interfere with the default frequency of the thermostat/
remote sensor communication.
Programmable Periods Programmable Periods
7)
Programmable Periods – This control can be config-
Programmable Periods Programmable Periods
ured for 4, 2 or 0 programmable periods. The display
indicates "
mable periods can be changed to 2 or 0 by pressing the
or keys. With "
mable, SYSTEM key selection will skip
temporary program override (item 15).
Select Energy Management Recovery OFF or ONSelect Energy Management Recovery OFF or ON
8)
Select Energy Management Recovery OFF or ON –
Select Energy Management Recovery OFF or ONSelect Energy Management Recovery OFF or ON
Energy Management Recovery (EMR) causes the
thermostat to start heating or cooling early to make the
building temperature reach the program setpoint at the
time you specify. Heating will start 5 minutes early for
every 1° of temperature required to reach setpoint.
Example:Example:
Example: You select EMR and have your heating
Example:Example:
programmed to 65° at night and 70° at 7 AM. If the
building temperature is 65° the difference between 65°
and 70° is 5°. Allowing 5 minutes per degree the thermostat setpoint will change to 70° at 6:35 AM. Cooling allows
more time per degree because it takes longer to reach
temperature.
Fast or Slow Cycle SelectionFast or Slow Cycle Selection
9)
Fast or Slow Cycle Selection – The factory default
Fast or Slow Cycle SelectionFast or Slow Cycle Selection
setting is fast cycle, which cycles 1st stage at approximately 1.2°F and 2nd stage 0.75°F. If you prefer slow
cycle, press the temperature key to change to SL. The 1st
stage and 2nd stage would be 1.5°F and 1.2°F respectively.
Select Compressor Lockout CL OFF or ONSelect Compressor Lockout CL OFF or ON
10)
Select Compressor Lockout CL OFF or ON – Selecting
Select Compressor Lockout CL OFF or ONSelect Compressor Lockout CL OFF or ON
CL ON will cause the thermostat to wait 5 minutes before
turning on the compressor if the heating and cooling
system loses power. It will also wait 5 minutes minimum
between cooling and heating cycles. This is intended to
help protect the compressor from short cycling. Some
newer compressors already have a time delay built in and
do not require this feature. Your compressor manufacturer can tell you if the lockout feature is already present
in their system. When the thermostat compressor time
delay occurs it will flash the setpoint for about five
minutes.
Select Backlight DisplaySelect Backlight Display
11)
Select Backlight Display – The display backlight
Select Backlight DisplaySelect Backlight Display
improves display contrast in low lighting conditions. When
the "C" terminal is powered, selecting backlight CdL ON
will keep the light on continuously. Select backlight OFF
will keep the light on momentarily after any key is
pressed. When the "C" terminal is not powered, the light
will be on momentarily after any key is pressed no matter
the backlight is selected ON or OFF.
Select Fast Second Stage On or OFFSelect Fast Second Stage On or OFF
12)
Select Fast Second Stage On or OFF –
Select Fast Second Stage On or OFFSelect Fast Second Stage On or OFF
During normal operation if the setpoint temperature is
manually raised by 3°F or more above the actual temperature with the
feature is enabled, FA ON, the second stage will energize
immediately.
For Cool: During normal operation if the setpoint temperature is manually lowered by 3°F or more below the actual
temperature with the
feature is enabled, FA ON, the second stage will energize
immediately.
Select filter replacement run timeSelect filter replacement run time
13)
Select filter replacement run time – The thermostat will
Select filter replacement run timeSelect filter replacement run time
display "
reminder to change or clean your air filter. This time can
be set from 0 to 1950 hours in 50 hour increments.
selection of 0 will cancel this featureselection of 0 will cancel this feature
selection of 0 will cancel this feature. When "
selection of 0 will cancel this featureselection of 0 will cancel this feature
displayed, you can clear it by pressing HOLD and RUN at
the same time. This resets the timer and starts counting
the hours until the next filter change. Contact your system
manufacturer for a specific replacement/maintenance
interval.
Select Temperature Display Adjustment 4 LO to 4 HISelect Temperature Display Adjustment 4 LO to 4 HI
14)
Select Temperature Display Adjustment 4 LO to 4 HI –
Select Temperature Display Adjustment 4 LO to 4 HISelect Temperature Display Adjustment 4 LO to 4 HI
Allows you to adjust the room temperature display up to
FLTRFLTR
FLTR"
FLTRFLTR
AA
T CONFIGURAT CONFIGURA
A
T CONFIGURA
AA
T CONFIGURAT CONFIGURA
PRG 4PRG 4
PRG 4" in the display as default. The program-
PRG 4PRG 4
PRG 0PRG 0
PRG 0" selected for non-program-
PRG 0PRG 0
button, and the fast second stage
button, and the fast second stage
after a set time of operation. This is a
TION MENUTION MENU
TION MENU
TION MENUTION MENU
EMREMR
EMR (item 8) and
EMREMR
For HeatFor Heat
For Heat:
For HeatFor Heat
FLTRFLTR
FLTR"
FLTRFLTR
4° higher or lower. Your thermostat was accurately
calibrated at the factory but you have the option to
change the display temperature to match your previous
thermostat. The current or adjusted room temperature will
be displayed on the left side of the display.
Select Temporary Program Override TimeSelect Temporary Program Override Time
15)
Select Temporary Program Override Time – The thermo-
Select Temporary Program Override TimeSelect Temporary Program Override Time
stat can hold any temperature you set it to for the amount
of time you select on this option. Your choices are 0:00 to
8:00 hours in 15 minute increments. 0:00 means disable.
Example:
1. You have selected 3:00 hours for the Temporary Program Override time period.
2. With the thermostat set to Heat or Cool, press HOLD
for approximately 5 secondsfor approximately 5 seconds
for approximately 5 seconds until "
for approximately 5 secondsfor approximately 5 seconds
(indicating 3 hours) appears as a setting reminder.
3. After releasing the button, "
blink.
4. Use
Select F° or C° ReadoutSelect F° or C° Readout
16)
Select F° or C° Readout – Changes the display readout
Select F° or C° ReadoutSelect F° or C° Readout
to Celsius or Fahrenheit as required.
Limited Heat RangeLimited Heat Range
17)
Limited Heat Range – This feature provides a maximum
Limited Heat RangeLimited Heat Range
setpoint temperature for heat. The default setting is 90°F. It
can be changed between 62°F and 89°F by pressing the
or key.
Limited Cool RangeLimited Cool Range
18)
Limited Cool Range – This feature provides a minimum
Limited Cool RangeLimited Cool Range
setpoint temperature for cool. The default setting is 45°F. It
can be changed between 46°F and 82°F by pressing the
or key.
Comfort Alert Comfort Alert
19)
Comfort Alert – This feature is available in Passive
Comfort Alert Comfort Alert
mode on this thermostat. If a Comfort Alert module is
connected, the thermostat will receive and flash the fault
codes from the Comfort Alert module.
20 & 21)
display
the function and display the
not locked out, default) indicating in the time digits to the
lock lock
lock icon and
lock lock
lockout function is enabled (
is pressed again, the display will indicate the number
(default, still disabled) in the time digits. The
are used to set the combination number from
a combination of
is pressed, the menu will be exited and keypad will not be
locked. If
pressed again, the combination is locked into non-volatile
memory and the menu is exited. The
designate keypad locked with a valid combination) will
display when the menu is exited. The SYSTEM button will
operate for 10 seconds after the menu mode is exited to
allow the user to change the mode from
desired system mode.
While the keypad is locked out, a simultaneous press of
and will enter the menu item from any mode
instead of only
with the keypad lockout feature enabled, the
item displayed is the combination code
keys are used to set the combination unlock number from
00
0 to
00
AA
A
AA
is
combination lock number stored in memory when the
SYSTEM button is pressed, the keypad is unlocked and
the
match when the SYSTEM
exited and the keypad remains disabled.
To reset the combination code and unlock the keypad if
the code is forgotten, see troubleshooting section, page
16.
or to set the temperature to your prefer
ence. The thermostat will maintain this temperature
setting for 3 hours with "
it is in Temporary Hold. After 3 hours, the thermostat
will go back to the program temperature and "
will no longer blink or display.
Keypad LockoutKeypad Lockout
Keypad Lockout – This menu selection will
Keypad LockoutKeypad Lockout
lock lock
) icon. The and are used to toggle
lock (
lock lock
ON ON
ON (keypad locked out). When the keypad
ON ON
000000
00 0 is selected and the SYSTEM button
000000
1 to 9991 to 999
1 to 999 is selected and the SYSTEM button is
1 to 9991 to 999
OFF OFF
OFF mode. When the menu is entered
OFF OFF
999999
99 9. If the unlock number matches exactly with the
999999
lock lock
lock icon is removed. If the unlock number does not
lock lock
HOLDHOLD
HOLD"
HOLDHOLD
HOLDHOLD
HOLD"
HOLDHOLD
lock lock
lock icon and
lock lock
ONON
ON), and the SYSTEM button
ONON
button is pressed, menu is
HOLD time 3:00HOLD time 3:00
HOLD time 3:00"
HOLD time 3:00HOLD time 3:00
on the display will
blinking to remind you
HOLDHOLD
HOLD"
HOLDHOLD
OFF OFF
OFF (keypad
OFF OFF
000000
000
000000
and
00
999999
0 to
999. If
00
999999
lock lock
lock icon (to
lock lock
OFF OFF
OFF to the
OFF OFF
first menu
00
0. The
00
or
7
Page 8
REMOREMO
REMO
REMOREMO
The configuration menus allow you to set certain remote sensor operating characteristics to your system or personal requirements. Two configuration menus are available, User Configuration and Installer Configuration.
User Configuration MenuUser Configuration Menu
User Configuration Menu
User Configuration MenuUser Configuration Menu
Momentarily press and keys at the same time and release to enter the User menu. To scroll through the menu
items press the
scroll through all menu items. If no buttons are pushed for 3 minutes, the control will also return to normal operation.
The User Configuration Menu table summarizes the configuration options. An explanation of each option follows.
StepStep
Step
StepStep
1
2 and
3
4
5 and dLOFSelect display backlight OFF or ON
6
7
TE SENSOR CONFIGURATE SENSOR CONFIGURA
TE SENSOR CONFIGURA
TE SENSOR CONFIGURATE SENSOR CONFIGURA
and keys at the same time. To change the item option press or . To exit the menu
Press button(s)Press button(s)
Press button(s)
Press button(s)Press button(s)
to scroll menuto scroll menu
to scroll menu
to scroll menuto scroll menu
and
and
and d
and
and __________Exits user menu and returns to normal
HLDHLD
(4h)in 1 hour incrementshold time
CALIBCALIB
CALIB1-4 bars (1°-4°) C toSelect temperature display adjustment
CALIBCALIB
(Sensed Temperature)1-4 bars (1°-4°) Hhigher or lower
F
(on)
(on)
o
F
(Sensed Temperature)
TION MENUTION MENU
TION MENU
TION MENUTION MENU
User configuration menuUser configuration menu
User configuration menu
User configuration menuUser configuration menu
Press Press
Press
Press Press
to change optionto change option
to change option
to change optionto change option
OFSelect display temperature OFF or ON
o
CSelect temperature display to F or C
or or
or
or or
Comments Comments
Comments
Comments Comments
operation
Select keypad lockout OFF or ONSelect keypad lockout OFF or ON
1)
Select keypad lockout OFF or ON – Selecting
Select keypad lockout OFF or ONSelect keypad lockout OFF or ON
ON ON
ON will cause the keypad to be locked in the normal
ON ON
operation mode. This prevents the and from
being used to adjust temperature. The display will
indicate "
is selected, the
When the keypad is locked, the and keys can
still be pressed at the same time to enter the configuration menu.
Select temporary adjust temperature hold time Select temporary adjust temperature hold time
2)
Select temporary adjust temperature hold time –
Select temporary adjust temperature hold time Select temporary adjust temperature hold time
Selects the length of time for the temporary temperature
adjustment. Hold time default is 4 hours and can be set
from 1 to 8 hours in 1 hour increments.
Select temperature display adjustment higher orSelect temperature display adjustment higher or
3)
Select temperature display adjustment higher or
Select temperature display adjustment higher orSelect temperature display adjustment higher or
lowerlower
lower – allows you to adjust the room temperature
lowerlower
display 1° to 4° higher or lower. Your sensor was accurately calibrated at the factory but you have the option to
LOCKLOCK
LOCK" when the keypad is locked. If
LOCKLOCK
and keys can still be used.
LOCKLOCK
LOCK
LOCKLOCK
LOCK OFLOCK OF
LOCK OF
LOCK OFLOCK OF
change the display temperature to match your previous
sensor or thermostat.
Select display temperature OFF or ONSelect display temperature OFF or ON
4)
Select display temperature OFF or ON – Selecting
Select display temperature OFF or ONSelect display temperature OFF or ON
allows you to disable displaying the sensed temperature.
Instead of the temperature, the sensor will display "
with the word
Select display backlight OFF or ONSelect display backlight OFF or ON
5)
Select display backlight OFF or ON -. The display
Select display backlight OFF or ONSelect display backlight OFF or ON
backlight improves display contrast in low lighting
conditions. Selecting
short period of time after any key is pressed. Selecting
OF OF
OF will keep the light off.
OF OF
Select temperature display to Select temperature display to
6)
Select temperature display to
Select temperature display to Select temperature display to
display readout to Celsius or Fahrenheit as required.
onon
on to indicate normal operation.
onon
dL ondL on
dL on will keep the light on for a
dL ondL on
oo
oo
o
o
oo
oo
F or F or
CC
F or
C - Changes the
F or F or
CC
OFOF
OF
OFOF
PWRPWR
PWR"
PWRPWR
8
Page 9
REMOREMO
REMO
REMOREMO
Installer Configuration MenuInstaller Configuration Menu
Installer Configuration Menu
Installer Configuration MenuInstaller Configuration Menu
Your thermostat is configured at the factory to recognize the remote sensor it is shipped with as indoor sensor A. The Installer
Configuration Menu is used only when adding or replacing a remote sensor or selecting a frequency offset.
Press
the menu items, momentarily press the
operation. The Installer Configuration Menu table summarizes the configuration options. An explanation of each option
follows.
StepStep
Step
StepStep
1
2
3
4 and __________Exit installer menu and return to normal
TE SENSOR CONFIGURATE SENSOR CONFIGURA
TE SENSOR CONFIGURA
TE SENSOR CONFIGURATE SENSOR CONFIGURA
and buttons for a minimum of five seconds at the same time to enter the Installer menu. To scroll through
and buttons at the same time. To change the item option, press or
. To exit the menu scroll through all menu items. If no buttons are pushed for 3 minutes, the control will return to normal
Installer Configuration MenuInstaller Configuration Menu
Installer Configuration Menu
Installer Configuration MenuInstaller Configuration Menu
CHB, C, OSelect sensor identification as A, B, C or O
CHCH
(A)
CC
C1 through 9Select transmitter frequency offset
CC
(0)
TION MENUTION MENU
TION MENU
TION MENUTION MENU
Press Press
Press
Press Press
to change optionsto change options
to change options
to change optionsto change options
operation
or or
or
or or
Comments Comments
Comments
Comments Comments
Select learn mode OFF or ONSelect learn mode OFF or ON
1)
Select learn mode OFF or ON – Selecting
Select learn mode OFF or ONSelect learn mode OFF or ON
enables the sensors learning mode. In the learning mode
the sensor will transmit identification information once
every 10 seconds for a period of 10 minutes. The LEARN
icon will be displayed during the learning mode. The
transmitter icon will be displayed for a short period of time
with each transmission. See Learn Mode Option.
Select sensor identification from A to OSelect sensor identification from A to O
2)
Select sensor identification from A to O – For multiple
Select sensor identification from A to OSelect sensor identification from A to O
sensors systems, each sensor must have a designated
identification. The thermostat can operate with one indoor
sensor and one outdoor sensor. For indoor sensors you
may select A, B or C. For outdoor sensor you must select
O.
OPERATING YOUR THERMOSTAT AND REMOTE SENSOROPERATING YOUR THERMOSTAT AND REMOTE SENSOR
OPERATING YOUR THERMOSTAT AND REMOTE SENSOR
OPERATING YOUR THERMOSTAT AND REMOTE SENSOROPERATING YOUR THERMOSTAT AND REMOTE SENSOR
To prevent static discharge problems, touch side ofTo prevent static discharge problems, touch side of
To prevent static discharge problems, touch side of
To prevent static discharge problems, touch side ofTo prevent static discharge problems, touch side of
thermostat to release static build-up before touchingthermostat to release static build-up before touching
thermostat to release static build-up before touching
thermostat to release static build-up before touchingthermostat to release static build-up before touching
any keys.any keys.
any keys.
any keys.any keys.
If at any time during testing your system does not operate
properly, contact a qualified service person.
Fan OperationFan Operation
Fan Operation
Fan OperationFan Operation
If your system does not have a
Heating SystemHeating System
Heating System.
Heating SystemHeating System
1. Turn on power to system.
2. Move FAN switch to
begin to operate.
3. Move FAN switch to
stop immediately.
ON ON
ON position. The blower should
ON ON
AUTO AUTO
AUTO position. The blower should
AUTO AUTO
G G
G terminal connection, skip to
G G
LEARN onLEARN on
LEARN on
LEARN onLEARN on
Select transmitter frequency offsetSelect transmitter frequency offset
3)
Select transmitter frequency offset – The sensor’s
Select transmitter frequency offsetSelect transmitter frequency offset
transmitter operates on 418MHz radio frequency by
default. Interference may occur if another device or
equipment operates on the same frequency. The interference may degrade the communications between the
sensor and the thermostat. To avoid interference, you
may select a different radio frequency for your sensor.
This menu item allows you to select a radio frequency
offset from 1 to 9MHz from the base frequency. For
example; if the you selected an offset of 4, the transmitter
radio frequency will be 418MHz + 4MHz = 422MHz. Note
that the sensor’s transmitter and the thermostat’s receiver
must operate on the same frequency to communicate. To
change thermostat’s receiver frequency please refer to
Thermostat Configuration Menu.
Heating SystemHeating System
Heating System
Heating SystemHeating System
1. Press SYSTEM button to select
heating system has a standing pilot, be sure to light it.
2. Press
temperature. The heat pump system should begin to
operate. The display should show "
system configuration is set to HP1 or HP2 and setpoint
temperature display is flashing, the 5 minute compressor
lockout feature is operating (see Configuration menu,
item 10).
3. Adjust temperature setting to 3° above room temperature.
If your system configuration is set at MS2, HP2 or HP1,
the auxiliary heat system should begin to operate and
the display will show "
4. Press
ture. The heating system should stop operating.
to adjust thermostat setting to 1° above room
STG 1+2STG 1+2
STG 1+2".
STG 1+2STG 1+2
to adjust the thermostat below room tempera-
HEATHEAT
HEAT. If the auxiliary
HEATHEAT
STG1STG1
STG1". However, if the
STG1STG1
CAUTION
!
Do not allow the compressor to run unless the compres-Do not allow the compressor to run unless the compres-
Do not allow the compressor to run unless the compres-
Do not allow the compressor to run unless the compres-Do not allow the compressor to run unless the compressor oil heaters have been operational for 6 hours andsor oil heaters have been operational for 6 hours and
sor oil heaters have been operational for 6 hours and
sor oil heaters have been operational for 6 hours andsor oil heaters have been operational for 6 hours and
the system has not been operational for at least 5the system has not been operational for at least 5
the system has not been operational for at least 5
the system has not been operational for at least 5the system has not been operational for at least 5
minutes.minutes.
minutes.
minutes.minutes.
9
Page 10
OPERATING YOUR THERMOSTAT AND REMOTE SENSOROPERATING YOUR THERMOSTAT AND REMOTE SENSOR
OPERATING YOUR THERMOSTAT AND REMOTE SENSOR
OPERATING YOUR THERMOSTAT AND REMOTE SENSOROPERATING YOUR THERMOSTAT AND REMOTE SENSOR
Emergency SystemEmergency System
Emergency System
Emergency SystemEmergency System
EMER EMER
EMER bypasses the Heat Pump to use the heat source wired
EMER EMER
to terminal
when compressor operation is not desired, or you prefer
back-up heat only.
1. Press SYSTEM button to select
on the display.
2. Press
temperature. The Emergency heating system will begin to
operate. The display will show "
and "
operating.
3. Press
ture. The Emergency heating system should stop operating.
To prevent compressor and/or property damage, if theTo prevent compressor and/or property damage, if the
To prevent compressor and/or property damage, if the
To prevent compressor and/or property damage, if theTo prevent compressor and/or property damage, if the
outdoor temperature is below 50°F, DO NOT operateoutdoor temperature is below 50°F, DO NOT operate
outdoor temperature is below 50°F, DO NOT operate
outdoor temperature is below 50°F, DO NOT operateoutdoor temperature is below 50°F, DO NOT operate
the cooling system.the cooling system.
the cooling system.
the cooling system.the cooling system.
1. Press SYSTEM button to select
2. Press
temperature. The blower should come on immediately on
high speed, followed by cold air circulation. The display
should show "
is flashing, the compressor lockout feature is operating
(see Configuration menu, item 5).
3. Adjust temperature setting to 3° below room temperature.
The second stage cooling should begin to operate and
the display should show "
4. Press
temperature. The cooling system should stop operating.
During normal operation, the upper left of the thermostat
display changes every 6 seconds to show the temperatures
at the sensors that are turned on in the configuration menu.
The sensors are the thermostat (
remote sensor (
REMOTEREMOTE
(
REMOTE). Below that, the display alternately shows the
REMOTEREMOTE
time and temperature average of the sensors that are turned
on.
The word "
3) indicating the relative signal strength. More bars mean
better reception. The
seconds when information from the remote sensor is
received.
If the thermostat does not receive an update signal from an
enabled remote sensor (REMOTE or OUTDOOR) for 30
minutes or more, the thermostat will display FAULT and
ANTENNA icons continuously. The REMOTE or OUTDOOR
sensor that has communication with the thermostat interrupted will display a temperature of 00. If the active sensor is
the REMOTE, the thermostat will revert back to LOCAL
sense only mode.
E/W1 E/W1
E/W1 on the thermostat.
E/W1 E/W1
to adjust thermostat setting above room
HEATHEAT
HEAT" to indicate that the Emergency system is
HEATHEAT
to adjust the thermostat below room tempera-
CAUTION
!
Cooling SystemCooling System
Cooling System
Cooling SystemCooling System
to adjust thermostat setting below room
STG1STG1
STG1". If the setpoint temperature display
STG1STG1
STG 1+2STG 1+2
STG 1+2".
STG 1+2STG 1+2
to adjust the temperature setting above room
Remote Temperature Sensor InformationRemote Temperature Sensor Information
Remote Temperature Sensor Information
Remote Temperature Sensor InformationRemote Temperature Sensor Information
on the Thermostat Displayon the Thermostat Display
on the Thermostat Display
on the Thermostat Displayon the Thermostat Display
OUTDOOROUTDOOR
OUTDOOR) and the indoor remote sensor
OUTDOOROUTDOOR
SIGNALSIGNAL
SIGNAL"
SIGNALSIGNAL
is shown along with number of bars (1-
antenna antenna
antenna icon also displays for few
antenna antenna
EMER EMER
EMER is typically used
EMER EMER
EMEREMER
EMER. "
EMEREMER
STG1STG1
STG1" flashing "
STG1STG1
COOLCOOL
COOL.
COOLCOOL
LOCALLOCAL
LOCAL), the outdoor
LOCALLOCAL
EMEREMER
EMER" will flash
EMEREMER
EMEREMER
EMER"
EMEREMER
Automatic System ChangeoverAutomatic System Changeover
Automatic System Changeover
Automatic System ChangeoverAutomatic System Changeover
When the thermostat is in the
will call for heat or cool depending on the room temperature.
The setpoint temperature displayed will be the last mode
called. If the last system cycle was heat, the
will be displayed. If the room temperature raises above the
HEAT HEAT
HEAT setpoint and the
HEAT HEAT
required, the temperature displayed will change to be the
COOL COOL
COOL setpoint.
COOL COOL
If you manually override the temperature in
does not switch to the mode (
press the
modes. At the end of your override time it will revert back to
AUTO.
Your thermostat is designed to determine the optimum time
to activate the second stage. Simply raising the temperature
in heating or lowering it in cooling will not always force the
thermostat to bring the second stage on quickly. If the fast
second stage option in the configuration menu (step 12) is
set to "OFF", there is a delay from 0-30 minutes depending
on the performance of the first stage of the system.
EXAMPLE: For the last 2 hours the thermostat is set on 70°
and the room temperature is 70° with the equipment using
only the first stage of heat. Since the equipment is keeping
the temperature within 1 degree of setpoint, the thermostat
will delay second stage for a longer time if you manually
raise the temperature or if the room temperature quickly
changes. Once the second stage comes on, it will come on
sooner the next time there is a difference between the
setpoint and the room temperature. The net effect of the
staging program is that when the first stage is capable of
holding temperature, the second stage will delay longer.
When the thermostat calculates that first stage cannot make
temperature in a reasonable time, the second stage will
come on sooner. This built in function automatically optimizes the use of additional stages of heat or cool.
and keys once, at the same time to switch
Second Stage Time DelaySecond Stage Time Delay
Second Stage Time Delay
Second Stage Time DelaySecond Stage Time Delay
AUTO AUTO
AUTO mode, the thermostat
AUTO AUTO
HEAT HEAT
HEAT setpoint
HEAT HEAT
COOL COOL
COOL setpoint and a call for cool is
COOL COOL
AUTO AUTO
AUTO and it
AUTO AUTO
HEAT HEAT
HEAT or
HEAT HEAT
COOLCOOL
COOL) that you want,
COOLCOOL
10
Page 11
OPERATING YOUR THERMOSTAT AND REMOTE SENSOROPERATING YOUR THERMOSTAT AND REMOTE SENSOR
OPERATING YOUR THERMOSTAT AND REMOTE SENSOR
OPERATING YOUR THERMOSTAT AND REMOTE SENSOROPERATING YOUR THERMOSTAT AND REMOTE SENSOR
Learn Mode OptionLearn Mode Option
Learn Mode Option
Your ther mosta t is configur ed at the factory to recognize the
wireless remote sensor shipped with it. This sensor is stored
as Sensor A. The Learn Mode Option must be performed on
the thermostat and wireless remote sensor if:
• A wireless remote sensor is added to another channel.
• The wireless remote sensor is replaced.
• The thermostat is replaced.
During the Learn Mode, the wireless remote sensor will
transmit identification information every ten seconds for ten
minutes. In this ten-minute period, the display will show
“LEARN” and the antenna icon will show for a short time with
each transmission. The thermostat will be receiving the
transmitted identification information.
To perform the Learn Mode on the thermostat and sensor:
Remove the batteries from all wireless remote sensors in
the same building except the sensor you are going to put
into the Learn Mode. This will prevent interference from
the other sensors.
Be sure that the remote sensor is set for the proper
identification (A, B or C for indoor or O for outdoor) and
the thermostat and remote sensor are set to the same
frequency.
On the thermostat, enter the thermostat Configuration
Menu by pressing the
momentarily pressing
Momentarily press
of the Configuration Menu. The display will show “
OFF”OFF”
and “
OFF”.
OFF”OFF”
Momentarily press
The display will flash “
stantly.
On the wireless remote sensor, enter the Installer
Configuration Menu by pressing
seconds. The remote sensor display will change to
LEARN OF”LEARN OF”
“
LEARN OF”.
LEARN OF”LEARN OF”
Momentarily press
After the thermostat has successfully identified the
remote sensor in approximately one minute, the sensor
information will be stored and the thermostat display will
change to “
If the identification sequence is not successful after ten
minutes, the thermostat display will show “
the antenna icon. If the Learn Mode is unsuccessful, refer to
Troubleshooting section, Antenna + Fault.
If you are replacing a thermostat that has more than one
wireless remote sensor, the Learn Mode must be performed
for each sensor. Once a sensor has been identified, it will
remain in the thermostat memory until the Learn Mode is
performed again and a different sensor for the stored
channel is identified.
Your thermostat is designed to sense the temperature of the
indoor remote sensor and average or weight it with the local
sensor in the thermostat for each program period. The
averaging will only be active when both the local and the
indoor remote sensors are functional and turned on in the
configuration menu. When the thermostat is placed in view
schedule mode (press PRGM once), the weight of the indoor
remote sensor will be shown on the left side of the display
when HOLD button is pressed. The weighting classes of the
indoor remote sensor are designated as A (default for
average weight), HI (high weight), or LO (low weight). The HI
weight is two times the weight of the average weight. The A
weight is two times the weight of the LO weight. The weight
of the local sensor is fixed to A (average weight). The actual
temperature displayed, in the clock digits, in the normal
operation mode is the mathematical weighted sum of the
enabled functioning sensors. For example, if the local sensed
temperature is 80°F and the remote sensed temperature is
Learn Mode OptionLearn Mode Option
SYSTEMSYSTEM
SYSTEM button to
SYSTEMSYSTEM
and at the same time.
SYSTEMSYSTEM
SYSTEM button to advance to step 2
SYSTEMSYSTEM
or to select “
LER”LER”
LER” with “
LER”LER”
or to select “
LER” LER”
LER” and “
LER” LER”
Wireless Remote IndoorWireless Remote Indoor
Wireless Remote Indoor
Wireless Remote IndoorWireless Remote Indoor
Temperature AveragingTemperature Averaging
Temperature Averaging
Temperature AveragingTemperature Averaging
OK”OK”
OK”.
OK”OK”
On”On”
On ” displayed con-
On”On”
OFFOFF
OFF and then
OFFOFF
LER”LER”
LER” and
LER”LER”
and for five
LEARN On”LEARN On”
LEARN On”.
LEARN On”LEARN On”
LER”,LER”,
LER”, “
LER”,LER”,
LER”LER”
LER”
LER”LER”
“On” “On”
“On”.
“On” “On”
Fault”Fault”
Fault” and
Fault”Fault”
70°F then:
If weight selected is HI , then the averaged temperature is
(2 x (80°F) + 4 x (70°F))/ 6 = 73.3°F.
If weight selected is A , then the averaged temperature is
(2 x (80°F) + 2 x (70°F))/ 4 = 75°F.
If weight selected is LO , then the averaged temperature is
(2 x (80°F) + 1 x (70°F))/ 3 = 76.6°F.
The example above shows that the weight selected would
prioritize the overall averaged temperature between the two
sensors. The high weight selection caused the remote
sensor to carry more weight in the calculated temperature
average than the local sensor. The low weight selection
caused the remote sensor to carry less weight in the calculated temperature average than the local sensor.
Choose the Fan Setting (Auto or On)Choose the Fan Setting (Auto or On)
Choose the Fan Setting (Auto or On)
Choose the Fan Setting (Auto or On)Choose the Fan Setting (Auto or On)
AA
uto uto
Set the FAN Switc h to
AA
uto uto
Fan
A
uto is the most commonly selected setting and runs
AA
uto uto
the fan only when the heating or cooling system is on.
OnOn
Fan
On r uns the fan continuously for increased air circula tion
OnOn
or to allow additional air cleaning.
Choose the System SettingChoose the System Setting
Choose the System Setting
Choose the System SettingChoose the System Setting
Cool: Thermostat controls only the cooling system.
CoolCool
AA
utouto
A
ut o: Auto Changeover is used in areas where both heating
AA
utouto
and cooling may be required on the same day.
the thermostat to automa tically select heating or cooling
depending on the indoor temperature and the selected heat
and cool temperatures. When using
Cooling temperatures more than 1° Fahrenheit higher than
the heating temperature.
EmerEmer
Emer: Setting is available only when the thermostat is
Press the SYSTEM button to select Heat or Cool and use
the
or buttons to adjust the temperature to your
desired setting. After selecting your desired settings you can
also press the SYSTEM button to select
the thermostat to automatically change between Heat and
Cool.
Manual Operation (Bypassing the Program)Manual Operation (Bypassing the Program)
Manual Operation (Bypassing the Program)
Manual Operation (Bypassing the Program)Manual Operation (Bypassing the Program)
Programmable ThermostatsProgrammable Thermostats
Programmable Thermostats
Programmable ThermostatsProgrammable Thermostats
Press or and adjust the temperature wherever you like.
Then press HOLD. This will override the program. The
feature bypasses the program and allows you to adjust the
temperature manually, as needed. Whatever temperature you
HOLDHOLD
set in
HOLD will be maintained 24 hours a day, until you
HOLDHOLD
manually change the temperature or press RUN to cancel
HOLDHOLD
HOLD and resume the programmed schedule.
HOLDHOLD
Program Override (Temporary Override)Program Override (Temporary Override)
Program Override (Temporary Override)
Program Override (Temporary Override)Program Override (Temporary Override)
Press or buttons to adjust the temperature. This will
override the temperature setting for a (default) four hour
override period. The override period can be shortened or
lengthened by adjusting the temporary hold time in the
configuration menu.
ExampleExample
Example: If you turn up the heat during the morning pro-
ExampleExample
gram, it will be automatically lowered later, w hen the temporary hold period ends. To cancel the temporar y setting a t any
time and return to the program, press RUN.
If the SYSTEM button is pressed to select
thermostat will change to Heat or Cool, whichever ran last. If
it switches to heat but you want cool, or it changes to cool
but you want heat, press both
neously to change to the other mode.
A
AA
Manual Operation forManual Operation for
Manual Operation for
Manual Operation forManual Operation for
uto or
uto uto
OnOn
On.
OnOn
AA
UTUT
A
UT
AA
UTUT
AA
UTUT
OO
A
UT
O, be sure to set the
AA
UTUT
OO
AUTOAUTO
AUTO to allow
AUTOAUTO
AUTOAUTO
AUTO the
AUTOAUTO
and buttons simulta-
OO
O allows
OO
HOLDHOLD
HOLD
HOLDHOLD
11
Page 12
OPERATING YOUR THERMOSTAT AND REMOTE SENSOROPERATING YOUR THERMOSTAT AND REMOTE SENSOR
OPERATING YOUR THERMOSTAT AND REMOTE SENSOR
OPERATING YOUR THERMOSTAT AND REMOTE SENSOROPERATING YOUR THERMOSTAT AND REMOTE SENSOR
Remote Sensor OperationRemote Sensor Operation
Remote Sensor Operation
Remote Sensor OperationRemote Sensor Operation
The sensor monitors the temperature and sends information
to the thermostat. Updated information is sent to the thermostat when the temperature changes 3/16 degree or more
from the last update.
Low Battery powerLow Battery power
Low Battery power: The sensor will display the word
Low Battery powerLow Battery power
along with
BATT BATT
BATT icon to indicate a low battery power
BATT BATT
LOLO
LO
LOLO
condition. The 2 "AAA" batteries must be replaced to ensure
a proper sensor performance. For optimum performance,
replace batteries once a year with new premium brand
®
alkaline batteries such as Duracell
or Energizer®.
Increasing the sensor setpoint decreases the displayed
remote temperature shown on the thermostat by 1°F per bar.
This will lower the actual calculated room temperature by up
to 4°F. Decreasing the sensor setpoint increases the
displayed remote temperature and will raise the actual
calculated room temperature. The table below shows how
the adjustment on the sensor affects the displayed remote
temperature on the thermostat and the calculated average
temperature.
PROGRAMMING YOUR THERMOSTATPROGRAMMING YOUR THERMOSTAT
PROGRAMMING YOUR THERMOSTAT
PROGRAMMING YOUR THERMOSTATPROGRAMMING YOUR THERMOSTAT
This section will help you plan your thermostat's program to
meet your needs. For maximum comfort and efficiency, keep
the following guidelines in mind when planning your program.
• When heating (cooling) your building, program the temper-
atures to be cooler (warmer) when the building is vacant or
during periods of low activity.
• During early morning hours, the need for cooling is usually
minimal.
Planning Your ProgramPlanning Your Program
Planning Your Program
Planning Your ProgramPlanning Your Program
Look at the factory preprogrammed times and temperatures
shown in the sample schedule. If this program will suit your
needs, simply set the time and day and press the RUN
button to begin running the factory preset program.
If you want to change the preprogrammed times and temperatures, follow these steps.
Determine the time periods and temperatures for your
program. You must program four periods for each day.
However, you may use the same heating and cooling
temperatures for consecutive time periods. You can choose
start times, heating temperatures, and cooling temperatures
independently (for example, you may select 5:00 AM and 70°
as the weekday
ture and also choose 7:00 AM and 76° as the weekday
period coolingperiod cooling
per io d c oo li ng start time and temperature).
period coolingperiod cooling
1st period heating1st period heating
1st p e ri o d h e a t in g start time and tempera-
1st period heating1st period heating
1st1st
1st
1st1st
Use the table to plan your program time periods and the
temperatures you want during each period. Fill in the
complete table to have a record of your programs.
DescriptionRemote Sensor Thermostat Display (Remote) Thermostat Display (Local) Calculated Room Temp.Setpoint Temp.
Increasing setting decreases roomH +4 barsDecreases by 4°F to 71°F70.5°F
temperature average causing system H +3 barsDecreases by 3°F to 72°F71°F
to increase temperature.H +2 barsDecreases by 2°F to 73°F71.5°F
H +1 barDecreases by 1°F to 74°F72°F
Remote 75°F75°F74.5°75°F
Decreasing setting increases roomC -1 barIncreases by 1°F to 76°F73°F
temperature causing more of aC -2 barsIncreases by 2°F to 77°F73.5°F
demand for Cooling.C -3 barsIncreases by 3°F to 78°F74°F
C -4 barsIncreases by 4°F to 79°F74.5°F
FACTORY PROGRAMFACTORY PROGRAM
FACTORY PROGRAM
FACTORY PROGRAMFACTORY PROGRAM
12
PERIODPERIOD
PERIOD
PERIODPERIOD
MORNMORN
MORN
MORNMORN
DAYDAY
DAY
DAYDAY
EVEEVE
EVE
EVEEVE
HEATHEAT
HEATHEAT
HEAT
NITENITE
NITE
NITENITE
MORNMORN
MORN
MORNMORN
DAYDAY
DAY
DAYDAY
EVEEVE
EVE
EVEEVE
COOLCOOL
COOLCOOL
COOL
NITENITE
NITE
NITENITE
PERIODPERIOD
PERIOD
PERIODPERIOD
MORNMORN
MORN
MORNMORN
DAYDAY
DAY
DAYDAY
EVEEVE
EVE
EVEEVE
HEATHEAT
HEATHEAT
HEAT
NITENITE
NITE
NITENITE
MORNMORN
MORN
MORNMORN
DAYDAY
DAY
DAYDAY
EVEEVE
EVE
EVEEVE
COOLCOOL
COOLCOOL
COOL
NITENITE
NITE
NITENITE
WEEKDAYS (5 DAYS)WEEKDAYS (5 DAYS)
WEEKDAYS (5 DAYS)
WEEKDAYS (5 DAYS)WEEKDAYS (5 DAYS)
STARTSTART
START
STARTSTART
TIMETIME
TIME
TIMETIME
6:00 AM6:00 AM
6:00 AM
6:00 AM6:00 AM
8:00 AM8:00 AM
8:00 AM
8:00 AM8:00 AM
5:00 PM5:00 PM
5:00 PM
5:00 PM5:00 PM
10:00 PM10:00 PM
10:00 PM
10:00 PM10:00 PM
6:00 AM6:00 AM
6:00 AM
6:00 AM6:00 AM
8:00 AM8:00 AM
8:00 AM
8:00 AM8:00 AM
5:00 PM5:00 PM
5:00 PM
5:00 PM5:00 PM
10:00 PM10:00 PM
10:00 PM
10:00 PM10:00 PM
WEEKDAYS (5 DAYS)WEEKDAYS (5 DAYS)
WEEKDAYS (5 DAYS)
WEEKDAYS (5 DAYS)WEEKDAYS (5 DAYS)
STARTSTART
START
STARTSTART
TIMETIME
TIME
TIMETIME
TEMPTEMP
TEMP
TEMPTEMP
70 F70 F
70 F
70 F70 F
62 F62 F
62 F
62 F62 F
70 F70 F
70 F
70 F70 F
62 F62 F
62 F
62 F62 F
78 F78 F
78 F
78 F78 F
85 F85 F
85 F
85 F85 F
78 F78 F
78 F
78 F78 F
82 F82 F
82 F
82 F82 F
TEMPTEMP
TEMP
TEMPTEMP
REMOTEREMOTE
REMOTE
REMOTEREMOTE
WEIGHTWEIGHT
WEIGHT
WEIGHTWEIGHT
REMOTEREMOTE
REMOTE
REMOTEREMOTE
WEIGHTWEIGHT
WEIGHT
WEIGHTWEIGHT
SATURDAY (1 DAY)SATURDAY (1 DAY)
SATURDAY (1 DAY)
SATURDAY (1 DAY)SATURDAY (1 DAY)
STARTSTART
START
STARTSTART
TIMETIME
TIME
AA
A
AA
AA
A
AA
AA
A
AA
AA
A
AA
AA
A
AA
AA
A
AA
AA
A
AA
AA
A
AA
TIMETIME
6:00 AM6:00 AM
6:00 AM
6:00 AM6:00 AM
8:00 AM8:00 AM
8:00 AM
8:00 AM8:00 AM
5:00 PM5:00 PM
5:00 PM
5:00 PM5:00 PM
10:00 PM10:00 PM
10:00 PM
10:00 PM10:00 PM
6:00 AM6:00 AM
6:00 AM
6:00 AM6:00 AM
8:00 AM8:00 AM
8:00 AM
8:00 AM8:00 AM
5:00 PM5:00 PM
5:00 PM
5:00 PM5:00 PM
10:00 PM10:00 PM
10:00 PM
10:00 PM10:00 PM
PERSONAL PROGRAMPERSONAL PROGRAM
PERSONAL PROGRAM
PERSONAL PROGRAMPERSONAL PROGRAM
SATURDAY (1 DAY)SATURDAY (1 DAY)
SATURDAY (1 DAY)
SATURDAY (1 DAY)SATURDAY (1 DAY)
STARTSTART
START
STARTSTART
TIMETIME
TIME
TIMETIME
TEMPTEMP
TEMP
TEMPTEMP
70 F70 F
70 F
70 F70 F
62 F62 F
62 F
62 F62 F
70 F70 F
70 F
70 F70 F
62 F62 F
62 F
62 F62 F
78 F78 F
78 F
78 F78 F
85 F85 F
85 F
85 F85 F
78 F78 F
78 F
78 F78 F
82 F82 F
82 F
82 F82 F
TEMPTEMP
TEMP
TEMPTEMP
REMOTEREMOTE
REMOTE
REMOTEREMOTE
WEIGHTWEIGHT
WEIGHT
WEIGHTWEIGHT
AA
A
AA
AA
A
AA
AA
A
AA
AA
A
AA
AA
A
AA
AA
A
AA
AA
A
AA
AA
A
AA
REMOTEREMOTE
REMOTE
REMOTEREMOTE
WEIGHTWEIGHT
WEIGHT
WEIGHTWEIGHT
SUNDAY (1 DAY)SUNDAY (1 DAY)
SUNDAY (1 DAY)
SUNDAY (1 DAY)SUNDAY (1 DAY)
STARTSTART
START
STARTSTART
TIMETIME
TIME
TIMETIME
6:00 AM6:00 AM
6:00 AM
6:00 AM6:00 AM
8:00 AM8:00 AM
8:00 AM
8:00 AM8:00 AM
5:00 PM5:00 PM
5:00 PM
5:00 PM5:00 PM
10:00 PM10:00 PM
10:00 PM
10:00 PM10:00 PM
6:00 AM6:00 AM
6:00 AM
6:00 AM6:00 AM
8:00 AM8:00 AM
8:00 AM
8:00 AM8:00 AM
5:00 PM5:00 PM
5:00 PM
5:00 PM5:00 PM
10:00 PM10:00 PM
10:00 PM
10:00 PM10:00 PM
SUNDAY (1 DAY)SUNDAY (1 DAY)
SUNDAY (1 DAY)
SUNDAY (1 DAY)SUNDAY (1 DAY)
STARTSTART
START
STARTSTART
TIMETIME
TIME
TIMETIME
TEMPTEMP
TEMP
TEMPTEMP
70 F70 F
70 F
70 F70 F
62 F62 F
62 F
62 F62 F
70 F70 F
70 F
70 F70 F
62 F62 F
62 F
62 F62 F
78 F78 F
78 F
78 F78 F
85 F85 F
85 F
85 F85 F
78 F78 F
78 F
78 F78 F
82 F82 F
82 F
82 F82 F
TEMPTEMP
TEMP
TEMPTEMP
REMOTEREMOTE
REMOTE
REMOTEREMOTE
WEIGHTWEIGHT
WEIGHT
WEIGHTWEIGHT
AA
A
AA
AA
A
AA
AA
A
AA
AA
A
AA
AA
A
AA
AA
A
AA
AA
A
AA
AA
A
AA
REMOTEREMOTE
REMOTE
REMOTEREMOTE
WEIGHTWEIGHT
WEIGHT
WEIGHTWEIGHT
Page 13
PROGRAMMINGPROGRAMMING
CAUTION
!
PROGRAMMING
PROGRAMMINGPROGRAMMING
Setting the Clock and DaySetting the Clock and Day
Setting the Clock and Day
Setting the Clock and DaySetting the Clock and Day
Set Current Time and DaySet Current Time and Day
Set Current Time and Day
Set Current Time and DaySet Current Time and Day
1. Press TIME button once. The display will show the hour
only.
EXAMPLE:
2. Press and hold either
correct hour and AM/PM designation (
PM PM
night;
PM begins at noon).
PM PM
indicate for PM in the minutes digits.
3. Press TIME once again. The display window will show
the minutes only.
EXAMPLE:
4. Press and hold either
correct minutes.
5. Press TIME once again. The display will show the day of
the week.
6. Press or until you reach the current day of the
week.
7. Press RUN once. The display will show the correct time
and room temperature alternately.
This thermostat starts the programmed temperature earlier
than the time selected in your program. This allows the
system to reach your setting by the time you specify in your
program. This feature is called EMR (Energy Management
Recovery). If you do not want the thermostat to start early,
you may cancel the EMR feature in the Configuration Menu.
Enter Heating ProgramEnter Heating Program
Enter Heating Program
Enter Heating ProgramEnter Heating Program
1. Press the SYSTEM button to
2. Press PRGM once. "
weekday program) will appear in the display. Also displayed are the currently programmed start time for the
1st heating period and the currently programmed temperature (flashing).
EXAMPLE:
This display window shows that for the 1st weekday
period, the start time is 6:00 AM and 68° is the programmed temperature (this example reflects factory preprogramming.
3. Press
to your selected temperature for the 1st heating program
period.
4. Press TIME once (the programmed time will flash). Press
will change in 15 minute increments. When your selected
time is displayed, press TIME again to return to the
change temperature mode.
5. If both the local and the remote sensors are enabled, then
you may press HOLD button to change the remote sensor
weighting setting. Remote icon will display. The programmed weight (A, HI or LO) will flash. Press or
to change the displayed weight to your selected weight
for the 1st heat program period.
or to change the displayed temperature
or until your selected time appears. The time
or until you reach the
AM AM
AM begins at mid-
AM AM
A A
A will indicate for AM.
A A
or until you reach the
HEATHEAT
HEAT.
HEATHEAT
MO TU WE TH FRMO TU WE TH FR
MO TU WE TH FR" (indicating
MO TU WE TH FRMO TU WE TH FR
P P
P will
P P
6. Press PRGM once. The currently programmed start time
and setpoint temperature for the
period will appear.
7. Repeat steps 3 and 5 to select the start time and heating
temperature for the 2nd heating program period.
8. Repeat steps 3 through 6 for the 3rd and 4th heating
program periods.
9. Press PRGM once "
will appear in the display, along with the start time for the
1st heating period and the currently programmed temperature.
10.Repeat steps 3 through 8 to complete Saturday heating
programming.
11.Press PRGM once to change to "
programming and repeat steps 3 through 7 to complete
Sunday programming.
12.When you have completed entering your heating program, press RUN.
Enter Cooling ProgramEnter Cooling Program
Enter Cooling Program
Enter Cooling ProgramEnter Cooling Program
If the outside temperature is below 50°F, disconnectIf the outside temperature is below 50°F, disconnect
If the outside temperature is below 50°F, disconnect
If the outside temperature is below 50°F, disconnectIf the outside temperature is below 50°F, disconnect
power to the cooling system before programming.power to the cooling system before programming.
power to the cooling system before programming.
power to the cooling system before programming.power to the cooling system before programming.
Energizing the air conditioner compressor duringEnergizing the air conditioner compressor during
Energizing the air conditioner compressor during
Energizing the air conditioner compressor duringEnergizing the air conditioner compressor during
cold weather may cause personal injury or propertycold weather may cause personal injury or property
cold weather may cause personal injury or property
cold weather may cause personal injury or propertycold weather may cause personal injury or property
damage.damage.
damage.
damage.damage.
1. Press SYSTEM button to
2. Follow Enter Heating Program for entering your cooling
program, using your selected cooling times and temperatures.
CHECK YOUR PROGRAMMINGCHECK YOUR PROGRAMMING
CHECK YOUR PROGRAMMING
CHECK YOUR PROGRAMMINGCHECK YOUR PROGRAMMING
Follow these steps to check your thermostat programming
one final time before beginning thermostat operation.
1. Press SYSTEM button to
2. Press PRGM to view the 1st weekday heating period
time and temperature. Each time you press PRGM, the
next heating period time and temperature will be displayed in sequence for weekday, then Saturday and Sunday
program periods (you may change any time or temperature during this procedure.
3. Press RUN.
4. Press SYSTEM button to
5. Repeat step 2 to check cooling program.
6. Press SYSTEM button to
RUN to begin program operation.
NOTE: Batteries are not required to keep your programming
or menu data. With two optional "AA" batteries installed,
your thermostat will maintain time and continuously
display the temperature during a loss of AC power.
Installed batteries will also allow programming prior to
installation.
YOUR THERMOSTAT IS NOW PROGRAMMED AND READY TOYOUR THERMOSTAT IS NOW PROGRAMMED AND READY TO
YOUR THERMOSTAT IS NOW PROGRAMMED AND READY TO
YOUR THERMOSTAT IS NOW PROGRAMMED AND READY TOYOUR THERMOSTAT IS NOW PROGRAMMED AND READY TO
PROVIDE MAXIMUM COMFORT AND EFFICIENCY!PROVIDE MAXIMUM COMFORT AND EFFICIENCY!
PROVIDE MAXIMUM COMFORT AND EFFICIENCY!
PROVIDE MAXIMUM COMFORT AND EFFICIENCY!PROVIDE MAXIMUM COMFORT AND EFFICIENCY!
SASA
SA" (indicating Saturday program)
SASA
2nd heating2nd heating
2nd heating program
2nd heating2nd heating
SUSU
SU" (Sunday) heating
SUSU
COOLCOOL
COOL.
COOLCOOL
HEAT HEAT
HEAT position.
HEAT HEAT
COOL COOL
COOL position.
COOL COOL
HEAT HEAT
HEAT or
HEAT HEAT
COOL COOL
COOL and press
COOL COOL
13
Page 14
TROUBLESHOOTINGTROUBLESHOOTING
TROUBLESHOOTING
TROUBLESHOOTINGTROUBLESHOOTING
Reset OperationReset Operation
Reset Operation
Reset OperationReset Operation
If a voltage spike or static discharge blanks out the display or causes erratic thermostat operation, you can reset the thermostat by removing the wires from terminals R and C and removing batteries for 2 minutes. After resetting the thermostat,
replace the wires and batteries. If the thermostat has been reset and still does not function correctly contact your heating/
cooling service person or place of purchase.
Pressing
also clear any limited temperature ranges or keypad lockout settings. Note default system configuration is multistage system
operation.
and and the SYSTEM keys at the same time will reset the thermostat to its factory default setting. This will
SymptomSymptom
Symptom
SymptomSymptom
No Heat/No Cool/No FanNo Heat/No Cool/No Fan
No Heat/No Cool/No Fan
No Heat/No Cool/No FanNo Heat/No Cool/No Fan
(common problems)(common problems)
(common problems)
(common problems)(common problems)
No HeatNo Heat
No Heat
No HeatNo Heat
Possible CausePossible Cause
Possible Cause
Possible CausePossible Cause
1.Blown fuse or tripped circuit breaker.
2.Furnace power switch to OFF.
3.Furnace blower compartment door or
panel loose or not properly installed.
1.Pilot light not lit.
2.SYSTEM Switch not set to
3.Loose connection to thermostat or
system.
4.Furnace Lock-Out Condition. Heat
may also be intermittent.
5.Heating system requires service or
thermostat requires replacement.
HEATHEAT
HEAT.
HEATHEAT
Corrective ActionCorrective Action
Corrective Action
Corrective ActionCorrective Action
Replace fuse or reset breaker.
Turn switch to ON.
Replace door panel in proper position to engage
safety interlock or door switch.
Re-light pilot.
Set SYSTEM Switch to
above room temperature.
Verify thermostat and system wires are securely
attached.
Many furnaces have safety devices that shut down
when a lock-out condition occurs. If the heat works
intermittently contact the furnace manufacturer or
local service person for assistance.
Diagnostic: Set SYSTEM Switch to
the setpoint above room temperature. Within a few
seconds the thermostat should make a soft click
sound. This sound usually indicates the thermostat
is operating properly. If the thermostat does not
click, try the reset operation listed above. If the
thermostat does not click after being reset contact
your heating and cooling service person or place of
purchase for a replacement. If the thermostat clicks,
contact the furnace manufacturer or a service
person to verify the heating is operating correctly.
HEAT HEAT
HEAT and raise setpoint
HEAT HEAT
HEAT HEAT
HEAT and raise
HEAT HEAT
No CoolNo Cool
No Cool
No CoolNo Cool
Thermostat does notThermostat does not
Thermostat does not
Thermostat does notThermostat does not
Follow ProgramFollow Program
Follow Program
Follow ProgramFollow Program
1.SYSTEM Switch not set to
2.Loose connection to thermostat or
system.
3.Cooling system requires service or
thermostat requires replacement.
1.Program or current time(s) set
incorrectly (AM, PM or Day of the
week).
2.Energy Management Recovery
(EMR) starting the program early.
COOLCOOL
COOL.
COOLCOOL
Set SYSTEM Switch to
below room temperature.
Verify thermostat and system wires are securely
attached.
Same procedure as diagnostic for No Heat condition
except set the thermostat to
setpoint below the room temperature. There may be
up to a five minute delay before the thermostat
clicks in Cooling.
Verify that the AM or PM settings are correct for
each program period and the current time of day.
Also verify the Day of the week is set correctly.
The EMR (Energy Management Recovery) feature
starts early to achieve the temperature it is programmed for by the time specified in the program.
See the Configuration Menu section to disable
EMR if you do not want the thermostat to start early.
COOL COOL
COOL and lower setpoint
COOL COOL
COOL COOL
COOL and lower the
COOL COOL
14
Page 15
TROUBLESHOOTINGTROUBLESHOOTING
TROUBLESHOOTING
TROUBLESHOOTINGTROUBLESHOOTING
SymptomSymptom
Symptom
SymptomSymptom
Furnace Inducer Fan,Furnace Inducer Fan,
Furnace Inducer Fan,
Furnace Inducer Fan,Furnace Inducer Fan,
Blower or Heat Turns OnBlower or Heat Turns On
Blower or Heat Turns On
Blower or Heat Turns OnBlower or Heat Turns On
with No Call for Heat orwith No Call for Heat or
with No Call for Heat or
with No Call for Heat orwith No Call for Heat or
does not Turn Off whendoes not Turn Off when
does not Turn Off when
does not Turn Off whendoes not Turn Off when
Call for Heat EndsCall for Heat Ends
Call for Heat Ends
Call for Heat EndsCall for Heat Ends
Antenna + FaultAntenna + Fault
Antenna + Fault
Antenna + FaultAntenna + Fault
Possible CausePossible Cause
Possible Cause
Possible CausePossible Cause
In power stealing mode (RC/PS Switch
set to PS), the thermostat draws a small
amount of power through the heating
circuit to operate. Some furnace
systems using high impedance input
electronic modules may react to the
current draw and actuate system
components.
1.Loss of power from heating/cooling
system to thermostat.
2.Remote sensor too far from
thermostat.
3.Thermostat or remote sensor set to
different channels or a different
frequency offset.
4.Incorrect sensor identification
selected.
5.Replacement Sensor requires
running learn mode.
6.Remote sensor requires replacement.
Corrective ActionCorrective Action
Corrective Action
Corrective ActionCorrective Action
1. Add a common connection from the system
transformer to the "C" terminal on the thermostat
and set the RC/PS switch to RC.
2. If the system has a standard cooling contactor
and no common connection is available at the
thermostat, clip jumper W25-W1 and separate the
ends. This prevents the thermostat from drawing
power from the W1 (heating) circuit. If the condition
persists after clipping the jumper, a heating and
cooling service person can install an isolation relay
to the system or add a common wire as mentioned
above.
1. Verify the thermostat is operating on AC power by
removing the thermostat batteries. If display goes
blank, AC power is lost.
2. Change remote sensor location.
3. Verify the thermostat and remote sensor are set
to the same channel and frequency offset.
4. For indoor sensor, verify sensor identification
selected is A, B or C. For an outdoor sensor, verify
the sensor identification selected is O.
5. If the sensor did not come with this thermostat
from the factory, perform the learn procedure for
thermostat and sensor.
6. If the sensor display indicate E0 or E1, replace
the remote sensor.
Temperature DifferenceTemperature Difference
Temperature Difference
Temperature DifferenceTemperature Difference
between Thermostatbetween Thermostat
between Thermostat
between Thermostatbetween Thermostat
and Remote Locationand Remote Location
and Remote Location
and Remote Locationand Remote Location
Heat, Cool or FanHeat, Cool or Fan
Heat, Cool or Fan
Heat, Cool or FanHeat, Cool or Fan
Runs ConstantlyRuns Constantly
Runs Constantly
Runs ConstantlyRuns Constantly
1.Improper system sizing or improper
heating and cooling distribution
between areas.
2.An uneven change in occupancy
level, sun load or conditioned space
activities (cooking, washing dishes,
showers, etc.) between the areas.
1.Possible short in wiring.
2.Possible short in thermostat.
3.Possible short in heat/cool/fan
system.
4.FAN Switch set to Fan
ONON
ON.
ONON
Selecting a high or low priority for the thermostat or
sensor location during program periods can help
even out minor temperature imbalances between
the thermostat and remote sensor locations. This is
also useful for scheduled or predictable events like
occupancy level or sun load during particular times
of the day. If the temperature difference remains
large after assigning priorities, system modification
or zoning may be necessary to balance the temperature distribution.
Check each wire connection to verify they are not
shorted or touching together. No bare wire should
stick out from under terminal screws. Try resetting
the thermostat as described above. If the condition
persists the manufacturer of your system or service
person can instruct you on how to test the Heat/Cool
system for correct operation. If the system operates
correctly, replace the thermostat.
15
Page 16
TROUBLESHOOTINGTROUBLESHOOTING
TROUBLESHOOTING
TROUBLESHOOTINGTROUBLESHOOTING
Possible CausePossible Cause
Possible Cause
SymptomSymptom
Symptom
SymptomSymptom
Possible CausePossible Cause
Corrective ActionCorrective Action
Corrective Action
Corrective ActionCorrective Action
FurnaceFurnace
Furnace
FurnaceFurnace
(Air Conditioner)(Air Conditioner)
(Air Conditioner)
(Air Conditioner)(Air Conditioner)
Cycles Too FastCycles Too Fast
Cycles Too Fast
Cycles Too FastCycles Too Fast
or Too Slow (narrow oror Too Slow (narrow or
or Too Slow (narrow or
or Too Slow (narrow oror Too Slow (narrow or
wide temperature swing)wide temperature swing)
1.The desired setpoint conflicts with the
setpoint of the COOL mode.
1.The desired setpoint conflicts with the
setpoint of the HEAT mode.
Digital thermostats normally provide precise
temperature control and may cycle faster than some
older mechanical models. A faster cycle rate means
the unit turns on and off more frequently but runs for
a shorter time so there is no increase in energy use.
If you would like to increase the cycle time, choose
SL SL
SL for slow cycle in the menu, step 4. If an accept-
SL SL
able cycle rate is not achieved as received or by
choosing slow cycle, contact a local service person
for additional suggestions.
The thermometer can be adjusted +/- 3 degrees.
See Temperature Display Adjustment in the
Configuration Menu section.
Use the Reset Operation at top of previous page.
Change system mode to COOL. Raise the Cool
setpoint. Return to HEAT mode and set desired
temperature.
Change system mode to HEAT. Lower the Heat
setpoint. Return to COOL mode and set desired
temperature.
With the thermostat in any mode, press
at the same time to enter the configuration menu at
the point where the lockout code is to be entered.
Press
time to reset the lockout code, unlock the keypad.
and and SYSTEM button at the same
and
Why won't my 2nd orWhy won't my 2nd or
Why won't my 2nd or
Why won't my 2nd orWhy won't my 2nd or
3rd stage come on?3rd stage come on?
3rd stage come on?
3rd stage come on?3rd stage come on?
White-Rodgers is a division
of Emerson Electric Co.
The Emerson logo is a
trademark and service mark
of Emerson Electric Co.
Your thermostat is designed to determine the
optimum time to activate the second stage. Simply
raising the temperature in heating or lowering it in
cooling will not always force the thermostat to bring
the second stage on quickly. There is a time delay
from 0-30 minutes depending on the performance of
the first stage of the system.
HOMEOWNER HELP LINE: 1-800-284-2925
St. Louis, MO
www.white-rodgers.com
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.