White Rodgers 1F85RF-275 User Manual

Page 1
Save these instructionsSave these instructions
Save these instructions
Save these instructionsSave these instructions
for future use!for future use!
for future use!
for future use!for future use!
FAILURE TO READ AND FOLLOW ALL INSTRUCTIONSFAILURE TO READ AND FOLLOW ALL INSTRUCTIONS
FAILURE TO READ AND FOLLOW ALL INSTRUCTIONS
FAILURE TO READ AND FOLLOW ALL INSTRUCTIONSFAILURE TO READ AND FOLLOW ALL INSTRUCTIONS CAREFULLY BEFORE INSTALLING OR OPERATING THISCAREFULLY BEFORE INSTALLING OR OPERATING THIS
CAREFULLY BEFORE INSTALLING OR OPERATING THIS
CAREFULLY BEFORE INSTALLING OR OPERATING THISCAREFULLY BEFORE INSTALLING OR OPERATING THIS CONTROL COULD CAUSE PERSONAL INJURY AND/ORCONTROL COULD CAUSE PERSONAL INJURY AND/OR
CONTROL COULD CAUSE PERSONAL INJURY AND/OR
CONTROL COULD CAUSE PERSONAL INJURY AND/ORCONTROL COULD CAUSE PERSONAL INJURY AND/OR PROPERTY DAMAGE.PROPERTY DAMAGE.
PROPERTY DAMAGE.
PROPERTY DAMAGE.PROPERTY DAMAGE.
APPLICATIONSAPPLICATIONS
APPLICATIONS
APPLICATIONSAPPLICATIONS
THERMOSTAT APPLICATION GUIDETHERMOSTAT APPLICATION GUIDE
THERMOSTAT APPLICATION GUIDE
THERMOSTAT APPLICATION GUIDETHERMOSTAT APPLICATION GUIDE
DescriptionDescription
Description
DescriptionDescription Heat Pump (No Auxiliary or Emergency Heat) Yes
Heat Pump (with Auxiliary or Emergency Heat) Yes Standard Heat & Cooling Systems Yes Multi-Stage Systems requiring more than Yes One Call for Heat or Cool Standard Heat Only Systems Yes Millivolt Heat Only Systems – Floor or Wall Furnaces No Standard Central Air Conditioning Yes Gas or Oil Heat Yes Electric Furnace Yes Hydronic (Hot Water) Zone Heat – 2 Wires * Yes Hydronic (Hot Water) Zone Heat – 3 Wires No
* Common Connection Required
1F85RF-275 Thermostat and
Wireless Remote Sensor Kit
Automatic Heat/Cool Changeover Thermostat for Single Stage/ Multi-Stage/Heat Pump Systems with Wireless Remote Sensor
Installation and Operating Instructions for Model:Installation and Operating Instructions for Model:
Installation and Operating Instructions for Model:
Installation and Operating Instructions for Model:Installation and Operating Instructions for Model:
Model Programming Choices
1F85RF-270 Non-Programmable 5/1/1 Day
F145RF-1328 Wireless Remote Sensor
1F85RF-270
Wireless Remote Sensor
SPECIFICATIONSSPECIFICATIONS
SPECIFICATIONS
SPECIFICATIONSSPECIFICATIONS
ThermostatThermostat
Thermostat:
ThermostatThermostat
Electrical Ratings .......................... 20 to 30 VAC 50/60 Hz
Setpoint Range.............................. 45 to 90°F (7 to 32°C)
Rated Differential (Single Stage) ... Heat 0.6° or 1.5°F, Cool 1.2°F
Rated Differential (Multi-Stage) ..... Heat 0.6° or 1.5°F, Cool 1.2°F
Rated Differential (Heat Pump)..... Heat & Cool 0.75° or 1.2°F
Operating Ambient ........................ 32 to +105°F (0 to +41°C)
Operating Humidity ....................... 90% non-condensing max.
Shipping Temp. Range.................. -4 to +150°F (-20 to +65°C)
Thermostat Dimensions ............... 3-3/4"H x 6"W x 1-1/4"D
!
To prevent electrical shock and/or equipment dam-To prevent electrical shock and/or equipment dam-
To prevent electrical shock and/or equipment dam-
To prevent electrical shock and/or equipment dam-To prevent electrical shock and/or equipment dam­age, disconnect electric power to system at main fuseage, disconnect electric power to system at main fuse
age, disconnect electric power to system at main fuse
age, disconnect electric power to system at main fuseage, disconnect electric power to system at main fuse or circuit breaker box until installation is complete.or circuit breaker box until installation is complete.
or circuit breaker box until installation is complete.
or circuit breaker box until installation is complete.or circuit breaker box until installation is complete.
Index Page
Installation 2 Wiring Connections 3 Thermostat/Sensor Quick Reference 4 Installer Configuration Menus 6 Operating Your Thermostat and Sensor 9 Programming 13 Troubleshooting 14
0.2 to 0.6 Amps per Load (Y1, E/W1, G)
1.5 Amps (Y2, W2, O, B Load per terminal)
1.5 Amps Max (All terminals combined)
CAUTION
Remote Sensor:Remote Sensor:
Remote Sensor:
Remote Sensor:Remote Sensor:
This device complies with Part 15 of the FCC Rules, OperationThis device complies with Part 15 of the FCC Rules, Operation
This device complies with Part 15 of the FCC Rules, Operation
This device complies with Part 15 of the FCC Rules, OperationThis device complies with Part 15 of the FCC Rules, Operation is subject to the following two conditions: (1) this device mayis subject to the following two conditions: (1) this device may
is subject to the following two conditions: (1) this device may
is subject to the following two conditions: (1) this device mayis subject to the following two conditions: (1) this device may not cause harmful interference, and (2) this device must acceptnot cause harmful interference, and (2) this device must accept
not cause harmful interference, and (2) this device must accept
not cause harmful interference, and (2) this device must acceptnot cause harmful interference, and (2) this device must accept any interference received, including interference that may causeany interference received, including interference that may cause
any interference received, including interference that may cause
any interference received, including interference that may causeany interference received, including interference that may cause undesired operation.undesired operation.
undesired operation.
undesired operation.undesired operation.
Maximum Wireless Remote Sensors.....1 indoor, 1 outdoor
Operating Range .................................... 45 to 90°F (7 to 32°C)
Operating Humidity Range .....................0 to 90% RH
(non-condensing)
Dimensions .............................................2-5/8"H x 4-1/4"W x 7/8"D
* Max. Distance from Thermostat .......... 200 feet
* Distance shown is for a typical application. Distances may vary in
some applications because obstacles that block the signal path may affect the strength of the signal.
ATTENTION: MERCURY NOTICEATTENTION: MERCURY NOTICE
ATTENTION: MERCURY NOTICE
ATTENTION: MERCURY NOTICEATTENTION: MERCURY NOTICE This product does not contain mercury. However, this prod­uct may replace a product which contains mercury.
Mercury and products containing mercury must not be dis­carded in household trash. Do not touch any spilled mercury. Wearing non-absorbent gloves, clean up any spilled mercury and place in a sealed container. For proper disposal of a product containing mercury or a sealed container of spilled mercury, place it in a suitable shipping container and send it to:
White-RodgersWhite-Rodgers
White-Rodgers
White-RodgersWhite-Rodgers 2895 Harrison Street2895 Harrison Street
2895 Harrison Street
2895 Harrison Street2895 Harrison Street Batesville, AR 72501Batesville, AR 72501
Batesville, AR 72501
Batesville, AR 72501Batesville, AR 72501
www.white-rodgers.com
PART NO. 37-6841BPART NO. 37-6841B
PART NO. 37-6841B
PART NO. 37-6841BPART NO. 37-6841B
Replaces 37-6841A
Page 2
ANTENNA
MOUNTING HOLE
MOUNTING HOLE
INSTALLATIONINSTALLATION
INSTALLATION
INSTALLATIONINSTALLATION
WARNING
!
Thermostat installation and all components of theThermostat installation and all components of the
Thermostat installation and all components of the
Thermostat installation and all components of theThermostat installation and all components of the control system shall conform to Class II circuits per thecontrol system shall conform to Class II circuits per the
control system shall conform to Class II circuits per the
control system shall conform to Class II circuits per thecontrol system shall conform to Class II circuits per the NEC code.NEC code.
NEC code.
NEC code.NEC code.
Remove Old ThermostatRemove Old Thermostat
Remove Old Thermostat
Remove Old ThermostatRemove Old Thermostat
A standard heat/cool thermostat consists of three basic parts:
1. The cover, which may be either a snap-on or hinge type.
2. The base, which is removed by loosening all captive screws.
3. The switching subbase, which is removed by unscrewing the mounting screws that hold it on the wall or adapter
Before removing wires from old thermostat,Before removing wires from old thermostat,
plate.
Before removing wires from old thermostat,
Before removing wires from old thermostat,Before removing wires from old thermostat,
label each wire with the terminal designation fromlabel each wire with the terminal designation from
label each wire with the terminal designation from
label each wire with the terminal designation fromlabel each wire with the terminal designation from which it was attachedwhich it was attached
which it was attached. Disconnect the wires from the old
which it was attachedwhich it was attached thermostat one at a time. the wallthe wall
the wall.
the wallthe wall
Guidelines for Thermostat/Sensor LocationsGuidelines for Thermostat/Sensor Locations
Guidelines for Thermostat/Sensor Locations
Guidelines for Thermostat/Sensor LocationsGuidelines for Thermostat/Sensor Locations
Do not let wires fall back intoDo not let wires fall back into
Do not let wires fall back into
Do not let wires fall back intoDo not let wires fall back into
Locate the thermostat/sensor about 5 ft. above floor level on an interior wall in an area that represents the average room temperature.
Do not mount directly on or near HVAC equipment or other sources of electrical noise.
Avoid locations close to windows or near adjoining outside walls, doors leading outside, areas close to air registers or their direct air flow or areas with poor circulation like alcoves. Avoid locating the sensor on a concrete wall, junction box or metal plate. Make sure there are no electrical wires, metal, pipes or duct work in the part of the wall chosen for the sensor location.
Thermostat and indoor sensor are not approved forThermostat and indoor sensor are not approved for
Thermostat and indoor sensor are not approved for
Thermostat and indoor sensor are not approved forThermostat and indoor sensor are not approved for installation in unconditioned space.installation in unconditioned space.
installation in unconditioned space.
installation in unconditioned space.installation in unconditioned space.
Mounting Thermostat and SensorMounting Thermostat and Sensor
Mounting Thermostat and Sensor
Mounting Thermostat and SensorMounting Thermostat and Sensor
1. Remove the packing material from the thermostat and sensor.
2. Pull the front covers of the thermostat and sensor straight off the bases. Forcing or prying will cause damage to the controls.
3. Using the thermostat and sensor bases as templates, place them on the selected wall locations and mark the location of all mounting holes (Figure 1 and 3), and the hole for the thermostat antenna wire illustrated in Figure 2.
4. Move bases out of the way and drill the holes. If mounting holes drilled are too large and do not allow you to tighten base snugly, use the plastic screw anchors (provided) for secure mounting.
5. Make sure the remote communication receiver is plugged in properly to the thermostat and that the antenna wire is routed through the thermostat subbase as shown in Figure 2.
6. Fasten bases loosely to wall, using two mounting screws for each. Place a level against bottom of base (leveling is for appearance only and will not affect sensor operation) and then tighten screws.
7. In the thermostat location, push excess wire into wall and plug hole with a fire resistant material (such as fiberglass insulation) to prevent drafts from affecting the thermostat operation.
2
8. Remove the battery tags in both the thermostat and sensor and replace the covers by lining them up with the base and pressing until they snap into place.
ELEC/GAS SWITCH
RC/PS SWITCH
ANTENNA
MOUNTING
HOLE
Figure 1 – Thermostat baseFigure 1 – Thermostat base
Figure 1 – Thermostat base
Figure 1 – Thermostat baseFigure 1 – Thermostat base
ANTENNA WIRE
Figure 2 – Back of thermostat baseFigure 2 – Back of thermostat base
Figure 2 – Back of thermostat base
Figure 2 – Back of thermostat baseFigure 2 – Back of thermostat base
Figure 3 – Remote sensor baseFigure 3 – Remote sensor base
Figure 3 – Remote sensor base
Figure 3 – Remote sensor baseFigure 3 – Remote sensor base
Battery LocationBattery Location
Battery Location
Battery LocationBattery Location
WIRE
MOUNTING HOLE
CM/NO CM SWITCH
REMOTE COMMUNICATION RECEIVER
The thermostat requires 2 "AA" alkaline batteries and the sensor requires 2 "AAA" alkaline batteries. Batteries are included at the factory with a battery tag to prevent power drainage. The battery tag must be removed to engage the batteries. For best results, replace batteries once a year with new premium brand alkaline batteries such as Duracell
®
Energizer
.
Electric/Gas Switch (Fan Option)Electric/Gas Switch (Fan Option)
Electric/Gas Switch (Fan Option)
Electric/Gas Switch (Fan Option)Electric/Gas Switch (Fan Option)
®
or
The ELEC/GAS switch is factory set to the ELEC position. In this position, the thermostat will power the circulator fan on a call for heat. Electric heat systems may require the switch to be in the ELEC position.
If your system does not require that the thermostat power the circulator fan, this switch should be set to the GAS position. Typically, gas and oil heating systems do not require the thermostat to power the circulator fan during a call for heat. If your heat is gas or oil, the switch should be set to the GAS position.
When the thermostat is configured for Heat Pump, the thermostat will always power the circulator fan on a call for heat in the HEAT mode. The ELEC/GAS switch must be set to match the type of Auxiliary heat your system uses for proper operation in the EMERgency mode.
RC/PS Switch (Thermostat Power Option)RC/PS Switch (Thermostat Power Option)
RC/PS Switch (Thermostat Power Option)
RC/PS Switch (Thermostat Power Option)RC/PS Switch (Thermostat Power Option)
RC/PSRC/PS
RC/PS
RC/PSRC/PS
SwitchSwitch
Switch
SwitchSwitch
PositionPosition
Position
PositionPosition
RC For Hardwire Applications. Requires Common Wire
from System Transformer to "C" Terminal on Thermostat
PS For Power Stealing Applications. Use When Common
from the System Transformer is not Available for Connection to the "C" Terminal on the Thermostat
NOTE: If set to PS (Power Stealing), the thermostat "C" terminal
must notmust not
must not
must notmust not
have a wire connected.
DescriptionDescription
Description
DescriptionDescription
Page 3
WIRING CONNECTIONSWIRING CONNECTIONS
WIRING CONNECTIONS
WIRING CONNECTIONSWIRING CONNECTIONS
Typical wiring diagrams are provided below for the following systems:
Single Stage Heat/Cool systems Multi-Stage Heat/Cool systems (No Heat Pump) Heat Pump system, one compressor or one speed compressor with Aux. Heat
Heat Pump systems, two compressors or two speed compressor with Aux. Heat Refer to the equipment manufacturers instructions for specific wiring information. After completing the connections configure the thermostat in the Installer Configuration Menu to match your system type.
Figure 4 – Single Stage (No Heat Pump) Terminal OutputsFigure 4 – Single Stage (No Heat Pump) Terminal Outputs
Figure 4 – Single Stage (No Heat Pump) Terminal Outputs
Figure 4 – Single Stage (No Heat Pump) Terminal OutputsFigure 4 – Single Stage (No Heat Pump) Terminal Outputs
W2
No Output
E/W1
Heat Mode 1st Stage (Heater)
G
Blower/ Circulator Fan Energized on Call for Cool or Fan, Energized on Call for Heat if Elect/Gas Switch Set to Electric
Energized in Cool Mode (Change­over Valve or Damper)
*C
Y1
Cool Mode 1st Stage (Compressor)
Y2
No Output
R
System
24 Volt
24 Volt
Single Stage
(SS1)
**
The RC/PS switch shown in Figure 1 configures the thermostat for Hardwire or Power Stealing.The RC/PS switch shown in Figure 1 configures the thermostat for Hardwire or Power Stealing.
*
The RC/PS switch shown in Figure 1 configures the thermostat for Hardwire or Power Stealing.
**
The RC/PS switch shown in Figure 1 configures the thermostat for Hardwire or Power Stealing.The RC/PS switch shown in Figure 1 configures the thermostat for Hardwire or Power Stealing.
(Hot)
(Common)
Optional
Connection
B
O
Energized in Heat, Off Mode (Change­over Valve or Damper)
L
Fault Indicator for Heat Pump Systems with Malfunction Switch
NEUTRAL
24VAC
HOT
CLASS II
TRANSFORMER
120VAC
The factory setting is RC (Hardwire) and requires a Common connection from the system transformer to the "C" terminal on the thermostat. If no common wire is available for the thermostat "C" terminal, move the RC/PS switch to PS (Power Steal-
G
Blower/ Circulator Fan Energized on Call for Cool or Fan, Energized on Call for Heat if Elect/Gas Switch Set to Electric
must notmust not
must not
must notmust not
O
Energized
Energized
in Heat, Off
in Cool
Mode
Mode
(Change-
(Change-
over Valve
over Valve
or Damper)
or Damper)
have a wire connected.
B
L
Fault Indicator for Heat Pump Systems with Malfunction Switch
NOTENOTE
ing).
NOTE: If set to PS (Power Stealing), the thermostat "C" terminal
NOTENOTE
Figure 5 – Multi-Stage (No Heat Pump) Terminal OutputsFigure 5 – Multi-Stage (No Heat Pump) Terminal Outputs
Figure 5 – Multi-Stage (No Heat Pump) Terminal Outputs
Figure 5 – Multi-Stage (No Heat Pump) Terminal OutputsFigure 5 – Multi-Stage (No Heat Pump) Terminal Outputs
W2
Y2
Heat
Heat
Mode
Mode
1st Stage
2nd Stage
System
Multi-Stage
(MS2)
R
24 Volt (Hot)
*C
24 Volt
(Common)
Optional
Connection
Y1
Cool Mode
1st Stage
(Compressor 1)
Cool Mode 2nd Stage
(Compressor 2)
E/W1
NEUTRAL
24VAC
HOT
CLASS II
TRANSFORMER
**
The RC/PS switch shown in Figure 1 configures the thermostat for Hardwire or Power Stealing.The RC/PS switch shown in Figure 1 configures the thermostat for Hardwire or Power Stealing.
*
The RC/PS switch shown in Figure 1 configures the thermostat for Hardwire or Power Stealing.
**
The RC/PS switch shown in Figure 1 configures the thermostat for Hardwire or Power Stealing.The RC/PS switch shown in Figure 1 configures the thermostat for Hardwire or Power Stealing.
120VAC
The factory setting is RC (Hardwire) and requires a Common connection from the system transformer to the "C" terminal on the thermostat. If no common wire is available for the thermostat "C" terminal, move the RC/PS switch to PS (Power Steal-
G
Blower/ Circulator Fan Energized on Call for Heat/Cool or Fan,
Note: Set Elect/Gas switch for Emergency Mode Heat Type
must notmust not
must not
must notmust not
O
Energized
Energized
in Heat, Off,
in Cool
Emergency
Mode
Mode
(Change-
(Change-
over Valve)
over Valve)
have a wire connected.
B
L
Fault Indicator for Heat Pump Systems with Malfunction Switch
NEUTRAL
24VAC
HOT
CLASS II
TRANSFORMER
120VAC
NOTENOTE
ing).
NOTE: If set to PS (Power Stealing), the thermostat "C" terminal
NOTENOTE
Figure 6 – Heat Pump Terminal OutputsFigure 6 – Heat Pump Terminal Outputs
Figure 6 – Heat Pump Terminal Outputs
Figure 6 – Heat Pump Terminal OutputsFigure 6 – Heat Pump Terminal Outputs
W2
Heat Mode 2nd Stage. Emergency Mode 2nd Stage
Heat Mode 3rd Stage. Emergency Mode 2nd Stage
E/W1
Emergency
Mode
1st Stage
R
*C
Y1
System
Heat Pump 1
(HP1) Single Compressor Heat Pump
Heat Pump 2
(HP2) Two Compressor or Two Speed Compressor
**
The RC/PS switch shown in Figure 1 configures the thermostat for Hardwire or Power Stealing.The RC/PS switch shown in Figure 1 configures the thermostat for Hardwire or Power Stealing.
*
The RC/PS switch shown in Figure 1 configures the thermostat for Hardwire or Power Stealing.
**
The RC/PS switch shown in Figure 1 configures the thermostat for Hardwire or Power Stealing.The RC/PS switch shown in Figure 1 configures the thermostat for Hardwire or Power Stealing.
24 Volt (Hot)
24 Volt
(Common)
Optional
Connection
Heat Mode-
1st Stage
Cool Mode-
1st Stage
(Compressor 1)
Y2
No Output
Heat Mode-
2nd Stage
Cool Mode-
2nd Stage
(Compressor 2)
The factory setting is RC (Hardwire) and requires a Common connection from the system transformer to the "C" terminal on the thermostat. If no common wire is available for the thermostat "C" terminal, move the RC/PS switch to PS (Power Steal-
NOTENOTE
ing).
NOTE: If set to PS (Power Stealing), the thermostat "C" terminal
NOTENOTE
must notmust not
must not
must notmust not
have a wire connected.
3
Page 4
THERMOSTAT/REMOTE SENSOR QUICK REFERENCETHERMOSTAT/REMOTE SENSOR QUICK REFERENCE
THERMOSTAT/REMOTE SENSOR QUICK REFERENCE
THERMOSTAT/REMOTE SENSOR QUICK REFERENCETHERMOSTAT/REMOTE SENSOR QUICK REFERENCE
Before operating the thermostat, familiarize yourself with the display and button functions. Both thermostat and remote sensor consist of two parts: the cover and the base. To remove a cover, pull it straight out from the base. To replace a cover, line it up with the base and press until the cover snaps into place on the base.
The Thermostat Buttons and Switches and DisplayThe Thermostat Buttons and Switches and Display
The Thermostat Buttons and Switches and Display
The Thermostat Buttons and Switches and DisplayThe Thermostat Buttons and Switches and Display
Raises and lowers the temperature setting.
1
Light flashes every 20 seconds indicating acceptable
2
signal reception from indoor or outdoor remote sensor. Buttons for setting time (Time), programming (Prgm),
3
running program (Run) and bypassing program to hold a constant temperature (Hold).
6
2
5
4
7
ONON
ON,
ONON
COOLCOOL
COOL,
COOLCOOL
AUTOAUTO
AUTO).
AUTOAUTO
SYSTEM button (
4
heat pump systems only). FAN switch (
5
Displays the active temperature sensor (outside,
6
remote, local) and its sensed temperature. Displays ( ) when in keypad lockout mode.
7
Indicates day of the week.
8
Indicates the thermostat mode information:
9
HOLDHOLD
"
HOLD" alternates with the system mode (see item 12)
HOLDHOLD if the HOLD button is pressed to bypass the program and maintain a constant temperature.
Displays currently programmed set temperature (blank
10
SYSTEM SYSTEM
when
SYSTEM is
SYSTEM SYSTEM
Alternately displays the current time and the tempera-
11
ture average of sensors (thermostat [local] and/or indoor remote) turned on.
HEATHEAT
"
HEAT" is displayed when set to heating,
HEATHEAT
12
COOLCOOL
"
COOL" is displayed when set to cooling,
COOLCOOL
AUTOAUTO
"
AUTO" is displayed when set for automatic change-
AUTOAUTO over between heating and cooling.
AUTOAUTO
When "
AUTO" is displayed, the currently active mode
AUTOAUTO
(Heat or Cool) will also display.
EMEREMER
"
EMER" is displayed flashing (heat pump systems
EMEREMER only) when the thermostat is set to the Emergency Mode. Emergency is used to bypass the heat pump and use only the back-up heating system.
FLTRFLTR
"
FLTR" is displayed as a reminder to change or clean
FLTRFLTR the air filter after system has run for the programmed filter time period.
OFFOFF
OFF).
OFFOFF
AUTOAUTO
AUTO,
AUTOAUTO
HEATHEAT
HEAT,
HEATHEAT
OFF, EMEROFF, EMER
OFF, EMER
OFF, EMEROFF, EMER
12
14
15
16
17
Figure 7 – Thermostat display, buttons and switchesFigure 7 – Thermostat display, buttons and switches
Figure 7 – Thermostat display, buttons and switches
Figure 7 – Thermostat display, buttons and switchesFigure 7 – Thermostat display, buttons and switches
Displays "
14
activated. Limited range limits the temperature the thermostat can be set to.
Indicates the system is sending a fault signal to the
15
thermostat "L" terminal. This does not indicate a fault in the thermostat.
Antenna will display for a few seconds when the remote
16
or outdoor transmitted signal is received.
LRLR
LR" when the limited range feature is
LRLR
18
1311
8
9
10
Stage 1 & 2 indicator.
13
STG 1STG 1
"
STG 1" indicates when the first stage heat or cool is
STG 1STG 1 energized. " heat or cool is energized. "+2" blinking indicates Auxiliary Heat stages are energized on Heat Pump Systems.
STG + 2STG + 2
STG + 2" indicates when the second stage
STG + 2STG + 2
4
Displays "LOW BATT" when the 2 "AA" batteries are
17
low and should be replaced. Indicates the current signal strength level of the remote
18
temperature system. Signal strength level is low (one bar on), medium (two bars on) or high (three bars on). The remote will operate with 1 bar showing.
Page 5
THERMOSTAT/SENSOR QUICK REFERENCETHERMOSTAT/SENSOR QUICK REFERENCE
THERMOSTAT/SENSOR QUICK REFERENCE
THERMOSTAT/SENSOR QUICK REFERENCETHERMOSTAT/SENSOR QUICK REFERENCE
The Sensor Buttons and DisplayThe Sensor Buttons and Display
The Sensor Buttons and Display
The Sensor Buttons and DisplayThe Sensor Buttons and Display
Raises the setting.
1
Lowers the setting.
2
Sensed temperature from –40 to 140°F with °F and °C
3
indicator
Channel identification A B C O indicator
4
9 bar comfort adjust graph with H (hotter) and C (cooler)
5
Transmission occurrence indicator
6
Keypad lockout indicator
7
Calibrate temperature offset indicator
8
Learn mode activated indicator
9
Low battery indicator
10
Temperature offset used when hold time is active
11
Figure 8 – Remote Sensor display and buttonsFigure 8 – Remote Sensor display and buttons
Figure 8 – Remote Sensor display and buttons
Figure 8 – Remote Sensor display and buttonsFigure 8 – Remote Sensor display and buttons
Normal OperationNormal Operation
Normal Operation
Normal OperationNormal Operation
3
o
6
A
Configuration ItemsConfiguration Items
Configuration Items
Configuration ItemsConfiguration Items
1
2
4
5
Alternates PWR and on to indicate normal operation
12
with display turned OFF
6
PWR HLD
12
11
3
BATT
10
o
LOCK
ABCO
CALIB
LEARN
9
H
C
5
7
4
8
5
5
5
Page 6
THERMOSTTHERMOST
THERMOST
THERMOSTTHERMOST
Press the System button until
PressPress
Press
PressPress
StepStep
Step
StepStep
Button(s)Button(s)
Button(s)
Button(s)Button(s)
AA
T CONFIGURAT CONFIGURA
A
T CONFIGURA
AA
T CONFIGURAT CONFIGURA
INSTALLER/CONFIGURATION MENUINSTALLER/CONFIGURATION MENU
INSTALLER/CONFIGURATION MENU
INSTALLER/CONFIGURATION MENUINSTALLER/CONFIGURATION MENU
DisplayedDisplayed
Displayed
DisplayedDisplayed
(Factory Default)(Factory Default)
(Factory Default)
(Factory Default)(Factory Default)
TION MENUTION MENU
TION MENU
TION MENUTION MENU
OFF OFF
OFF is displayed, then press the and simultaneously
OFF OFF
Press Press
Press
Press Press
or or
or
or or
to selectto select
to select
to selectto select
CommentsComments
Comments
CommentsComments
10 11 12 13 14
15
16
17 18 19 20 21
1
2 3
4 5 6 7 8 9
SystemSystem
System
SystemSystem
SystemSystem
System
SystemSystem SystemSystem
System
SystemSystem SystemSystem
System
SystemSystem SystemSystem
System
SystemSystem SystemSystem
System
SystemSystem SystemSystem
System
SystemSystem SystemSystem
System
SystemSystem SystemSystem
System
SystemSystem SystemSystem
System
SystemSystem SystemSystem
System
SystemSystem SystemSystem
System
SystemSystem SystemSystem
System
SystemSystem SystemSystem
System
SystemSystem
SystemSystem
System
SystemSystem
SystemSystem
System
SystemSystem
SystemSystem
System
SystemSystem SystemSystem
System
SystemSystem SystemSystem
System
SystemSystem SystemSystem
System
SystemSystem
RunRun
Run Returns to the OFF mode
RunRun
CR HEAT COOL CR HEAT COOL
CR HEAT COOL
CR HEAT COOL CR HEAT COOL
FA HEAT COOL FA HEAT COOL
FA HEAT COOL
FA HEAT COOL FA HEAT COOL
(Room Temperature)(Room Temperature)
(Room Temperature)
(Room Temperature)(Room Temperature)
MS2MS2
MS2
MS2MS2
LER (OFF)LER (OFF)
LER (OFF)
LER (OFF)LER (OFF)
OUTSIDE OUTSIDE
OUTSIDE
OUTSIDE OUTSIDE REMOTE REMOTE
REMOTE
REMOTE REMOTE
LOCAL LOCAL
LOCAL
LOCAL LOCAL
CH CH
CH
CH CH PRG 4PRG 4
PRG 4
PRG 4PRG 4
EMR EMR
(ON)(ON)
EMR
(ON)
EMR EMR
(ON)(ON)
CL CL
(OFF)(OFF)
CL
(OFF)
CL CL
(OFF)(OFF)
CdL CdL
(ON)(ON)
CdL
(ON)
CdL CdL
(ON)(ON)
0 FLTR0 FLTR
0 FLTR
0 FLTR0 FLTR
0 F0 F
0 F
0 F0 F
4:00 HOLD4:00 HOLD
4:00 HOLD
4:00 HOLD4:00 HOLD
FF
F
FF
LR HEAT LR HEAT
LR HEAT
LR HEAT LR HEAT LR COOL LR COOL
LR COOL
LR COOL LR COOL
CA CA
(OFF)(OFF)
CA
(OFF)
CA CA
(OFF)(OFF)
OFF LOCKOFF LOCK
OFF LOCK
OFF LOCKOFF LOCK 0 00 LOCK0 00 LOCK
0 00 LOCK
0 00 LOCK0 00 LOCK
(OFF)(OFF)
(OFF)
(OFF)(OFF)
(OFF)(OFF)
(OFF)
(OFF)(OFF)
(ON)(ON)
(ON)
(ON)(ON)
(0)(0)
(0)
(0)(0)
(90)(90)
(90)
(90)(90)
(45)(45)
(45)
(45)(45)
SS1, HP2, HP1SS1, HP2, HP1
SS1, HP2, HP1 Selects Single stage, Multi-stage, or Heat Pump
SS1, HP2, HP1SS1, HP2, HP1
LER (ON)LER (ON)
LER (ON) Selects learn mode OFF or ON
LER (ON)LER (ON)
OUTSIDE OUTSIDE
OUTSIDE
OUTSIDE OUTSIDE
REMOTE REMOTE
REMOTE
REMOTE REMOTE
LOCAL LOCAL
LOCAL
LOCAL LOCAL
PRG 0, PRG 2PRG 0, PRG 2
PRG 0, PRG 2 Selects Programmable Periods
PRG 0, PRG 2PRG 0, PRG 2
EMR EMR
EMR
EMR EMR
(FA)(FA)
(FA)
(FA)(FA)
(ON)(ON)
(ON)
(ON)(ON)
FA HEAT COOL FA HEAT COOL
FA HEAT COOL
FA HEAT COOL FA HEAT COOL
0–19500–1950
0–1950
0–19500–1950
4 LO to 4 HI4 LO to 4 HI
4 LO to 4 HI Selects Temperature Display Adjustment 4 LO 4 HI
4 LO to 4 HI4 LO to 4 HI
0:00 to 8:000:00 to 8:00
0:00 to 8:00 Selects Temporary Program Override Time
0:00 to 8:000:00 to 8:00
(Increments of 15 minutes)(Increments of 15 minutes)
(Increments of 15 minutes) 0:00 =Disabled
(Increments of 15 minutes)(Increments of 15 minutes)
LR 62 to LR 89LR 62 to LR 89
LR 62 to LR 89 Selects Limited HEAT range
LR 62 to LR 89LR 62 to LR 89 LR 46 to LR 82LR 46 to LR 82
LR 46 to LR 82 Selects Limited COOL range
LR 46 to LR 82LR 46 to LR 82
(ON)(ON)
(ON) Selects OUTSIDE sensor OFF or ON
(ON)(ON) (ON)(ON)
(ON) Selects REMOTE (indoor) sensor OFF or ON
(ON)(ON)
(OFF)(OFF)
(OF F) Selects LOCAL sensor ON or OFF
(OFF)(OFF)
1 to 91 to 9
1 to 9 Select Receiver frequency offset
1 to 91 to 9
(OFF)(OFF)
(OFF) Selects Energy Management Recovery OFF or ON
(OFF)(OFF)
SLSL
SL Selects Fast or Slow cycle selection
SLSL
CL CL
(ON)(ON)
CL
(ON) Selects Compressor Lockout CL OFF or ON
CL CL
(ON)(ON)
CdL CdL
(OFF)(OFF)
CdL
(OF F ) Selects Backlight Display ON or OFF
CdL CdL
(OFF)(OFF)
(OFF)(OFF)
(OF F ) Selects Fast Second Stage ON or OFF
(OFF)(OFF)
(increments of 50)(increments of 50)
(increments of 50) Selects filter replacement run time.0 =Disabled
(increments of 50)(increments of 50)
CC
C For C selection
CC
CA CA
(ON)(ON)
CA
(ON) Selects Comfort Alert Lock
CA CA
(ON)(ON)
ON LOCKON LOCK
ON LOCK Selects Buttonpad Lockout
ON LOCKON LOCK
001 to 999001 to 999
001 to 999 Selects Buttonpad lockout combination number
001 to 999001 to 999
(Single stage or 2-stage) system configuration
Selects temperature display as F° or C°
Press System to set code
The configuration menu allows you to set certain thermostat operating characteristics to your system or personal require­ments.
Set SYSTEM button to
OFFOFF
OFF, then simultaneously press
OFFOFF
and to enter configuration menu. The display will
show the first item in the configuration menu.
The configuration menu table summarizes the configuration options. An explanation of each option follows.
Press SYSTEM to change to the next menu item. To exit the menu and return to the program operation, press RUN. If no keys are pressed within fifteen minutes, the thermostat will revert to normal operation.
Single Stage, Multi-stage or Heat Pump ConfigurationSingle Stage, Multi-stage or Heat Pump Configuration
1)
Single Stage, Multi-stage or Heat Pump Configuration
Single Stage, Multi-stage or Heat Pump ConfigurationSingle Stage, Multi-stage or Heat Pump Configuration This menu item requires you configure the thermostat to match your system. Choose your system option from the table below:
System TypeSystem Type
System Type
System TypeSystem Type Single Stage Heat/Cool systems SS1 Multi-Stage Heat/Cool systems (No Heat Pump) MS2 Heat Pump system, 1 compressor or 1 speed compressor HP1 Heat Pump systems, 2 compressors or 2 speed compressor HP2
Select OptionSelect Option
Select Option
Select OptionSelect Option
The thermostat is factory defaulted to MS2. To select a different option, press the or key to scroll through the choices.
6
Select Learn Mode On or OffSelect Learn Mode On or Off
2)
Select Learn Mode On or Off – Selecting
Select Learn Mode On or OffSelect Learn Mode On or Off
LER OnLER On
LER On
LER OnLER On enables the learn mode of the thermostat receiver. Your thermostat is configured at the factory to recognize the remote sensor shipped with it. The Learn Mode Option is used only when required as described in OptionOption
Option.
OptionOption Selects OUTSIDE sensor OFF or ONSelects OUTSIDE sensor OFF or ON
3)
Selects OUTSIDE sensor OFF or ON – Selec ting
Selects OUTSIDE sensor OFF or ONSelects OUTSIDE sensor OFF or ON
Learn ModeLearn Mode
Learn Mode
Learn ModeLearn Mode
OUTSIDE ON enables the thermostat to read a wireless outdoor temperature sensor that has been configured for Sensor O in the Learn Mode. This allows the thermostat to display the outdoor temperature reading. Selects REMOTE sensor OFF or ON Selects REMOTE sensor OFF or ON
4)
Selects REMOTE sensor OFF or ON – Selecting
Selects REMOTE sensor OFF or ON Selects REMOTE sensor OFF or ON REMOTE ON allows the thermostat to sense an indoor remote sensor that has been set-up the Learn mode. The maximum number of Indoor Remote Sensors is 1 configured to sensor A, B or C. Selects LOCAL sensor ON or OFF Selects LOCAL sensor ON or OFF
5)
Selects LOCAL sensor ON or OFF – Selecting LOCAL
Selects LOCAL sensor ON or OFF Selects LOCAL sensor ON or OFF ON allows the thermostat to use the onboard temperature sensor exclusively or for averaging with the remote sensor readings. To control temperature using only the indoor remote sensor temperature(s), use the buttons to select Select Receiver frequency offsetSelect Receiver frequency offset
6)
Select Receiver frequency offset – This option allows
Select Receiver frequency offsetSelect Receiver frequency offset
LOCAL OFFLOCAL OFF
LOCAL OFF.
LOCAL OFFLOCAL OFF
or
you to select a different channel than the factory default for communication between the thermostat and remote sensor. Note: If a different channel is selected on the thermostat it must also be changed to the same
Page 7
THERMOSTTHERMOST
THERMOST
THERMOSTTHERMOST
setting on the remote. This is only used in areas where there are other wireless devices or electronic equipment that interfere with the default frequency of the thermostat/ remote sensor communication. Programmable Periods Programmable Periods
7)
Programmable Periods – This control can be config-
Programmable Periods Programmable Periods ured for 4, 2 or 0 programmable periods. The display indicates " mable periods can be changed to 2 or 0 by pressing the
or keys. With " mable, SYSTEM key selection will skip temporary program override (item 15). Select Energy Management Recovery OFF or ONSelect Energy Management Recovery OFF or ON
8)
Select Energy Management Recovery OFF or ON –
Select Energy Management Recovery OFF or ONSelect Energy Management Recovery OFF or ON Energy Management Recovery (EMR) causes the thermostat to start heating or cooling early to make the building temperature reach the program setpoint at the time you specify. Heating will start 5 minutes early for every 1° of temperature required to reach setpoint. Example:Example:
Example: You select EMR and have your heating
Example:Example: programmed to 65° at night and 70° at 7 AM. If the building temperature is 65° the difference between 65° and 70° is 5°. Allowing 5 minutes per degree the thermo­stat setpoint will change to 70° at 6:35 AM. Cooling allows more time per degree because it takes longer to reach temperature. Fast or Slow Cycle SelectionFast or Slow Cycle Selection
9)
Fast or Slow Cycle Selection – The factory default
Fast or Slow Cycle SelectionFast or Slow Cycle Selection setting is fast cycle, which cycles 1st stage at approxi­mately 1.2°F and 2nd stage 0.75°F. If you prefer slow cycle, press the temperature key to change to SL. The 1st stage and 2nd stage would be 1.5°F and 1.2°F respec­tively. Select Compressor Lockout CL OFF or ONSelect Compressor Lockout CL OFF or ON
10)
Select Compressor Lockout CL OFF or ON – Selecting
Select Compressor Lockout CL OFF or ONSelect Compressor Lockout CL OFF or ON CL ON will cause the thermostat to wait 5 minutes before turning on the compressor if the heating and cooling system loses power. It will also wait 5 minutes minimum between cooling and heating cycles. This is intended to help protect the compressor from short cycling. Some newer compressors already have a time delay built in and do not require this feature. Your compressor manufac­turer can tell you if the lockout feature is already present in their system. When the thermostat compressor time delay occurs it will flash the setpoint for about five minutes. Select Backlight DisplaySelect Backlight Display
11)
Select Backlight Display – The display backlight
Select Backlight DisplaySelect Backlight Display improves display contrast in low lighting conditions. When the "C" terminal is powered, selecting backlight CdL ON will keep the light on continuously. Select backlight OFF will keep the light on momentarily after any key is pressed. When the "C" terminal is not powered, the light will be on momentarily after any key is pressed no matter the backlight is selected ON or OFF. Select Fast Second Stage On or OFFSelect Fast Second Stage On or OFF
12)
Select Fast Second Stage On or OFF –
Select Fast Second Stage On or OFFSelect Fast Second Stage On or OFF During normal operation if the setpoint temperature is manually raised by 3°F or more above the actual tem­perature with the feature is enabled, FA ON, the second stage will energize immediately. For Cool: During normal operation if the setpoint tempera­ture is manually lowered by 3°F or more below the actual temperature with the feature is enabled, FA ON, the second stage will energize immediately. Select filter replacement run timeSelect filter replacement run time
13)
Select filter replacement run time – The thermostat will
Select filter replacement run timeSelect filter replacement run time display " reminder to change or clean your air filter. This time can be set from 0 to 1950 hours in 50 hour increments. selection of 0 will cancel this featureselection of 0 will cancel this feature
selection of 0 will cancel this feature. When "
selection of 0 will cancel this featureselection of 0 will cancel this feature displayed, you can clear it by pressing HOLD and RUN at the same time. This resets the timer and starts counting the hours until the next filter change. Contact your system manufacturer for a specific replacement/maintenance interval. Select Temperature Display Adjustment 4 LO to 4 HISelect Temperature Display Adjustment 4 LO to 4 HI
14)
Select Temperature Display Adjustment 4 LO to 4 HI –
Select Temperature Display Adjustment 4 LO to 4 HISelect Temperature Display Adjustment 4 LO to 4 HI Allows you to adjust the room temperature display up to
FLTRFLTR
FLTR"
FLTRFLTR
AA
T CONFIGURAT CONFIGURA
A
T CONFIGURA
AA
T CONFIGURAT CONFIGURA
PRG 4PRG 4
PRG 4" in the display as default. The program-
PRG 4PRG 4
PRG 0PRG 0
PRG 0" selected for non-program-
PRG 0PRG 0
button, and the fast second stage
button, and the fast second stage
after a set time of operation. This is a
TION MENUTION MENU
TION MENU
TION MENUTION MENU
EMREMR
EMR (item 8) and
EMREMR
For HeatFor Heat
For Heat:
For HeatFor Heat
FLTRFLTR
FLTR"
FLTRFLTR
4° higher or lower. Your thermostat was accurately calibrated at the factory but you have the option to change the display temperature to match your previous thermostat. The current or adjusted room temperature will be displayed on the left side of the display. Select Temporary Program Override TimeSelect Temporary Program Override Time
15)
Select Temporary Program Override Time – The thermo-
Select Temporary Program Override TimeSelect Temporary Program Override Time stat can hold any temperature you set it to for the amount of time you select on this option. Your choices are 0:00 to 8:00 hours in 15 minute increments. 0:00 means disable. Example:
1. You have selected 3:00 hours for the Temporary Pro­gram Override time period.
2. With the thermostat set to Heat or Cool, press HOLD for approximately 5 secondsfor approximately 5 seconds
for approximately 5 seconds until "
for approximately 5 secondsfor approximately 5 seconds (indicating 3 hours) appears as a setting reminder.
3. After releasing the button, " blink.
4. Use
Select F° or C° ReadoutSelect F° or C° Readout
16)
Select F° or C° Readout – Changes the display readout
Select F° or C° ReadoutSelect F° or C° Readout to Celsius or Fahrenheit as required. Limited Heat RangeLimited Heat Range
17)
Limited Heat Range – This feature provides a maximum
Limited Heat RangeLimited Heat Range setpoint temperature for heat. The default setting is 90°F. It can be changed between 62°F and 89°F by pressing the
or key.
Limited Cool RangeLimited Cool Range
18)
Limited Cool Range – This feature provides a minimum
Limited Cool RangeLimited Cool Range setpoint temperature for cool. The default setting is 45°F. It can be changed between 46°F and 82°F by pressing the
or key.
Comfort Alert Comfort Alert
19)
Comfort Alert – This feature is available in Passive
Comfort Alert Comfort Alert mode on this thermostat. If a Comfort Alert module is connected, the thermostat will receive and flash the fault codes from the Comfort Alert module.
20 & 21)
display the function and display the not locked out, default) indicating in the time digits to the lock lock
lock icon and
lock lock lockout function is enabled ( is pressed again, the display will indicate the number (default, still disabled) in the time digits. The are used to set the combination number from a combination of is pressed, the menu will be exited and keypad will not be locked. If pressed again, the combination is locked into non-volatile memory and the menu is exited. The designate keypad locked with a valid combination) will display when the menu is exited. The SYSTEM button will operate for 10 seconds after the menu mode is exited to allow the user to change the mode from desired system mode.
While the keypad is locked out, a simultaneous press of
and will enter the menu item from any mode instead of only with the keypad lockout feature enabled, the item displayed is the combination code keys are used to set the combination unlock number from 00
0 to
00
AA
A
AA
is
combination lock number stored in memory when the SYSTEM button is pressed, the keypad is unlocked and the match when the SYSTEM exited and the keypad remains disabled.
To reset the combination code and unlock the keypad if the code is forgotten, see troubleshooting section, page
16.
or to set the temperature to your prefer ence. The thermostat will maintain this temperature setting for 3 hours with " it is in Temporary Hold. After 3 hours, the thermostat will go back to the program temperature and " will no longer blink or display.
Keypad LockoutKeypad Lockout
Keypad Lockout – This menu selection will
Keypad LockoutKeypad Lockout
lock lock
) icon. The and are used to toggle
lock (
lock lock
ON ON
ON (keypad locked out). When the keypad
ON ON
000000
00 0 is selected and the SYSTEM button
000000
1 to 9991 to 999
1 to 999 is selected and the SYSTEM button is
1 to 9991 to 999
OFF OFF
OFF mode. When the menu is entered
OFF OFF
999999
99 9. If the unlock number matches exactly with the
999999
lock lock
lock icon is removed. If the unlock number does not
lock lock
HOLDHOLD
HOLD"
HOLDHOLD
HOLDHOLD
HOLD"
HOLDHOLD
lock lock
lock icon and
lock lock
ONON
ON), and the SYSTEM button
ONON
button is pressed, menu is
HOLD time 3:00HOLD time 3:00
HOLD time 3:00"
HOLD time 3:00HOLD time 3:00
on the display will
blinking to remind you
HOLDHOLD
HOLD"
HOLDHOLD
OFF OFF
OFF (keypad
OFF OFF
000000
000
000000
and
00
999999
0 to
999. If
00
999999
lock lock
lock icon (to
lock lock
OFF OFF
OFF to the
OFF OFF
first menu
00
0. The
00
or
7
Page 8
REMOREMO
REMO
REMOREMO
The configuration menus allow you to set certain remote sensor operating characteristics to your system or personal require­ments. Two configuration menus are available, User Configuration and Installer Configuration.
User Configuration MenuUser Configuration Menu
User Configuration Menu
User Configuration MenuUser Configuration Menu Momentarily press and keys at the same time and release to enter the User menu. To scroll through the menu items press the scroll through all menu items. If no buttons are pushed for 3 minutes, the control will also return to normal operation. The User Configuration Menu table summarizes the configuration options. An explanation of each option follows.
StepStep
Step
StepStep
1 2 and 3 4 5 and dL OF Select display backlight OFF or ON 6 7
TE SENSOR CONFIGURATE SENSOR CONFIGURA
TE SENSOR CONFIGURA
TE SENSOR CONFIGURATE SENSOR CONFIGURA
and keys at the same time. To change the item option press or . To exit the menu
Press button(s)Press button(s)
Press button(s)
Press button(s)Press button(s) to scroll menuto scroll menu
to scroll menu
to scroll menuto scroll menu
and
and and d
and and _____ _____ Exits user menu and returns to normal
DisplayedDisplayed
Displayed
DisplayedDisplayed (factory default)(factory default)
(factory default)
(factory default)(factory default) LOCKLOCK
LOCK on Select keypad lockout OFF or ON
LOCKLOCK (OF) HLDHLD
HL D 1 to 8 hrs Select temporary adjust temperature
HLDHLD (4h) in 1 hour increments hold time CALIBCALIB
CALIB 1-4 bars (1°-4°) C to Select temperature display adjustment
CALIBCALIB (Sensed Temperature) 1-4 bars (1°-4°) H higher or lower
F
(on) (on)
o
F
(Sensed Temperature)
TION MENUTION MENU
TION MENU
TION MENUTION MENU
User configuration menuUser configuration menu
User configuration menu
User configuration menuUser configuration menu
Press Press
Press
Press Press to change optionto change option
to change option
to change optionto change option
OF Select display temperature OFF or ON
o
C Select temperature display to F or C
or or
or
or or
Comments Comments
Comments
Comments Comments
operation
Select keypad lockout OFF or ONSelect keypad lockout OFF or ON
1)
Select keypad lockout OFF or ON – Selecting
Select keypad lockout OFF or ONSelect keypad lockout OFF or ON ON ON
ON will cause the keypad to be locked in the normal
ON ON operation mode. This prevents the and from being used to adjust temperature. The display will indicate " is selected, the When the keypad is locked, the and keys can still be pressed at the same time to enter the configura­tion menu.
Select temporary adjust temperature hold time Select temporary adjust temperature hold time
2)
Select temporary adjust temperature hold time –
Select temporary adjust temperature hold time Select temporary adjust temperature hold time Selects the length of time for the temporary temperature adjustment. Hold time default is 4 hours and can be set from 1 to 8 hours in 1 hour increments.
Select temperature display adjustment higher orSelect temperature display adjustment higher or
3)
Select temperature display adjustment higher or
Select temperature display adjustment higher orSelect temperature display adjustment higher or lowerlower
lower – allows you to adjust the room temperature
lowerlower display 1° to 4° higher or lower. Your sensor was accu­rately calibrated at the factory but you have the option to
LOCKLOCK
LOCK" when the keypad is locked. If
LOCKLOCK
and keys can still be used.
LOCKLOCK
LOCK
LOCKLOCK
LOCK OFLOCK OF
LOCK OF
LOCK OFLOCK OF
change the display temperature to match your previous sensor or thermostat.
Select display temperature OFF or ONSelect display temperature OFF or ON
4)
Select display temperature OFF or ON – Selecting
Select display temperature OFF or ONSelect display temperature OFF or ON allows you to disable displaying the sensed temperature. Instead of the temperature, the sensor will display " with the word
Select display backlight OFF or ONSelect display backlight OFF or ON
5)
Select display backlight OFF or ON -. The display
Select display backlight OFF or ONSelect display backlight OFF or ON backlight improves display contrast in low lighting conditions. Selecting short period of time after any key is pressed. Selecting OF OF
OF will keep the light off.
OF OF Select temperature display to Select temperature display to
6)
Select temperature display to
Select temperature display to Select temperature display to display readout to Celsius or Fahrenheit as required.
onon
on to indicate normal operation.
onon
dL ondL on
dL on will keep the light on for a
dL ondL on
oo
oo
o
o
oo
oo
F or F or
CC
F or
C - Changes the
F or F or
CC
OFOF
OF
OFOF
PWRPWR
PWR"
PWRPWR
8
Page 9
REMOREMO
REMO
REMOREMO
Installer Configuration MenuInstaller Configuration Menu
Installer Configuration Menu
Installer Configuration MenuInstaller Configuration Menu Your thermostat is configured at the factory to recognize the remote sensor it is shipped with as indoor sensor A. The Installer Configuration Menu is used only when adding or replacing a remote sensor or selecting a frequency offset. Press the menu items, momentarily press the
operation. The Installer Configuration Menu table summarizes the configuration options. An explanation of each option follows.
StepStep
Step
StepStep 1
2 3 4 and _____ _____ Exit installer menu and return to normal
TE SENSOR CONFIGURATE SENSOR CONFIGURA
TE SENSOR CONFIGURA
TE SENSOR CONFIGURATE SENSOR CONFIGURA
and buttons for a minimum of five seconds at the same time to enter the Installer menu. To scroll through
and buttons at the same time. To change the item option, press or
. To exit the menu scroll through all menu items. If no buttons are pushed for 3 minutes, the control will return to normal
Installer Configuration MenuInstaller Configuration Menu
Installer Configuration Menu
Installer Configuration MenuInstaller Configuration Menu
Press button(s)Press button(s)
Press button(s)
Press button(s)Press button(s)
to scroll menuto scroll menu
to scroll menu
to scroll menuto scroll menu
and and and
DisplayedDisplayed
Displayed
DisplayedDisplayed (factory default)(factory default)
(factory default)
(factory default)(factory default) LEARNLEARN
LEARN on Select learn mode OFF or ON
LEARNLEARN (OF) CHCH
CH B, C, O Select sensor identification as A, B, C or O
CHCH (A) CC
C 1 through 9 Select transmitter frequency offset
CC (0)
TION MENUTION MENU
TION MENU
TION MENUTION MENU
Press Press
Press
Press Press to change optionsto change options
to change options
to change optionsto change options
operation
or or
or
or or
Comments Comments
Comments
Comments Comments
Select learn mode OFF or ONSelect learn mode OFF or ON
1)
Select learn mode OFF or ON – Selecting
Select learn mode OFF or ONSelect learn mode OFF or ON enables the sensors learning mode. In the learning mode the sensor will transmit identification information once every 10 seconds for a period of 10 minutes. The LEARN icon will be displayed during the learning mode. The transmitter icon will be displayed for a short period of time with each transmission. See Learn Mode Option.
Select sensor identification from A to OSelect sensor identification from A to O
2)
Select sensor identification from A to O – For multiple
Select sensor identification from A to OSelect sensor identification from A to O sensors systems, each sensor must have a designated identification. The thermostat can operate with one indoor sensor and one outdoor sensor. For indoor sensors you may select A, B or C. For outdoor sensor you must select O.
OPERATING YOUR THERMOSTAT AND REMOTE SENSOROPERATING YOUR THERMOSTAT AND REMOTE SENSOR
OPERATING YOUR THERMOSTAT AND REMOTE SENSOR
OPERATING YOUR THERMOSTAT AND REMOTE SENSOROPERATING YOUR THERMOSTAT AND REMOTE SENSOR
Check Thermostat OperationCheck Thermostat Operation
Check Thermostat Operation
Check Thermostat OperationCheck Thermostat Operation
NOTE
To prevent static discharge problems, touch side ofTo prevent static discharge problems, touch side of
To prevent static discharge problems, touch side of
To prevent static discharge problems, touch side ofTo prevent static discharge problems, touch side of thermostat to release static build-up before touchingthermostat to release static build-up before touching
thermostat to release static build-up before touching
thermostat to release static build-up before touchingthermostat to release static build-up before touching any keys.any keys.
any keys.
any keys.any keys.
If at any time during testing your system does not operate properly, contact a qualified service person.
Fan OperationFan Operation
Fan Operation
Fan OperationFan Operation
If your system does not have a Heating SystemHeating System
Heating System.
Heating SystemHeating System
1. Turn on power to system.
2. Move FAN switch to begin to operate.
3. Move FAN switch to stop immediately.
ON ON
ON position. The blower should
ON ON AUTO AUTO
AUTO position. The blower should
AUTO AUTO
G G
G terminal connection, skip to
G G
LEARN onLEARN on
LEARN on
LEARN onLEARN on
Select transmitter frequency offsetSelect transmitter frequency offset
3)
Select transmitter frequency offset – The sensor’s
Select transmitter frequency offsetSelect transmitter frequency offset transmitter operates on 418MHz radio frequency by default. Interference may occur if another device or equipment operates on the same frequency. The interfer­ence may degrade the communications between the sensor and the thermostat. To avoid interference, you may select a different radio frequency for your sensor. This menu item allows you to select a radio frequency offset from 1 to 9MHz from the base frequency. For example; if the you selected an offset of 4, the transmitter radio frequency will be 418MHz + 4MHz = 422MHz. Note that the sensor’s transmitter and the thermostat’s receiver must operate on the same frequency to communicate. To change thermostat’s receiver frequency please refer to Thermostat Configuration Menu.
Heating SystemHeating System
Heating System
Heating SystemHeating System
1. Press SYSTEM button to select heating system has a standing pilot, be sure to light it.
2. Press temperature. The heat pump system should begin to operate. The display should show " system configuration is set to HP1 or HP2 and setpoint temperature display is flashing, the 5 minute compressor lockout feature is operating (see Configuration menu, item 10).
3. Adjust temperature setting to 3° above room temperature. If your system configuration is set at MS2, HP2 or HP1, the auxiliary heat system should begin to operate and the display will show "
4. Press ture. The heating system should stop operating.
to adjust thermostat setting to 1° above room
STG 1+2STG 1+2
STG 1+2".
STG 1+2STG 1+2
to adjust the thermostat below room tempera-
HEATHEAT
HEAT. If the auxiliary
HEATHEAT
STG1STG1
STG1". However, if the
STG1STG1
CAUTION
!
Do not allow the compressor to run unless the compres-Do not allow the compressor to run unless the compres-
Do not allow the compressor to run unless the compres-
Do not allow the compressor to run unless the compres-Do not allow the compressor to run unless the compres­sor oil heaters have been operational for 6 hours andsor oil heaters have been operational for 6 hours and
sor oil heaters have been operational for 6 hours and
sor oil heaters have been operational for 6 hours andsor oil heaters have been operational for 6 hours and the system has not been operational for at least 5the system has not been operational for at least 5
the system has not been operational for at least 5
the system has not been operational for at least 5the system has not been operational for at least 5 minutes.minutes.
minutes.
minutes.minutes.
9
Page 10
OPERATING YOUR THERMOSTAT AND REMOTE SENSOROPERATING YOUR THERMOSTAT AND REMOTE SENSOR
OPERATING YOUR THERMOSTAT AND REMOTE SENSOR
OPERATING YOUR THERMOSTAT AND REMOTE SENSOROPERATING YOUR THERMOSTAT AND REMOTE SENSOR
Emergency SystemEmergency System
Emergency System
Emergency SystemEmergency System
EMER EMER
EMER bypasses the Heat Pump to use the heat source wired
EMER EMER to terminal when compressor operation is not desired, or you prefer back-up heat only.
1. Press SYSTEM button to select on the display.
2. Press temperature. The Emergency heating system will begin to operate. The display will show " and " operating.
3. Press ture. The Emergency heating system should stop operat­ing.
To prevent compressor and/or property damage, if theTo prevent compressor and/or property damage, if the
To prevent compressor and/or property damage, if the
To prevent compressor and/or property damage, if theTo prevent compressor and/or property damage, if the outdoor temperature is below 50°F, DO NOT operateoutdoor temperature is below 50°F, DO NOT operate
outdoor temperature is below 50°F, DO NOT operate
outdoor temperature is below 50°F, DO NOT operateoutdoor temperature is below 50°F, DO NOT operate the cooling system.the cooling system.
the cooling system.
the cooling system.the cooling system.
1. Press SYSTEM button to select
2. Press temperature. The blower should come on immediately on high speed, followed by cold air circulation. The display should show " is flashing, the compressor lockout feature is operating (see Configuration menu, item 5).
3. Adjust temperature setting to 3° below room temperature. The second stage cooling should begin to operate and the display should show "
4. Press temperature. The cooling system should stop operating.
During normal operation, the upper left of the thermostat display changes every 6 seconds to show the temperatures at the sensors that are turned on in the configuration menu. The sensors are the thermostat ( remote sensor (
REMOTEREMOTE
(
REMOTE). Below that, the display alternately shows the
REMOTEREMOTE time and temperature average of the sensors that are turned on.
The word "
3) indicating the relative signal strength. More bars mean better reception. The seconds when information from the remote sensor is received.
If the thermostat does not receive an update signal from an enabled remote sensor (REMOTE or OUTDOOR) for 30 minutes or more, the thermostat will display FAULT and ANTENNA icons continuously. The REMOTE or OUTDOOR sensor that has communication with the thermostat inter­rupted will display a temperature of 00. If the active sensor is the REMOTE, the thermostat will revert back to LOCAL sense only mode.
E/W1 E/W1
E/W1 on the thermostat.
E/W1 E/W1
to adjust thermostat setting above room
HEATHEAT
HEAT" to indicate that the Emergency system is
HEATHEAT
to adjust the thermostat below room tempera-
CAUTION
!
Cooling SystemCooling System
Cooling System
Cooling SystemCooling System
to adjust thermostat setting below room
STG1STG1
STG1". If the setpoint temperature display
STG1STG1
STG 1+2STG 1+2
STG 1+2".
STG 1+2STG 1+2
to adjust the temperature setting above room
Remote Temperature Sensor InformationRemote Temperature Sensor Information
Remote Temperature Sensor Information
Remote Temperature Sensor InformationRemote Temperature Sensor Information
on the Thermostat Displayon the Thermostat Display
on the Thermostat Display
on the Thermostat Displayon the Thermostat Display
OUTDOOROUTDOOR
OUTDOOR) and the indoor remote sensor
OUTDOOROUTDOOR
SIGNALSIGNAL
SIGNAL"
SIGNALSIGNAL
is shown along with number of bars (1-
antenna antenna
antenna icon also displays for few
antenna antenna
EMER EMER
EMER is typically used
EMER EMER
EMEREMER
EMER. "
EMEREMER
STG1STG1
STG1" flashing "
STG1STG1
COOLCOOL
COOL.
COOLCOOL
LOCALLOCAL
LOCAL), the outdoor
LOCALLOCAL
EMEREMER
EMER" will flash
EMEREMER
EMEREMER
EMER"
EMEREMER
Automatic System ChangeoverAutomatic System Changeover
Automatic System Changeover
Automatic System ChangeoverAutomatic System Changeover
When the thermostat is in the will call for heat or cool depending on the room temperature. The setpoint temperature displayed will be the last mode called. If the last system cycle was heat, the will be displayed. If the room temperature raises above the HEAT HEAT
HEAT setpoint and the
HEAT HEAT required, the temperature displayed will change to be the COOL COOL
COOL setpoint.
COOL COOL If you manually override the temperature in
does not switch to the mode ( press the
modes. At the end of your override time it will revert back to AUTO.
Your thermostat is designed to determine the optimum time to activate the second stage. Simply raising the temperature in heating or lowering it in cooling will not always force the thermostat to bring the second stage on quickly. If the fast second stage option in the configuration menu (step 12) is set to "OFF", there is a delay from 0-30 minutes depending on the performance of the first stage of the system.
EXAMPLE: For the last 2 hours the thermostat is set on 70° and the room temperature is 70° with the equipment using only the first stage of heat. Since the equipment is keeping the temperature within 1 degree of setpoint, the thermostat will delay second stage for a longer time if you manually raise the temperature or if the room temperature quickly changes. Once the second stage comes on, it will come on sooner the next time there is a difference between the setpoint and the room temperature. The net effect of the staging program is that when the first stage is capable of holding temperature, the second stage will delay longer.
When the thermostat calculates that first stage cannot make temperature in a reasonable time, the second stage will come on sooner. This built in function automatically opti­mizes the use of additional stages of heat or cool.
and keys once, at the same time to switch
Second Stage Time DelaySecond Stage Time Delay
Second Stage Time Delay
Second Stage Time DelaySecond Stage Time Delay
AUTO AUTO
AUTO mode, the thermostat
AUTO AUTO
HEAT HEAT
HEAT setpoint
HEAT HEAT
COOL COOL
COOL setpoint and a call for cool is
COOL COOL
AUTO AUTO
AUTO and it
AUTO AUTO
HEAT HEAT
HEAT or
HEAT HEAT
COOLCOOL
COOL) that you want,
COOLCOOL
10
Page 11
OPERATING YOUR THERMOSTAT AND REMOTE SENSOROPERATING YOUR THERMOSTAT AND REMOTE SENSOR
OPERATING YOUR THERMOSTAT AND REMOTE SENSOR
OPERATING YOUR THERMOSTAT AND REMOTE SENSOROPERATING YOUR THERMOSTAT AND REMOTE SENSOR
Learn Mode OptionLearn Mode Option
Learn Mode Option
Your ther mosta t is configur ed at the factory to recognize the wireless remote sensor shipped with it. This sensor is stored as Sensor A. The Learn Mode Option must be performed on the thermostat and wireless remote sensor if:
• A wireless remote sensor is added to another channel.
• The wireless remote sensor is replaced.
• The thermostat is replaced.
During the Learn Mode, the wireless remote sensor will transmit identification information every ten seconds for ten minutes. In this ten-minute period, the display will show “LEARN” and the antenna icon will show for a short time with each transmission. The thermostat will be receiving the transmitted identification information.
To perform the Learn Mode on the thermostat and sensor:
Remove the batteries from all wireless remote sensors in the same building except the sensor you are going to put into the Learn Mode. This will prevent interference from the other sensors. Be sure that the remote sensor is set for the proper identification (A, B or C for indoor or O for outdoor) and the thermostat and remote sensor are set to the same frequency. On the thermostat, enter the thermostat Configuration Menu by pressing the momentarily pressing Momentarily press of the Configuration Menu. The display will show “
OFF”OFF”
and “
OFF”.
OFF”OFF” Momentarily press The display will flash “ stantly. On the wireless remote sensor, enter the Installer Configuration Menu by pressing seconds. The remote sensor display will change to
LEARN OF”LEARN OF”
LEARN OF”.
LEARN OF”LEARN OF” Momentarily press After the thermostat has successfully identified the remote sensor in approximately one minute, the sensor information will be stored and the thermostat display will change to “
If the identification sequence is not successful after ten minutes, the thermostat display will show “ the antenna icon. If the Learn Mode is unsuccessful, refer to Troubleshooting section, Antenna + Fault.
If you are replacing a thermostat that has more than one wireless remote sensor, the Learn Mode must be performed for each sensor. Once a sensor has been identified, it will remain in the thermostat memory until the Learn Mode is performed again and a different sensor for the stored channel is identified.
Your thermostat is designed to sense the temperature of the indoor remote sensor and average or weight it with the local sensor in the thermostat for each program period. The averaging will only be active when both the local and the indoor remote sensors are functional and turned on in the configuration menu. When the thermostat is placed in view schedule mode (press PRGM once), the weight of the indoor remote sensor will be shown on the left side of the display when HOLD button is pressed. The weighting classes of the indoor remote sensor are designated as A (default for average weight), HI (high weight), or LO (low weight). The HI weight is two times the weight of the average weight. The A weight is two times the weight of the LO weight. The weight of the local sensor is fixed to A (average weight). The actual temperature displayed, in the clock digits, in the normal operation mode is the mathematical weighted sum of the enabled functioning sensors. For example, if the local sensed temperature is 80°F and the remote sensed temperature is
Learn Mode OptionLearn Mode Option
SYSTEMSYSTEM
SYSTEM button to
SYSTEMSYSTEM
and at the same time.
SYSTEMSYSTEM
SYSTEM button to advance to step 2
SYSTEMSYSTEM
or to select “
LER”LER”
LER” with “
LER”LER”
or to select “
LER” LER”
LER” and “
LER” LER”
Wireless Remote IndoorWireless Remote Indoor
Wireless Remote Indoor
Wireless Remote IndoorWireless Remote Indoor
Temperature AveragingTemperature Averaging
Temperature Averaging
Temperature AveragingTemperature Averaging
OK”OK”
OK”.
OK”OK”
On”On”
On ” displayed con-
On”On”
OFFOFF
OFF and then
OFFOFF
LER”LER”
LER” and
LER”LER”
and for five
LEARN On”LEARN On”
LEARN On”.
LEARN On”LEARN On”
LER”,LER”,
LER”, “
LER”,LER”,
LER”LER”
LER”
LER”LER”
“On” “On”
“On”.
“On” “On”
Fault”Fault”
Fault” and
Fault”Fault”
70°F then: If weight selected is HI , then the averaged temperature is (2 x (80°F) + 4 x (70°F))/ 6 = 73.3°F. If weight selected is A , then the averaged temperature is (2 x (80°F) + 2 x (70°F))/ 4 = 75°F. If weight selected is LO , then the averaged temperature is (2 x (80°F) + 1 x (70°F))/ 3 = 76.6°F. The example above shows that the weight selected would prioritize the overall averaged temperature between the two sensors. The high weight selection caused the remote sensor to carry more weight in the calculated temperature average than the local sensor. The low weight selection caused the remote sensor to carry less weight in the calcu­lated temperature average than the local sensor.
Choose the Fan Setting (Auto or On)Choose the Fan Setting (Auto or On)
Choose the Fan Setting (Auto or On)
Choose the Fan Setting (Auto or On)Choose the Fan Setting (Auto or On)
AA
uto uto
Set the FAN Switc h to
AA
uto uto
Fan
A
uto is the most commonly selected setting and runs
AA
uto uto
the fan only when the heating or cooling system is on.
OnOn
Fan
On r uns the fan continuously for increased air circula tion
OnOn
or to allow additional air cleaning.
Choose the System SettingChoose the System Setting
Choose the System Setting
Choose the System SettingChoose the System Setting
(Heat, Off, Cool, Auto, Emer)(Heat, Off, Cool, Auto, Emer)
(Heat, Off, Cool, Auto, Emer)
(Heat, Off, Cool, Auto, Emer)(Heat, Off, Cool, Auto, Emer)
Press the SYSTEM button to select: HeaHea
tt
Hea
t: Thermosta t controls only the hea ting system.
HeaHea
tt
OfOf
ff
Of
f: Heating and Cooling systems are of f.
OfOf
ff
CoolCool
Cool: Thermostat controls only the cooling system.
CoolCool AA
utouto
A
ut o: Auto Changeover is used in areas where both heating
AA
utouto and cooling may be required on the same day. the thermostat to automa tically select heating or cooling depending on the indoor temperature and the selected heat and cool temperatures. When using Cooling temperatures more than 1° Fahrenheit higher than the heating temperature. EmerEmer
Emer: Setting is available only when the thermostat is
EmerEmer configured in HP1 or HP2 mode.
Non-Programmable ThermostatsNon-Programmable Thermostats
Non-Programmable Thermostats
Non-Programmable ThermostatsNon-Programmable Thermostats
Press the SYSTEM button to select Heat or Cool and use the
or buttons to adjust the temperature to your desired setting. After selecting your desired settings you can also press the SYSTEM button to select the thermostat to automatically change between Heat and Cool.
Manual Operation (Bypassing the Program)Manual Operation (Bypassing the Program)
Manual Operation (Bypassing the Program)
Manual Operation (Bypassing the Program)Manual Operation (Bypassing the Program)
Programmable ThermostatsProgrammable Thermostats
Programmable Thermostats
Programmable ThermostatsProgrammable Thermostats
Press or and adjust the temperature wherever you like. Then press HOLD. This will override the program. The feature bypasses the program and allows you to adjust the temperature manually, as needed. Whatever temperature you
HOLDHOLD
set in
HOLD will be maintained 24 hours a day, until you
HOLDHOLD manually change the temperature or press RUN to cancel HOLDHOLD
HOLD and resume the programmed schedule.
HOLDHOLD
Program Override (Temporary Override)Program Override (Temporary Override)
Program Override (Temporary Override)
Program Override (Temporary Override)Program Override (Temporary Override)
Press or buttons to adjust the temperature. This will override the temperature setting for a (default) four hour override period. The override period can be shortened or lengthened by adjusting the temporary hold time in the configuration menu. ExampleExample
Example: If you turn up the heat during the morning pro-
ExampleExample gram, it will be automatically lowered later, w hen the tempo­rary hold period ends. To cancel the temporar y setting a t any time and return to the program, press RUN. If the SYSTEM button is pressed to select thermostat will change to Heat or Cool, whichever ran last. If it switches to heat but you want cool, or it changes to cool but you want heat, press both neously to change to the other mode.
A
AA
Manual Operation forManual Operation for
Manual Operation for
Manual Operation forManual Operation for
uto or
uto uto
OnOn
On.
OnOn
AA
UTUT
A
UT
AA
UTUT
AA
UTUT
OO
A
UT
O, be sure to set the
AA
UTUT
OO
AUTOAUTO
AUTO to allow
AUTOAUTO
AUTOAUTO
AUTO the
AUTOAUTO
and buttons simulta-
OO
O allows
OO
HOLDHOLD
HOLD
HOLDHOLD
11
Page 12
OPERATING YOUR THERMOSTAT AND REMOTE SENSOROPERATING YOUR THERMOSTAT AND REMOTE SENSOR
OPERATING YOUR THERMOSTAT AND REMOTE SENSOR
OPERATING YOUR THERMOSTAT AND REMOTE SENSOROPERATING YOUR THERMOSTAT AND REMOTE SENSOR
Remote Sensor OperationRemote Sensor Operation
Remote Sensor Operation
Remote Sensor OperationRemote Sensor Operation
The sensor monitors the temperature and sends information to the thermostat. Updated information is sent to the thermo­stat when the temperature changes 3/16 degree or more from the last update.
Low Battery powerLow Battery power
Low Battery power: The sensor will display the word
Low Battery powerLow Battery power along with
BATT BATT
BATT icon to indicate a low battery power
BATT BATT
LOLO
LO
LOLO
condition. The 2 "AAA" batteries must be replaced to ensure a proper sensor performance. For optimum performance, replace batteries once a year with new premium brand
®
alkaline batteries such as Duracell
or Energizer®.
Increasing the sensor setpoint decreases the displayed remote temperature shown on the thermostat by 1°F per bar. This will lower the actual calculated room temperature by up to 4°F. Decreasing the sensor setpoint increases the displayed remote temperature and will raise the actual calculated room temperature. The table below shows how the adjustment on the sensor affects the displayed remote temperature on the thermostat and the calculated average temperature.
PROGRAMMING YOUR THERMOSTATPROGRAMMING YOUR THERMOSTAT
PROGRAMMING YOUR THERMOSTAT
PROGRAMMING YOUR THERMOSTATPROGRAMMING YOUR THERMOSTAT
This section will help you plan your thermostat's program to meet your needs. For maximum comfort and efficiency, keep the following guidelines in mind when planning your program.
• When heating (cooling) your building, program the temper-
atures to be cooler (warmer) when the building is vacant or during periods of low activity.
• During early morning hours, the need for cooling is usually
minimal.
Planning Your ProgramPlanning Your Program
Planning Your Program
Planning Your ProgramPlanning Your Program
Look at the factory preprogrammed times and temperatures shown in the sample schedule. If this program will suit your needs, simply set the time and day and press the RUN button to begin running the factory preset program.
If you want to change the preprogrammed times and tem­peratures, follow these steps.
Determine the time periods and temperatures for your program. You must program four periods for each day. However, you may use the same heating and cooling temperatures for consecutive time periods. You can choose start times, heating temperatures, and cooling temperatures independently (for example, you may select 5:00 AM and 70° as the weekday ture and also choose 7:00 AM and 76° as the weekday period coolingperiod cooling
per io d c oo li ng start time and temperature).
period coolingperiod cooling
1st period heating1st period heating
1st p e ri o d h e a t in g start time and tempera-
1st period heating1st period heating
1st1st
1st
1st1st
Use the table to plan your program time periods and the temperatures you want during each period. Fill in the complete table to have a record of your programs.
Description Remote Sensor Thermostat Display (Remote) Thermostat Display (Local) Calculated Room Temp. Setpoint Temp. Increasing setting decreases room H +4 bars Decreases by 4°F to 71°F 70.5°F temperature average causing system H +3 bars Decreases by 3°F to 72°F 71°F to increase temperature. H +2 bars Decreases by 2°F to 73°F 71.5°F
H +1 bar Decreases by 1°F to 74°F 72°F
Remote 75°F 75°F 74.5° 75°F Decreasing setting increases room C -1 bar Increases by 1°F to 76°F 73°F temperature causing more of a C -2 bars Increases by 2°F to 77°F 73.5°F demand for Cooling. C -3 bars Increases by 3°F to 78°F 74°F
C -4 bars Increases by 4°F to 79°F 74.5°F
FACTORY PROGRAMFACTORY PROGRAM
FACTORY PROGRAM
FACTORY PROGRAMFACTORY PROGRAM
12
PERIODPERIOD
PERIOD
PERIODPERIOD
MORNMORN
MORN
MORNMORN DAYDAY
DAY
DAYDAY EVEEVE
EVE
EVEEVE
HEATHEAT
HEATHEAT
HEAT
NITENITE
NITE
NITENITE MORNMORN
MORN
MORNMORN DAYDAY
DAY
DAYDAY EVEEVE
EVE
EVEEVE
COOLCOOL
COOLCOOL
COOL
NITENITE
NITE
NITENITE
PERIODPERIOD
PERIOD
PERIODPERIOD
MORNMORN
MORN
MORNMORN DAYDAY
DAY
DAYDAY EVEEVE
EVE
EVEEVE
HEATHEAT
HEATHEAT
HEAT
NITENITE
NITE
NITENITE MORNMORN
MORN
MORNMORN DAYDAY
DAY
DAYDAY EVEEVE
EVE
EVEEVE
COOLCOOL
COOLCOOL
COOL
NITENITE
NITE
NITENITE
WEEKDAYS (5 DAYS)WEEKDAYS (5 DAYS)
WEEKDAYS (5 DAYS)
WEEKDAYS (5 DAYS)WEEKDAYS (5 DAYS) STARTSTART
START
STARTSTART TIMETIME
TIME
TIMETIME 6:00 AM6:00 AM
6:00 AM
6:00 AM6:00 AM 8:00 AM8:00 AM
8:00 AM
8:00 AM8:00 AM 5:00 PM5:00 PM
5:00 PM
5:00 PM5:00 PM 10:00 PM10:00 PM
10:00 PM
10:00 PM10:00 PM 6:00 AM6:00 AM
6:00 AM
6:00 AM6:00 AM 8:00 AM8:00 AM
8:00 AM
8:00 AM8:00 AM 5:00 PM5:00 PM
5:00 PM
5:00 PM5:00 PM 10:00 PM10:00 PM
10:00 PM
10:00 PM10:00 PM
WEEKDAYS (5 DAYS)WEEKDAYS (5 DAYS)
WEEKDAYS (5 DAYS)
WEEKDAYS (5 DAYS)WEEKDAYS (5 DAYS) STARTSTART
START
STARTSTART TIMETIME
TIME
TIMETIME
TEMPTEMP
TEMP
TEMPTEMP 70 F70 F
70 F
70 F70 F 62 F62 F
62 F
62 F62 F 70 F70 F
70 F
70 F70 F 62 F62 F
62 F
62 F62 F 78 F78 F
78 F
78 F78 F 85 F85 F
85 F
85 F85 F 78 F78 F
78 F
78 F78 F 82 F82 F
82 F
82 F82 F
TEMPTEMP
TEMP
TEMPTEMP
REMOTEREMOTE
REMOTE
REMOTEREMOTE WEIGHTWEIGHT
WEIGHT
WEIGHTWEIGHT
REMOTEREMOTE
REMOTE
REMOTEREMOTE WEIGHTWEIGHT
WEIGHT
WEIGHTWEIGHT
SATURDAY (1 DAY)SATURDAY (1 DAY)
SATURDAY (1 DAY)
SATURDAY (1 DAY)SATURDAY (1 DAY) STARTSTART
START
STARTSTART TIMETIME
TIME
AA
A
AA
AA
A
AA AA
A
AA AA
A
AA AA
A
AA AA
A
AA AA
A
AA AA
A
AA
TIMETIME 6:00 AM6:00 AM
6:00 AM
6:00 AM6:00 AM 8:00 AM8:00 AM
8:00 AM
8:00 AM8:00 AM 5:00 PM5:00 PM
5:00 PM
5:00 PM5:00 PM 10:00 PM10:00 PM
10:00 PM
10:00 PM10:00 PM 6:00 AM6:00 AM
6:00 AM
6:00 AM6:00 AM 8:00 AM8:00 AM
8:00 AM
8:00 AM8:00 AM 5:00 PM5:00 PM
5:00 PM
5:00 PM5:00 PM 10:00 PM10:00 PM
10:00 PM
10:00 PM10:00 PM
PERSONAL PROGRAMPERSONAL PROGRAM
PERSONAL PROGRAM
PERSONAL PROGRAMPERSONAL PROGRAM
SATURDAY (1 DAY)SATURDAY (1 DAY)
SATURDAY (1 DAY)
SATURDAY (1 DAY)SATURDAY (1 DAY) STARTSTART
START
STARTSTART TIMETIME
TIME
TIMETIME
TEMPTEMP
TEMP
TEMPTEMP 70 F70 F
70 F
70 F70 F 62 F62 F
62 F
62 F62 F 70 F70 F
70 F
70 F70 F 62 F62 F
62 F
62 F62 F 78 F78 F
78 F
78 F78 F 85 F85 F
85 F
85 F85 F 78 F78 F
78 F
78 F78 F 82 F82 F
82 F
82 F82 F
TEMPTEMP
TEMP
TEMPTEMP
REMOTEREMOTE
REMOTE
REMOTEREMOTE WEIGHTWEIGHT
WEIGHT
WEIGHTWEIGHT
AA
A
AA AA
A
AA AA
A
AA AA
A
AA AA
A
AA AA
A
AA AA
A
AA AA
A
AA
REMOTEREMOTE
REMOTE
REMOTEREMOTE WEIGHTWEIGHT
WEIGHT
WEIGHTWEIGHT
SUNDAY (1 DAY)SUNDAY (1 DAY)
SUNDAY (1 DAY)
SUNDAY (1 DAY)SUNDAY (1 DAY) STARTSTART
START
STARTSTART TIMETIME
TIME
TIMETIME 6:00 AM6:00 AM
6:00 AM
6:00 AM6:00 AM 8:00 AM8:00 AM
8:00 AM
8:00 AM8:00 AM 5:00 PM5:00 PM
5:00 PM
5:00 PM5:00 PM 10:00 PM10:00 PM
10:00 PM
10:00 PM10:00 PM 6:00 AM6:00 AM
6:00 AM
6:00 AM6:00 AM 8:00 AM8:00 AM
8:00 AM
8:00 AM8:00 AM 5:00 PM5:00 PM
5:00 PM
5:00 PM5:00 PM 10:00 PM10:00 PM
10:00 PM
10:00 PM10:00 PM
SUNDAY (1 DAY)SUNDAY (1 DAY)
SUNDAY (1 DAY)
SUNDAY (1 DAY)SUNDAY (1 DAY) STARTSTART
START
STARTSTART TIMETIME
TIME
TIMETIME
TEMPTEMP
TEMP
TEMPTEMP 70 F70 F
70 F
70 F70 F 62 F62 F
62 F
62 F62 F 70 F70 F
70 F
70 F70 F 62 F62 F
62 F
62 F62 F 78 F78 F
78 F
78 F78 F 85 F85 F
85 F
85 F85 F 78 F78 F
78 F
78 F78 F 82 F82 F
82 F
82 F82 F
TEMPTEMP
TEMP
TEMPTEMP
REMOTEREMOTE
REMOTE
REMOTEREMOTE WEIGHTWEIGHT
WEIGHT
WEIGHTWEIGHT
AA
A
AA AA
A
AA AA
A
AA
AA
A
AA AA
A
AA AA
A
AA AA
A
AA AA
A
AA
REMOTEREMOTE
REMOTE
REMOTEREMOTE WEIGHTWEIGHT
WEIGHT
WEIGHTWEIGHT
Page 13
PROGRAMMINGPROGRAMMING
CAUTION
!
PROGRAMMING
PROGRAMMINGPROGRAMMING
Setting the Clock and DaySetting the Clock and Day
Setting the Clock and Day
Setting the Clock and DaySetting the Clock and Day
Set Current Time and DaySet Current Time and Day
Set Current Time and Day
Set Current Time and DaySet Current Time and Day
1. Press TIME button once. The display will show the hour only.
EXAMPLE:
2. Press and hold either correct hour and AM/PM designation (
PM PM
night;
PM begins at noon).
PM PM
indicate for PM in the minutes digits.
3. Press TIME once again. The display window will show the minutes only.
EXAMPLE:
4. Press and hold either correct minutes.
5. Press TIME once again. The display will show the day of the week.
6. Press or until you reach the current day of the week.
7. Press RUN once. The display will show the correct time and room temperature alternately.
This thermostat starts the programmed temperature earlier than the time selected in your program. This allows the system to reach your setting by the time you specify in your program. This feature is called EMR (Energy Management Recovery). If you do not want the thermostat to start early, you may cancel the EMR feature in the Configuration Menu.
Enter Heating ProgramEnter Heating Program
Enter Heating Program
Enter Heating ProgramEnter Heating Program
1. Press the SYSTEM button to
2. Press PRGM once. " weekday program) will appear in the display. Also dis­played are the currently programmed start time for the 1st heating period and the currently programmed temp­erature (flashing).
EXAMPLE:
This display window shows that for the 1st weekday period, the start time is 6:00 AM and 68° is the program­med temperature (this example reflects factory prepro­gramming.
3. Press to your selected temperature for the 1st heating program period.
4. Press TIME once (the programmed time will flash). Press will change in 15 minute increments. When your selected
time is displayed, press TIME again to return to the change temperature mode.
5. If both the local and the remote sensors are enabled, then you may press HOLD button to change the remote sensor weighting setting. Remote icon will display. The pro­grammed weight (A, HI or LO) will flash. Press or to change the displayed weight to your selected weight for the 1st heat program period.
or to change the displayed temperature
or until your selected time appears. The time
or until you reach the
AM AM
AM begins at mid-
AM AM
A A
A will indicate for AM.
A A
or until you reach the
HEATHEAT
HEAT.
HEATHEAT
MO TU WE TH FRMO TU WE TH FR
MO TU WE TH FR" (indicating
MO TU WE TH FRMO TU WE TH FR
P P
P will
P P
6. Press PRGM once. The currently programmed start time and setpoint temperature for the period will appear.
7. Repeat steps 3 and 5 to select the start time and heating temperature for the 2nd heating program period.
8. Repeat steps 3 through 6 for the 3rd and 4th heating program periods.
9. Press PRGM once " will appear in the display, along with the start time for the 1st heating period and the currently programmed temp­erature.
10.Repeat steps 3 through 8 to complete Saturday heating programming.
11.Press PRGM once to change to " programming and repeat steps 3 through 7 to complete Sunday programming.
12.When you have completed entering your heating pro­gram, press RUN.
Enter Cooling ProgramEnter Cooling Program
Enter Cooling Program
Enter Cooling ProgramEnter Cooling Program
If the outside temperature is below 50°F, disconnectIf the outside temperature is below 50°F, disconnect
If the outside temperature is below 50°F, disconnect
If the outside temperature is below 50°F, disconnectIf the outside temperature is below 50°F, disconnect power to the cooling system before programming.power to the cooling system before programming.
power to the cooling system before programming.
power to the cooling system before programming.power to the cooling system before programming. Energizing the air conditioner compressor duringEnergizing the air conditioner compressor during
Energizing the air conditioner compressor during
Energizing the air conditioner compressor duringEnergizing the air conditioner compressor during cold weather may cause personal injury or propertycold weather may cause personal injury or property
cold weather may cause personal injury or property
cold weather may cause personal injury or propertycold weather may cause personal injury or property damage.damage.
damage.
damage.damage.
1. Press SYSTEM button to
2. Follow Enter Heating Program for entering your cooling program, using your selected cooling times and tempera­tures.
CHECK YOUR PROGRAMMINGCHECK YOUR PROGRAMMING
CHECK YOUR PROGRAMMING
CHECK YOUR PROGRAMMINGCHECK YOUR PROGRAMMING
Follow these steps to check your thermostat programming one final time before beginning thermostat operation.
1. Press SYSTEM button to
2. Press PRGM to view the 1st weekday heating period time and temperature. Each time you press PRGM, the next heating period time and temperature will be display­ed in sequence for weekday, then Saturday and Sunday program periods (you may change any time or tempera­ture during this procedure.
3. Press RUN.
4. Press SYSTEM button to
5. Repeat step 2 to check cooling program.
6. Press SYSTEM button to RUN to begin program operation.
NOTE: Batteries are not required to keep your programming
or menu data. With two optional "AA" batteries installed, your thermostat will maintain time and continuously display the temperature during a loss of AC power. Installed batteries will also allow programming prior to installation.
YOUR THERMOSTAT IS NOW PROGRAMMED AND READY TOYOUR THERMOSTAT IS NOW PROGRAMMED AND READY TO
YOUR THERMOSTAT IS NOW PROGRAMMED AND READY TO
YOUR THERMOSTAT IS NOW PROGRAMMED AND READY TOYOUR THERMOSTAT IS NOW PROGRAMMED AND READY TO PROVIDE MAXIMUM COMFORT AND EFFICIENCY!PROVIDE MAXIMUM COMFORT AND EFFICIENCY!
PROVIDE MAXIMUM COMFORT AND EFFICIENCY!
PROVIDE MAXIMUM COMFORT AND EFFICIENCY!PROVIDE MAXIMUM COMFORT AND EFFICIENCY!
SASA
SA" (indicating Saturday program)
SASA
2nd heating2nd heating
2nd heating program
2nd heating2nd heating
SUSU
SU" (Sunday) heating
SUSU
COOLCOOL
COOL.
COOLCOOL
HEAT HEAT
HEAT position.
HEAT HEAT
COOL COOL
COOL position.
COOL COOL
HEAT HEAT
HEAT or
HEAT HEAT
COOL COOL
COOL and press
COOL COOL
13
Page 14
TROUBLESHOOTINGTROUBLESHOOTING
TROUBLESHOOTING
TROUBLESHOOTINGTROUBLESHOOTING
Reset OperationReset Operation
Reset Operation
Reset OperationReset Operation
If a voltage spike or static discharge blanks out the display or causes erratic thermostat operation, you can reset the thermo­stat by removing the wires from terminals R and C and removing batteries for 2 minutes. After resetting the thermostat, replace the wires and batteries. If the thermostat has been reset and still does not function correctly contact your heating/ cooling service person or place of purchase. Pressing also clear any limited temperature ranges or keypad lockout settings. Note default system configuration is multistage system operation.
and and the SYSTEM keys at the same time will reset the thermostat to its factory default setting. This will
SymptomSymptom
Symptom
SymptomSymptom
No Heat/No Cool/No FanNo Heat/No Cool/No Fan
No Heat/No Cool/No Fan
No Heat/No Cool/No FanNo Heat/No Cool/No Fan (common problems)(common problems)
(common problems)
(common problems)(common problems)
No HeatNo Heat
No Heat
No HeatNo Heat
Possible CausePossible Cause
Possible Cause
Possible CausePossible Cause
1.Blown fuse or tripped circuit breaker.
2.Furnace power switch to OFF.
3.Furnace blower compartment door or panel loose or not properly installed.
1.Pilot light not lit.
2.SYSTEM Switch not set to
3.Loose connection to thermostat or system.
4.Furnace Lock-Out Condition. Heat may also be intermittent.
5.Heating system requires service or thermostat requires replacement.
HEATHEAT
HEAT.
HEATHEAT
Corrective ActionCorrective Action
Corrective Action
Corrective ActionCorrective Action
Replace fuse or reset breaker. Turn switch to ON. Replace door panel in proper position to engage safety interlock or door switch.
Re-light pilot. Set SYSTEM Switch to above room temperature. Verify thermostat and system wires are securely attached. Many furnaces have safety devices that shut down when a lock-out condition occurs. If the heat works intermittently contact the furnace manufacturer or local service person for assistance. Diagnostic: Set SYSTEM Switch to the setpoint above room temperature. Within a few seconds the thermostat should make a soft click sound. This sound usually indicates the thermostat is operating properly. If the thermostat does not click, try the reset operation listed above. If the thermostat does not click after being reset contact your heating and cooling service person or place of purchase for a replacement. If the thermostat clicks, contact the furnace manufacturer or a service person to verify the heating is operating correctly.
HEAT HEAT
HEAT and raise setpoint
HEAT HEAT
HEAT HEAT
HEAT and raise
HEAT HEAT
No CoolNo Cool
No Cool
No CoolNo Cool
Thermostat does notThermostat does not
Thermostat does not
Thermostat does notThermostat does not Follow ProgramFollow Program
Follow Program
Follow ProgramFollow Program
1.SYSTEM Switch not set to
2.Loose connection to thermostat or system.
3.Cooling system requires service or thermostat requires replacement.
1.Program or current time(s) set incorrectly (AM, PM or Day of the week).
2.Energy Management Recovery (EMR) starting the program early.
COOLCOOL
COOL.
COOLCOOL
Set SYSTEM Switch to below room temperature. Verify thermostat and system wires are securely attached. Same procedure as diagnostic for No Heat condition except set the thermostat to setpoint below the room temperature. There may be up to a five minute delay before the thermostat clicks in Cooling.
Verify that the AM or PM settings are correct for each program period and the current time of day. Also verify the Day of the week is set correctly. The EMR (Energy Management Recovery) feature starts early to achieve the temperature it is pro­grammed for by the time specified in the program. See the Configuration Menu section to disable EMR if you do not want the thermostat to start early.
COOL COOL
COOL and lower setpoint
COOL COOL
COOL COOL
COOL and lower the
COOL COOL
14
Page 15
TROUBLESHOOTINGTROUBLESHOOTING
TROUBLESHOOTING
TROUBLESHOOTINGTROUBLESHOOTING
SymptomSymptom
Symptom
SymptomSymptom
Furnace Inducer Fan,Furnace Inducer Fan,
Furnace Inducer Fan,
Furnace Inducer Fan,Furnace Inducer Fan, Blower or Heat Turns OnBlower or Heat Turns On
Blower or Heat Turns On
Blower or Heat Turns OnBlower or Heat Turns On with No Call for Heat orwith No Call for Heat or
with No Call for Heat or
with No Call for Heat orwith No Call for Heat or does not Turn Off whendoes not Turn Off when
does not Turn Off when
does not Turn Off whendoes not Turn Off when Call for Heat EndsCall for Heat Ends
Call for Heat Ends
Call for Heat EndsCall for Heat Ends
Antenna + FaultAntenna + Fault
Antenna + Fault
Antenna + FaultAntenna + Fault
Possible CausePossible Cause
Possible Cause
Possible CausePossible Cause
In power stealing mode (RC/PS Switch set to PS), the thermostat draws a small amount of power through the heating circuit to operate. Some furnace systems using high impedance input electronic modules may react to the current draw and actuate system components.
1.Loss of power from heating/cooling system to thermostat.
2.Remote sensor too far from thermostat.
3.Thermostat or remote sensor set to different channels or a different frequency offset.
4.Incorrect sensor identification selected.
5.Replacement Sensor requires running learn mode.
6.Remote sensor requires replacement.
Corrective ActionCorrective Action
Corrective Action
Corrective ActionCorrective Action
1. Add a common connection from the system transformer to the "C" terminal on the thermostat and set the RC/PS switch to RC.
2. If the system has a standard cooling contactor and no common connection is available at the thermostat, clip jumper W25-W1 and separate the ends. This prevents the thermostat from drawing power from the W1 (heating) circuit. If the condition persists after clipping the jumper, a heating and cooling service person can install an isolation relay to the system or add a common wire as mentioned above.
1. Verify the thermostat is operating on AC power by removing the thermostat batteries. If display goes blank, AC power is lost.
2. Change remote sensor location.
3. Verify the thermostat and remote sensor are set to the same channel and frequency offset.
4. For indoor sensor, verify sensor identification selected is A, B or C. For an outdoor sensor, verify the sensor identification selected is O.
5. If the sensor did not come with this thermostat from the factory, perform the learn procedure for thermostat and sensor.
6. If the sensor display indicate E0 or E1, replace the remote sensor.
Temperature DifferenceTemperature Difference
Temperature Difference
Temperature DifferenceTemperature Difference between Thermostatbetween Thermostat
between Thermostat
between Thermostatbetween Thermostat and Remote Locationand Remote Location
and Remote Location
and Remote Locationand Remote Location
Heat, Cool or FanHeat, Cool or Fan
Heat, Cool or Fan
Heat, Cool or FanHeat, Cool or Fan Runs ConstantlyRuns Constantly
Runs Constantly
Runs ConstantlyRuns Constantly
1.Improper system sizing or improper heating and cooling distribution between areas.
2.An uneven change in occupancy level, sun load or conditioned space activities (cooking, washing dishes, showers, etc.) between the areas.
1.Possible short in wiring.
2.Possible short in thermostat.
3.Possible short in heat/cool/fan system.
4.FAN Switch set to Fan
ONON
ON.
ONON
Selecting a high or low priority for the thermostat or sensor location during program periods can help even out minor temperature imbalances between the thermostat and remote sensor locations. This is also useful for scheduled or predictable events like occupancy level or sun load during particular times of the day. If the temperature difference remains large after assigning priorities, system modification or zoning may be necessary to balance the tem­perature distribution.
Check each wire connection to verify they are not shorted or touching together. No bare wire should stick out from under terminal screws. Try resetting the thermostat as described above. If the condition persists the manufacturer of your system or service person can instruct you on how to test the Heat/Cool system for correct operation. If the system operates correctly, replace the thermostat.
15
Page 16
TROUBLESHOOTINGTROUBLESHOOTING
TROUBLESHOOTING
TROUBLESHOOTINGTROUBLESHOOTING
Possible CausePossible Cause
Possible Cause
SymptomSymptom
Symptom
SymptomSymptom
Possible CausePossible Cause
Corrective ActionCorrective Action
Corrective Action
Corrective ActionCorrective Action
FurnaceFurnace
Furnace
FurnaceFurnace (Air Conditioner)(Air Conditioner)
(Air Conditioner)
(Air Conditioner)(Air Conditioner) Cycles Too FastCycles Too Fast
Cycles Too Fast
Cycles Too FastCycles Too Fast or Too Slow (narrow oror Too Slow (narrow or
or Too Slow (narrow or
or Too Slow (narrow oror Too Slow (narrow or wide temperature swing)wide temperature swing)
wide temperature swing)
wide temperature swing)wide temperature swing)
Thermostat Setting &Thermostat Setting &
Thermostat Setting &
Thermostat Setting &Thermostat Setting & Thermostat ThermometerThermostat Thermometer
Thermostat Thermometer
Thermostat ThermometerThermostat Thermometer DisagreeDisagree
Disagree
DisagreeDisagree Blank Display and/orBlank Display and/or
Blank Display and/or
Blank Display and/orBlank Display and/or Keypad Not RespondingKeypad Not Responding
Keypad Not Responding
Keypad Not RespondingKeypad Not Responding Heat Setpoint willHeat Setpoint will
Heat Setpoint will
Heat Setpoint willHeat Setpoint will not Respond to thenot Respond to the
not Respond to the
not Respond to thenot Respond to the Temperature Up KeyTemperature Up Key
Temperature Up Key
Temperature Up KeyTemperature Up Key Cool Setpoint willCool Setpoint will
Cool Setpoint will
Cool Setpoint willCool Setpoint will not Respond to thenot Respond to the
not Respond to the
not Respond to thenot Respond to the Temperature Down KeyTemperature Down Key
Temperature Down Key
Temperature Down KeyTemperature Down Key Forgot KeypadForgot Keypad
Forgot Keypad
Forgot KeypadForgot Keypad Lockout CodeLockout Code
Lockout Code
Lockout CodeLockout Code
1.The location of the thermostat and/or the size of the Heating System may be influencing the cycle rate.
1.Thermostat thermometer setting requires adjustment.
1.Voltage spike or static discharge.
1.The desired setpoint conflicts with the setpoint of the COOL mode.
1.The desired setpoint conflicts with the setpoint of the HEAT mode.
Digital thermostats normally provide precise temperature control and may cycle faster than some older mechanical models. A faster cycle rate means the unit turns on and off more frequently but runs for a shorter time so there is no increase in energy use. If you would like to increase the cycle time, choose SL SL
SL for slow cycle in the menu, step 4. If an accept-
SL SL able cycle rate is not achieved as received or by choosing slow cycle, contact a local service person for additional suggestions.
The thermometer can be adjusted +/- 3 degrees. See Temperature Display Adjustment in the Configuration Menu section.
Use the Reset Operation at top of previous page.
Change system mode to COOL. Raise the Cool setpoint. Return to HEAT mode and set desired temperature.
Change system mode to HEAT. Lower the Heat setpoint. Return to COOL mode and set desired temperature.
With the thermostat in any mode, press at the same time to enter the configuration menu at the point where the lockout code is to be entered. Press time to reset the lockout code, unlock the keypad.
and and SYSTEM button at the same
and
Why won't my 2nd orWhy won't my 2nd or
Why won't my 2nd or
Why won't my 2nd orWhy won't my 2nd or 3rd stage come on?3rd stage come on?
3rd stage come on?
3rd stage come on?3rd stage come on?
White-Rodgers is a division of Emerson Electric Co.
The Emerson logo is a trademark and service mark of Emerson Electric Co.
Your thermostat is designed to determine the optimum time to activate the second stage. Simply raising the temperature in heating or lowering it in cooling will not always force the thermostat to bring the second stage on quickly. There is a time delay from 0-30 minutes depending on the performance of the first stage of the system.
HOMEOWNER HELP LINE: 1-800-284-2925
St. Louis, MO
www.white-rodgers.com
Loading...