Operator: Save these instructions for future use!Operator: Save these instructions for future use!
Operator: Save these instructions for future use!
Operator: Save these instructions for future use!Operator: Save these instructions for future use!
FAILURE TO READ AND FOLLOW ALL INSTRUCTIONS CAREFULLY BEFOREFAILURE TO READ AND FOLLOW ALL INSTRUCTIONS CAREFULLY BEFORE
FAILURE TO READ AND FOLLOW ALL INSTRUCTIONS CAREFULLY BEFORE
FAILURE TO READ AND FOLLOW ALL INSTRUCTIONS CAREFULLY BEFOREFAILURE TO READ AND FOLLOW ALL INSTRUCTIONS CAREFULLY BEFORE
INSTALLING OR OPERATING THIS CONTROL COULD CAUSE PERSONALINSTALLING OR OPERATING THIS CONTROL COULD CAUSE PERSONAL
INSTALLING OR OPERATING THIS CONTROL COULD CAUSE PERSONAL
INSTALLING OR OPERATING THIS CONTROL COULD CAUSE PERSONALINSTALLING OR OPERATING THIS CONTROL COULD CAUSE PERSONAL
INJURY AND/OR PROPERTY DAMAGE.INJURY AND/OR PROPERTY DAMAGE.
DescriptionDescription
Heat Pump (No Aux. or Emergency Heat)Yes
Heat Pump (with Aux. or Emergency Heat)Yes
Standard Heat & Cooling SystemsYes
Two Stage Heat & Two Stage CoolYes
Standard Heat Only SystemsYes
Millivolt Heat Only Systems – Floor or Wall FurnacesYes
Standard Central Air ConditioningYes
Gas or Oil HeatYes
Electric FurnaceYes
Hydronic (Hot Water) Zone Heat – 2 WiresYes
Hydronic (Hot Water) Zone Heat – 3 WiresNo
1F85-2771F85-277
1F85-277
1F85-2771F85-277
Assemble tools required as shown below.
HAND OR POWER
DRILL WITH 3/16 INCH
DRILL BIT, IF NEEDED
To prevent electrical shock and/or equipment dam-To prevent electrical shock and/or equipment damage, disconnect electric power to system at main fuseage, disconnect electric power to system at main fuse
age, disconnect electric power to system at main fuse
age, disconnect electric power to system at main fuseage, disconnect electric power to system at main fuse
or circuit breaker box until installation is complete.or circuit breaker box until installation is complete.
or circuit breaker box until installation is complete.
or circuit breaker box until installation is complete.or circuit breaker box until installation is complete.
Before removing wires from old thermostat's switching sub-
label each wirelabel each wire
base,
label each wire with the terminal designation it was
label each wirelabel each wire
removed from.
1. Shut off electricity at the main fuse box until installation is
complete. Ensure that electrical power is disconnected.
Remove Old ThermostatRemove Old Thermostat
2.
Remove Old Thermostat: A standard heat/cool
Remove Old ThermostatRemove Old Thermostat
thermostat consists of three basic parts:
a. The cover, which may be either a snap-on or
hinge type.
b. The base, which is removed by loosening all
captive screws.
c. The switching subbase, which is removed by
unscrewing the mounting screws that hold it on
the wall or adaptor plate.
3. Remove the front cover of the old thermostat.
wireswires
still attachedstill attached
wires
still attached, remove wall plate from the wall. If
wireswires
still attachedstill attached
the old thermostat has a wall mounting plate, remove the
thermostat and the wall mounting plate as an assembly.
4. Identify each wire attached to the old thermostat.
5. Disconnect the wires from the old thermostat one at a
DO NOT LET WIRES FALL BACK INTO THEDO NOT LET WIRES FALL BACK INTO THE
time.
DO NOT LET WIRES FALL BACK INTO THE
DO NOT LET WIRES FALL BACK INTO THEDO NOT LET WIRES FALL BACK INTO THE
WALLWALL
WALL.
WALLWALL
6. Install new thermostat using the following procedures.
WithWith
With
WithWith
Y2
C
R
E/W1
Y1
Mounting
Hole
Figure 1 – Thermostat baseFigure 1 – Thermostat base
Figure 1 – Thermostat base
Figure 1 – Thermostat baseFigure 1 – Thermostat base
ATTENTION!ATTENTION!
ATTENTION! This product does not contain mercury. How-
ATTENTION!ATTENTION!
ever, this product may replace a unit which contains mercury.
Do not open mercury cells. If a cell becomes damaged, do
touch any spilled mercury. Wearing non-absorbent gloves,
clean up the spilled mercury and place into a container which
can be sealed. If a cell becomes damaged, the unit should be
discarded.
Mercury must not be discarded in household trash. When the
unit this product is replacing is to be discarded, place in a
suitable container and return to White-Rodgers at 2895 Harrison
Street, Batesville, AR 72501 for proper disposal.
OBLW2G
ELEC.GAS
AUTOON
Mounting
Hole
Elec-Gas
Switch
notnot
not
notnot
White-Rodgers is a division
of Emerson Electric Co.
www.white-rodgers.com
PART NO. 37-6560APART NO. 37-6560A
PART NO. 37-6560A
PART NO. 37-6560APART NO. 37-6560A
0430
MOUNTING AND WIRINGMOUNTING AND WIRING
MOUNTING AND WIRING
MOUNTING AND WIRINGMOUNTING AND WIRING
CAUTION
WARNING
!
Do not use on circuits exceeding specified voltage.Do not use on circuits exceeding specified voltage.
Do not use on circuits exceeding specified voltage.
Do not use on circuits exceeding specified voltage.Do not use on circuits exceeding specified voltage.
Higher voltage will damage control and could causeHigher voltage will damage control and could cause
Higher voltage will damage control and could cause
Higher voltage will damage control and could causeHigher voltage will damage control and could cause
shock or fire hazard.shock or fire hazard.
shock or fire hazard.
shock or fire hazard.shock or fire hazard.
Do not short out terminals on gas valve or primaryDo not short out terminals on gas valve or primary
Do not short out terminals on gas valve or primary
Do not short out terminals on gas valve or primaryDo not short out terminals on gas valve or primary
control to test. Short or incorrect wiring will damagecontrol to test. Short or incorrect wiring will damage
control to test. Short or incorrect wiring will damage
control to test. Short or incorrect wiring will damagecontrol to test. Short or incorrect wiring will damage
thermostat and could cause personal injury and/orthermostat and could cause personal injury and/or
thermostat and could cause personal injury and/or
thermostat and could cause personal injury and/orthermostat and could cause personal injury and/or
property damage.property damage.
property damage.
property damage.property damage.
Thermostat installation and all components of the
system shall conform to Class II circuits per the NEC
code.
This thermostat is configured from the factory to operate a heat/
cool, fossil fuel (gas, oil, etc.), forced air system. It is configured
correctly for any system that DOES NOT require the thermostat
to energize the fan on a call for heat. If you system is an electric
heat or heat-pump system that REQUIRES the thermostat to
turn on the fan on a call for heat, locate the ELEC/GAS switch
on the back of the thermostat (see fig. 1) and switch it to the
ELEC position. This will allow the thermostat to energize the fan
immediately on a call for heat. If you are unsure if the heating/
cooling system requires the thermostat to control the fan,
contact a qualified heating and air conditioning service person.
When the thermostat is configured for Heat Pump, the thermostat will always power the circulator fan on a call for heat in the
HEAT mode. The ELEC/GAS switch must be set to match the
type of Auxiliary heat your system uses for proper operation in
the EMERgency mode.
Take care when securing and routing wires so they doTake care when securing and routing wires so they do
Take care when securing and routing wires so they do
Take care when securing and routing wires so they doTake care when securing and routing wires so they do
not short to adjacent terminals or rear of thermostat.not short to adjacent terminals or rear of thermostat.
not short to adjacent terminals or rear of thermostat.
not short to adjacent terminals or rear of thermostat.not short to adjacent terminals or rear of thermostat.
Personal injury and/or property damage may occur.Personal injury and/or property damage may occur.
Personal injury and/or property damage may occur.
Personal injury and/or property damage may occur.Personal injury and/or property damage may occur.
Attach Thermostat Base to WallAttach Thermostat Base to Wall
Attach Thermostat Base to Wall
Attach Thermostat Base to WallAttach Thermostat Base to Wall
1. Remove the packing material from the thermostat. Gently
pull the cover straight off the base. Forcing or prying on
the thermostat will cause damage to the unit.
2. Connect wires beneath terminal screws on base using
appropriate wiring schematic (see figs. 2 through 4).
3. Place base over hole in wall and mark mounting hole
locations on wall using base as a template.
4. Move base out of the way. Drill mounting holes.
5. Fasten base loosely to wall, as shown in fig. 1, using two
mounting screws. Place a level against bottom of base,
adjust until level, and then tighten screws. (Leveling is for
appearance only and will not affect thermostat operation.)
If you are using existing mounting holes, or if holes drilled
are too large and do not allow you to tighten base snugly,
use plastic screw anchors to secure subbase.
6. Push excess wire into wall and plug hole with a fireresistant material (such as fiberglass insulation) to
prevent drafts from affecting thermostat operation.
2 “AA” alkaline batteries are included in the thermostat at the
factory with a battery tag to prevent power drainage. You
must remove the battery tag to engage the batteries.
“BATT”“BATT”
If
“BATT” is displayed, the batteries are low and should be
“BATT”“BATT”
!
Battery LocationBattery Location
Battery Location
Battery LocationBattery Location
replaced with fresh “AA” Energizer® alkaline batteries. To
All wiring diagrams are for typical systems only. Refer to
equipment manufacturers’ instructions for specific system wiring information.
O
Reversing Valve
Energized in Cool
Mode
B
Reversing Valve
Energized in Heat,
Off, Emergency
Mode
Y2
2nd Stage
Compressor
Compressor
Contactor
replace batteries, press system button to
batteries along the top of the base (see Fig. 1). The batteries
must be installed with the positive (+) end to the left.
GW2
Fan
Relay
Aux
Heat
Relay
E/W1
Emergency
Heat
Relay
CY1
*
MONITOR
Figure 2. Typical wiring diagram for single transformer heat pump systems
*The 24 volt neutral connection to terminal C on the thermostat is not required if you replace the batteries once a year with fresh “AA” Energizer® alkaline batteries.
If safety circuits are in only one of the systems, remove
the transformer of the system with NO safety circuits.
NOTE
OFFOFF
OFF, install the
OFFOFF
L
SYSTEM
SWITCH
24 VAC
TRANSFORMER
(Class II Current Limited)
THERMOSTAT
R
SYSTEM
Hot
120 VAC
Neutral
TAPE OFF!
HOT
120 VAC
NEUTRAL
CUT AND
24 VAC
O
Reversing
Valve
Energized in
Cool Mode
B
Reversing
Valve
Energized in
Heat, Off,
Emergency
Mode
Y2
2nd Stage
Compressor
Compressor
Contactor
GW2
Fan
Relay
E/W1
Emergency
Aux
Heat
Relay
Heat
Relay
TWO COMMONS MUST
BE JUMPERED TOGETHER!
CY1
*
SYSTEM
MONITOR
SWITCH
L
THERMOSTAT
R
SYSTEM
Limit or
Safety
Switches
24 VAC
TRANSFORMER
(Class II Current Limited)
Hot
120 VAC
Neutral
Figure 3. Typical wiring diagram for two transformer heat pump systems with NO safety circuits
*The 24 volt neutral connection to terminal C on the thermostat is not required if you replace the batteries once a year with fresh “AA” Energizer® alkaline batteries.
2
WIRING DIAGRAMSWIRING DIAGRAMS
WIRING DIAGRAMS
WIRING DIAGRAMSWIRING DIAGRAMS
O
Reversing
Valve
Energized in
Cool Mode
B
Reversing
Valve
Energized in
Heat, Off,
Emergency
Mode
Y2
2nd Stage
Compressor
Compressor
Contactor
GW2
Fan
Relay
Polarity must be observed. If the HOT side of the second transformer
is jumpered to the COMMON side of the first transformer a short will
be made. Damage to equipment will occur when power is restored.
E/W1
Emergency
Heat
Relay
Aux
Heat
Relay
TWO COMMONS MUST
BE JUMPERED TOGETHER!
CY1
*
SYSTEM
MONITOR
SWITCH
NOTE
L
COMMON
R
Limit or
Switches
Limit or
Safety
Switches
THERMOSTAT
Safety
24 VAC
24 VAC
ACCESSORY
RELAY N.O.
CONTACT
Current Limited)
COMMON
24 VAC120 VAC
Heat Pump Transformer
(Class II Current Limited)
SYSTEM
Auxiliary
Heating
Transformer
(Class II
Limit or
Safety
HOT
Switches
120 VAC
The accessory relay scheme
is required when safety
circuits exist in both systems.
Limit or
Safety
Switches
NEUTRAL
NOTE
HOT
NEUTRAL
Figure 4. Typical wiring diagram for two transformer heat pump systems with safety circuits in BOTH systems
*The 24 volt neutral connection to terminal C on the thermostat is not required if you replace the batteries once a year with fresh “AA” Energizer® alkaline batteries.
Refer to equipment manufacturers' instructions for specific
system wiring information.
You can configure the thermostat for use with the following
heat pump system types:
HEAT PUMP TYPE 1HEAT PUMP TYPE 1
HEAT PUMP TYPE 1. Single stage compressor system; gas
HEAT PUMP TYPE 1HEAT PUMP TYPE 1
or electric backup.
This thermostat is designed to operate a single-transformer
system. If you have a two-transformer system, cut and tape off
one transformer. If transformer safety circuits are in only one of
the systems, remove the transformer of the system with NO
safety circuits. If required, replace remaining transformer with
a 75VA Class II transformer. After disconnecting one transformer, the two commons must be jumpered together.
Use the terminal output information below to help you wire the
thermostat properly for your heat pump system. After wiring, see
CONFIGURATION CONFIGURATION
CONFIGURATION section for proper thermostat configuration.
HeatMalfunction 24 Volt24 Volt HP 1 and EmergencyNoHeat andBlower/Fan Energized Energized Energized
Pump 1Light(Common) (Hot) EmergencyModeOutputCool modeon call for Heatin Coolin Heat
2nd stage 1st stage1st stageand CoolModeOFF
HeatHP 22nd(compressor) Set GAS/ELEC switchEmergency
Pump 23rd stagestagefor Emergency modemode
compressor
*The 24 volt neutral connection to terminal C on the thermostat is not required if you replace the batteries once a year with fresh “AA” Energizer® alkaline batteries.
O
Reversing
Valve
Energized in
Cool Mode
B
Reversing
Valve
Energized in
Heat Mode
Off Emergency
Y1
Compressor
Contactor
Stage 1
Y2
Compressor
Contactor
Stage 2
G
Fan
Relay
E/W1
Heat
Relay
Stage 1
W2
Heat
Relay
Stage 2
*
CR
THERMOSTAT
SYSTEM
Hot
24 VAC120 VAC
Neutral
TRANSFORMER
(Class II, Current Limited)
Figure 5. Typical wiring diagram for single transformer multi-stage systems
*The 24 volt neutral connection to terminal C on the thermostat is not required if you replace the batteries once a year with fresh “AA” Energizer® alkaline batteries.
Refer to equipment manufacturers' instructions for specific
system wiring information.
You can configure the thermostat for use with either multi-stage
electric heat systems or multi-stage gas systems. When configured for
energized on a call for heat.
This thermostat is designed to operate a single-transformer
system. If you have a two-transformer system, cut and tape off
*The 24 volt neutral connection to terminal C on the thermostat is not required if you replace the batteries once a year with fresh “AA” Energizer® alkaline batteries.
To prevent static discharge problems, touch side ofTo prevent static discharge problems, touch side of
To prevent static discharge problems, touch side of
To prevent static discharge problems, touch side ofTo prevent static discharge problems, touch side of
thermostat to release static build-up before touchingthermostat to release static build-up before touching
thermostat to release static build-up before touching
thermostat to release static build-up before touchingthermostat to release static build-up before touching
any keys.any keys.
any keys.
any keys.any keys.
If at any time during testing your system does not operate
properly, contact a qualified serviceperson.
Fan OperationFan Operation
Fan Operation
Fan OperationFan Operation
If your system does not have a
Heating SystemHeating System
Heating System.
Heating SystemHeating System
1. Turn on power to system.
2. Move FAN switch to
to operate.
3. Move FAN switch to
stop immediately.
ON ON
ON position. The blower should begin
ON ON
AUTO AUTO
AUTO position. The blower should
AUTO AUTO
!
Do not allow the compressor to run unless the com-Do not allow the compressor to run unless the com-
Do not allow the compressor to run unless the com-
Do not allow the compressor to run unless the com-Do not allow the compressor to run unless the compressor oil heaters have been operational for 6 hourspressor oil heaters have been operational for 6 hours
pressor oil heaters have been operational for 6 hours
pressor oil heaters have been operational for 6 hourspressor oil heaters have been operational for 6 hours
and the system has not been operational for at leastand the system has not been operational for at least
and the system has not been operational for at least
and the system has not been operational for at leastand the system has not been operational for at least
5 minutes.5 minutes.
5 minutes.
5 minutes.5 minutes.
Heating SystemHeating System
Heating System
Heating SystemHeating System
1. Press SYSTEM button to select the
the auxiliary heating system has a standing pilot, be sure
to light it.
2. Press
temperature. The heating system should begin to
operate. The display should show
setpoint temperature display is flashing, the compressor
lockout feature is operating (see Configuration menu,
item 5).
3. Adjust temperature setting to 3° above room temperature.
If your system configuration is set at MS2, HP2 or HP1,
the auxiliary heat system should begin to operate and the
display should show
4. Press
ture. The heating system should stop operating.
to adjust thermostat setting to 1° above room
“STG1+2”“STG1+2”
“STG1+2”.
“STG1+2”“STG1+2”
to adjust the thermostat below room tempera-
G G
G terminal connection, skip to
G G
CAUTION
Flame iconFlame icon
Flame icon ( ). If
Flame iconFlame icon
“STG1”“STG1”
“STG1”. However, if the
“STG1”“STG1”
one transformer. If transformer safety circuits are in only one of
the systems, remove the transformer of the system with NO
safety circuits. If required, replace remaining transformer with
a 75VA Class II transformer. After disconnecting one transformer, the two commons must be jumpered together.
Use the terminal output information below to help you wire the
thermostat properly for your multi-stage system. After wiring,
CONFIGURATION CONFIGURATION
see
CONFIGURATION section for proper thermostat configu-
CONFIGURATION CONFIGURATION
ration.
Y2Y2
Y2
Y2Y2
EMER bypasses the Heat Pump to use the heat source wired
to terminal E on the thermostat. EMER is typically used when
compressor operation is not desired, or you prefer back-up
heat only.
1. Press SYSTEM button to select EMER.
on the display.
2. Press to adjust thermostat setting above room
temperature. The Aux. heating system will begin to
operate. The display will show
and
operating.
3. Adjust temperature setting to 3° above room temperature.
The auxiliary heat system should begin to operate and the
display should show
4. Press
ture. The Aux. heating system should stop operating.
To prevent compressor and/or property damage, ifTo prevent compressor and/or property damage, if
To prevent compressor and/or property damage, if
To prevent compressor and/or property damage, ifTo prevent compressor and/or property damage, if
the outdoor temperature is below 50°F, DO NOTthe outdoor temperature is below 50°F, DO NOT
the outdoor temperature is below 50°F, DO NOT
the outdoor temperature is below 50°F, DO NOTthe outdoor temperature is below 50°F, DO NOT
operate the cooling system.operate the cooling system.
operate the cooling system.
operate the cooling system.operate the cooling system.
1. Press SYSTEM button to select the
2. Press
temperature. The blower should come on immediately on
high speed, followed by cold air circulation. The display
should show
3. Adjust temperature setting to 3° below room temperature.
The second stage cooling should begin to operate and
the display should show
4. Press
temperature. The cooling system should stop operating.
Y1Y1
Y1
Y1Y1
Emergency SystemEmergency System
Emergency System
Emergency SystemEmergency System
Flame iconFlame icon
Flame icon (
Flame iconFlame icon
to adjust the thermostat below room tempera-
!
Cooling SystemCooling System
Cooling System
Cooling SystemCooling System
to adjust thermostat setting below room
“STG1”“STG1”
“STG1”.
“STG1”“STG1”
to adjust the temperature setting above room
GG
G
GG
Heat if configuredModeEmergency
to Electric Heat)Modes
“STG1”“STG1”
“STG1” flashing
“STG1”“STG1”
) to indicate that the Aux. system is
“STG1+2”“STG1+2”
“STG1+2”.
“STG1+2”“STG1+2”
OO
O
OO
“EMER”“EMER”
“EMER” will flash
“EMER”“EMER”
CAUTION
Snowflake iconSnowflake icon
Snowflake icon ( ).
Snowflake iconSnowflake icon
“STG1+2”“STG1+2”
“STG1+2”.
“STG1+2”“STG1+2”
BB
B
BB
“EMER”“EMER”
“EMER”
“EMER”“EMER”
4
Loading...
+ 8 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.