White Rodgers 1F85-277 User Manual

Page 1
1F85-2771F85-277
1F85-277
1F85-2771F85-277
Heating & Air Conditioning
7 Day/5-1-1 Programmable/Non-programmable, Auto
Changeover, Multi-Stage/Heat Pump Thermostat
INSTALLATION INSTRUCTIONS
Operator: Save these instructions for future use!Operator: Save these instructions for future use!
Operator: Save these instructions for future use!
Operator: Save these instructions for future use!Operator: Save these instructions for future use!
FAILURE TO READ AND FOLLOW ALL INSTRUCTIONS CAREFULLY BEFOREFAILURE TO READ AND FOLLOW ALL INSTRUCTIONS CAREFULLY BEFORE
FAILURE TO READ AND FOLLOW ALL INSTRUCTIONS CAREFULLY BEFORE
FAILURE TO READ AND FOLLOW ALL INSTRUCTIONS CAREFULLY BEFOREFAILURE TO READ AND FOLLOW ALL INSTRUCTIONS CAREFULLY BEFORE INSTALLING OR OPERATING THIS CONTROL COULD CAUSE PERSONALINSTALLING OR OPERATING THIS CONTROL COULD CAUSE PERSONAL
INSTALLING OR OPERATING THIS CONTROL COULD CAUSE PERSONAL
INSTALLING OR OPERATING THIS CONTROL COULD CAUSE PERSONALINSTALLING OR OPERATING THIS CONTROL COULD CAUSE PERSONAL INJURY AND/OR PROPERTY DAMAGE.INJURY AND/OR PROPERTY DAMAGE.
INJURY AND/OR PROPERTY DAMAGE.
INJURY AND/OR PROPERTY DAMAGE.INJURY AND/OR PROPERTY DAMAGE.
PREPARATIONSPREPARATIONS
PREPARATIONS
PREPARATIONSPREPARATIONS
YOUR THERMOSTAT REPLACESYOUR THERMOSTAT REPLACES
YOUR THERMOSTAT REPLACES
YOUR THERMOSTAT REPLACESYOUR THERMOSTAT REPLACES
DescriptionDescription
Description
DescriptionDescription Heat Pump (No Aux. or Emergency Heat) Yes Heat Pump (with Aux. or Emergency Heat) Yes Standard Heat & Cooling Systems Yes Two Stage Heat & Two Stage Cool Yes Standard Heat Only Systems Yes Millivolt Heat Only Systems – Floor or Wall Furnaces Yes Standard Central Air Conditioning Yes Gas or Oil Heat Yes Electric Furnace Yes Hydronic (Hot Water) Zone Heat – 2 Wires Yes Hydronic (Hot Water) Zone Heat – 3 Wires No
1F85-2771F85-277
1F85-277
1F85-2771F85-277
Assemble tools required as shown below.
HAND OR POWER DRILL WITH 3/16 INCH DRILL BIT, IF NEEDED
REMOVING OLD THERMOSTATREMOVING OLD THERMOSTAT
REMOVING OLD THERMOSTAT
REMOVING OLD THERMOSTATREMOVING OLD THERMOSTAT
FLAT BLADE SCREWDRIVER
WIRE CUTTER/STRIPPER
CAUTION
!
To prevent electrical shock and/or equipment dam-To prevent electrical shock and/or equipment dam-
To prevent electrical shock and/or equipment dam-
To prevent electrical shock and/or equipment dam-To prevent electrical shock and/or equipment dam­age, disconnect electric power to system at main fuseage, disconnect electric power to system at main fuse
age, disconnect electric power to system at main fuse
age, disconnect electric power to system at main fuseage, disconnect electric power to system at main fuse or circuit breaker box until installation is complete.or circuit breaker box until installation is complete.
or circuit breaker box until installation is complete.
or circuit breaker box until installation is complete.or circuit breaker box until installation is complete.
Before removing wires from old thermostat's switching sub-
label each wirelabel each wire
base,
label each wire with the terminal designation it was
label each wirelabel each wire
removed from.
1. Shut off electricity at the main fuse box until installation is complete. Ensure that electrical power is disconnected.
Remove Old ThermostatRemove Old Thermostat
2.
Remove Old Thermostat: A standard heat/cool
Remove Old ThermostatRemove Old Thermostat thermostat consists of three basic parts: a. The cover, which may be either a snap-on or
hinge type.
b. The base, which is removed by loosening all
captive screws.
c. The switching subbase, which is removed by
unscrewing the mounting screws that hold it on the wall or adaptor plate.
3. Remove the front cover of the old thermostat. wireswires
still attachedstill attached
wires
still attached, remove wall plate from the wall. If
wireswires
still attachedstill attached the old thermostat has a wall mounting plate, remove the thermostat and the wall mounting plate as an assembly.
4. Identify each wire attached to the old thermostat.
5. Disconnect the wires from the old thermostat one at a DO NOT LET WIRES FALL BACK INTO THEDO NOT LET WIRES FALL BACK INTO THE
time.
DO NOT LET WIRES FALL BACK INTO THE
DO NOT LET WIRES FALL BACK INTO THEDO NOT LET WIRES FALL BACK INTO THE
WALLWALL
WALL.
WALLWALL
6. Install new thermostat using the following procedures.
WithWith
With
WithWith
Y2
C R
E/W1
Y1
Mounting Hole
Figure 1 – Thermostat baseFigure 1 – Thermostat base
Figure 1 – Thermostat base
Figure 1 – Thermostat baseFigure 1 – Thermostat base
ATTENTION!ATTENTION!
ATTENTION! This product does not contain mercury. How-
ATTENTION!ATTENTION! ever, this product may replace a unit which contains mercury.
Do not open mercury cells. If a cell becomes damaged, do touch any spilled mercury. Wearing non-absorbent gloves, clean up the spilled mercury and place into a container which can be sealed. If a cell becomes damaged, the unit should be discarded.
Mercury must not be discarded in household trash. When the unit this product is replacing is to be discarded, place in a suitable container and return to White-Rodgers at 2895 Harrison Street, Batesville, AR 72501 for proper disposal.
OBLW2G
ELEC. GAS
AUTOON
Mounting Hole
Elec-Gas Switch
notnot
not
notnot
White-Rodgers is a division
of Emerson Electric Co.
www.white-rodgers.com
PART NO. 37-6560APART NO. 37-6560A
PART NO. 37-6560A
PART NO. 37-6560APART NO. 37-6560A
0430
Page 2
MOUNTING AND WIRINGMOUNTING AND WIRING
MOUNTING AND WIRING
MOUNTING AND WIRINGMOUNTING AND WIRING
CAUTION
WARNING
!
Do not use on circuits exceeding specified voltage.Do not use on circuits exceeding specified voltage.
Do not use on circuits exceeding specified voltage.
Do not use on circuits exceeding specified voltage.Do not use on circuits exceeding specified voltage. Higher voltage will damage control and could causeHigher voltage will damage control and could cause
Higher voltage will damage control and could cause
Higher voltage will damage control and could causeHigher voltage will damage control and could cause shock or fire hazard.shock or fire hazard.
shock or fire hazard.
shock or fire hazard.shock or fire hazard.
Do not short out terminals on gas valve or primaryDo not short out terminals on gas valve or primary
Do not short out terminals on gas valve or primary
Do not short out terminals on gas valve or primaryDo not short out terminals on gas valve or primary control to test. Short or incorrect wiring will damagecontrol to test. Short or incorrect wiring will damage
control to test. Short or incorrect wiring will damage
control to test. Short or incorrect wiring will damagecontrol to test. Short or incorrect wiring will damage thermostat and could cause personal injury and/orthermostat and could cause personal injury and/or
thermostat and could cause personal injury and/or
thermostat and could cause personal injury and/orthermostat and could cause personal injury and/or property damage.property damage.
property damage.
property damage.property damage.
Thermostat installation and all components of the system shall conform to Class II circuits per the NEC code.
Electric/Gas Switch (Fan Option)Electric/Gas Switch (Fan Option)
Electric/Gas Switch (Fan Option)
Electric/Gas Switch (Fan Option)Electric/Gas Switch (Fan Option)
This thermostat is configured from the factory to operate a heat/ cool, fossil fuel (gas, oil, etc.), forced air system. It is configured correctly for any system that DOES NOT require the thermostat to energize the fan on a call for heat. If you system is an electric heat or heat-pump system that REQUIRES the thermostat to turn on the fan on a call for heat, locate the ELEC/GAS switch on the back of the thermostat (see fig. 1) and switch it to the ELEC position. This will allow the thermostat to energize the fan immediately on a call for heat. If you are unsure if the heating/ cooling system requires the thermostat to control the fan, contact a qualified heating and air conditioning service person.
When the thermostat is configured for Heat Pump, the thermo­stat will always power the circulator fan on a call for heat in the HEAT mode. The ELEC/GAS switch must be set to match the type of Auxiliary heat your system uses for proper operation in the EMERgency mode.
Take care when securing and routing wires so they doTake care when securing and routing wires so they do
Take care when securing and routing wires so they do
Take care when securing and routing wires so they doTake care when securing and routing wires so they do not short to adjacent terminals or rear of thermostat.not short to adjacent terminals or rear of thermostat.
not short to adjacent terminals or rear of thermostat.
not short to adjacent terminals or rear of thermostat.not short to adjacent terminals or rear of thermostat. Personal injury and/or property damage may occur.Personal injury and/or property damage may occur.
Personal injury and/or property damage may occur.
Personal injury and/or property damage may occur.Personal injury and/or property damage may occur.
Attach Thermostat Base to WallAttach Thermostat Base to Wall
Attach Thermostat Base to Wall
Attach Thermostat Base to WallAttach Thermostat Base to Wall
1. Remove the packing material from the thermostat. Gently pull the cover straight off the base. Forcing or prying on the thermostat will cause damage to the unit.
2. Connect wires beneath terminal screws on base using appropriate wiring schematic (see figs. 2 through 4).
3. Place base over hole in wall and mark mounting hole locations on wall using base as a template.
4. Move base out of the way. Drill mounting holes.
5. Fasten base loosely to wall, as shown in fig. 1, using two mounting screws. Place a level against bottom of base, adjust until level, and then tighten screws. (Leveling is for appearance only and will not affect thermostat operation.) If you are using existing mounting holes, or if holes drilled are too large and do not allow you to tighten base snugly, use plastic screw anchors to secure subbase.
6. Push excess wire into wall and plug hole with a fire­resistant material (such as fiberglass insulation) to prevent drafts from affecting thermostat operation.
2 “AA” alkaline batteries are included in the thermostat at the factory with a battery tag to prevent power drainage. You must remove the battery tag to engage the batteries.
“BATT”“BATT”
If
“BATT” is displayed, the batteries are low and should be
“BATT”“BATT”
!
Battery LocationBattery Location
Battery Location
Battery LocationBattery Location
replaced with fresh “AA” Energizer® alkaline batteries. To
All wiring diagrams are for typical systems only. Refer to equipment manufacturers’ instructions for specific system wir­ing information.
O
Reversing Valve
Energized in Cool
Mode
B
Reversing Valve
Energized in Heat,
Off, Emergency
Mode
Y2
2nd Stage
Compressor
Compressor
Contactor
replace batteries, press system button to batteries along the top of the base (see Fig. 1). The batteries must be installed with the positive (+) end to the left.
G W2
Fan
Relay
Aux
Heat
Relay
E/W1
Emergency
Heat
Relay
CY1
*
MONITOR
Figure 2. Typical wiring diagram for single transformer heat pump systems
*The 24 volt neutral connection to terminal C on the thermostat is not required if you replace the batteries once a year with fresh “AA” Energizer® alkaline batteries.
If safety circuits are in only one of the systems, remove the transformer of the system with NO safety circuits.
NOTE
OFFOFF
OFF, install the
OFFOFF
L
SYSTEM SWITCH
24 VAC
TRANSFORMER
(Class II Current Limited)
THERMOSTAT
R
SYSTEM
Hot
120 VAC
Neutral
TAPE OFF!
HOT
120 VAC
NEUTRAL
CUT AND
24 VAC
O
Reversing
Valve
Energized in
Cool Mode
B
Reversing
Valve
Energized in
Heat, Off,
Emergency
Mode
Y2
2nd Stage
Compressor
Compressor
Contactor
G W2
Fan
Relay
E/W1
Emergency
Aux
Heat
Relay
Heat
Relay
TWO COMMONS MUST BE JUMPERED TOGETHER!
CY1
*
SYSTEM
MONITOR
SWITCH
L
THERMOSTAT
R
SYSTEM
Limit or
Safety
Switches
24 VAC
TRANSFORMER
(Class II Current Limited)
Hot
120 VAC
Neutral
Figure 3. Typical wiring diagram for two transformer heat pump systems with NO safety circuits
*The 24 volt neutral connection to terminal C on the thermostat is not required if you replace the batteries once a year with fresh “AA” Energizer® alkaline batteries.
2
Page 3
WIRING DIAGRAMSWIRING DIAGRAMS
WIRING DIAGRAMS
WIRING DIAGRAMSWIRING DIAGRAMS
O
Reversing
Valve
Energized in
Cool Mode
B
Reversing
Valve
Energized in
Heat, Off,
Emergency
Mode
Y2
2nd Stage
Compressor
Compressor
Contactor
G W2
Fan
Relay
Polarity must be observed. If the HOT side of the second transformer is jumpered to the COMMON side of the first transformer a short will be made. Damage to equipment will occur when power is restored.
E/W1
Emergency
Heat
Relay
Aux Heat
Relay
TWO COMMONS MUST BE JUMPERED TOGETHER!
CY1
*
SYSTEM
MONITOR
SWITCH
NOTE
L
COMMON
R
Limit or
Switches
Limit or
Safety
Switches
THERMOSTAT
Safety
24 VAC
24 VAC
ACCESSORY
RELAY N.O.
CONTACT
Current Limited)
COMMON
24 VAC 120 VAC
Heat Pump Transformer
(Class II Current Limited)
SYSTEM
Auxiliary
Heating
Transformer
(Class II
Limit or
Safety
HOT
Switches
120 VAC
The accessory relay scheme is required when safety circuits exist in both systems.
Limit or
Safety
Switches
NEUTRAL
NOTE
HOT
NEUTRAL
Figure 4. Typical wiring diagram for two transformer heat pump systems with safety circuits in BOTH systems
*The 24 volt neutral connection to terminal C on the thermostat is not required if you replace the batteries once a year with fresh “AA” Energizer® alkaline batteries.
Heat Pump Terminal OutputsHeat Pump Terminal Outputs
Heat Pump Terminal Outputs
Heat Pump Terminal OutputsHeat Pump Terminal Outputs
Refer to equipment manufacturers' instructions for specific system wiring information.
You can configure the thermostat for use with the following heat pump system types: HEAT PUMP TYPE 1HEAT PUMP TYPE 1
HEAT PUMP TYPE 1. Single stage compressor system; gas
HEAT PUMP TYPE 1HEAT PUMP TYPE 1 or electric backup.
This thermostat is designed to operate a single-transformer system. If you have a two-transformer system, cut and tape off
one transformer. If transformer safety circuits are in only one of the systems, remove the transformer of the system with NO safety circuits. If required, replace remaining transformer with a 75VA Class II transformer. After disconnecting one trans­former, the two commons must be jumpered together.
Use the terminal output information below to help you wire the thermostat properly for your heat pump system. After wiring, see CONFIGURATION CONFIGURATION
CONFIGURATION section for proper thermostat configuration.
CONFIGURATION CONFIGURATION
THERMOSTAT TERMINALS (HEAT PUMP)THERMOSTAT TERMINALS (HEAT PUMP)
THERMOSTAT TERMINALS (HEAT PUMP)
THERMOSTAT TERMINALS (HEAT PUMP)THERMOSTAT TERMINALS (HEAT PUMP)
SYSTEMSYSTEM
SYSTEM
SYSTEMSYSTEM
LL
L
LL
C*C*
C*
C*C*
RR
R
RR
W2W2
W2
W2W2
E/W1E/W1
E/W1
E/W1E/W1
Y2Y2
Y2
Y2Y2
Y1Y1
Y1
Y1Y1
GG
G
GG
OO
O
OO
BB
B
BB
Heat Malfunction 24 Volt 24 Volt HP 1 and Emergency No Heat and Blower/Fan Energized Energized Energized Pump 1 Light (Common) (Hot) Emergency Mode Output Cool mode on call for Heat in Cool in Heat
2nd stage 1st stage 1st stage and Cool Mode OFF
Heat HP 2 2nd (compressor) Set GAS/ELEC switch Emergency Pump 2 3rd stage stage for Emergency mode mode
compressor
*The 24 volt neutral connection to terminal C on the thermostat is not required if you replace the batteries once a year with fresh “AA” Energizer® alkaline batteries.
O
Reversing
Valve
Energized in
Cool Mode
B
Reversing
Valve
Energized in
Heat Mode
Off Emergency
Y1
Compressor
Contactor
Stage 1
Y2
Compressor
Contactor
Stage 2
G
Fan
Relay
E/W1
Heat
Relay
Stage 1
W2
Heat
Relay
Stage 2
*
C R
THERMOSTAT
SYSTEM
Hot
24 VAC 120 VAC
Neutral
TRANSFORMER
(Class II, Current Limited)
Figure 5. Typical wiring diagram for single transformer multi-stage systems
*The 24 volt neutral connection to terminal C on the thermostat is not required if you replace the batteries once a year with fresh “AA” Energizer® alkaline batteries.
3
Page 4
Multi-Stage Terminal OutputsMulti-Stage Terminal Outputs
Multi-Stage Terminal Outputs
Multi-Stage Terminal OutputsMulti-Stage Terminal Outputs
Refer to equipment manufacturers' instructions for specific system wiring information.
You can configure the thermostat for use with either multi-stage electric heat systems or multi-stage gas systems. When con­figured for energized on a call for heat.
This thermostat is designed to operate a single-transformer system. If you have a two-transformer system, cut and tape off
SYSTEMSYSTEM
SYSTEM
SYSTEMSYSTEM
Multi-stage Malfunction 24 Volt 24 Volt Heat Mode Heat mode Cool Mode Cool Mode Blower/Fan Energized Energized Energized
*The 24 volt neutral connection to terminal C on the thermostat is not required if you replace the batteries once a year with fresh “AA” Energizer® alkaline batteries.
CHECK THERMOSTAT OPERATIONCHECK THERMOSTAT OPERATION
CHECK THERMOSTAT OPERATION
CHECK THERMOSTAT OPERATIONCHECK THERMOSTAT OPERATION
electric electric
electric heat, the
electric electric
LL
L
LL
Light (Common) (Hot) 2nd stage 1st stage 2nd stage 1st stage on call for Cool (and in Cool in Heat, Off,
GG
G terminal (blower/fan) will be
GG
THERMOSTAT TERMINALS (MULTI-STAGE)THERMOSTAT TERMINALS (MULTI-STAGE)
THERMOSTAT TERMINALS (MULTI-STAGE)
THERMOSTAT TERMINALS (MULTI-STAGE)THERMOSTAT TERMINALS (MULTI-STAGE)
C*C*
C*
C*C*
RR
R
RR
W2W2
W2
W2W2
E/W1E/W1
E/W1
E/W1E/W1
NOTE
To prevent static discharge problems, touch side ofTo prevent static discharge problems, touch side of
To prevent static discharge problems, touch side of
To prevent static discharge problems, touch side ofTo prevent static discharge problems, touch side of thermostat to release static build-up before touchingthermostat to release static build-up before touching
thermostat to release static build-up before touching
thermostat to release static build-up before touchingthermostat to release static build-up before touching any keys.any keys.
any keys.
any keys.any keys.
If at any time during testing your system does not operate properly, contact a qualified serviceperson.
Fan OperationFan Operation
Fan Operation
Fan OperationFan Operation
If your system does not have a Heating SystemHeating System
Heating System.
Heating SystemHeating System
1. Turn on power to system.
2. Move FAN switch to to operate.
3. Move FAN switch to stop immediately.
ON ON
ON position. The blower should begin
ON ON
AUTO AUTO
AUTO position. The blower should
AUTO AUTO
!
Do not allow the compressor to run unless the com-Do not allow the compressor to run unless the com-
Do not allow the compressor to run unless the com-
Do not allow the compressor to run unless the com-Do not allow the compressor to run unless the com­pressor oil heaters have been operational for 6 hourspressor oil heaters have been operational for 6 hours
pressor oil heaters have been operational for 6 hours
pressor oil heaters have been operational for 6 hourspressor oil heaters have been operational for 6 hours and the system has not been operational for at leastand the system has not been operational for at least
and the system has not been operational for at least
and the system has not been operational for at leastand the system has not been operational for at least 5 minutes.5 minutes.
5 minutes.
5 minutes.5 minutes.
Heating SystemHeating System
Heating System
Heating SystemHeating System
1. Press SYSTEM button to select the the auxiliary heating system has a standing pilot, be sure to light it.
2. Press temperature. The heating system should begin to operate. The display should show setpoint temperature display is flashing, the compressor lockout feature is operating (see Configuration menu, item 5).
3. Adjust temperature setting to 3° above room temperature. If your system configuration is set at MS2, HP2 or HP1, the auxiliary heat system should begin to operate and the display should show
4. Press ture. The heating system should stop operating.
to adjust thermostat setting to 1° above room
“STG1+2”“STG1+2”
“STG1+2”.
“STG1+2”“STG1+2”
to adjust the thermostat below room tempera-
G G
G terminal connection, skip to
G G
CAUTION
Flame iconFlame icon
Flame icon ( ). If
Flame iconFlame icon
“STG1”“STG1”
“STG1”. However, if the
“STG1”“STG1”
one transformer. If transformer safety circuits are in only one of the systems, remove the transformer of the system with NO safety circuits. If required, replace remaining transformer with a 75VA Class II transformer. After disconnecting one trans­former, the two commons must be jumpered together.
Use the terminal output information below to help you wire the thermostat properly for your multi-stage system. After wiring,
CONFIGURATION CONFIGURATION
see
CONFIGURATION section for proper thermostat configu-
CONFIGURATION CONFIGURATION
ration.
Y2Y2
Y2
Y2Y2
EMER bypasses the Heat Pump to use the heat source wired to terminal E on the thermostat. EMER is typically used when compressor operation is not desired, or you prefer back-up heat only.
1. Press SYSTEM button to select EMER. on the display.
2. Press to adjust thermostat setting above room temperature. The Aux. heating system will begin to operate. The display will show
and operating.
3. Adjust temperature setting to 3° above room temperature. The auxiliary heat system should begin to operate and the display should show
4. Press ture. The Aux. heating system should stop operating.
To prevent compressor and/or property damage, ifTo prevent compressor and/or property damage, if
To prevent compressor and/or property damage, if
To prevent compressor and/or property damage, ifTo prevent compressor and/or property damage, if the outdoor temperature is below 50°F, DO NOTthe outdoor temperature is below 50°F, DO NOT
the outdoor temperature is below 50°F, DO NOT
the outdoor temperature is below 50°F, DO NOTthe outdoor temperature is below 50°F, DO NOT operate the cooling system.operate the cooling system.
operate the cooling system.
operate the cooling system.operate the cooling system.
1. Press SYSTEM button to select the
2. Press temperature. The blower should come on immediately on high speed, followed by cold air circulation. The display should show
3. Adjust temperature setting to 3° below room temperature. The second stage cooling should begin to operate and the display should show
4. Press temperature. The cooling system should stop operating.
Y1Y1
Y1
Y1Y1
Emergency SystemEmergency System
Emergency System
Emergency SystemEmergency System
Flame iconFlame icon
Flame icon (
Flame iconFlame icon
to adjust the thermostat below room tempera-
!
Cooling SystemCooling System
Cooling System
Cooling SystemCooling System
to adjust thermostat setting below room
“STG1”“STG1”
“STG1”.
“STG1”“STG1”
to adjust the temperature setting above room
GG
G
GG
Heat if configured Mode Emergency
to Electric Heat) Modes
“STG1”“STG1”
“STG1” flashing
“STG1”“STG1”
) to indicate that the Aux. system is
“STG1+2”“STG1+2”
“STG1+2”.
“STG1+2”“STG1+2”
OO
O
OO
“EMER”“EMER”
“EMER” will flash
“EMER”“EMER”
CAUTION
Snowflake iconSnowflake icon
Snowflake icon ( ).
Snowflake iconSnowflake icon
“STG1+2”“STG1+2”
“STG1+2”.
“STG1+2”“STG1+2”
BB
B
BB
“EMER”“EMER”
“EMER”
“EMER”“EMER”
4
Page 5
Before you begin programming your thermostat, you should be familiar with its features and with the display and the location and operation of the thermostat buttons. Your thermostat consists of two parts: the thermostat cover and the base. To remove the cover, pull it straight out from the base. To replace the cover, line up the cover with the base and press until the cover snaps onto the base.
The Thermostat Buttons and SwitchesThe Thermostat Buttons and Switches
The Thermostat Buttons and Switches
The Thermostat Buttons and SwitchesThe Thermostat Buttons and Switches
Raises temperature setting
1
Lowers temperature setting.
2
TIME button.
3
PRGM (program) button.
4
RUN (run program) button.
5
HOLD temperature button.
6
ONON
FAN switch (
7
ON,
ONON
AUTOAUTO
AUTO)
AUTOAUTO
OPERATIONOPERATION
OPERATION
OPERATIONOPERATION
SYSTEM button (
8
Indicates day of the week.
9
Flame iconFlame icon
Flame icon ( ) is displayed when the system is in
Flame iconFlame icon
10
HEAT HEAT
HEAT mode.
HEAT HEAT the system is in
Snowflake icon Snowflake icon
Snowflake icon (
Snowflake icon Snowflake icon when thermostat is in
Displays
11
should be replaced. Only minutes field are displayed when batteries are low and with no system power.
Alternately displays current time and temperature. Dis-
12
plays The word
13
in the HOLD mode. when the thermostat is in a temporary HOLD mode.when the thermostat is in a temporary HOLD mode.
when the thermostat is in a temporary HOLD mode.
when the thermostat is in a temporary HOLD mode.when the thermostat is in a temporary HOLD mode. Displays currently programmed set temperature (this
14
is blank when SYSTEM is OFF). Displays
15
programmed filter time period as a reminder to change or clean your filter.
The configuration menu allows you to set certain thermostat operating characteristics to your system or personal require­ments.
Set SYSTEM
and to enter configuration menu. The display will
show the first item in the configuration menu.
The configuration menu table summarizes the configuration options. An explanation of each option follows.
Press SYSTEM menu and return to the program operation, press RUN. If no keys are pressed within fifteen minutes, the thermostat will revert to normal operation.
“BATT” “BATT”
“BATT” when the 2 "AA" batteries are low and
“BATT” “BATT”
“LO” “LO”
“LO” in the minutes field when batteries are low.
“LO” “LO”
“FLTR” “FLTR”
“FLTR” when the system has run for the
“FLTR” “FLTR”
COOLCOOL
COOL,
COOLCOOL
The DisplayThe Display
The Display
The DisplayThe Display
Snowflake icon Snowflake icon
Snowflake icon (
Snowflake icon Snowflake icon
COOL COOL
COOL mode.
COOL COOL
“HOLD” “HOLD”
“HOLD” is displayed when the thermostat is
“HOLD” “HOLD”
button to
to change to the next menu item. To exit the
AUTOAUTO
AUTO,
AUTOAUTO
) are displayed simultaneously
AUTO AUTO
AUTO mode.
AUTO AUTO
“HOLD” is displayed flashing“HOLD” is displayed flashing
“HOLD” is displayed flashing
“HOLD” is displayed flashing“HOLD” is displayed flashing
OFFOFF
OFF, then simultaneously press
OFFOFF
HEATHEAT
HEAT,
HEATHEAT
) is displayed when
Flame iconFlame icon
Flame icon ( ) and
Flame iconFlame icon
“BATT” “BATT”
“BATT” and
“BATT” “BATT”
“LO” “LO”
“LO” in the
“LO” “LO”
EMEREMER
EMER,
EMEREMER
OFFOFF
OFF)
OFFOFF
Figure 6 – Thermostat display, buttons and switchesFigure 6 – Thermostat display, buttons and switches
Figure 6 – Thermostat display, buttons and switches
Figure 6 – Thermostat display, buttons and switchesFigure 6 – Thermostat display, buttons and switches
Display ( ) when in keypad lockout mode.
16
“EMER” “EMER”
“EMER” is displayed flashing when the system is in
“EMER” “EMER”
17
EMER mode. The word
18
malfunction in the HEAT/COOL system. Display ( ) when limited HEAT/COOL range is activated.
19
The “ the temperature beyond the limited HEAT/COOL temperature range.
Stage1 & 2Stage1 & 2
Stage1 & 2 indicators: The thermostat shall indicate
Stage1 & 2Stage1 & 2
20
when the first and second stage is energized except in emergency mode. The icon is stage energized. The icons for the first and second stage energized are right side of the display.
Single Stage, Multi-stage or Heat Pump SystemSingle Stage, Multi-stage or Heat Pump System
1)
Single Stage, Multi-stage or Heat Pump System
Single Stage, Multi-stage or Heat Pump SystemSingle Stage, Multi-stage or Heat Pump System ConfigurationConfiguration
Configuration – This control can be configured for Heat
ConfigurationConfiguration Pump or two stage heat/two stage cool multi-stage opera­tion. The display indicates mode) in the display. The Multi-stage configuration can be
toggled to
key. In Multi-stage configuration, SYSTEM button will
not have Programs Per Week Programs Per Week
2)
Programs Per Week – This control can be configured for 7
Programs Per Week Programs Per Week independent day or 5/1/1/ programming or non-program­mable mode. The display indicates programs per week can be toggled to pressing the
“FAULT”“FAULT”
“FAULT” will be displayed when there is a
“FAULT”“FAULT”
” icon will flash if an attempt is made to adjust
“STG 1”“STG 1”
“STG 1” for the first
“STG 1”“STG 1”
“STG1+2”“STG1+2”
“STG1+2” located in the upper
“STG1+2”“STG1+2”
CONFIGURATION MENUCONFIGURATION MENU
CONFIGURATION MENU
CONFIGURATION MENUCONFIGURATION MENU
“MS 2”“MS 2”
“MS 2” (default for multi-stage
“MS 2”“MS 2”
“SS1”“SS1”
“SS1”,
EMEREMER
EMERgency mode.
EMEREMER
“HP2”“HP2”
“HP2”, or
“SS1”“SS1”
“HP2”“HP2”
or keys. With
“HP1”“HP1”
“HP1” by pressing the
“HP1”“HP1”
“7d”“7d”
“7d” as default. The
“7d”“7d”
“5d”“5d”
“5d” or
“5d”“5d”
“0d”“0d”
“0d” selected for non-
“0d”“0d”
“0d”“0d”
“0d” by
“0d”“0d”
or
5
Page 6
CONFIGURATION MENUCONFIGURATION MENU
CONFIGURATION MENU
CONFIGURATION MENUCONFIGURATION MENU
StepStep
Step
StepStep
1
2
3
4
5
6
7
8
9
Press the SYSTEM button until
PressPress
Press
PressPress
Button(s)Button(s)
Button(s)
Button(s)Button(s)
SystemSystem
System
SystemSystem
SystemSystem
System
SystemSystem
SystemSystem
System
SystemSystem
SystemSystem
System
SystemSystem
SystemSystem
System
SystemSystem
SystemSystem
System
SystemSystem
SystemSystem
System
SystemSystem
SystemSystem
System
SystemSystem
SystemSystem
System
SystemSystem
DisplayedDisplayed
Displayed
DisplayedDisplayed
(Factory Default)(Factory Default)
(Factory Default)
(Factory Default)(Factory Default)
MS 2MS 2
MS 2
MS 2MS 2
7d7d
7d
7d7d
PRG 4PRG 4
PRG 4
PRG 4PRG 4
4:00 HOLD4:00 HOLD
4:00 HOLD
4:00 HOLD4:00 HOLD
EMREMR
EMR
EMREMR (ON)(ON)
(ON)
(ON)(ON)
FAFA
FA
FAFA
CLCL
CL
CLCL
(OFF)(OFF)
(OFF)
(OFF)(OFF)
CDLCDL
CDL
CDLCDL
(ON)(ON)
(ON)
(ON)(ON)
FAFA
FA
FAFA
(ON)(ON)
(ON)
(ON)(ON)
OFF OFF
OFF is displayed, then press the and simultaneously
OFF OFF
INSTALLER/CONFIGURATION MENUINSTALLER/CONFIGURATION MENU
INSTALLER/CONFIGURATION MENU
INSTALLER/CONFIGURATION MENUINSTALLER/CONFIGURATION MENU
Press Press
Press
Press Press
SS1, HP2, HP1SS1, HP2, HP1
SS1, HP2, HP1 Selects Single stage, Multi-stage, or Heat Pump
SS1, HP2, HP1SS1, HP2, HP1
(increments of 15 minutes)
or or
or
or or
to selectto select
to select
to selectto select
(Single stage or 2-stage) System Configuration
5d, 0d5d, 0d
5d, 0d Selects Programs Per Week
5d, 0d5d, 0d
PRG 2PRG 2
PRG 2 Selects Programmable Periods (PRG 2 = 2
PRG 2PRG 2
programmable periods; PRG 4 = 4 programmable periods)
0:15 to 4:000:15 to 4:00
0:15 to 4:00 Selects Temporary Program Override Time
0:15 to 4:000:15 to 4:00
OFFOFF
OFF Selects Energy Management Recovery
OFFOFF
SLSL
SL Selects Fast or Slow Cycle Selection
SLSL
CLCL
CL Selects Compressor Lockout
CLCL
(ON)(ON)
(ON)
(ON)(ON)
CDLCDL
CDL Selects Backlight Display
CDLCDL
(OFF)(OFF)
(OFF)
(OFF)(OFF)
FAFA
FA Selects Fast Second Stage
FAFA
(OFF)(OFF)
(OFF)
(OFF)(OFF)
CommentsComments
Comments
CommentsComments
OFF OFF
OFF or
OFF OFF
CL OFFCL OFF
CL OFF or
CL OFFCL OFF
ON ON
OFFOFF
ON or
OFF
ON ON
OFFOFF
ONON
ON
ONON
ONON
ON
ONON
10
11
12
13
14
15
16
17
18
19
SystemSystem
System
SystemSystem
SystemSystem
System
SystemSystem
SystemSystem
System
SystemSystem
SystemSystem
System
SystemSystem
SystemSystem
System
SystemSystem
SystemSystem
System
SystemSystem
SystemSystem
System
SystemSystem
SystemSystem
System
SystemSystem
SystemSystem
System
SystemSystem
RunRun
Run Returns to the OFF position
RunRun
0 FLTR0 FLTR
0 FLTR
0 FLTR0 FLTR
0°F0°F
0°F
0°F0°F
(Room Temperature)
°F°F
°F
°F°F
AU OnAU On
AU On
AU OnAU On
LRLR
LR
LRLR
(90)(90)
(90)
(90)(90)
LRLR
LR
LRLR
(45)(45)
(45)
(45)(45)
CACA
CA
CACA
(OFF)(OFF)
(OFF)
(OFF)(OFF)
(OFF)(OFF)
(OFF)
(OFF)(OFF)
00
0
00
50-195050-1950
50-1950 (increments of 50) Selects filter replacement run time
50-195050-1950
4 LO to 4 HI4 LO to 4 HI
4 LO to 4 HI Selects Temperature Display Adjustment
4 LO to 4 HI4 LO to 4 HI
LR 62 to LR89LR 62 to LR89
LR 62 to LR89 Selects Limited
LR 62 to LR89LR 62 to LR89
LR 46 to LR 82LR 46 to LR 82
LR 46 to LR 82 Selects Limited COOL range
LR 46 to LR 82LR 46 to LR 82
programmable, SYSTEM button selection will skip Programmable periods (item 3), programmable hold time (item 4) and EMR (item 5).
Programmable Periods Programmable Periods
3)
Programmable Periods – This control can be configured
Programmable Periods Programmable Periods for 4 or 2 programmable periods. The display indicates “PRG 4”“PRG 4”
“PRG 4” in the display as default. The programmable
“PRG 4”“PRG 4” periods can be toggled to
“PRG 2”“PRG 2”
“PRG 2” by pressing the
“PRG 2”“PRG 2”
or keys. Select Temporary Program Override TimeSelect Temporary Program Override Time
4)
Select Temporary Program Override Time – The thermo-
Select Temporary Program Override TimeSelect Temporary Program Override Time stat can hold any temperature you set it to for the amount of time you select on this option. Your choices are 0:15 to 4:00 hours in 15 minute increments.
6
4 LO4 LO
4 LO to
4 LO4 LO
°C°C
°C Selects temperature display
°C°C
OFFOFF
OFF Selects AUTO Mode ON or OFF
OFFOFF
CACA
CA Feature Not Available
CACA
(ON)(ON)
(ON)
(ON)(ON)
(ON)(ON)
(ON) Selects Keypad Lockout
(ON)(ON)
001 to 999001 to 999
001 to 999 Selects Keypad lockout combination number
001 to 999001 to 999
Press System to set code
°C°C
F° or
°C selection
°C°C
HEAT HEAT
HEAT range
HEAT HEAT
Example:
1. You have selected 3:00 hours for the Temporary Pro­gram Override time period.
2. With the thermostat set to Heat or Cool, press to set the temperature to your preference. The thermostat will maintain this temperature setting for 3 hours with
“HOLD” “HOLD”
“HOLD” blinking to remind you it is in
“HOLD” “HOLD” Temporary Hold. After 3 hours, the thermostat will go back to the program temperature and
“HOLD” “HOLD”
“HOLD” will no
“HOLD” “HOLD”
longer blink or display.
4 HI4 HI
4 HI
4 HI4 HI
or
Page 7
Select Energy Management Recovery OFF or ONSelect Energy Management Recovery OFF or ON
5)
Select Energy Management Recovery OFF or ON –
Select Energy Management Recovery OFF or ONSelect Energy Management Recovery OFF or ON Energy Management Recovery (EMR) causes the thermo­stat to start heating or cooling early to make the building temperature reach the program setpoint at the time you specify. Heating will start 5 minutes early for every 1° of temperature required to reach setpoint. Cooling allows more time per degree because it takes longer to reach temperature.
Example:Example:
Example: You select EMR and have your heating program-
Example:Example: med to 65° at night and 70° at 7 AM. If the building temp­erature is 65° the difference between 65° and 70° is 5°. Allowing 5 minutes per degree the thermostat setpoint will change to 70° at 6:35 AM.
Fast or Slow Cycle SelectionFast or Slow Cycle Selection
6)
Fast or Slow Cycle Selection – The factory default setting
Fast or Slow Cycle SelectionFast or Slow Cycle Selection is fast cycle, which cycles 1st stage at approximately 1.2°F and 2nd stage 0.75°F. If you prefer slow cycle, press the
or key to change to SL. The 1st stage and 2nd
stage would be 1.5°F and 1.2°F respectively. Select Compressor Lockout CL OFF or ONSelect Compressor Lockout CL OFF or ON
7)
Select Compressor Lockout CL OFF or ON – Selecting
Select Compressor Lockout CL OFF or ONSelect Compressor Lockout CL OFF or ON CL ON will cause the thermostat to wait 5 minutes before turning on the compressor if the heating and cooling system loses power. It will also wait 5 minutes minimum between cooling and heating cycles. This is intended to help protect the compressor from short cycling. Some newer compres­sors already have a time delay built in and do not require this feature. Your compressor manufacturer can tell you if the lockout feature is already present in their system. When the thermostat compressor time delay occurs it will flash the setpoint for about five minutes.
Select Backlight DisplaySelect Backlight Display
8)
Select Backlight Display – The display backlight improves
Select Backlight DisplaySelect Backlight Display display contrast in low lighting conditions. When the terminal is powered, selecting backlight CdL ON will turn the light on continuously. Select backlight OFF will keep the light on momentarily after any key is pressed. When the CC
C terminal is not powered, this selection has no effect.
CC Select (Fast) Second Stage ON or OFFSelect (Fast) Second Stage ON or OFF
9)
Select (Fast) Second Stage ON or OFF – In the run mode,
Select (Fast) Second Stage ON or OFFSelect (Fast) Second Stage ON or OFF if the setpoint temperature is manually raised by 3°F (2°C) or more above the actual temperature with the fast second stage feature is enabled, FA ON, the second stage will energize immediately. With FA OFF, second stage will not energize until the setpoint temperature is 1°F or more above actual temperature for more than ten min­utes.
Select filter replacement run timeSelect filter replacement run time
10)
Select filter replacement run time – The thermostat will
Select filter replacement run timeSelect filter replacement run time
FLTR FLTR
display
FLTR after a set time of operation. This is a remind-
FLTR FLTR er to change or clean your air filter. This time can be set from 0 to 1950 hours in 50 hour increments. will cancel this featurewill cancel this feature
will cancel this feature. When
will cancel this featurewill cancel this feature can clear it by pressing HOLD and RUN This resets the timer and starts counting the hours until the next filter change. Contact your system manufacturer for a specific replacement/maintenance interval.
Select Temperature Display Adjustment 4 LO to 4 HISelect Temperature Display Adjustment 4 LO to 4 HI
11)
Select Temperature Display Adjustment 4 LO to 4 HI –
Select Temperature Display Adjustment 4 LO to 4 HISelect Temperature Display Adjustment 4 LO to 4 HI Allows you to adjust the room temperature display up to 4° higher or lower. Your thermostat was accurately calibrated at the factory but you have the option to change the display temperature to match your previous thermostat. The cur­rent or adjusted room temperature will be displayed on the left side of the display.
A selection of 000A selection of 000
A selection of 000
A selection of 000A selection of 000
“FLTR” “FLTR”
“FLTR” is displayed, you
“FLTR” “FLTR”
at the same time.
, and the
Select F° or C° ReadoutSelect F° or C° Readout
12)
Select F° or C° Readout – Changes the display readout to
Select F° or C° ReadoutSelect F° or C° Readout Centigrade or Fahrenheit as required.
Selected Auto mode Selected Auto mode
13)
Selected Auto mode – This control will feature AUTO
Selected Auto mode Selected Auto mode changeover mode when AU on is selected (default). Press the
or keys in the menu mode to defeat the auto
changeover mode (OFF). Limited Heat RangeLimited Heat Range
14)
Limited Heat Range – This feature provides a maximum
Limited Heat RangeLimited Heat Range setpoint temperature for heat. The default setting is 90°F. It can be changed between 62°F and 89°F by pressing the
or key.
Limited Cool RangeLimited Cool Range
15)
Limited Cool Range – This feature provides a minimum
Limited Cool RangeLimited Cool Range setpoint temperature for cool. The default setting is 45°F. It can be changed between 46°F and 82°F by pressing the
or key.
Compressor Defeat on Comfort Alert errorCompressor Defeat on Comfort Alert error
16)
Compressor Defeat on Comfort Alert error – By selecting
Compressor Defeat on Comfort Alert errorCompressor Defeat on Comfort Alert error CAL on (default), the compressor will be locked when any CA error is detected. The compressor will not be locked when CA error is detected if CAL is OFF.
17 & 18) Keypad Lockout
lock icon ( ) and “OFF” (default, keypad not locked out).
The and are used to toggle the selection between OFF and ON (keypad locked out). When the keypad lockout selection is enabled (ON), and the SYSTEM button is pressed again, the display will indicate the number “0” (default, still disabled) in the time digits. The and are used to set the combination number from 0 to 999. If a combination of 0is selected and the SYSTEM button is pressed, the menu will be exited and keypad will not be locked. If 1 to 999 is selected and the SYSTEM button is
CC
C
CC
pressed, the combination is stored into memory and the menu is exited. The ( ) will display designating keypad locked with a valid combination. The SYSTEM button will operate for 10 seconds after the menu mode is exited to allow the user to change the mode from OFF to the desired SYSTEM mode.
While the keypad is locked out, a simultaneous press of
and will enter the configuration menu from any mode instead of only OFF mode. When the menu is entered with the keypad lockout feature enabled, the first menu item displayed is the combination code 0. The or
keys are used to set the combination unlock number from 0 to 999. If the unlock number matches exactly with the combination lock number stored in memory when the SYSTEM button is pressed, the keypad is unlocked and the ( ) is removed. If the unlock number does not match when the SYSTEM button is pressed, the menu is exited and the keypad remains disabled.
To reset the combination code and unlock the keypad if the code is forgotten, see troubleshooting section.
CONFIGURATION MENUCONFIGURATION MENU
CONFIGURATION MENU
CONFIGURATION MENUCONFIGURATION MENU
This menu selection will display
7
Page 8
SPECIFICASPECIFICA
SPECIFICA
SPECIFICASPECIFICA
ELECTRICAL DATAELECTRICAL DATA
ELECTRICAL DATA
ELECTRICAL DATAELECTRICAL DATA
Electrical RatingElectrical Rating
Electrical Rating:
Electrical RatingElectrical Rating
20 to 30 VAC 50/60 Hz or DC
0.05 to 1.5 Amps (Load per terminal)
2.5 Amps Maximum Total Load (All terminals combined)
TIONSTIONS
TIONS
TIONSTIONS
THERMAL DATATHERMAL DATA
THERMAL DATA
THERMAL DATATHERMAL DATA
Setpoint Temperature RangeSetpoint Temperature Range
Setpoint Temperature Range:
Setpoint Temperature RangeSetpoint Temperature Range
45°F to 90°F (7°C to 32°C)
Operating Ambient Temperature RangeOperating Ambient Temperature Range
Operating Ambient Temperature Range:
Operating Ambient Temperature RangeOperating Ambient Temperature Range
32°F to 105°F
Operating Humidity RangeOperating Humidity Range
Operating Humidity Range:
Operating Humidity RangeOperating Humidity Range
0 to 90% RH (non-condensing)
Shipping Temperature RangeShipping Temperature Range
Shipping Temperature Range:
Shipping Temperature RangeShipping Temperature Range
-40°F to 150°F
OPERAOPERA
OPERA
OPERAOPERA
The system "mode" is selected by pressing the SYSTEM button. Icons on the bottom right corner of the display will indicate the mode: any mode except on the right side of the display. In The current temperature will be displayed on the left side of the display.
To operate properly in the temperature cannot be the same as or higher than the cool setpoint temperature. The heat setpoint must be at least 1° lower than the cool setpoint.
When the thermostat is in the Snowflake Snowflake
Snowflake icons are displayed. The thermostat will call for heat
Snowflake Snowflake or cool depending on the room temperature. The setpoint temperature displayed will be that of the last mode called. If the last system cycle was heat, the If the room temperature raises above the COOL COOL
COOL setpoint and a call for cool is required, the temperature
COOL COOL displayed will change to be the
Your thermostat is designed to determine the optimum time to activate the second stage. Simply raising the temperature in heating or lowering it in cooling will not always force the thermostat to bring the second stage on quickly. There is a time delay from 0-30 minutes depending on the performance of the first stage of the system.
EXAMPLE: For the last 2 hours the thermostat is set on 70° and the room temperature is 70° with the equipment using only the first stage of heat. Since the equipment is keeping the tempera­ture within 1° of setpoint, the thermostat will delay second stage for a longer time if you manually raise the temperature or if the room temperature quickly changes. Once the second stage comes on, it will come on sooner the next time there is a difference between the setpoint and the room temperature. The net effect of the staging program is that when the first stage is capable of making temperature the second stage will delay longer. When the thermostat calculates that first stage cannot make temperature in a reasonable time, the second stage will come on sooner. This built in function automatically optimizes the use of additional stages of heat or cool.
TIONTION
TION
TIONTION
COOL COOL
COOL (
COOL COOL
Automatic System ChangeoverAutomatic System Changeover
Automatic System Changeover
Automatic System ChangeoverAutomatic System Changeover
AUTO AUTO
),
AUTO ( ),
AUTO AUTO
OFFOFF
OFF, the setpoint temperature will be shown
OFFOFF
Second Stage Time DelaySecond Stage Time Delay
Second Stage Time Delay
Second Stage Time DelaySecond Stage Time Delay
HEAT HEAT
HEAT ( ),
HEAT HEAT
OFFOFF
OFF, this area will be blank.
OFFOFF
AUTO AUTO
AUTO mode, the heat setpoint
AUTO AUTO
AUTO AUTO
AUTO mode, both the
AUTO AUTO
HEAT HEAT
HEAT setpoint will be displayed.
HEAT HEAT
COOL COOL
COOL setpoint.
COOL COOL
EMEREMER
EMER, or
EMEREMER
HEAT HEAT
HEAT setpoint and the
HEAT HEAT
OFFOFF
OFF. In
OFFOFF
Flame Flame
Flame and
Flame Flame
Manual OperationManual Operation
Manual Operation
Manual OperationManual Operation
Permanent Program OverridePermanent Program Override
Permanent Program Override (
Permanent Program OverridePermanent Program Override button set to release. temperature. The thermostat will hold the room temperature at the selected setting until you press RUN button to start program operation again.
Temperature Program OverrideTemperature Program Override
Temperature Program Override – Press
Temperature Program OverrideTemperature Program Override display shows the temperature you want. The thermostat will override current programming and keep the room temperature at the selected temperature for a programmed time period. “HOLD”“HOLD”
“HOLD” will be displayed and flashing. The thermostat will
“HOLD”“HOLD” automatically revert to the program after programmed period.
LOW BATTERY INDICATORLOW BATTERY INDICATOR
LOW BATTERY INDICATOR — If the 2 “AA” alkaline batter-
LOW BATTERY INDICATORLOW BATTERY INDICATOR ies are low and should be replaced, the display will be blank except for “ any button will cause the display to operated for ten seconds. After ten seconds, the display will be blank except for “ BATTBATT
BATT”. You cannot program with low batteries, but you can
BATTBATT override setpoint temperature. After “ displayed for 4 weeks, the thermostat will raise the tempera­ture 10 degrees above your setpoint on COOL mode and will drop the temperature 10 degrees below your setpoint on HEAT mode. If the “ when it reaches certain value, the thermostat will turn off all the loads and “
SIMPLIFIED COPY DAY FUNCTIONSIMPLIFIED COPY DAY FUNCTION
SIMPLIFIED COPY DAY FUNCTION — This feature allows
SIMPLIFIED COPY DAY FUNCTIONSIMPLIFIED COPY DAY FUNCTION Monday’s program to be copied into the rest of the week’s programming. programmed your thermostat.programmed your thermostat.
programmed your thermostat. To use this feature, simply
programmed your thermostat.programmed your thermostat. enter the program for Monday as described in ENTERING YOUR PROGRAM, then press RUN or HOLD. The only way to restore this feature is to complete a software reset (see Reset Operation under TROUBLESHOOTING section).
COPY DAY FUNCTIONCOPY DAY FUNCTION
COPY DAY FUNCTION — This feature allows
COPY DAY FUNCTIONCOPY DAY FUNCTION a selected day’s program to be copied to the desired day’s programming. To use this feature: in PRGM mode, select the day to be copied program for the selected day as described in ENTERING YOUR PROGRAM. Press and hold the TIME button for 4 seconds to begin the COPY mode. The LCD will display “COPY”“COPY”
“COPY” and the selected day to be copied. The day the
“COPY”“COPY” program will copy to select the day you want to copy the Copy Day operation and return to PRGM mode. Press RUN to exit.
HEAT HEAT
HEAT or
HEAT HEAT
“HOLD” “HOLD”
“HOLD” will be displayed. Use or to adjust the
“HOLD” “HOLD”
LO BATTLO BATT
LO BATT”. When the batteries are low, pressing
LO BATTLO BATT
COOLCOOL
COOL, press the HOLD button once and
COOLCOOL
LO BATTLO BATT
LO BATT” condition continues, and
LO BATTLO BATT
LO BATTLO BATT
LO BATT” will flash.
LO BATTLO BATT
This feature is available the first time youThis feature is available the first time you
This feature is available the first time you
This feature is available the first time youThis feature is available the first time you
from by pressing the HOLD button. Enter the
to will be flashing. Press the HOLD button
HOLDHOLD
HOLD) – With the SYSTEM
HOLDHOLD
or until the
LOLO
LO
LOLO
LO BATTLO BATT
LO BATT” has been
LO BATTLO BATT
to. Press TIME to complete
8
Page 9
OPERATIONOPERATION
PM
OPERATION
OPERATIONOPERATION
PROGRAMMING YOUR THERMOSTATPROGRAMMING YOUR THERMOSTAT
PROGRAMMING YOUR THERMOSTAT
PROGRAMMING YOUR THERMOSTATPROGRAMMING YOUR THERMOSTAT
This section will help you plan your thermostat's program to meet your needs. For maximum comfort and efficiency, keep the following guidelines in mind when planning your program.
• When heating (cooling) your building, program the temper­atures to be cooler (warmer) when the building is vacant or during periods of low activity.
• During early morning hours, the need for cooling is usually minimal.
Planning Your ProgramPlanning Your Program
Planning Your Program
Planning Your ProgramPlanning Your Program
Look at the factory preprogrammed times and temperatures shown in the sample schedule. If this program will suit your needs, simply press the RUN button to begin running the factory preset program.
If you want to change the preprogrammed times and tempera­tures, follow these steps.
Determine the time periods and temperatures for your program. You can program four or two periods for each day (see Configu­ration menu, item 3). You may use the same heating and cooling temperatures for consecutive time periods. You can choose start times, heating temperatures, and cooling temperatures independently (for example, you may select 5:00 AM and 70° as the weekday also choose 7:00 AM and 76° as the weekday coolingcooling
cooling start time and temperature).
coolingcooling
1st period heating1st period heating
1st period heating start time and temperature and
1st period heating1st period heating
1st period1st period
1st period
1st period1st period
Use the table to plan your program time periods and the temperatures you want during each period. Fill in the complete table to have a record of your programs.
Heating/Cooling Schedule Plan (Factory Program)
Period
1ST 2ND 3RD 4TH 1ST 2ND 3RD
COOL HEAT
4TH
SAMPLE
ALL DAYS OF THE WEEK
Start Time Temperature
6:00 AM 8:00 AM 5:00 PM
10:00 PM
6:00 AM 8:00 AM 5:00 PM
10:00 PM
70 F 62 F 70 F 62 F 78 F 85 F 78 F 82 F
Entering Your ProgramEntering Your Program
Entering Your Program
Entering Your ProgramEntering Your Program
Set Current Time and DaySet Current Time and Day
Set Current Time and Day
Set Current Time and DaySet Current Time and Day
1. Press TIME button once. The display will show the hour only.
EXAMPLE:
2. Press and hold either correct hour and AM/PM designation (
PM PM
night;
PM begins at noon).
PM PM
or until you reach the
AM AM
AM begins at mid-
AM AM
3. Press TIME once again. The display window will show the minutes only.
EXAMPLE:
4. Press and hold either
or until you reach the
correct minutes.
5. Press TIME once again. The display will show the day of the week.
6. Press
or until you reach the current day of the
week.
7. Press RUN once. The display will show the correct time and room temperature alternately.
Enter Heating ProgramEnter Heating Program
Enter Heating Program
Enter Heating ProgramEnter Heating Program
1. Move the SYSTEM switch to HEAT.
2. Press PRGM once. MO (indicating Monday program) will appear in the display. Also displayed are the currently programmed start time for the 1st heating period and the currently programmed temperature (flashing).
EXAMPLE:
This display window shows that for Mondays 1st heating period, the start time is 6:00 AM, and 70° is the programmed temperature (this example reflects factory preprogramming).
3. Press or to change the displayed temperature to your selected temperature for Mondays 1st heating program period.
4. Press TIME once (the programmed time will flash). Press
or until your selected start time for Monday’s 1st
Mon Tues Wed Thur Fri Sat Sun
PERIOD 1
HEAT COOL
Time Temp Time Temp
Heating/Cooling Schedule Plan
PERIOD 2
HEAT COOL
Time Temp Time Temp
PERIOD 3
HEAT COOL
Time Temp Time Temp
PERIOD 4
HEAT COOL
Time Temp Time Temp
9
Page 10
OPERAOPERA
OPERA
OPERAOPERA
heating program period appears. The time will change in 15­minute increments. When your selected time is displayed, press TIME again to return to the change temperature mode.
5. Press PRGM once. The currently programmed start time and setpoint temperature for the Mondays 2nd heating program period will appear.
6. Repeat steps 3 and 4 to select the start time and heating temperature for Mondays 2nd heating program period.
7. Repeat steps 3 through 5 for the 3rd and 4th heating program periods. Monday heating programs are now complete.
TIONTION
TION
TIONTION
NOTE
If you are programming your thermostat for the first time and you want programming for all days of the week to be the same as Mondays program, press RUN or HOLD at this point, and proceed to Enter Cooling Program. (This simplified COPY DAY feature only works the first time you program your thermo­stat. If you want to copy one days programming to a specific day programming, refer to COPY DAY FUNCTION in OPERATING FEATURES. If you are changing your thermostats program­ming, you must program each day separately.)
8. Press PRGM once. TU (indicating Tuesday program) will appear in the display, along with the start time for the 1st heating period and the currently programmed temperature.
9. Repeat steps 3 through 7 to complete Tuesday’s heating programming.
10.Continue entering each days programming until all heating periods time and temperatures have been entered.
11.When you have complete entering your heating program, press RUN.
Enter Cooling ProgramEnter Cooling Program
Enter Cooling Program
Enter Cooling ProgramEnter Cooling Program
CAUTION
!
If the outside temperature is below 50°F, disconnectIf the outside temperature is below 50°F, disconnect
If the outside temperature is below 50°F, disconnect
If the outside temperature is below 50°F, disconnectIf the outside temperature is below 50°F, disconnect power to the cooling system before programming.power to the cooling system before programming.
power to the cooling system before programming.
power to the cooling system before programming.power to the cooling system before programming. Energizing the air conditioner compressor duringEnergizing the air conditioner compressor during
Energizing the air conditioner compressor during
Energizing the air conditioner compressor duringEnergizing the air conditioner compressor during cold weather may cause personal injury or propertycold weather may cause personal injury or property
cold weather may cause personal injury or property
cold weather may cause personal injury or propertycold weather may cause personal injury or property damage.damage.
damage.
damage.damage.
1. Press SYSTEM button to
2. Follow
Follow these steps to check your thermostat programming one final time before beginning thermostat operation.
1. Press SYSTEM button to
2. Press PRGM to view the 1st Monday heating period
3. Press RUN.
4. Press SYSTEM button to
5. Repeat step 2 to check cooling program.
6. Press SYSTEM button to
NOTE: Batteries are not required to keep your programming
YOUR THERMOSTAT IS NOW PROGRAMMED AND READY TOYOUR THERMOSTAT IS NOW PROGRAMMED AND READY TO
YOUR THERMOSTAT IS NOW PROGRAMMED AND READY TO
YOUR THERMOSTAT IS NOW PROGRAMMED AND READY TOYOUR THERMOSTAT IS NOW PROGRAMMED AND READY TO PROVIDE MAXIMUM COMFORT AND EFFICIENCY!PROVIDE MAXIMUM COMFORT AND EFFICIENCY!
PROVIDE MAXIMUM COMFORT AND EFFICIENCY!
PROVIDE MAXIMUM COMFORT AND EFFICIENCY!PROVIDE MAXIMUM COMFORT AND EFFICIENCY!
Enter Heating ProgramEnter Heating Program
Enter Heating Program for entering your cooling
Enter Heating ProgramEnter Heating Program program, using your selected cooling times and tempera­tures.
CHECK YOUR PROGRAMMINGCHECK YOUR PROGRAMMING
CHECK YOUR PROGRAMMING
CHECK YOUR PROGRAMMINGCHECK YOUR PROGRAMMING
time and temperature. Each time you press PRGM, the next heating period time and temperature will be display­ed in sequence for each weekday, then Saturday and Sunday program periods (you may change any time or temperature during this procedure).
RUN to begin program operation.
or menu data. With two optional "AA" batteries installed, your thermostat will maintain time and continuously display the temperature during a loss of AC power. Installed batteries will also allow programming prior to installation.
COOLCOOL
COOL position.
COOLCOOL
HEAT HEAT
HEAT position.
HEAT HEAT
COOL COOL
COOL position.
COOL COOL
HEAT HEAT
HEAT or
HEAT HEAT
COOL COOL
COOL and press
COOL COOL
TROUBLESHOOTINGTROUBLESHOOTING
TROUBLESHOOTING
TROUBLESHOOTINGTROUBLESHOOTING
Reset OperationReset Operation
Reset Operation
Reset OperationReset Operation
If a voltage spike or static discharge blanks out the display or causes erratic thermostat operation, you can reset the thermo-
RR
stat by removing the wires from terminals the wires and batteries. If the thermostat has been reset and still does not function correctly, contact your heating/cooling service person or place of purchase.
Possible CausePossible Cause
Possible Cause
SymptomSymptom
Symptom
SymptomSymptom
No Heat/No Cool/No FanNo Heat/No Cool/No Fan
No Heat/No Cool/No Fan
No Heat/No Cool/No FanNo Heat/No Cool/No Fan (common problems)(common problems)
(common problems)
(common problems)(common problems)
No HeatNo Heat
No Heat
No HeatNo Heat
Possible CausePossible Cause
1. Blown fuse or tripped circuit breaker.
2. Furnace power switch to OFF.
3. Furnace blower compartment door or panel loose or not properly installed.
1. Pilot light not lit.
2. SYSTEM button not set to
3. Loose connection to thermostat or system.
4. Furnace Lock-Out Condition. Heat may also be intermittent.
5. Heating system requires service or thermostat requires replacement.
CC
R and
C and removing batteries for 2 minutes. After resetting the thermostat, replace
RR
CC
Corrective ActionCorrective Action
Corrective Action
Corrective ActionCorrective Action
Replace fuse or reset breaker. Turn switch to ON. Replace door panel in proper position to engage safety interlock or door switch.
Re-light pilot.
HEATHEAT
HEAT.
HEATHEAT
Press SYSTEM button to above room temperature. Verify thermostat and system wires are securely attached. Many furnaces have safety devices that shut down when a lock-out condition occurs. If the heat works intermittently contact the furnace manufacturer or local service person for assistance. Diagnostic: Press SYSTEM button to raise the setpoint above room temperature. Within a few seconds the thermostat should make a soft click
HEATHEAT
HEAT and raise setpoint
HEATHEAT
HEATHEAT
HEAT and
HEATHEAT
10
Page 11
TROUBLESHOOTINGTROUBLESHOOTING
TROUBLESHOOTING
TROUBLESHOOTINGTROUBLESHOOTING
SymptomSymptom
Symptom
SymptomSymptom
No Heat (continued)
No Cool
Heat, Cool or Fan Runs Constantly
Possible CausePossible Cause
Possible Cause
Possible CausePossible Cause
5.Heating system requires service or thermostat requires replacement.
(continued)
1.SYSTEM button not pressed to COOL.
2.Loose connection to thermostat or system.
3.Cooling system requires service or thermostat requires replacement.
1.Possible short in wiring.
2.Possible short in thermostat.
3.Possible short in heat/cool/fan system.
4.FAN Switch set to Fan On.
Corrective ActionCorrective Action
Corrective Action
Corrective ActionCorrective Action
sound. This sound usually indicates the thermostat is operating properly. If the thermostat does not click, try the reset operation listed above. If the thermostat does not click after being reset contact your heating and cooling service person or place of
purchase for a replacement. If the thermostat clicks, contact the furnace manufacturer or a service person to verify the heating is operating correctly.
Press SYSTEM button to COOL and lower setpoint below room temperature. Verify thermostat and system wires are securely attached. Same procedure as diagnostic for No Heat condition except set the thermostat to COOL and lower the setpoint below the room temperature. There may be up to a five minute delay before the thermostat clicks in Cooling.
Check each wire connection to verify they are not shorted or touching together. No bare wire should stick out from under terminal screws. Try resetting the thermostat as described above. If the condition persists the manufacturer of your system or service person can instruct you on how to test the Heat/Cool system for correct operation. If the system operates correctly, replace the thermostat.
Furnace (Air Conditioner) Cycles Too Fast or Too Slow (narrow or wide temperature swing)
Thermostat Setting & Thermostat Thermometer Disagree
Blank Display and/or Keypad Not Responding
Heat Setpoint will not Respond to the Temperature Up Key
Cool Setpoint will not Respond to the Temperature Down Key
Forgot Keypad Lockout Code
1.The location of the thermostat and/or the size of the Heating System may be influencing the cycle rate.
1.Thermostat thermometer setting requires adjustment.
1.Voltage spike or static discharge.
1.The desired setpoint conflicts with the setpoint of the COOL mode.
1.The desired setpoint conflicts with the setpoint of the HEAT mode.
Digital thermostats normally provide precise tem­perature control and may cycle faster than some older mechanical models. A faster cycle rate means the unit turns on and off more frequently but runs for a shorter time so there is no increase in energy use. If you would like to increase the cycle time, choose SL for slow cycle in the menu, step 4. If an accept­able cycle rate is not achieved as received or by choosing slow cycle, contact a local service person for additional suggestions.
The thermometer can be adjusted +/- 4 degrees. See Temperature Display Adjustment in the Configu­ration Menu section.
Use the Reset Operation at top of previous page.
Change system mode to COOL. Raise the Cool setpoint. Return to HEAT mode and set desired temperature.
Change system mode to HEAT. Lower the Heat setpoint. Return to COOL mode and set desired temperature.
CAUTION: This resets the thermostat to factory default settings of the configuration menu. After performing this reset, the thermostat will require configuration again. Be sure that you know the required configuration settings before resetting.
With the thermostat in any mode, press the same time to enter the configuration menu at the point where the lockout code is to be entered. Press
and at
11
Page 12
TROUBLESHOOTINGTROUBLESHOOTING
TROUBLESHOOTING
TROUBLESHOOTINGTROUBLESHOOTING
SymptomSymptom
Symptom
SymptomSymptom
Forgot Keypad Lockout Code (continued)
Why wont my 2nd or 3rd stage come on?
FF
AA
QQ
F
A
Q
FF
AA
QQ
SymptomSymptom
Symptom
SymptomSymptom
My thermostat is reading in Celsius. How do I change it to Fahrenheit?
Do I have to program a stop time for each program period?
My thermostat does not follow it’s program. What should I do?
Possible Cause
First stage is keeping up with demand.
Corrective ActionCorrective Action
Corrective Action
Corrective ActionCorrective Action
and and SYSTEM button at the same time to reset the lockout code, unlock the keypad and reset all configuration menu settings.
Your thermostat is designed to determine the optimum time to activate the second stage. Simply raising the temperature in heating or lowering it in cooling will not always force the thermostat to bring the second stage on quickly. There is a time delay from 0-30 minutes depending on the performance of the first stage of the system.
Corrective Action
Your thermostat display can be set to display temperature in Fahrenheit or Celsius. This option can be set in the INSTALLER/CONFIGURATION MENU of your thermostat. See page 6 step 12.
There is no need to select a time to stop a programming period. Starting a new programming period will stop the previous program period.
Unless the thermostat appears to be damaged it will follow the program that is in the memory. The most common reason a thermostat will appear not to be following the program is a programming error. Verify that the AM or PM settings are correct for each period. Also verify that the Day of the week is set correctly. Models with EMR (Energy Management Recovery) start early to make the temperature they are programmed for by the time specified in the program. See the CONFIGURATION MENU on page 6 step 3.
Between heating and cooling seasons, I want to turn my system off. Will this change my program?
My display light does not work. Can it be fixed or replaced?
Do I have to reprogram my thermostat after I change the batteries?
My setpoint temperature is flashing. What does that mean?
How can I get a copy of the Operating Manual for my thermostat?
My program or configuration menu is all messed up, how do I start from the beginning?
Any time you wish to turn your system off, simply press the SYSTEM button until OFF is displayed. This will not affect your thermostats programming in any way. To turn the system back on, press the SYSTEM button to HEAT or COOL and press RUN. The system will begin operating according to the current thermostat program. See under OPERATION page 8 & 9.
Because it is soldered to the circuit board it is not possible to repair or replace.
No. This thermostat has permanent memory, although you will have to reset your clock.
When the thermostat compressor time delay occurs it will flash the setpoint for about five minutes. This is intended to help protect the compressor from short cycling.
Visit our website at www.white-rodgers.com for operating manuals.
You can perform software reset by pressing simultaneously when SYSTEM mode is OFF. See Forget Keypad Lockout
Code under TROUBLESHOOTING” for details.
and SYSTEM buttons
The Emerson logo is a trademark and service mark of Emerson Electric Co.
Loading...