White Rodgers 1F85-275 User Manual

Page 1
1F85-2751F85-275
1F85-275
1F85-2751F85-275
Heating & Air Conditioning
5-1-1 Programmable/Non-programmable, Auto
Changeover, Multi-Stage/Heat Pump Thermostat
INSTALLATION INSTRUCTIONSINSTALLATION INSTRUCTIONS
INSTALLATION INSTRUCTIONS
INSTALLATION INSTRUCTIONSINSTALLATION INSTRUCTIONS
OperOper
Oper
OperOper
FAILURE TO READ AND FOLLOW ALL INSTRUCTIONS CAREFULLY BE-FAILURE TO READ AND FOLLOW ALL INSTRUCTIONS CAREFULLY BE-
FAILURE TO READ AND FOLLOW ALL INSTRUCTIONS CAREFULLY BE-
FAILURE TO READ AND FOLLOW ALL INSTRUCTIONS CAREFULLY BE-FAILURE TO READ AND FOLLOW ALL INSTRUCTIONS CAREFULLY BE­FORE INSTALLING OR OPERATING THIS CONTROL COULD CAUSE PER-FORE INSTALLING OR OPERATING THIS CONTROL COULD CAUSE PER-
FORE INSTALLING OR OPERATING THIS CONTROL COULD CAUSE PER-
FORE INSTALLING OR OPERATING THIS CONTROL COULD CAUSE PER-FORE INSTALLING OR OPERATING THIS CONTROL COULD CAUSE PER­SONAL INJURY AND/OR PROPERTY DAMAGE.SONAL INJURY AND/OR PROPERTY DAMAGE.
SONAL INJURY AND/OR PROPERTY DAMAGE.
SONAL INJURY AND/OR PROPERTY DAMAGE.SONAL INJURY AND/OR PROPERTY DAMAGE.
YOUR THERMOSTAT REPLACESYOUR THERMOSTAT REPLACES
YOUR THERMOSTAT REPLACES
YOUR THERMOSTAT REPLACESYOUR THERMOSTAT REPLACES
DescriptionDescription
Description
DescriptionDescription
Heat Pump (No Aux. or Emergency Heat) Yes
Heat Pump (with Aux. or Emergency Heat) Yes
Standard Heat & Cooling Systems Yes
Two Stage Heat & Two Stage Cool Yes
Standard Heat Only Systems Yes
Millivolt Heat Only Systems – Floor or Wall Furnaces Yes
Standard Central Air Conditioning Yes
Gas or Oil Heat Yes
Electric Furnace Yes
Hydronic (Hot Water) Zone Heat – 2 Wires Yes
Hydronic (Hot Water) Zone Heat – 3 Wires No
!
To prevent electrical shock and/or equipment damage,To prevent electrical shock and/or equipment damage,
To prevent electrical shock and/or equipment damage,
To prevent electrical shock and/or equipment damage,To prevent electrical shock and/or equipment damage, disconnect electric power to system at main fuse ordisconnect electric power to system at main fuse or
disconnect electric power to system at main fuse or
disconnect electric power to system at main fuse ordisconnect electric power to system at main fuse or circuit breaker box until installation is complete.circuit breaker box until installation is complete.
circuit breaker box until installation is complete.
circuit breaker box until installation is complete.circuit breaker box until installation is complete.
aa
tortor
::
a
tor
:
aa
tortor
::
CAUTION
Sa Sa
Sa
Sa Sa
vv
e these instre these instr
v
e these instr
vv
e these instre these instr
1F85-2751F85-275
1F85-275
1F85-2751F85-275
uctions fuctions f
uctions f
uctions fuctions f
Assemble tools required as shown below.
HAND OR POWER DRILL WITH 3/16 INCH DRILL BIT, IF NEEDED
REMOREMO
REMO
REMOREMO
or futuror futur
or futur
or futuror futur
FLAT BLADE SCREWDRIVER
VING OLD VING OLD
VING OLD
VING OLD VING OLD
e use!e use!
e use!
e use!e use!
PREPPREP
PREP
PREPPREP
ARAARA
TIONSTIONS
ARA
TIONS
ARAARA
TIONSTIONS
WIRE CUTTER/STRIPPER
THERMOSTTHERMOST
THERMOST
THERMOSTTHERMOST
AA
A
AA
TT
T
TT
Before removing wires from old thermostat's switching sub-
label each wirelabel each wire
base,
label each wire with the terminal designation it was
label each wirelabel each wire
removed from.
1. Shut off electricity at the main fuse box until installation is complete. Ensure that electrical power is disconnected.
Remove Old ThermostatRemove Old Thermostat
2.
Remove Old Thermostat: A standard heat/cool
Remove Old ThermostatRemove Old Thermostat thermostat consists of three basic parts: a. The cover, which may be either a snap-on or
hinge type.
b. The base, which is removed by loosening all
captive screws.
c. The switching subbase, which is removed by
unscrewing the mounting screws that hold it on the wall or adaptor plate.
3. Remove the front cover of the old thermostat. wireswires
still attachedstill attached
wires
still attached, remove wall plate from the wall. If
wireswires
still attachedstill attached the old thermostat has a wall mounting plate, remove the thermostat and the wall mounting plate as an assembly.
4. Identify each wire attached to the old thermostat.
5. Disconnect the wires from the old thermostat one at a DO NOT LET WIRES FALL BACK INTO THEDO NOT LET WIRES FALL BACK INTO THE
time.
DO NOT LET WIRES FALL BACK INTO THE
DO NOT LET WIRES FALL BACK INTO THEDO NOT LET WIRES FALL BACK INTO THE
WALLWALL
WALL.
WALLWALL
6. Install new thermostat using the following procedures.
WithWith
With
WithWith
Y2
C
R
E/W1
Y1
Mounting Hole
Figure 1 – Thermostat baseFigure 1 – Thermostat base
Figure 1 – Thermostat base
Figure 1 – Thermostat baseFigure 1 – Thermostat base
ATTENTION!ATTENTION!
ATTENTION! This product does not contain mercury. How-
ATTENTION!ATTENTION! ever, this product may replace a unit which contains mercury.
Do not open mercury cells. If a cell becomes damaged, do touch any spilled mercury. Wearing non-absorbent gloves, clean up the spilled mercury and place into a container which can be sealed. If a cell becomes damaged, the unit should be discarded.
Mercury must not be discarded in household trash. When the unit this product is replacing is to be discarded, place in a suitable container. Refer to www.white-rodgers.com for loca­tion to send the product containing mercury.
OBLW2G
ELEC. GAS
AUTOON
Mounting Hole
Elec-Gas Switch
notnot
not
notnot
White-Rodgers is a division
of Emerson Electric Co.
www.white-rodgers.com
PART NO. 37-6488CPART NO. 37-6488C
PART NO. 37-6488C
PART NO. 37-6488CPART NO. 37-6488C
Replaces 37-6488B
Page 2
MOUNTING AND WIRINGMOUNTING AND WIRING
MOUNTING AND WIRING
MOUNTING AND WIRINGMOUNTING AND WIRING
WARNING
!
Do not use on circuits exceeding specified voltage.Do not use on circuits exceeding specified voltage.
Do not use on circuits exceeding specified voltage.
Do not use on circuits exceeding specified voltage.Do not use on circuits exceeding specified voltage. Higher voltage will damage control and could causeHigher voltage will damage control and could cause
Higher voltage will damage control and could cause
Higher voltage will damage control and could causeHigher voltage will damage control and could cause shock or fire hazard.shock or fire hazard.
shock or fire hazard.
shock or fire hazard.shock or fire hazard.
Do not short out terminals on gas valve or primaryDo not short out terminals on gas valve or primary
Do not short out terminals on gas valve or primary
Do not short out terminals on gas valve or primaryDo not short out terminals on gas valve or primary control to test. Short or incorrect wiring will damagecontrol to test. Short or incorrect wiring will damage
control to test. Short or incorrect wiring will damage
control to test. Short or incorrect wiring will damagecontrol to test. Short or incorrect wiring will damage thermostat and could cause personal injury and/orthermostat and could cause personal injury and/or
thermostat and could cause personal injury and/or
thermostat and could cause personal injury and/orthermostat and could cause personal injury and/or property damage.property damage.
property damage.
property damage.property damage.
Thermostat installation and all components of the system shall conform to Class II circuits per the NEC code.
Electric/Gas Switch (Fan Option)Electric/Gas Switch (Fan Option)
Electric/Gas Switch (Fan Option)
Electric/Gas Switch (Fan Option)Electric/Gas Switch (Fan Option)
This thermostat is configured from the factory to operate a heat/ cool, fossil fuel (gas, oil, etc.), forced air system. It is configured correctly for any system that DOES NOT require the thermostat to energize the fan on a call for heat. If you system is an electric heat or heat-pump system that REQUIRES the thermostat to turn on the fan on a call for heat, locate the ELEC/GAS switch on the back of the thermostat (see fig. 1) and switch it to the ELEC position. This will allow the thermostat to energize the fan immediately on a call for heat. If you are unsure if the heating/ cooling system requires the thermostat to control the fan, contact a qualified heating and air conditioning service person.
When the thermostat is configured for Heat Pump, the thermo­stat will always power the circulator fan on a call for heat in the HEAT mode. The ELEC/GAS switch must be set to match the type of Auxiliary heat your system uses for proper operation in the EMERgency mode.
All wiring diagrams are for typical systems only. Refer to equipment manufacturers’ instructions for specific system wir­ing information.
CAUTION
!
Take care when securing and routing wires so they doTake care when securing and routing wires so they do
Take care when securing and routing wires so they do
Take care when securing and routing wires so they doTake care when securing and routing wires so they do not short to adjacent terminals or rear of thermostat.not short to adjacent terminals or rear of thermostat.
not short to adjacent terminals or rear of thermostat.
not short to adjacent terminals or rear of thermostat.not short to adjacent terminals or rear of thermostat. Personal injury and/or property damage may occur.Personal injury and/or property damage may occur.
Personal injury and/or property damage may occur.
Personal injury and/or property damage may occur.Personal injury and/or property damage may occur.
Attach Thermostat Base to Wall
1. Remove the packing material from the thermostat. Gently pull the cover straight off the base. Forcing or prying on the thermostat will cause damage to the unit.
2. Connect wires beneath terminal screws on base using appropriate wiring schematic (see figs. 2 through 3).
3. Place base over hole in wall and mark mounting hole locations on wall using base as a template.
4. Move base out of the way. Drill mounting holes.
5. Fasten base loosely to wall, as shown in fig. 1, using two mounting screws. Place a level against bottom of base, adjust until level, and then tighten screws. (Leveling is for appearance only and will not affect thermostat operation.) If you are using existing mounting holes, or if holes drilled are too large and do not allow you to tighten base snugly, use plastic screw anchors to secure subbase.
6. Push excess wire into wall and plug hole with a fire­resistant material (such as fiberglass insulation) to prevent drafts from affecting thermostat operation.
Battery Location
2 “AA” alkaline batteries are included in the thermostat at the factory with a battery tag to prevent power drainage. You must remove the battery tag to engage the batteries.
If “BATT” is displayed, the batteries are low and should be replaced. For best results, replace all batteries with new premium brand alkaline batteries such as Duracell® or Energizer®. To replace batteries, press system button to OFF, install the batteries along the top of the base (see Fig.
1). The batteries must be installed with the positive (+) end to
the left.
2
Page 3
Heat Pump ConnectionsHeat Pump Connections
Heat Pump Connections
Heat Pump ConnectionsHeat Pump Connections
WIRING DIAWIRING DIA
WIRING DIA
WIRING DIAWIRING DIA
GRAMSGRAMS
GRAMS
GRAMSGRAMS
Refer to equipment manufacturers' instructions for specific system wiring information. The thermostat can be configured for use with the following heat pump systems:
HEAT PUMP TYPE 1 (HP 1). Single Stage compressor system; gas or electric backup, 2-heat/1-cool stages maximum.
HEAT PUMP TYPE 2 (HP 2). Multi-Stage compressor or two compressor system with gas or electric backup, 3-heat/2-cool stages
maximum.
See figure 2 below to help you wire the thermostat properly. After wiring, see CONFIGURATION section for proper thermostat configuration.
L
W2
Heat Mode 2nd Stage. Emergency Mode 2nd Stage
Heat Mode 3rd Stage. Emergency Mode 2nd Stage
G
Blower/ Circulator Fan Energized on Call for Heat or Cool. Set Elect/Gas Switch for Emergency Mode
Y1
Heat and Cool Mode 1st Stage (Compressor)
E/W1
Emergency Mode 1st Stage
R
24 Volt (Hot)
C*
24 Volt (Common)
Y2
No Output
2nd Stage (Compressor)
NEUTRAL
24VAC
HOT
NOTE: If your system
does not provide an E connection, jumper W2 to E/W1 to use the Auxiliary
Heat in the Emergency
Mode.
120VAC
CLASS II
TRANSFORMER
System
Heat Pump 1
(HP1)
Heat Pump 2
(HP2)
O
Energized in Cool Mode
B
Energized in Heat, Off, Emergency Mode
Fault Indicator or System Malfunc­tion Switch
Figure 2 – Heat Pump Systems
*The 24 volt neutral connection to terminal C on the thermostat is not required if you replace the batteries once a year with fresh “AA” alkaline batteries.
Single Stage/Multi-Stage ConnectionsSingle Stage/Multi-Stage Connections
Single Stage/Multi-Stage Connections
Single Stage/Multi-Stage ConnectionsSingle Stage/Multi-Stage Connections
(No Heat Pump)(No Heat Pump)
(No Heat Pump)
(No Heat Pump)(No Heat Pump)
Refer to equipment manufacturers' instructions for specific system wiring information. The thermostat can be configured for use with the following Single Stage and Multi-Stage systems:
SINGLE STAGE (SS 1). Gas, oil or electric, 1-heat/1-cool stage maximum.
MULTI-STAGE (MS 2). Gas, oil or electric, 2-heat/2-cool stages maximum.
See figure 3 below to help you wire the thermostat properly. After wiring, see CONFIGURATION section for proper thermostat configuration.
L
W2
No Output
Heat Mode 2nd Stage
G
Blower/ Circulator Fan Energized on Call for Cool (and Heat) if configured for Electric Heat
Y1
Cool Mode 1st Stage
E/W1
Heat Mode 1st Stage
R
24 Volt (Hot)
C*
24 Volt (Common)
Y2
No Output
Cool Mode 2nd Stage
NEUTRAL
24VAC
HOT
CLASS II
TRANSFORMER
120VAC
System
Single Stage 1
(SS1)
Multi­Stage 2
(MS2)
O
Energized Constantly in Cool Mode
B
Energized Constantly in Heat, Off, Emergency Mode
Fault Indicator (NOT USED)
Figure 3 – Single Stage or Multi-Stage System (No Heat Pump)
*The 24 volt neutral connection to terminal C on the thermostat is not required if you replace the batteries once a year with fresh “AA” alkaline batteries.
3
Page 4
CHECK CHECK
CHECK
CHECK CHECK
THERMOSTTHERMOST
THERMOST
THERMOSTTHERMOST
AA
T OPERAT OPERA
A
T OPERA
AA
T OPERAT OPERA
TIONTION
TION
TIONTION
NOTE
To prevent static discharge problems, touch side ofTo prevent static discharge problems, touch side of
To prevent static discharge problems, touch side of
To prevent static discharge problems, touch side ofTo prevent static discharge problems, touch side of thermostat to release static build-up before touchingthermostat to release static build-up before touching
thermostat to release static build-up before touching
thermostat to release static build-up before touchingthermostat to release static build-up before touching any keys.any keys.
any keys.
any keys.any keys.
If at any time during testing your system does not operate properly, contact a qualified serviceperson.
Fan Operation
If your system does not have a G terminal connection, skip to Heating System.
1. Turn on power to system.
2. Move FAN switch to ON position. The blower should be ­gin to operate.
3. Move FAN switch to AUTO position. The blower should stop immediately.
CAUTION
!
Do not allow the compressor to run unless the com-Do not allow the compressor to run unless the com-
Do not allow the compressor to run unless the com-
Do not allow the compressor to run unless the com-Do not allow the compressor to run unless the com­pressor oil heaters have been operational for 6 hourspressor oil heaters have been operational for 6 hours
pressor oil heaters have been operational for 6 hours
pressor oil heaters have been operational for 6 hourspressor oil heaters have been operational for 6 hours and the system has not been operational for at least 5and the system has not been operational for at least 5
and the system has not been operational for at least 5
and the system has not been operational for at least 5and the system has not been operational for at least 5 minutes.minutes.
minutes.
minutes.minutes.
Heating System
1. Press SYSTEM button to select the Flame icon ( ). If the auxiliary heating system has a standing pilot, be sure to light it.
2. Press temperature. The heating system should begin to operate. The display should show “STG1”. However, if the setpoint temperature display is flashing, the compres­sor lockout feature is operating (see Configuration menu, item 5).
3. Adjust temperature setting to 3° above room temperature. If your system configuration is set at MS2, HP2 or HP1, the auxiliary heat system should begin to operate and the display should show “STG1+2”.
4. Press ture. The heating system should stop operating.
to adjust thermostat setting to 1° above room
to adjust the thermostat below room tempera-
Emergency System
EMER bypasses the Heat Pump to use the heat source wired to terminal E on the thermostat. EMER is typically used when compressor operation is not desired, or you prefer back-up heat only.
1. Press SYSTEM button to select EMER. “EMER” will flash on the display.
2. Press temperature. The Aux. heating system will begin to operate. The display will show “STG1” flashing “EMER”
and Flame icon ( operating.
3. Adjust temperature setting to 3° above room temperature. The auxiliary heat system should begin to operate and the display should show “STG1+2”.
4. Press ture. The Aux. heating system should stop operating.
To prevent compressor and/or property damage, if theTo prevent compressor and/or property damage, if the
To prevent compressor and/or property damage, if the
To prevent compressor and/or property damage, if theTo prevent compressor and/or property damage, if the outdoor temperature is below 50°F, DO NOT operateoutdoor temperature is below 50°F, DO NOT operate
outdoor temperature is below 50°F, DO NOT operate
outdoor temperature is below 50°F, DO NOT operateoutdoor temperature is below 50°F, DO NOT operate the cooling system.the cooling system.
the cooling system.
the cooling system.the cooling system.
to adjust thermostat setting above room
) to indicate that the Aux. system is
to adjust the thermostat below room tempera-
CAUTION
!
Cooling System
1. Press SYSTEM button to select the Snowflake icon ( ).
2. Press temperature. The blower should come on immediately on high speed, followed by cold air circulation. The display should show “STG1”.
3. Adjust temperature setting to 3° below room temperature. The second stage cooling should begin to operate and the display should show “STG1+2”.
4. Press temperature. The cooling system should stop operating.
to adjust thermostat setting below room
to adjust the temperature setting above room
4
Page 5
Before you begin programming your thermostat, you should be familiar with its features and with the display and the location and operation of the thermostat buttons. Your thermostat con­sists of two parts: the thermostat cover and the base. To remove the cover, pull it straight out from the base. To replace the cover, line up the cover with the base and press until the cover snaps onto the base.
The Thermostat Buttons and Switches
Raises temperature setting
1
Lowers temperature setting.
2
TIME button.
3
PRGM (program) button.
4
RUN (run program) button.
5
HOLD temperature button.
6
FAN switch (ON, AUTO)
7
SYSTEM button (COOL, AUTO, HEAT, EMER, OFF)
8
OPERAOPERA
OPERA
OPERAOPERA
TIONTION
TION
TIONTION
The Display
Indicates day of the week.
9
Flame icon ( ) is displayed when the system is in
10
HEAT mode. Snowflake icon (
the system is in COOL mode. Flame icon ( ) and Snowflake icon ( when thermostat is in AUTO mode.
Displays “BATT” when the 2 "AA" batteries are low
11
and should be replaced. Only “BATT” and “LO” in the minutes field are displayed when batteries are low and with no system power.
Alternately displays current time and temperature. Dis-
12
plays “LO” in the minutes field when batteries are low.
The word “HOLD” is displayed when the thermostat is
13
in the HOLD mode. “HOLD” is displayed flashing
when the thermostat is in a temporary HOLD mode.
Displays currently programmed set temperature (this
14
is blank when SYSTEM is OFF).
Displays “FLTR” when the system has run for the
15
programmed filter time period as a reminder to change or clean your filter.
The configuration menu allows you to set certain thermostat operating characteristics to your system or personal require­ments.
Set SYSTEM button to OFF, then simultaneously press
and to enter configuration menu. The display will
show the first item in the configuration menu.
The configuration menu table summarizes the configuration options. An explanation of each option follows.
Press SYSTEM to change to the next menu item. To exit the menu and return to the program operation, press RUN. If no keys are pressed within fifteen minutes, the thermostat will revert to normal operation.
) are displayed simultaneously
) is displayed when
Figure 4 – Thermostat display, buttons and switchesFigure 4 – Thermostat display, buttons and switches
Figure 4 – Thermostat display, buttons and switches
Figure 4 – Thermostat display, buttons and switchesFigure 4 – Thermostat display, buttons and switches
Display ( ) when in keypad lockout mode.
16
“EMER” is displayed flashing when the system is in
17
EMER mode.
The word “FAULT” will be displayed when there is a
18
malfunction in the HEAT/COOL system.
Display ( ) when limited HEAT/COOL range is activated.
19
The “
” icon will flash if an attempt is made to adjust the temperature beyond the limited HEAT/COOL temperature range.
Stage1 & 2 indicators: The thermostat shall indicate
20
when the first and second stage is energized except in emergency mode. The icon is “STG 1” for the first stage energized. The icons for the first and second stage energized are “STG1+2” located in the upper right side of the display.
CONFIGURACONFIGURA
CONFIGURA
CONFIGURACONFIGURA
1) Single Stage, Multi-Stage or Heat Pump System Configuration – This control can be configured for Heat
Pump or two stage heat/two stage cool Multi-Stage opera­tion. The display indicates “MS 2” (default for Multi-Stage mode) in the display. The Multi-Stage configuration can changed to “SS1”, “HP2”, or “HP1” by pressing the
key. In Multi-Stage configuration, SYSTEM button will
not have EMERgency mode.
TION MENUTION MENU
TION MENU
TION MENUTION MENU
or
2) Programmable Periods – This control can be configured
for 4, 2 or 0 programmable periods. The display indicates “PRG 4” in the display as default. The programmable periods can be toggled to 2 or 0 by pressing the or keys. With "PRG 0" selected for non-programmable, sys-
5
Page 6
CONFIGURACONFIGURA
CONFIGURA
CONFIGURACONFIGURA
TION MENUTION MENU
TION MENU
TION MENUTION MENU
Press the SYSTEM button until OFF is displayed, then press the and simultaneously
INSTALLER/CONFIGURATION MENU
Press Displayed Press or
Step Button(s) (Factory Default) to select Comments
1 System MS 2 SS1, HP2, HP1 Selects Single Stage, Multi-Stage, or Heat Pump
(Single Stage or 2-stage) System Configuration
2 System PRG 4 PRG 0, PRG 2 Selects Programmable Periods
3 System 4:00 HOLD 0:15 to 8:00 Selects Temporary Program Override Time
(increments of 15 minutes)
4 System EMR OFF Selects Energy Management Recovery OFF or ON
(ON)
5 System FA SL Selects Fast or Slow Cycle Selection
6 System CL CL Selects Compressor Lockout CL OFF or ON
(OFF) (ON)
7 System CDL CDL Selects Backlight Display
(ON) (OFF)
8 System FA FA Selects Fast Second Stage ON or OFF
(ON) (OFF) (Not available if SS1 is selected above)
9 System 0 FLTR 50-1950 (increments of 50) Selects filter replacement run time
10 System 0°F 4 LO to 4 HI Selects Temperature Display Adjustment 4 LO to 4 HI
(Room Temperature)
11 System °F °C Selects temperature display or °C selection
12 System AU On OFF Selects AUTO Mode ON or OFF
13 System LR LR 62 to LR89 Selects Limited HEAT range
(90)
14 System LR LR 46 to LR 82 Selects Limited COOL range
(45)
15 System (ON) Selects Keypad Lockout
(OFF)
16 System 000 001 to 999 Selects Keypad lockout combination number
Press System to set code
17 Run Returns to the OFF position
tem key selection will skip EMR (item 4) and temporary program override (item 3).
3) Select Temporary Program Override Time – The thermo- stat can hold any temperature you set it to for the amount of time you select on this option. Your choices are 0:15 to 8:00 hours in 15 minute increments.
Example:
a. You have selected 3:00 hours for the Temporary Pro-
gram Override time period.
b. With the thermostat set to Heat or Cool, press
to set the temperature to your preference. The thermostat will maintain this temperature setting for 3 hours with “HOLD” blinking to remind you it is in Temporary Hold. After 3 hours, the thermostat will
or
go back to the program temperature and “HOLD” will no longer blink or display.
4) Select Energy Management Recovery OFF or ON – Energy Management Recovery (EMR) causes the thermo­stat to start heating or cooling early to make the building temperature reach the program setpoint at the time you specify. Heating will start 5 minutes early for every 1° of temperature required to reach setpoint. Cooling allows more time per degree because it takes longer to reach temperature.
Example: You select EMR and have your heating program­med to 65° at night and 70° at 7 AM. If the building temp­erature is 65° the difference between 65° and 70° is 5°. Allowing 5 minutes per degree the thermostat setpoint will change to 70° at 6:35 AM.
6
Page 7
CONFIGURACONFIGURA
CONFIGURA
CONFIGURACONFIGURA
TION MENUTION MENU
TION MENU
TION MENUTION MENU
5) Fast or Slow Cycle Selection – The factory default setting is fast cycle, which cycles 1st stage at approximately 1.2°F and 2nd stage 0.75°F. If you prefer slow cycle, press the
or key to change to SL. The 1st stage and 2nd
stage would be 1.5°F and 1.2°F respectively.
6) Select Compressor Lockout CL OFF or ON – Selecting CL ON will cause the thermostat to wait 5 minutes before turning on the compressor if the heating and cooling system loses power. It will also wait 5 minutes minimum between cooling and heating cycles. This is intended to help protect the compressor from short cycling. Some newer compres­sors already have a time delay built in and do not require this feature. Your compressor manufacturer can tell you if the lockout feature is already present in their system. When the thermostat compressor time delay occurs it will flash the setpoint for about five minutes.
7) Select Backlight Display – The display backlight improves display contrast in low lighting conditions. When the C terminal is powered, selecting backlight CdL ON will turn the light on continuously. Select backlight OFF will keep the light on momentarily after any key is pressed. When the C terminal is not powered, this selection has no effect.
8) Select (Fast) Second Stage ON or OFF (not available in Single Stage configuration) – In the run mode, if the setpoint temperature is manually raised by 3°F (2°C) or more above the actual temperature with the fast second stage feature is enabled, FA ON, the second stage will energize immediately. With FA OFF, second stage will not energize until the setpoint temperature is 1°F or more above actual temperature for more than ten min­utes.
9) Select filter replacement run time – The thermostat will display FLTR after a set time of operation. This is a remind- er to change or clean your air filter. This time can be set from 0 to 1950 hours in 50 hour increments. A selection of 000 will cancel this feature. When “FLTR” is displayed, you can clear it by pressing HOLD and RUN at the same time. This resets the timer and starts counting the hours until the next filter change. Contact your system manufacturer for a specific replacement/maintenance interval.
10)Select Temperature Display Adjustment 4 LO to 4 HI – Allows you to adjust the room temperature display up to 4° higher or lower. Your thermostat was accurately calibrated at the factory but you have the option to change the display temperature to match your previous thermostat. The cur­rent or adjusted room temperature will be displayed on the left side of the display.
, and the
11)Select F° or C° Readout – Changes the display readout to Centigrade or Fahrenheit as required.
12)Selected Auto mode – This control will feature AUTO changeover mode when AU on is selected (default). Press
or keys in the menu mode to defeat the auto
the changeover mode (OFF).
13)Limited Heat Range – This feature provides a maximum setpoint temperature for heat. The default setting is 90°F. It can be changed between 62°F and 89°F by pressing the
or key.
14)Limited Cool Range – This feature provides a minimum setpoint temperature for cool. The default setting is 45°F. It can be changed between 46°F and 82°F by pressing the
or key.
15 & 16) Keypad Lockout – This menu selection will display
lock icon ( The and are used to toggle the selection between OFF and ON (keypad locked out). When the keypad lockout selection is enabled (ON), and the SYSTEM button is pressed again, the display will indicate the number “0” (default, still disabled) in the time digits. The and are used to set the combination number from 0 to 999. If a combination of 0 is selected and the SYSTEM button is pressed, the menu will be exited and keypad will not be locked. If 1 to 999 is selected and the SYSTEM button is pressed, the combination is stored into memory and the menu is exited. The ( ) will display designating keypad locked with a valid combination. The SYSTEM button will operate for 10 seconds after the menu mode is exited to allow the user to change the mode from OFF to the desired SYSTEM mode.
While the keypad is locked out, a simultaneous press of
and will enter the configuration menu from any mode instead of only OFF mode. When the menu is entered with the keypad lockout feature enabled, the first
menu item displayed is the combination code 0. The or
keys are used to set the combination unlock number from 0 to 999. If the unlock number matches exactly with the combination lock number stored in memory when the SYSTEM button is pressed, the keypad is unlocked and the ( ) is removed. If the unlock number does not match when the SYSTEM button is pressed, the menu is exited and the keypad remains disabled.
To reset the combination code and unlock the keypad if the code is forgotten, see troubleshooting section.
) and “OFF” (default, keypad not locked out).
SPECIFICASPECIFICA
SPECIFICA
SPECIFICASPECIFICA
ELECTRICAL DATAELECTRICAL DATA
ELECTRICAL DATA
ELECTRICAL DATAELECTRICAL DATA
Electrical RatingElectrical Rating
Electrical Rating:
Electrical RatingElectrical Rating
Mv to 30 VAC 50/60 Hz or DC
0.05 to 1.5 Amps (Load per terminal)
2.5 Amps Maximum Total Load (All terminals combined)
TIONSTIONS
TIONS
TIONSTIONS
THERMAL DATATHERMAL DATA
THERMAL DATA
THERMAL DATATHERMAL DATA
Setpoint Temperature RangeSetpoint Temperature Range
Setpoint Temperature Range:
Setpoint Temperature RangeSetpoint Temperature Range
45°F to 90°F (7°C to 32°C)
Operating Ambient Temperature RangeOperating Ambient Temperature Range
Operating Ambient Temperature Range:
Operating Ambient Temperature RangeOperating Ambient Temperature Range
32°F to 105°F
Operating Humidity RangeOperating Humidity Range
Operating Humidity Range:
Operating Humidity RangeOperating Humidity Range
0 to 90% RH (non-condensing)
Shipping Temperature RangeShipping Temperature Range
Shipping Temperature Range:
Shipping Temperature RangeShipping Temperature Range
-40°F to 150°F
7
Page 8
OPERAOPERA
OPERA
OPERAOPERA
The system "mode" is selected by pressing the SYSTEM button. Icons on the bottom right corner of the display will indicate the mode:
OFFOFF
or
OFF. In any mode except
OFFOFF be shown on the right side of the display. In be blank. The current temperature will be displayed on the left side of the display.
To operate properly in the temperature cannot be the same as or higher than the cool setpoint temperature. The heat setpoint must be at least 1° lower than the cool setpoint.
When the thermostat is in the Snowflake Snowflake
Snowflake icons are displayed. The thermostat will call for heat
Snowflake Snowflake or cool depending on the room temperature. The setpoint temperature displayed will be that of the last mode called. If the last system cycle was heat, the If the room temperature raises above the COOL COOL
COOL setpoint and a call for cool is required, the temperature
COOL COOL displayed will change to be the
Your thermostat is designed to determine the optimum time to activate the second stage. Simply raising the temperature in heating or lowering it in cooling will not always force the thermostat to bring the second stage on quickly. There is a time delay from 0-30 minutes depending on the performance of the first stage of the system.
EXAMPLE: For the last 2 hours the thermostat is set on 70° and the room temperature is 70° with the equipment using only the first stage of heat. Since the equipment is keeping the tempera­ture within 1° of setpoint, the thermostat will delay second stage for a longer time if you manually raise the temperature or if the room temperature quickly changes. Once the second stage comes on, it will come on sooner the next time there is a difference between the setpoint and the room temperature. The net effect of the staging program is that when the first stage is capable of making temperature the second stage will delay longer. When the thermostat calculates that first stage cannot make temperature in a reasonable time, the second stage will come on sooner. This built in function automatically optimizes the use of additional stages of heat or cool.
Permanent Program OverridePermanent Program Override
Permanent Program Override (
Permanent Program OverridePermanent Program Override button set to release. temperature. The thermostat will hold the room temperature at the selected setting until you press RUN button to start program operation again.
Temperature Program OverrideTemperature Program Override
Temperature Program Override – Press
Temperature Program OverrideTemperature Program Override display shows the temperature you want. The thermostat will override current programming and keep the room temperature at the selected temperature for a programmed time period. “HOLD”“HOLD”
“HOLD” will be displayed and flashing. The thermostat will
“HOLD”“HOLD” automatically revert to the program after programmed period.
TIONTION
TION
TIONTION
COOL COOL
COOL (
COOL COOL
Automatic System ChangeoverAutomatic System Changeover
Automatic System Changeover
Automatic System ChangeoverAutomatic System Changeover
Second Stage Time DelaySecond Stage Time Delay
Second Stage Time Delay
Second Stage Time DelaySecond Stage Time Delay
Manual OperationManual Operation
Manual Operation
Manual OperationManual Operation
HEAT HEAT
HEAT or
HEAT HEAT
“HOLD” “HOLD”
“HOLD” will be displayed. Use
“HOLD” “HOLD”
COOLCOOL
COOL, press the HOLD button once and
COOLCOOL
AUTO AUTO
),
AUTO ( ),
AUTO AUTO
OFFOFF
OFF, the setpoint temperature will
OFFOFF
AUTO AUTO
AUTO mode, the heat setpoint
AUTO AUTO
AUTO AUTO
AUTO mode, both the
AUTO AUTO
HEAT HEAT
HEAT setpoint will be displayed.
HEAT HEAT
COOL COOL
COOL setpoint.
COOL COOL
HOLDHOLD
HOLD) – With the SYSTEM
HOLDHOLD
HEAT HEAT
HEAT ( ),
HEAT HEAT
OFFOFF
OFF, this area will
OFFOFF
HEAT HEAT
HEAT setpoint and the
HEAT HEAT
or to adjust the
or until the
EMEREMER
EMER,
EMEREMER
Flame Flame
Flame and
Flame Flame
LOW BATTERY INDICATORLOW BATTERY INDICATOR
LOW BATTERY INDICATOR — If the 2 “AA” alkaline batter-
LOW BATTERY INDICATORLOW BATTERY INDICATOR ies are low and should be replaced, the display will be blank except for “ every 2 years. If the home is going to be unoccupied for an extended period (over 3 months), the batteries should be replaced before leaving. When the batteries are low, pressing any button will cause the display to operated for ten seconds. After ten seconds, the display will be blank except for “ BATTBATT
BATT”. You cannot program with low batteries, but you can
BATTBATT override setpoint temperature. After “ displayed for 4 weeks, the thermostat will raise the tempera­ture 10 degrees above your setpoint in COOL mode and will drop the temperature 10 degrees below your setpoint in HEAT mode. If the “ when it reaches certain value, the thermostat will turn off all the loads and “
SIMPLIFIED COPY DAY FUNCTIONSIMPLIFIED COPY DAY FUNCTION
SIMPLIFIED COPY DAY FUNCTION — This feature allows
SIMPLIFIED COPY DAY FUNCTIONSIMPLIFIED COPY DAY FUNCTION Monday’s program to be copied into the rest of the week’s programming. programmed your thermostat.programmed your thermostat.
programmed your thermostat. To use this feature, simply
programmed your thermostat.programmed your thermostat. enter the program for Monday as described in ENTERING YOUR PROGRAM, then press RUN or HOLD. The only way to restore this feature is to complete a software reset (see Reset Operation under TROUBLESHOOTING section).
COPY DAY FUNCTIONCOPY DAY FUNCTION
COPY DAY FUNCTION — This feature allows
COPY DAY FUNCTIONCOPY DAY FUNCTION a selected day’s program to be copied to the desired day’s programming. To use this feature: in PRGM mode, select the day to be copied program for the selected day as described in ENTERING YOUR PROGRAM. Press and hold the TIME button for 4 seconds to begin the COPY mode. The LCD will display “COPY”“COPY”
“COPY” and the selected day to be copied. The day the
“COPY”“COPY” program will copy to select the day you want to copy the Copy Day operation and return to PRGM mode. Press RUN to exit.
PROGRAMMING YOUR THERMOSTATPROGRAMMING YOUR THERMOSTAT
PROGRAMMING YOUR THERMOSTAT
PROGRAMMING YOUR THERMOSTATPROGRAMMING YOUR THERMOSTAT
This section will help you plan your thermostat's program to meet your needs. For maximum comfort and efficiency, keep the following guidelines in mind when planning your program.
• When heating (cooling) your building, program the temper­atures to be cooler (warmer) when the building is vacant or during periods of low activity.
• During early morning hours, the need for cooling is usually minimal.
Look at the factory preprogrammed times and temperatures shown in the sample schedule. If this program will suit your needs, simply press the RUN button to begin running the factory preset program.
If you want to change the preprogrammed times and tempera­tures, follow these steps.
Determine the time periods and temperatures for your program. You can program four or two periods for each day (see Configu­ration menu, item 2). You may use the same heating and cooling temperatures for consecutive time periods. You can choose start times, heating temperatures, and cooling temperatures independently (for example, you may select 5:00 AM and 70° as
LO BATTLO BATT
LO BATT”. We recommend replacing batteries
LO BATTLO BATT
LOLO
LO
LOLO
LO BATTLO BATT
LO BATT” has been
LO BATTLO BATT
LO BATTLO BATT
LO BATT” condition continues, and
LO BATTLO BATT
LO BATTLO BATT
LO BATT” will flash.
LO BATTLO BATT
This feature is available the first time youThis feature is available the first time you
This feature is available the first time you
This feature is available the first time youThis feature is available the first time you
from by pressing the HOLD button. Enter the
to will be flashing. Press the HOLD button
to. Press TIME to complete
Planning Your ProgramPlanning Your Program
Planning Your Program
Planning Your ProgramPlanning Your Program
8
Page 9
the weekday also choose 7:00 AM and 76° as the weekday coolingcooling
cooling start time and temperature).
coolingcooling
1st period heating1st period heating
1st period heating start time and temperature and
1st period heating1st period heating
1st period1st period
1st period
1st period1st period
Use the table to plan your program time periods and the temperatures you want during each period. Fill in the complete table to have a record of your programs.
Heating/Cooling Schedule Plan (Factory Program)
Period
1ST
2ND
3RD
4TH
1ST
2ND
3RD
COOL HEAT
4TH
Heating/Cooling Schedule Plan
WEEKDAYS
(5 Day)
Period
1ST
2ND
3RD
HEAT
4TH
1ST
2ND
COOL
3RD
4TH
Set Current Time and DaySet Current Time and Day
Set Current Time and Day
Set Current Time and DaySet Current Time and Day
Start Time Temp
Entering Your ProgramEntering Your Program
Entering Your Program
Entering Your ProgramEntering Your Program
SAMPLE
ALL DAYS OF THE WEEK
Start Time Temperature
6:00 AM
8:00 AM
5:00 PM
10:00 PM
6:00 AM
8:00 AM
5:00 PM
10:00 PM
SATURDAY
(1 Day)
Start Time Temp
70 F
62 F
70 F
62 F
78 F
85 F
78 F
82 F
SUNDAY
(1 Day)
Start Time Temp
1. Press TIME button once. The display will show the hour only.
EXAMPLE:
2. Press and hold either correct hour and AM/PM designation (
PM PM
night;
PM begins at noon).
PM PM
PM
or until you reach the
AM AM
AM begins at mid-
AM AM
3. Press TIME once again. The display window will show the minutes only.
OPERAOPERA
OPERA
OPERAOPERA
TIONTION
TION
TIONTION
5. Press TIME once again. The display will show the day of the week.
6. Press
or until you reach the current day of the
week.
7. Press RUN once. The display will show the correct time and room temperature alternately.
Enter Heating ProgramEnter Heating Program
Enter Heating Program
Enter Heating ProgramEnter Heating Program
1. Move the SYSTEM switch to HEAT.
2. Press PRGM once. “MO TU WE TH FR” (indicating weekday program) will appear in the display. Also dis­played are the currently programmed start time for the 1st heating period and the currently programmed tempera­ture (flashing).
MO TU WE TH FR
EXAMPLE:
AM
This display window shows that for the 1st weekday period, the start time is 6:00 AM, and 70° is the programmed temperature (this example reflects factory preprogramming).
3. Press or to change the displayed temperature to your selected temperature for Monday’s 1st heating program period.
4. Press TIME once (the programmed time will flash). Press
or until your selected start time appears. The time
will change in 15-minute increments. When your selected time is displayed, press TIME again to return to the change temperature mode.
5. Press PRGM once. The currently programmed start time and setpoint temperature for the 2nd heatingpro­gram period will appear.
6. Repeat steps 3 and 4 to select the start time and heating temperature for the 2nd heating program period.
7. Repeat steps 3 through 5 for the 3rd and 4th heating program periods. Weekday heating programs are now complete.
8. Press PRGM once "SA" (indicating Saturday program) will appear in the display, along with the start time for the 1st heating period and the currently programmed temp­erature.
9. Repeat steps 3 through 7 to complete Saturday heating programming.
10.Press PRGM once to change to "SU" (Sunday) heating programming and repeat steps 3 through 7 to complete Sunday programming.
11.When you have completed entering your heating pro­gram, press RUN.
EXAMPLE:
4. Press and hold either correct minutes.
or until you reach the
9
Page 10
OPERAOPERA
OPERA
OPERAOPERA
If the outside temperature is below 50°F, disconnectIf the outside temperature is below 50°F, disconnect
If the outside temperature is below 50°F, disconnect
If the outside temperature is below 50°F, disconnectIf the outside temperature is below 50°F, disconnect power to the cooling system before programming.power to the cooling system before programming.
power to the cooling system before programming.
power to the cooling system before programming.power to the cooling system before programming. Energizing the air conditioner compressor duringEnergizing the air conditioner compressor during
Energizing the air conditioner compressor during
Energizing the air conditioner compressor duringEnergizing the air conditioner compressor during cold weather may cause personal injury or propertycold weather may cause personal injury or property
cold weather may cause personal injury or property
cold weather may cause personal injury or propertycold weather may cause personal injury or property damage.damage.
damage.
damage.damage.
1. Press SYSTEM button to COOL position.
2. Follow Enter Heating Program for entering your cooling program, using your selected cooling times and tempera­tures.
TIONTION
TION
TIONTION
Enter Cooling ProgramEnter Cooling Program
Enter Cooling Program
Enter Cooling ProgramEnter Cooling Program
CAUTION
!
CHECK YOUR PROGRAMMING
Follow these steps to check your thermostat programming one final time before beginning thermostat operation.
1. Press SYSTEM button to HEAT position.
2. Press PRGM to view the 1st Monday heating period time and temperature. Each time you press PRGM, the next heating period time and temperature will be display­ed in sequence for each weekday, then Saturday and Sunday program periods (you may change any time or temperature during this procedure).
3. Press RUN.
4. Press SYSTEM button to COOL position.
5. Repeat step 2 to check cooling program.
6. Press SYSTEM button to HEAT or COOL and press RUN to begin program operation.
NOTE: Batteries are not required to keep your programming
or menu data. With two optional "AA" batteries installed, your thermostat will maintain time and continuously display the temperature during a loss of AC power. Installed batteries will also allow programming prior to installation.
YOUR THERMOSTAT IS NOW PROGRAMMED AND READY TO PROVIDE MAXIMUM COMFORT AND EFFICIENCY!
TRTR
OUBLESHOOOUBLESHOO
TR
OUBLESHOO
TRTR
OUBLESHOOOUBLESHOO
Reset OperationReset Operation
Reset Operation
Reset OperationReset Operation
If a voltage spike or static discharge blanks out the display or causes erratic thermostat operation, you can reset the thermo­stat by removing the wires from terminals replace the wires and batteries. If the thermostat has been reset and still does not function correctly, contact your heating/ cooling service person or place of purchase.
SymptomSymptom
Symptom
SymptomSymptom
No Heat/No Cool/No FanNo Heat/No Cool/No Fan
No Heat/No Cool/No Fan
No Heat/No Cool/No FanNo Heat/No Cool/No Fan (common problems)(common problems)
(common problems)
(common problems)(common problems)
No HeatNo Heat
No Heat
No HeatNo Heat
TINGTING
TING
TINGTING
RR
CC
R and
C and removing batteries for 2 minutes. After resetting the thermostat,
RR
CC
Possible CausePossible Cause
Possible Cause
Possible CausePossible Cause
1. Blown fuse or tripped circuit breaker.
2. Furnace power switch to OFF.
3. Furnace blower compartment door or panel loose or not properly installed.
1. Pilot light not lit.
2. SYSTEM button not set to
3. Loose connection to thermostat or system.
4. Furnace Lock-Out Condition. Heat may also be intermittent.
5. Heating system requires service or thermostat requires replacement.
HEATHEAT
HEAT.
HEATHEAT
Corrective ActionCorrective Action
Corrective Action
Corrective ActionCorrective Action
Replace fuse or reset breaker. Turn switch to ON. Replace door panel in proper position to engage safety interlock or door switch.
Re-light pilot. Press SYSTEM button to above room temperature. Verify thermostat and system wires are securely attached. Many furnaces have safety devices that shut down when a lock-out condition occurs. If the heat works intermittently contact the furnace manufacturer or local service person for assistance. Diagnostic: Press SYSTEM button to raise the setpoint above room temperature. Within a few seconds the thermostat should make a soft click sound. This sound usually indicates the thermostat is operating properly. If the thermostat does not click, try the reset operation listed above. If the thermostat does not click after being reset contact your heating and cooling service person or place of purchase for a replacement. If the thermostat clicks, contact the furnace manufacturer or a service person to verify the heating is operating correctly.
HEATHEAT
HEAT and raise setpoint
HEATHEAT
HEATHEAT
HEAT and
HEATHEAT
10
Page 11
TRTR
OUBLESHOOOUBLESHOO
TR
OUBLESHOO
TRTR
OUBLESHOOOUBLESHOO
TINGTING
TING
TINGTING
Symptom
No Cool
Heat, Cool or Fan Runs Constantly
Furnace (Air Conditioner) Cycles Too Fast or Too Slow (narrow or wide temperature swing)
Possible Cause
1. SYSTEM button not pressed to COOL.
2. Loose connection to thermostat or system.
3. Cooling system requires service or thermostat requires replacement.
1. Possible short in wiring.
2. Possible short in thermostat.
3. Possible short in heat/cool/fan system.
4. FAN Switch set to Fan On.
1. The location of the thermostat and/or the size of the Heating System may be influencing the cycle rate.
Corrective Action
Press SYSTEM button to COOL and lower setpoint below room temperature. Verify thermostat and system wires are securely attached. Same procedure as diagnostic for No Heat condition except set the thermostat to COOL and lower the setpoint below the room temperature. There may be up to a five minute delay before the thermostat clicks in Cooling.
Check each wire connection to verify they are not shorted or touching together. No bare wire should stick out from under terminal screws. Try resetting the thermostat as described above. If the condition persists the manufacturer of your system or service person can instruct you on how to test the Heat/Cool system for correct operation. If the system operates correctly, replace the thermostat.
Digital thermostats normally provide precise temperature control and may cycle faster than some older mechanical models. A faster cycle rate means the unit turns on and off more frequently but runs for a shorter time so there is no increase in energy use. If you would like to increase the cycle time, choose SL for slow cycle in the menu, step 4. If an accept­able cycle rate is not achieved as received or by choosing slow cycle, contact a local service person for additional suggestions.
Thermostat Setting & Thermostat Thermometer Disagree
Blank Display and/or Keypad Not Responding
Heat Setpoint will not Respond to the Temperature Up Key
Cool Setpoint will not Respond to the Temperature Down Key
Forgot Keypad Lockout Code
Why won’t my 2nd or 3rd stage come on?
1. Thermostat thermometer setting requires adjustment.
1. Voltage spike or static discharge.
1. The desired setpoint conflicts with the setpoint of the COOL mode.
1. The desired setpoint conflicts with the setpoint of the HEAT mode.
First stage is keeping up with demand.
The thermometer can be adjusted +/- 4 degrees. See Temperature Display Adjustment in the Configuration Menu section.
Use the Reset Operation at top of previous page.
Change system mode to COOL. Raise the Cool setpoint. Return to HEAT mode and set desired temperature.
Change system mode to HEAT. Lower the Heat setpoint. Return to COOL mode and set desired temperature.
CAUTION: This resets the thermostat to factory default settings of the configuration menu. After performing this reset, the thermostat will require configuration again. Be sure that you know the required configuration settings before resetting.
With the thermostat in any mode, press the same time to enter the configuration menu at the point where the lockout code is to be entered. Press
and and SYSTEM button at the same time to reset the lockout code, unlock the keypad and reset all configuration menu settings.
Your thermostat is designed to determine the optimum time to activate the second stage. Simply raising the temperature in heating or lowering it in cooling will not always force the thermostat to bring the second stage on quickly. There is a time delay from 0-30 minutes depending on the performance of the first stage of the system.
and at
11
Page 12
FF
AA
QQ
F
A
Q
FF
AA
QQ
Symptom
Corrective Action
My thermostat is reading in Celsius. How do I change it to Fahrenheit?
Do I have to program a stop time for each program period?
My thermostat does not follow it’s program. What should I do?
Between heating and cooling seasons, I want to turn my system off. Will this change my program?
My display light does not work. Can it be fixed or replaced?
Do I have to reprogram my thermostat after I change the batteries?
My setpoint temperature is flashing. What does that mean?
Your thermostat display can be set to display temperature in Fahrenheit or Celsius. This option can be set in the INSTALLER/CONFIGURATION MENU of your thermostat. See page 6 step 12.
There is no need to select a time to stop a programming period. Starting a new programming period will stop the previous program period.
Unless the thermostat appears to be damaged it will follow the program that is in the memory. The most common reason a thermostat will appear not to be following the program is a programming error. Verify that the AM or PM settings are correct for each period. Also verify that the Day of the week is set correctly. Models with EMR (Energy Management Recovery) start early to make the temperature they are programmed for by the time specified in the program. See the CONFIGURATION MENU on page 6 step 3.
Any time you wish to turn your system off, simply press the SYSTEM button until “OFF” is displayed. This will not affect your thermostat’s programming in any way. To turn the system back on, press the SYSTEM button to HEAT or COOL and press RUN. The system will begin operating according to the current thermostat program. See under OPERATION page 8 & 9.
Because it is soldered to the circuit board it is not possible to repair or replace.
No. This thermostat has permanent memory, although you will have to reset your clock.
When the thermostat compressor time delay occurs it will flash the setpoint for about five minutes. This is intended to help protect the compressor from short cycling.
How can I get a copy of the Operating Manual for my thermostat?
My program or configuration menu is all messed up, how do I start from the beginning?
HOMEOWNER HELP LINE: 1-800-284-2925
Visit our website at www.white-rodgers.com for operating manuals.
You can perform software reset by pressing and SYSTEM buttons simultaneously when SYSTEM mode is OFF. See “Forget Keypad Lockout Code” under “TROUBLESHOOTING” for details.
The Emerson logo is a trademark and service mark of Emerson Electric Co.
www.white-rodgers.com
Loading...