Operating Ambient .................................. 32°F to +105°F (0° to +41°C)
Display Temperature Range ....................... 32°F to +99°F (0 to 37°C)
Operating Humidity ................................. 90% non-condensing maximum
Shipping Temperature Range ................... -20°F to + 150°F (-29° to +65°C)
Thermostat Dimensions ........................... 3-3/4” H x 6” W x 1-1/8” D
white-rodgers.com
emersonclimate.com
PART NO. 37-7572B-EN
Maximum
Stages
Heat/ Cool
2/2
2/1
1535
THERMOSTAT INSTALLATION
WIRING
Refer to equipment manufacturer’s instructions for specic system wiring information. After wiring, see
INSTALLER MENU for proper thermostat conguration. Wiring table shown are for typical systems and
describe the thermostat terminal functions. Wiring will change when dedicated emergency heat is on
(See Installer Menu #15).
Terminal DesignationsTerminal Function
RC
RH
O/B
6 (not shown) - 3 wire zone valve
Y
GFan Relay
W/E
C
L
Y22nd Stage compressor (conventional only)
W2
Power (24V) - Cooling
Power (24V) - Heating
Reversing Valve or output for 3 wire zone valves
Congurable as “O” or “B” Reversing Valve or 3 wire
Can operate as Emergency Heat only
(See Installer Menu #15)
Common wire for 24V (optional with batteries)
Heat Pump Malfunction / Diagnostic terminal
(input signal requires common)
2nd Stage Heat (Conventional)
Can operate as 1st Stage Auxiliary Heat
(See Installer Menu #15)
Leveling Thermostat
Leveling is for appearance only and
will not aect thermostat operation.
Precautions
• Do not exceed the specication ratings.
• All wiring must conform to local and national electrical codes and ordinances.
• This control is a precision instrument, and should be handled carefully. Rough handling or
distorting components could cause the control to malfunction.
Do not use on circuits exceeding specied voltage.
Higher voltage will damage control and could
cause shock or re hazard.
Do not short out terminals on gas valve or primary
control to test. Short or incorrect wiring will burn
out thermostat and could cause personal injury
and/or property damage.
To prevent compressor and/or property damage, if the outdoor temperature is below 50°F,
Do not allow the compressor to run unless the compressor oil heaters have been operational
for 6 hours and the system has not been operational for at least 5 minutes.
DO NOT operate the cooling system.
To prevent electrical shock and/or equipment
damage, disconnect electrical power to system,
at main fuse or circuit breaker box,until
installation is complete.
2
RC/RH Jumper Wire
This thermostat electrically connects
the RC and RH terminals so a jumper
wire is not required. If the application
provides a separate wire for RC and
RH, clip the RC/RH jumper. This will
isolate both terminals so they can be
independently used.
Baery Locaon
Premium AA alkaline batteries are
required when C-wire is not available.
When C-wire is available, the batteries
provide a back-up source of power
(this will maintain the clock in the
INSTALLER MENU
event of a power outage).
To prevent changes that may aect system performance, this thermostat has an INSTALLER
MENU and a USER MENU. The INSTALLER MENU provides access to every option, while the
USER MENU provides access to items that will not aect system performance. To access the
INSTALLER MENU press the Menu button for 8 seconds. The display will show item 05 in the
table below. Use Next and Back to navigate through menu items. Press or to change a
menu setting.
Installer Menu #
(Hold Menu 8 Seconds)
05
10
15
20
30
32
35
50
65
66
Description
Outdoor Equipment: selects air
conditioner (AC) or heat pump (HP)
equipment as well as the number of
stage
Indoor Equipment: selects whether
the equipment is a gas furnace, electric furnace or fan only
Dedicated Emergency: W/E only
operates in Emergency Aux mode. W2
becomes 1st stage Aux. Heat
O,B or 3 Wire Zone Valve Selection
Heat Cycle Rate: how often
the heat will turn on
Aux Cycle Rate: how often the
auxiliary heat will turn on
Cool Cycle Rate: how often
the cooling will turn on
Compressor Lockout:
protects the compressor
from short cycling
Max Heat Limit: maximum set point
for heat mode
Minimum Cool Limit: minimum set
point for cool mode
Default Setting
(ashing icons)
AC2
EL2
OFF
O
MEd
MEd
MEd
OFF
99
4545 to 97
Settings
(Press or )
AC0
AC1
AC2
HP1
FAN
GA1
GA2 (convenonal only)
EL1
EL2 (convenonal only)
On
OFF
O
B
3
SLO – slow
MEd – medium
FAS – fast
SLO – slow
MEd – medium
FAS – fast
SLO – slow
MEd – medium
FAS – fast
On – 5 minute delay
OFF – no delay
47 to 99
INSTALLER MENU (C0ntinued)
Installer’s Menu #
(Hold Menu 8 Seconds)
79
81
83
88
99
Description
Fahrenheit or Celsius°F
Temperature Display Adjustment:
adjust the displayed “Room
Temperature”
Continuous Display Light: keep
the backlight always on – “C” wire
required
Auto Changeover: thermostat
automatically switches between
heat and cool
Keypad Lock: prevent unwanted
changes to the thermostat
Default Setting
(ashing icons)
OFF
OFF
OFF
0-5 to +5
Settings
(Press or )
°F – Fahrenheit
°C – Celsius
On – always on
OFF – momentarily
On – enable auto
OFF – disable auto
On – disable buttons
OFF – all buttons are active
TEST EQUIPMENT
Turn on power to the system.
Fan Operation
If your system does not have a G terminal connection, skip to Heating System.
1.) Press the fan button to select the On position. The blower should begin to operate.
2.) Press the fan button to select the Auto position. The blower should stop immediately.
Heating System
1.) Press the System button to select the Heat position. Heat Pumps only - if the auxiliary
heating system has a standing pilot, be sure to light it.
2.) Press to adjust thermostat setting to 1° above room temperature. The heating system
should begin to operate and the thermostat will indicate Heat On.
3.) For heat pumps with auxiliary- Press to adjust thermostat setting to 3° above room
temperature. The auxiliary heat should begin to operate and the thermostat will indicate
Heat On Aux.
4.) Press to adjust thermostat setting 1° below room temperature. The heating system
should stop operating and the Heat On iconwill disappear.
Auxiliary System ( only for heat pumps with auxiliary)
1.) Press the system button to select the Aux position. This bypasses the heat pump and
runs auxiliary only heat.
2.) Press to adjust thermostat setting to 1° above room temperature. The auxiliary heating
system should begin to operate and the thermostat will indicate Heat On Aux.
3.) Press to adjust thermostat setting 1° below room temperature. The auxiliary heating
system should stop operating and the Heat On Aux icon will disappear.
Cooling System
1.) Press the System button to select the Cool position.
2.) Press to adjust thermostat setting 1° below room temperature. The blower should
come on immediately on high speed, followed by cold air circulation. The thermostat will
indicate Cool On. There can be up to a 5 minute delay. (see INSTALLER MENU, item 50)
3.) Press to adjust thermostat setting to 1° above room temperature. The cooling system
should stop operating and the Cool On icon will disappear.
Note: If Starting Soon is shown on the display, the compressor lockout feature is operating. There will
be up to a 5 minute delay before the compressor turns on (see INSTALLER MENU, item 50).
3
4
USING THE THERMOSTAT
THERMOSTAT OVERVIEW
Before you begin using your thermostat, you should be familiar with its features, display and
the location/operation of the thermostat buttons and switches.
THERMOSTAT BUTTONS
AND SWITCHES
1.) Fan Button8.) Next (Menu button) is used to navigate within a menu
2.) Away Button (set a frequently used
temperature)
3.) System Button10.) Exit (Away button) returns to the home screen
4.) Backlight Button (located on the top
of the thermostat)
5.) Raises Temperature Setting12.) Indicates that the system is running in Cool, Heat or Auxiliary
6.) Access Menu Options13.) SEE TROUBLESHOOTING
7.) Lowers Temperature Setting14.) Battery status indicator
14
13
12
THE DISPLAY
9.) Back (Fan button) is used to navigate within a menu
11.) Thermostat is protecting the equipment from short cycling
(5-minute delay)
mode. (Heat Pump Only -The auxiliary will run in Heat mode
when the heat pump cannot maintain the set temperature.)
15.) Replace battery indicator
16.) Temperature setpoint
17.) Appears when the keypad is locked (to prevent unwanted
changes)
1516
4
5
6
17
USER MENU
To customize thermostat settings, press the Menu button from the home screen. Use the
or buttons to highlight Settings and press Next. Use Next and Back to navigate
through menu items. Press or to change the setting.
User’s Menu #
(Press Menu button
and release)
01
02
03
04
05
Description
Fahrenheit or Celsius °F
Temperature Display
Adjustment: adjust the Room
Temperature
Continuous Display Light:
keep the backlight always on –
“C” wire required
Auto-Changeover: thermostat
automatically switches between
heat and cool
Keypad Lock: prevent unwanted changes to the thermostat
Default Setting
(ashing icons)
0-5 to +5
OFF
OFF
OFF
Settings
(Press or )
°F – Fahrenheit
°C – Celsius
On – always on
OFF – momentarily
On - enable auto
OFF - disable auto
On – disable buttons
OFF – all buttons are active
THERMOSTAT OPERATION
• Away – Stores a frequently used temperature setting so that you can select it with a
touch of the Away button. To set an Away temperature press temp up or temp down
to the temperature you want. At the desired setting, hold the Away button for 3 seconds.
When the setting is stored the set point will ash one time. You can store an Away setting
for both Cool and Heat modes. (Example: Set an Away temperature to 88°F in the summer
for cooling and 55°F in the winter for heating.)
• Keypad Lockout – To prevent unwanted changes, the buttons can be disabled.
To turn this feature On, press and hold and the Menu button unl the icon appears
(this can also be turned on in the menu). To turn O, press and hold and the Menu but-
ton for 3 seconds.
11
8
3
10
” appears in the display, new premium brand AA alkaline batteries
Whenever
“
should be installed. If the house will be unoccupied for an extended period and either
or “
5
Replace
” is displayed, install new batteries before leaving.
Replace
2
1
9
7
“ ”
6
TROUBLESHOOTING
Symptom Possible CauseCorrective Action
1.) Blown fuse or tripped circuit
breaker
No Heat/
No Cool/
No Fan
(common problem)
No Heat
No Cool
Heat, Cool or Fan
Runs Constantly
Thermostat
Display &
Thermometer
Disagree
Furnace (Air
Conditioner)
Cycles Too Fast or
Slow (narrow or
wide temperature
swing)
(Troubleshooting continued on next page)
7
2.) Furnace power switch to OFF
3.) Furnace blower compartment
door panel loose or not properly
installed
4.) Loose connection to thermostat
or system
1.) System not set to Heat
2.) Loose connection to thermostat
or system
3.) Heating System requires
service or thermostat requires
replacement
1.) System not set to Cool
2.) Loose connection to thermostat
or system
3.) Cooling System requires
service or thermostat requires
replacement
Possible short in wiring, thermostat,
heat, cool or fan system
Thermostat display requires
adjustment
The location of the thermostat and/
or the size of the Heating System
may be inuencing the cycle rate
1.) Replace fuse or reset breaker
2.) Turn switch to ON
3.) Replace door panel in proper position to
engage safety interlock or door switch
4.) Tighten Connections
1.) Set thermostat to Heat.
2.) Verify thermostat and system wires are
securely aached.
3.) Diagnosc: Set System to Heat and raise the
setpoint above room temperature. Within ve
minutes the thermostat should make a so click
sound and “Heat On” should appear on display.
This sound indicates the thermostat is operang
properly. If the thermostat does not click, try the
reset operaon listed below. If the thermostat
does not click aer being reset, contact your
heang and cooling service person or place of
purchase for a replacement. If the thermostat
clicks, contact the furnace manufacturer or a
service person to verify the heang system is
operang correctly.
1.) Set thermostat to Cool.
2.) Verify thermostat and system wires are securely
aached.
3.) Diagnosc: Set System to Cool and lower
setpoint below room temperature. Same
procedures as diagnosc for “No Heat” condion
except set the thermostat to Cool and lower the
setpoint below the room temperature. There may
be up to a ve minute delay before the thermostat
clicks in Cooling if the compressor lock-out opon
is selected in the installer menu. (see INSTALLER
MENU, item 50)
Check each wire connection to verify they are not
shorted or touching other wires. Try resetting the
thermostat. If the condition persists contact your
HVAC service person.
Display can be adjusted +/-5°. See User Menu
item 05
Digital thermostats provide precise control and
cycle faster than older mechanical models. The
system turns on and o more frequently, but runs
for a shorter time. If you would like to increase
cycle time, choose SLO for slow cycle in the
Installer menu. (Reference menu items 30, 32 &
35.) If an acceptable cycle rate is not achieved,
contact your HVAC service person.
TROUBLESHOOTING (C0ntinued)
Symptom Possible CauseCorrective Action
1.) Heating system is not able to heat
the space to within 10 degrees of
the setpoint within 2 hours
2.) Cooling system is not able to cool
the space to within 10 degrees of
“Call for Service”
icon appears on
displayed
the setpoint within 2 hours
3.) If “--” is displayed for the Room
Temperature, a replacement
thermostat is needed
4.) None of the buttons operate on
the thermostat
5.) If “Call for Service” is ashing,
compressor self diagnostic is
detecting an issue with the
outdoor unit
Resetting the Thermostat or Thermostat Settings
If the thermostat has good batteries, but has a blank display or does not respond to key
presses, the thermostat should be reset by removing the batteries for 2 minutes. This reset
will not change the menu settings or program. If the condition persists after reinstalling the
batteries, replace the thermostat.
To conveniently reset only the schedule and user settings back to factory defaults, press Menu
and Backlight buttons at the same time and hold until the display goes blank and resets.
HOMEOWNER HELP LINE: 1-800-284-2925
White-Rodgers is a business
of Emerson Electric Co.
The Emerson logo is a
trademark and service mark
of Emerson Electric Co.
www.white-rodgers.com
www.emersonclimate.com
1.) See corrective action for “No Heat”
2.) See corrective action for “No Cool”
3.) Replace thermostat
4.) Make sure keypad lockout is not turned on ( ),
If it’s OFF, try reset shown below.
5.) Contact a service person to verify the outdoor
equipment is operating correctly
Loading...
+ 8 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.