White-Rodgers 1F83C-11NP-Instruction Sheet, 1F85U-22NP Instruction Sheet Manuals & Guides

1F85U-22NP (Non-Programmable)
WARNING
!
CAUTION
!
CAUTION
!
INDEX
Thermostat Installation
Wiring
Installer Menu
Test Equipment
Using the Thermostat
Thermostat Overview
User Menu
Thermostat Operation
Troubleshooting
Homeowner Help Line
Optional Accessory: Wall Cover-Up Plate F61-2663, 6-3/4” W x 4-1/2” H
2-4
2
3-4
4
5-7
5
6
6
7-8
8
Installation and Operating Instructions
Battery Powered or Hardwired with Common
Thermostat Applications
Conventional Gas, Oil, Electric (mV and 24V), Heat only, Cool only or Heat/Cool Systems
Heat Pump (Air Source or Geothermal) with Aux. Heat
MERCURY NOTICE: This product does not contain
mercury. However, this product may replace a product
that contains mercury. Mercury and products containing
mercury must not be discarded in household trash.
Refer to www.thermostat-recycle.org for information
on disposing of products containing mercury.
80 SeriesTM Universal Thermostat
SPECIFICATIONS
Electrical Rating:
Battery Power ..................................... mV to 30 VAC, NEC Class II, 50/60 Hz
Input-Hardwire .................................... 20 to 30 VAC, NEC Class II, 50/60 Hz
Terminal Load .......................................... 1.5 A per terminal, 2.5A maximum all terminals combined
Setpoint Range ........................................ 45° to 99° F (to 37° C)
Rated Dierentials (@ 6°F/ Hr): Fast Med Slow
Heat (Conventional Gas / Oil / Elect) ..... 0.5°F 0.75°F 1.9°F
Cool (Central Air) ................................. 0.9°F 1.2°F 1.7°F
Heat Pump (Heat and Cool) ................ 0.9°F 1.2°F 1.7°F
Heat Pump Aux. .................................. 0.5°F 0.75°F 1.9°F
Operating Ambient .................................. 32°F to +105°F (0° to +41°C)
Display Temperature Range ....................... 32°F to +99°F (0 to 37°C)
Operating Humidity ................................. 90% non-condensing maximum
Shipping Temperature Range ................... -20°F to + 150°F (-29° to +65°C)
Thermostat Dimensions ........................... 3-3/4” H x 6” W x 1-1/8” D
PART NO. 37-7572B-EN
Maximum
Stages
Heat/ Cool
2/2
2/1
1535
THERMOSTAT INSTALLATION
WIRING
Refer to equipment manufacturer’s instructions for specic system wiring information. After wiring, see INSTALLER MENU for proper thermostat conguration. Wiring table shown are for typical systems and
describe the thermostat terminal functions. Wiring will change when dedicated emergency heat is on (See Installer Menu #15).
Terminal Designations Terminal Function
RC
RH
O/B
6 (not shown) - 3 wire zone valve
Y
G Fan Relay
W/E
C
L
Y2 2nd Stage compressor (conventional only)
W2
Power (24V) - Cooling
Power (24V) - Heating
Reversing Valve or output for 3 wire zone valves
Congurable as “O” or “B” Reversing Valve or 3 wire
zone heat (power close)
1st Stage Compressor (conventional or heat pump)
1st Stage Heat (conventional); 1st Stage Auxiliary Heat (heat pump)
Can operate as Emergency Heat only (See Installer Menu #15)
Common wire for 24V (optional with batteries)
Heat Pump Malfunction / Diagnostic terminal (input signal requires common)
2nd Stage Heat (Conventional) Can operate as 1st Stage Auxiliary Heat (See Installer Menu #15)
Leveling Thermostat
Leveling is for appearance only and
will not aect thermostat operation.
Precautions
• Do not exceed the specication ratings.
• All wiring must conform to local and national electrical codes and ordinances.
• This control is a precision instrument, and should be handled carefully. Rough handling or distorting components could cause the control to malfunction.
Do not use on circuits exceeding specied voltage.
Higher voltage will damage control and could
cause shock or re hazard.
Do not short out terminals on gas valve or primary
control to test. Short or incorrect wiring will burn
out thermostat and could cause personal injury
and/or property damage.
To prevent compressor and/or property damage, if the outdoor temperature is below 50°F,
Do not allow the compressor to run unless the compressor oil heaters have been operational
for 6 hours and the system has not been operational for at least 5 minutes.
DO NOT operate the cooling system.
To prevent electrical shock and/or equipment
damage, disconnect electrical power to system,
at main fuse or circuit breaker box,until
installation is complete.
2
RC/RH Jumper Wire
This thermostat electrically connects
the RC and RH terminals so a jumper wire is not required. If the application provides a separate wire for RC and RH, clip the RC/RH jumper. This will isolate both terminals so they can be independently used.
Baery Locaon
Premium AA alkaline batteries are required when C-wire is not available. When C-wire is available, the batteries provide a back-up source of power (this will maintain the clock in the
INSTALLER MENU
event of a power outage).
To prevent changes that may aect system performance, this thermostat has an INSTALLER
MENU and a USER MENU. The INSTALLER MENU provides access to every option, while the
USER MENU provides access to items that will not aect system performance. To access the
INSTALLER MENU press the Menu button for 8 seconds. The display will show item 05 in the table below. Use Next and Back to navigate through menu items. Press or to change a menu setting.
Installer Menu #
(Hold Menu 8 Seconds)
05
10
15
20
30
32
35
50
65
66
Description
Outdoor Equipment: selects air
conditioner (AC) or heat pump (HP) equipment as well as the number of stage
Indoor Equipment: selects whether the equipment is a gas furnace, elec­tric furnace or fan only
Dedicated Emergency: W/E only operates in Emergency Aux mode. W2 becomes 1st stage Aux. Heat
O,B or 3 Wire Zone Valve Selection
Heat Cycle Rate: how often the heat will turn on
Aux Cycle Rate: how often the auxiliary heat will turn on
Cool Cycle Rate: how often the cooling will turn on
Compressor Lockout: protects the compressor from short cycling
Max Heat Limit: maximum set point for heat mode
Minimum Cool Limit: minimum set point for cool mode
Default Setting
(ashing icons)
AC2
EL2
OFF
O
MEd
MEd
MEd
OFF
99
45 45 to 97
Settings
(Press or )
AC0 AC1 AC2 HP1
FAN GA1
GA2 (convenonal only)
EL1
EL2 (convenonal only)
On OFF
O B
3
SLO – slow MEd – medium FAS – fast
SLO – slow MEd – medium FAS – fast
SLO – slow MEd – medium FAS – fast
On – 5 minute delay OFF – no delay
47 to 99
INSTALLER MENU (C0ntinued)
Installer’s Menu #
(Hold Menu 8 Seconds)
79
81
83
88
99
Description
Fahrenheit or Celsius °F
Temperature Display Adjustment:
adjust the displayed “Room
Temperature” Continuous Display Light: keep
the backlight always on – “C” wire
required Auto Changeover: thermostat
automatically switches between heat and cool
Keypad Lock: prevent unwanted changes to the thermostat
Default Setting
(ashing icons)
OFF
OFF
OFF
0 -5 to +5
Settings
(Press or )
°F – Fahrenheit °C – Celsius
On – always on OFF – momentarily
On – enable auto OFF – disable auto
On – disable buttons OFF – all buttons are active
TEST EQUIPMENT
Turn on power to the system.
Fan Operation If your system does not have a G terminal connection, skip to Heating System.
1.) Press the fan button to select the On position. The blower should begin to operate.
2.) Press the fan button to select the Auto position. The blower should stop immediately.
Heating System
1.) Press the System button to select the Heat position. Heat Pumps only - if the auxiliary
heating system has a standing pilot, be sure to light it.
2.) Press to adjust thermostat setting to above room temperature. The heating system
should begin to operate and the thermostat will indicate Heat On.
3.) For heat pumps with auxiliary- Press to adjust thermostat setting to 3° above room
temperature. The auxiliary heat should begin to operate and the thermostat will indicate Heat On Aux.
4.) Press to adjust thermostat setting below room temperature. The heating system
should stop operating and the Heat On icon will disappear.
Auxiliary System ( only for heat pumps with auxiliary)
1.) Press the system button to select the Aux position. This bypasses the heat pump and
runs auxiliary only heat.
2.) Press to adjust thermostat setting to above room temperature. The auxiliary heating
system should begin to operate and the thermostat will indicate Heat On Aux.
3.) Press to adjust thermostat setting below room temperature. The auxiliary heating
system should stop operating and the Heat On Aux icon will disappear.
Cooling System
1.) Press the System button to select the Cool position.
2.) Press to adjust thermostat setting below room temperature. The blower should
come on immediately on high speed, followed by cold air circulation. The thermostat will indicate Cool On. There can be up to a 5 minute delay. (see INSTALLER MENU, item 50)
3.) Press to adjust thermostat setting to above room temperature. The cooling system
should stop operating and the Cool On icon will disappear.
Note: If Starting Soon is shown on the display, the compressor lockout feature is operating. There will
be up to a 5 minute delay before the compressor turns on (see INSTALLER MENU, item 50).
3
4
USING THE THERMOSTAT
THERMOSTAT OVERVIEW
Before you begin using your thermostat, you should be familiar with its features, display and the location/operation of the thermostat buttons and switches.
THERMOSTAT BUTTONS AND SWITCHES
1.) Fan Button 8.) Next (Menu button) is used to navigate within a menu
2.) Away Button (set a frequently used
temperature)
3.) System Button 10.) Exit (Away button) returns to the home screen
4.) Backlight Button (located on the top
of the thermostat)
5.) Raises Temperature Setting 12.) Indicates that the system is running in Cool, Heat or Auxiliary
6.) Access Menu Options 13.) SEE TROUBLESHOOTING
7.) Lowers Temperature Setting 14.) Battery status indicator
14
13
12
THE DISPLAY
9.) Back (Fan button) is used to navigate within a menu
11.) Thermostat is protecting the equipment from short cycling
(5-minute delay)
mode. (Heat Pump Only -The auxiliary will run in Heat mode when the heat pump cannot maintain the set temperature.)
15.) Replace battery indicator
16.) Temperature setpoint
17.) Appears when the keypad is locked (to prevent unwanted
changes)
15 16
4
5
6
17
USER MENU
To customize thermostat settings, press the Menu button from the home screen. Use the
or buttons to highlight Settings and press Next. Use Next and Back to navigate
through menu items. Press or to change the setting.
User’s Menu # (Press Menu button and release)
01
02
03
04
05
Description
Fahrenheit or Celsius °F
Temperature Display Adjustment: adjust the Room
Temperature
Continuous Display Light: keep the backlight always on –
“C” wire required
Auto-Changeover: thermostat automatically switches between heat and cool
Keypad Lock: prevent unwant­ed changes to the thermostat
Default Setting
(ashing icons)
0 -5 to +5
OFF
OFF
OFF
Settings (Press or )
°F – Fahrenheit °C – Celsius
On – always on OFF – momentarily
On - enable auto OFF - disable auto
On – disable buttons OFF – all buttons are active
THERMOSTAT OPERATION
Away – Stores a frequently used temperature setting so that you can select it with a
touch of the Away button. To set an Away temperature press temp up or temp down to the temperature you want. At the desired setting, hold the Away button for 3 seconds.
When the setting is stored the set point will ash one time. You can store an Away setting
for both Cool and Heat modes. (Example: Set an Away temperature to 88°F in the summer for cooling and 55°F in the winter for heating.)
Keypad Lockout – To prevent unwanted changes, the buttons can be disabled.
To turn this feature On, press and hold and the Menu button unl the icon appears
(this can also be turned on in the menu). To turn O, press and hold and the Menu but- ton for 3 seconds.
11
8
3
10
” appears in the display, new premium brand AA alkaline batteries
Whenever
“ should be installed. If the house will be unoccupied for an extended period and either
or “
5
Replace
” is displayed, install new batteries before leaving.
Replace
2
1
9
7
“ ”
6
TROUBLESHOOTING
Symptom Possible Cause Corrective Action
1.) Blown fuse or tripped circuit breaker
No Heat/ No Cool/ No Fan (common problem)
No Heat
No Cool
Heat, Cool or Fan Runs Constantly
Thermostat Display & Thermometer Disagree
Furnace (Air Conditioner) Cycles Too Fast or Slow (narrow or wide temperature swing)
(Troubleshooting continued on next page)
7
2.) Furnace power switch to OFF
3.) Furnace blower compartment
door panel loose or not properly installed
4.) Loose connection to thermostat or system
1.) System not set to Heat
2.) Loose connection to thermostat
or system
3.) Heating System requires service or thermostat requires replacement
1.) System not set to Cool
2.) Loose connection to thermostat
or system
3.) Cooling System requires service or thermostat requires replacement
Possible short in wiring, thermostat, heat, cool or fan system
Thermostat display requires adjustment
The location of the thermostat and/ or the size of the Heating System
may be inuencing the cycle rate
1.) Replace fuse or reset breaker
2.) Turn switch to ON
3.) Replace door panel in proper position to
engage safety interlock or door switch
4.) Tighten Connections
1.) Set thermostat to Heat.
2.) Verify thermostat and system wires are
securely aached.
3.) Diagnosc: Set System to Heat and raise the setpoint above room temperature. Within ve minutes the thermostat should make a so click
sound and “Heat On” should appear on display.
This sound indicates the thermostat is operang
properly. If the thermostat does not click, try the
reset operaon listed below. If the thermostat does not click aer being reset, contact your heang and cooling service person or place of
purchase for a replacement. If the thermostat clicks, contact the furnace manufacturer or a
service person to verify the heang system is operang correctly.
1.) Set thermostat to Cool.
2.) Verify thermostat and system wires are securely
aached.
3.) Diagnosc: Set System to Cool and lower
setpoint below room temperature. Same
procedures as diagnosc for “No Heat” condion
except set the thermostat to Cool and lower the setpoint below the room temperature. There may
be up to a ve minute delay before the thermostat clicks in Cooling if the compressor lock-out opon is selected in the installer menu. (see INSTALLER MENU, item 50)
Check each wire connection to verify they are not shorted or touching other wires. Try resetting the thermostat. If the condition persists contact your HVAC service person.
Display can be adjusted +/-5°. See User Menu item 05
Digital thermostats provide precise control and cycle faster than older mechanical models. The
system turns on and o more frequently, but runs
for a shorter time. If you would like to increase cycle time, choose SLO for slow cycle in the Installer menu. (Reference menu items 30, 32 &
35.) If an acceptable cycle rate is not achieved, contact your HVAC service person.
TROUBLESHOOTING (C0ntinued)
Symptom Possible Cause Corrective Action
1.) Heating system is not able to heat the space to within 10 degrees of the setpoint within 2 hours
2.) Cooling system is not able to cool the space to within 10 degrees of
“Call for Service”
icon appears on displayed
the setpoint within 2 hours
3.) If “--” is displayed for the Room
Temperature, a replacement thermostat is needed
4.) None of the buttons operate on the thermostat
5.) If “Call for Service” is ashing,
compressor self diagnostic is detecting an issue with the outdoor unit
Resetting the Thermostat or Thermostat Settings
If the thermostat has good batteries, but has a blank display or does not respond to key presses, the thermostat should be reset by removing the batteries for 2 minutes. This reset will not change the menu settings or program. If the condition persists after reinstalling the batteries, replace the thermostat.
To conveniently reset only the schedule and user settings back to factory defaults, press Menu and Backlight buttons at the same time and hold until the display goes blank and resets.
HOMEOWNER HELP LINE: 1-800-284-2925
White-Rodgers is a business of Emerson Electric Co.
The Emerson logo is a trademark and service mark of Emerson Electric Co.
www.white-rodgers.com
www.emersonclimate.com
1.) See corrective action for “No Heat”
2.) See corrective action for “No Cool”
3.) Replace thermostat
4.) Make sure keypad lockout is not turned on ( ),
If it’s OFF, try reset shown below.
5.) Contact a service person to verify the outdoor equipment is operating correctly
Loading...
+ 8 hidden pages