White Rodgers 1F83-277 User Manual

Page 1
1F83-2771F83-277
1F83-277
1F83-2771F83-277
Heating & Air Conditioning
Non-programmable, Auto Changeover, Multi-Stage/Heat
Pump Thermostat
INSTALLATION INSTRUCTIONS
Operator: Save these instructions for future use!Operator: Save these instructions for future use!
Operator: Save these instructions for future use!
Operator: Save these instructions for future use!Operator: Save these instructions for future use!
FAILURE TO READ AND FOLLOW ALL INSTRUCTIONS CAREFULLY BEFOREFAILURE TO READ AND FOLLOW ALL INSTRUCTIONS CAREFULLY BEFORE
FAILURE TO READ AND FOLLOW ALL INSTRUCTIONS CAREFULLY BEFORE
FAILURE TO READ AND FOLLOW ALL INSTRUCTIONS CAREFULLY BEFOREFAILURE TO READ AND FOLLOW ALL INSTRUCTIONS CAREFULLY BEFORE INSTALLING OR OPERATING THIS CONTROL COULD CAUSE PERSONALINSTALLING OR OPERATING THIS CONTROL COULD CAUSE PERSONAL
INSTALLING OR OPERATING THIS CONTROL COULD CAUSE PERSONAL
INSTALLING OR OPERATING THIS CONTROL COULD CAUSE PERSONALINSTALLING OR OPERATING THIS CONTROL COULD CAUSE PERSONAL INJURY AND/OR PROPERTY DAMAGE.INJURY AND/OR PROPERTY DAMAGE.
INJURY AND/OR PROPERTY DAMAGE.
INJURY AND/OR PROPERTY DAMAGE.INJURY AND/OR PROPERTY DAMAGE.
PREPARATIONSPREPARATIONS
PREPARATIONS
PREPARATIONSPREPARATIONS
YOUR THERMOSTAT REPLACESYOUR THERMOSTAT REPLACES
YOUR THERMOSTAT REPLACES
YOUR THERMOSTAT REPLACESYOUR THERMOSTAT REPLACES
DescriptionDescription
Description
DescriptionDescription Heat Pump (No Aux. or Emergency Heat) Yes Heat Pump (with Aux. or Emergency Heat) Yes Standard Heat & Cooling Systems Yes Two Stage Heat & Two Stage Cool Yes Standard Heat Only Systems Yes Millivolt Heat Only Systems – Floor or Wall Furnaces Yes Standard Central Air Conditioning Yes Gas or Oil Heat Yes Electric Furnace Yes Hydronic (Hot Water) Zone Heat – 2 Wires Yes Hydronic (Hot Water) Zone Heat – 3 Wires No
Assemble tools required as shown below.
FLAT BLADE SCREWDRIVER
HAND OR POWER DRILL WITH 3/16 INCH DRILL BIT, IF NEEDED
SPIRIT LEVEL OR PLUMB BOB AND LINE OPTIONAL—
THERMOSTAT DOES NOT NEED TO BE LEVEL TO WORK PROPERLY
REMOVING OLD THERMOSTATREMOVING OLD THERMOSTAT
REMOVING OLD THERMOSTAT
REMOVING OLD THERMOSTATREMOVING OLD THERMOSTAT
WIRE CUTTER/STRIPPER
CAUTION
!
To prevent electrical shock and/or equipment dam-To prevent electrical shock and/or equipment dam-
To prevent electrical shock and/or equipment dam-
To prevent electrical shock and/or equipment dam-To prevent electrical shock and/or equipment dam­age, disconnect electric power to system at main fuseage, disconnect electric power to system at main fuse
age, disconnect electric power to system at main fuse
age, disconnect electric power to system at main fuseage, disconnect electric power to system at main fuse or circuit breaker box until installation is complete.or circuit breaker box until installation is complete.
or circuit breaker box until installation is complete.
or circuit breaker box until installation is complete.or circuit breaker box until installation is complete.
Before removing wires from old thermostat's switching sub-
label each wirelabel each wire
base,
label each wire with the terminal designation it was
label each wirelabel each wire
removed from.
1. Shut off electricity at the main fuse box until installation is complete. Ensure that electrical power is disconnected.
Remove Old ThermostatRemove Old Thermostat
2.
Remove Old Thermostat: A standard heat/cool
Remove Old ThermostatRemove Old Thermostat thermostat consists of three basic parts: a. The cover, which may be either a snap-on or
hinge type.
b. The base, which is removed by loosening all
captive screws.
c. The switching subbase, which is removed by
unscrewing the mounting screws that hold it on the wall or adaptor plate.
3. Remove the front cover of the old thermostat. wireswires
still attachedstill attached
wires
still attached, remove wall plate from the wall. If
wireswires
still attachedstill attached the old thermostat has a wall mounting plate, remove the thermostat and the wall mounting plate as an assembly.
4. Identify each wire attached to the old thermostat.
5. Disconnect the wires from the old thermostat one at a DO NOT LET WIRES FALL BACK INTO THEDO NOT LET WIRES FALL BACK INTO THE
time.
DO NOT LET WIRES FALL BACK INTO THE
DO NOT LET WIRES FALL BACK INTO THEDO NOT LET WIRES FALL BACK INTO THE
WALLWALL
WALL.
WALLWALL
6. Install new thermostat using the following procedures.
WithWith
With
WithWith
Y2
C R
E/W1
Y1
Mounting Hole
Figure 1 – Thermostat baseFigure 1 – Thermostat base
Figure 1 – Thermostat base
Figure 1 – Thermostat baseFigure 1 – Thermostat base
ATTENTION!ATTENTION!
ATTENTION! This product does not contain mercury. How-
ATTENTION!ATTENTION! ever, this product may replace a unit which contains mercury.
Do not open mercury cells. If a cell becomes damaged, do touch any spilled mercury. Wearing non-absorbent gloves, clean up the spilled mercury and place into a container which can be sealed. If a cell becomes damaged, the unit should be discarded.
Mercury must not be discarded in household trash. When the unit this product is replacing is to be discarded, place in a suitable container and return to White-Rodgers at 2895 Harrison Street, Batesville, AR 72501 for proper disposal.
OBLW2G
ELEC. GAS
AUTOON
Mounting Hole
Elec-Gas Switch
notnot
not
notnot
White-Rodgers is a division
of Emerson Electric Co.
www.white-rodgers.com
PART NO. 37-6509APART NO. 37-6509A
PART NO. 37-6509A
PART NO. 37-6509APART NO. 37-6509A
0405
Page 2
MOUNTING AND WIRINGMOUNTING AND WIRING
MOUNTING AND WIRING
MOUNTING AND WIRINGMOUNTING AND WIRING
WARNING
!
Do not use on circuits exceeding specified voltage.Do not use on circuits exceeding specified voltage.
Do not use on circuits exceeding specified voltage.
Do not use on circuits exceeding specified voltage.Do not use on circuits exceeding specified voltage. Higher voltage will damage control and could causeHigher voltage will damage control and could cause
Higher voltage will damage control and could cause
Higher voltage will damage control and could causeHigher voltage will damage control and could cause shock or fire hazard.shock or fire hazard.
shock or fire hazard.
shock or fire hazard.shock or fire hazard.
Do not short out terminals on gas valve or primaryDo not short out terminals on gas valve or primary
Do not short out terminals on gas valve or primary
Do not short out terminals on gas valve or primaryDo not short out terminals on gas valve or primary control to test. Short or incorrect wiring will damagecontrol to test. Short or incorrect wiring will damage
control to test. Short or incorrect wiring will damage
control to test. Short or incorrect wiring will damagecontrol to test. Short or incorrect wiring will damage thermostat and could cause personal injury and/orthermostat and could cause personal injury and/or
thermostat and could cause personal injury and/or
thermostat and could cause personal injury and/orthermostat and could cause personal injury and/or property damage.property damage.
property damage.
property damage.property damage.
Thermostat installation and all components of the system shall conform to Class II circuits per the NEC code.
Electric/Gas Switch (Fan Option)Electric/Gas Switch (Fan Option)
Electric/Gas Switch (Fan Option)
Electric/Gas Switch (Fan Option)Electric/Gas Switch (Fan Option)
The ELEC/GAS switch is factory set to the ELEC position. In this position, the thermostat will power the circulator fan on a call for heat. Electric heat systems require the switch to be in the ELEC position.
If your system does not require that the thermostat power the circulator fan, this switch should be set to the GAS position. Typically, gas and oil heating systems do not require the thermostat to power the circulator fan during a call for heat. If your heat is gas or oil, the switch should be set to the GAS position.
When the thermostat is configured for Heat Pump, the thermo­stat will always power the circulator fan on a call for heat in the HEAT mode. The ELEC/GAS switch must be set to match the type of Auxiliary heat your system uses for proper operation in the EMERgency mode.
All wiring diagrams are for typical systems only. Refer to equipment manufacturers' instructions for specific system wir­ing information.
CAUTION
!
Take care when securing and routing wires so they doTake care when securing and routing wires so they do
Take care when securing and routing wires so they do
Take care when securing and routing wires so they doTake care when securing and routing wires so they do not short to adjacent terminals or rear of thermostat.not short to adjacent terminals or rear of thermostat.
not short to adjacent terminals or rear of thermostat.
not short to adjacent terminals or rear of thermostat.not short to adjacent terminals or rear of thermostat. Personal injury and/or property damage may occur.Personal injury and/or property damage may occur.
Personal injury and/or property damage may occur.
Personal injury and/or property damage may occur.Personal injury and/or property damage may occur.
Attach Thermostat Base to WallAttach Thermostat Base to Wall
Attach Thermostat Base to Wall
Attach Thermostat Base to WallAttach Thermostat Base to Wall
1. Remove the packing material from the thermostat. Gently pull the cover straight off the base. Forcing or prying on the thermostat will cause damage to the unit.
2. Connect wires beneath terminal screws on base using appropriate wiring schematic (see figs. 2 through 4).
3. Place base over hole in wall and mark mounting hole locations on wall using base as a template.
4. Move base out of the way. Drill mounting holes.
5. Fasten base loosely to wall, as shown in fig. 1, using two mounting screws. Place a level against bottom of base, adjust until level, and then tighten screws. (Leveling is for appearance only and will not affect thermostat operation.) If you are using existing mounting holes, or if holes drilled are too large and do not allow you to tighten base snugly, use plastic screw anchors to secure subbase.
6. Push excess wire into wall and plug hole with a fire­resistant material (such as fiberglass insulation) to prevent drafts from affecting thermostat operation.
Battery LocationBattery Location
Battery Location
Battery LocationBattery Location
2 "AA" alkaline batteries are included in the thermostat at the factory with a battery tag to prevent power drainage. You must remove the battery tag to engage the batteries.
If BATT is displayed, the batteries are low and should be replaced with fresh "AA" Energizer® alkaline batteries. To replace batteries, set system to OFF, install the batteries along the top of the base (see Fig. 1). The batteries must be installed with the positive (+) end to the left.
O
Reversing Valve
Energized in Cool
Mode
CUT AND
TAPE OFF!
HOT
120 VAC
NEUTRAL
2
E/W1
Reversing Valve
Energized in Heat,
Off, Emergency
Reversing
Energized in
24 VAC
Cool Mode
B
Mode
Figure 2. Typical wiring diagram for single transformer heat pump systems
O
Reversing
Valve
Energized in
Heat, Off,
Emergency
Compressor
B
Valve
Mode
Y2
2nd Stage
2nd Stage
Compressor
G W2
Compressor
Contactor
If safety circuits are in only one of the systems, remove the transformer of the system with NO safety circuits.
Y2
Compressor
Contactor
Fan
Relay
NOTE
G W2
Fan
Relay
Aux
Relay
(Stage 2)
Aux
Relay
(Stage 2)
TWO COMMONS MUST BE JUMPERED TOGETHER!
Emergency
or 1st Aux.
E/W1
Emergency
or 1st Aux.
Stage Relay
Stage Relay
CY1
CY1
SYSTEM
MONITOR
SWITCH
SYSTEM
MONITOR
SWITCH
24 VAC
(Class II Current Limited)
L
Limit or
Safety
Switches
Figure 3. Typical wiring diagram for two transformer heat pump systems with NO safety circuits
L
THERMOSTAT
R
SYSTEM
Hot
120 VAC
TRANSFORMER
THERMOSTAT
R
24 VAC
(Class II Current Limited)
Neutral
SYSTEM
TRANSFORMER
Hot
120 VAC
Neutral
Page 3
WIRING DIAGRAMSWIRING DIAGRAMS
WIRING DIAGRAMS
WIRING DIAGRAMSWIRING DIAGRAMS
Polarity must be observed. If the HOT side of the second transformer is jumpered to the COMMON side of the first transformer a short will be made. Damage to equipment will occur when power is restored.
O
Reversing
Valve
Energized in
Cool Mode
B
Reversing
Valve
Energized in
Heat, Off,
Emergency
Mode
Y2
2nd Stage
Compressor
Compressor
Contactor
G W2
Fan
Relay
Aux
Relay
(Stage 2)
E/W1
Emergency
or 1st Aux.
Stage Relay
TWO COMMONS MUST BE JUMPERED TOGETHER!
Figure 4. Typical wiring diagram for two transformer heat pump systems with safety circuits in BOTH systems
Heat Pump Terminal OutputsHeat Pump Terminal Outputs
Heat Pump Terminal Outputs
Heat Pump Terminal OutputsHeat Pump Terminal Outputs
Refer to equipment manufacturers' instructions for specific system wiring information.
You can configure the thermostat for use with the following heat pump system types: HEAT PUMP TYPE 1HEAT PUMP TYPE 1
HEAT PUMP TYPE 1. Single stage compressor system; gas
HEAT PUMP TYPE 1HEAT PUMP TYPE 1 or electric backup.
This thermostat is designed to operate a single-transformer system. If you have a two-transformer system, cut and tape off
NOTE
CY1
SYSTEM
MONITOR
SWITCH
L
COMMON
R
Switches
Limit or
Safety
Switches
Limit or
Safety
ACCESSORY
RELAY N.O.
CONTACT
THERMOSTAT
SYSTEM
24 VAC
24 VAC
COMMON
24 VAC 120 VAC
Heat Pump Transformer
(Class II Current Limited)
Auxiliary
Heating
Transformer
(Class II
Current Limited)
Limit or
Safety
Switches
120 VAC
The accessory relay scheme is required when safety circuits exist in both systems.
Limit or
Safety
Switches
HOT
NEUTRAL
NOTE
HOT
NEUTRAL
one transformer. If transformer safety circuits are in only one of the systems, remove the transformer of the system with NO safety circuits. If required, replace remaining transformer with a 75VA Class II transformer. After disconnecting one trans­former, the two commons must be jumpered together.
Use the terminal output information below to help you wire the thermostat properly for your multi-stage system. After wiring,
CONFIGURATION CONFIGURATION
see
CONFIGURATION section for proper thermostat configu-
CONFIGURATION CONFIGURATION
ration.
THERMOSTAT TERMINALS (HEAT PUMP)THERMOSTAT TERMINALS (HEAT PUMP)
THERMOSTAT TERMINALS (HEAT PUMP)
THERMOSTAT TERMINALS (HEAT PUMP)THERMOSTAT TERMINALS (HEAT PUMP)
SYSTEMSYSTEM
SYSTEM
SYSTEMSYSTEM
LL
L
LL
CC
C
CC
RR
R
RR
W2W2
W2
W2W2
E/W1E/W1
E/W1
E/W1E/W1
Y2Y2
Y2
Y2Y2
Y1Y1
Y1
Y1Y1
GG
G
GG
OO
O
OO
BB
B
BB
Heat Malfunction 24 Volt 24 Volt Heat Mode Heat mode No Heat and Blower/Fan Energized Energized Energized Pump 1 Light (Common) (Hot) 3rd stage 2nd stage Output Cool mode on call for Heat in Cool in Heat
Emergency or 1st stage and Cool Mode OFF Heat mode Emergency 2nd (compressor) Set GAS/ELEC switch Emergency Pump 2 2nd stage Mode stage for Emergency mode mode
1st stage compressor
O
Reversing
Valve
Energized in
Cool Mode
B
Reversing
Valve
Energized in
Heat Mode
Off Emergency
Y1
Compressor
Contactor
Stage 1
Y2
Compressor
Contactor
Stage 2
G
Fan
Relay
E/W1
Heat
Relay
Stage 1
W2
Heat
Relay
Stage 2
C R
THERMOSTAT
SYSTEM
Hot
24 VAC 120 VAC
Neutral
TRANSFORMER
(Class II, Current Limited)
Figure 5. Typical wiring diagram for single transformer multi-stage systems
3
Page 4
Multi-Stage Terminal OutputsMulti-Stage Terminal Outputs
Multi-Stage Terminal Outputs
Multi-Stage Terminal OutputsMulti-Stage Terminal Outputs
Refer to equipment manufacturers' instructions for specific system wiring information.
You can configure the thermostat for use with either multi-stage electric heat systems or multi-stage gas systems. When con­figured for energized on a call for heat.
This thermostat is designed to operate a single-transformer system. If you have a two-transformer system, cut and tape off
SYSTEMSYSTEM
SYSTEM
SYSTEMSYSTEM
Multi-stage Malfunction 24 Volt 24 Volt Heat Mode Heat mode Cool Mode Cool Mode Blower/Fan Energized Energized Energized
CHECK THERMOSTAT OPERATIONCHECK THERMOSTAT OPERATION
CHECK THERMOSTAT OPERATION
CHECK THERMOSTAT OPERATIONCHECK THERMOSTAT OPERATION
electric electric
electric heat, the
electric electric
LL
L
LL
Light (Common) (Hot) 2nd stage 1st stage 2nd stage 1st stage on call for Cool (and in Cool in Heat, Off,
GG
G terminal (blower/fan) will be
GG
THERMOSTAT TERMINALS (MULTI-STAGE)THERMOSTAT TERMINALS (MULTI-STAGE)
THERMOSTAT TERMINALS (MULTI-STAGE)
THERMOSTAT TERMINALS (MULTI-STAGE)THERMOSTAT TERMINALS (MULTI-STAGE)
CC
C
CC
RR
R
RR
W2W2
W2 E
W2W2
/W1/W1
/W1
/W1/W1
NOTE
To prevent static discharge problems, touch side ofTo prevent static discharge problems, touch side of
To prevent static discharge problems, touch side of
To prevent static discharge problems, touch side ofTo prevent static discharge problems, touch side of thermostat to release static build-up before touchingthermostat to release static build-up before touching
thermostat to release static build-up before touching
thermostat to release static build-up before touchingthermostat to release static build-up before touching any keys.any keys.
any keys.
any keys.any keys.
If at any time during testing your system does not operate properly, contact a qualified serviceperson.
Fan OperationFan Operation
Fan Operation
Fan OperationFan Operation
If your system does not have a Heating SystemHeating System
Heating System.
Heating SystemHeating System
1. Turn on power to system.
2. Move fan switch to to operate.
3. Move fan switch to stop immediately.
ON ON
ON position. The blower should begin
ON ON
AUTO AUTO
AUTO position. The blower should
AUTO AUTO
!
Do not allow the compressor to run unless the com-Do not allow the compressor to run unless the com-
Do not allow the compressor to run unless the com-
Do not allow the compressor to run unless the com-Do not allow the compressor to run unless the com­pressor oil heaters have been operational for 6 hourspressor oil heaters have been operational for 6 hours
pressor oil heaters have been operational for 6 hours
pressor oil heaters have been operational for 6 hourspressor oil heaters have been operational for 6 hours and the system has not been operational for at leastand the system has not been operational for at least
and the system has not been operational for at least
and the system has not been operational for at leastand the system has not been operational for at least 5 minutes.5 minutes.
5 minutes.
5 minutes.5 minutes.
Heating SystemHeating System
Heating System
Heating SystemHeating System
1. Press SYSTEM button to select the the auxiliary heating system has a standing pilot, be sure to light it.
2. Press temperature. The heat pump system should begin to operate. The display should show STG1. However, if the set point temperature display is flashing, the compressor lockout feature is operating (see Configuration menu, item 5).
3. Adjust temperature setting to 3° above room temperature. If your system configuration is set at MS2, HP2 or HP1, the auxiliary heat system should begin to operate and the display should show STG 1+2.
4. Press ture. The heating system should stop operating.
to adjust thermostat setting to 1° above room
to adjust the thermostat below room tempera-
G G
G terminal connection, skip to
G G
CAUTION
Flame iconFlame icon
Flame icon ( ). If
Flame iconFlame icon
one transformer. If transformer safety circuits are in only one of the systems, remove the transformer of the system with NO safety circuits. If required, replace remaining transformer with a 75VA Class II transformer. After disconnecting one trans­former, the two commons must be jumpered together.
Use the terminal output information below to help you wire the thermostat properly for your multi-stage system. After wiring,
CONFIGURATION CONFIGURATION
see
CONFIGURATION section for proper thermostat configu-
CONFIGURATION CONFIGURATION
ration.
Y2Y2
Y2
Y2Y2
EMER bypasses the Heat Pump to use the heat source wired to terminal E on the thermostat. EMER is typically used when compressor operation is not desired, or you prefer back-up heat only.
1. Press SYSTEM button to select EMER. EMER will flash on the display.
2. Press to adjust thermostat setting above room temperature. The Aux. heating system will begin to operate. The display will show STG1 flashing EMER
and flame icon ( operating.
3. Adjust temperature setting to 3° above room temperature. The auxiliary heat system should begin to operate and the display should show STG 1+2.
4. Press ture. The Aux. heating system should stop operating.
To prevent compressor and/or property damage, ifTo prevent compressor and/or property damage, if
To prevent compressor and/or property damage, if
To prevent compressor and/or property damage, ifTo prevent compressor and/or property damage, if the outdoor temperature is below 50°F, DO NOTthe outdoor temperature is below 50°F, DO NOT
the outdoor temperature is below 50°F, DO NOT
the outdoor temperature is below 50°F, DO NOTthe outdoor temperature is below 50°F, DO NOT operate the cooling system.operate the cooling system.
operate the cooling system.
operate the cooling system.operate the cooling system.
1. Press SYSTEM button to select the
2. Press temperature. The blower should come on immediately on high speed, followed by cold air circulation. The display should show STG1.
3. Adjust temperature setting to 3° below room temperature. The second stage cooling should begin to operate and the display should show STG 1+2.
4. Press temperature. The cooling system should stop operating.
Y1Y1
Y1
Y1Y1
Emergency SystemEmergency System
Emergency System
Emergency SystemEmergency System
) to indicate that the Aux. system is
to adjust the thermostat below room tempera-
!
Cooling SystemCooling System
Cooling System
Cooling SystemCooling System
to adjust thermostat setting below room
to adjust the temperature setting above room
GG
G
GG
Heat if configured Mode Emergency
to Electric Heat) Modes
OO
O
OO
BB
B
BB
CAUTION
Snowflake iconSnowflake icon
Snowflake icon ( ).
Snowflake iconSnowflake icon
4
Page 5
Before you begin programming your thermostat, you should be familiar with its features and with the display and the location and operation of the thermostat buttons. Your thermostat consists of two parts: the thermostat cover and the base. To remove the cover, pull it straight out from the base. To replace the cover, line up the cover with the base and press until the cover snaps onto the base.
The Thermostat Buttons and SwitchesThe Thermostat Buttons and Switches
The Thermostat Buttons and Switches
The Thermostat Buttons and SwitchesThe Thermostat Buttons and Switches
Raises temperature setting
1
Lowers temperature setting.
2
ONON
FAN switch (
3
ON,
ONON
AUTOAUTO
AUTO)
AUTOAUTO
OPERATIONOPERATION
OPERATION
OPERATIONOPERATION
SYSTEM button (
4
Flame iconFlame icon
Flame icon ( ) is displayed when the system is in
Flame iconFlame icon
5
HEAT HEAT
HEAT mode.
HEAT HEAT the system is in
Snowflake icon Snowflake icon
Snowflake icon (
Snowflake icon Snowflake icon when thermostat is in
Displays
6
should be replaced. Only when batteries are low with no system power.
Displays current temperature or
7
are low. Displays currently programmed set temperature (this
8
is blank when SYSTEM is OFF). Displays
9
programmed filter time period as a reminder to change or clean your filter.
Display ( ) when in keypad lockout mode.
10
BATT BATT
BATT when the 2 "AA" batteries are low and
BATT BATT
FLTR FLTR
FLTR when the system has run for the
FLTR FLTR
COOLCOOL
COOL,
COOLCOOL
The DisplayThe Display
The Display
The DisplayThe Display
Snowflake icon Snowflake icon
Snowflake icon (
Snowflake icon Snowflake icon
COOL COOL
COOL mode.
COOL COOL
AUTOAUTO
AUTO,
AUTOAUTO
) are displayed simultaneously
AUTO AUTO
AUTO mode.
AUTO AUTO
HEATHEAT
HEAT,
HEATHEAT
) is displayed when
Flame iconFlame icon
Flame icon ( ) and
Flame iconFlame icon
BATT BATT
BATT and
BATT BATT
LO LO
LO are displayed
LO LO
LO LO
LO when batteries
LO LO
EMEREMER
EMER,
EMEREMER
OFFOFF
OFF)
OFFOFF
STG1+2
EMER
Figure 6 – Thermostat display, buttons and switchesFigure 6 – Thermostat display, buttons and switches
Figure 6 – Thermostat display, buttons and switches
Figure 6 – Thermostat display, buttons and switchesFigure 6 – Thermostat display, buttons and switches
EMER EMER
EMER is displayed flashing when the system is in
EMER EMER
11
EMER mode. Indicates a fault in the heating/cooling system. It does
12
not indicate a fault in the thermostat. Display ( ) when limited range is activated.
13
Stage1 & 2Stage1 & 2
Stage1 & 2 indicators: The thermostat shall indicate
Stage1 & 2Stage1 & 2
14
when the first and second stage is energized except in emergency mode. The icon is stage energized. The icons for the first and second stage energized are right side of the display.
STG1+2STG1+2
STG1+2 located in the upper
STG1+2STG1+2
CONFIGURATION MENUCONFIGURATION MENU
CONFIGURATION MENU
CONFIGURATION MENUCONFIGURATION MENU
FAULT
STG 1STG 1
STG 1 for the first
STG 1STG 1
The configuration menu allows you to set certain thermostat operating characteristics to your system or personal require­ments.
SYSTEM SYSTEM
Set
SYSTEM button to
SYSTEM SYSTEM
and to enter configuration menu. The display will
show the first item in the configuration menu.
The configuration menu table summarizes the configuration options. An explanation of each option follows.
SYSTEM SYSTEM
Press
SYSTEM to change to the next menu item. To exit the
SYSTEM SYSTEM menu and return to the program operation, press keys are pressed within fifteen minutes, the thermostat will revert to normal operation.
Single Stage, Multi-stage or Heat Pump SystemSingle Stage, Multi-stage or Heat Pump System
1)
Single Stage, Multi-stage or Heat Pump System
Single Stage, Multi-stage or Heat Pump SystemSingle Stage, Multi-stage or Heat Pump System ConfigurationConfiguration
Configuration – This control can be configured for Heat
ConfigurationConfiguration Pump or two stage heat/two stage cool multi-stage opera­tion. The display indicates mode) in the display. The Multi-stage configuration can be
SS1SS1
toggled to ture Upture Up
ture Up or
ture Upture Up ration, system button will not have
HP2HP2
SS1,
HP2, or
SS1SS1
HP2HP2
Temperature DownTemperature Down
Temperature Down key. In Multi-stage configu-
Temperature DownTemperature Down
OFFOFF
OFF, then simultaneously press
OFFOFF
RUNRUN
RUN. If no
RUNRUN
MS 2MS 2
MS 2 (default for multi-stage
MS 2MS 2
HP1HP1
HP1 by pressing the
HP1HP1
EMEREMER
EMERgency mode.
EMEREMER
Tempera-Tempera-
Tempera-
Tempera-Tempera-
Fast or Slow Cycle SelectionFast or Slow Cycle Selection
2)
Fast or Slow Cycle Selection – The factory default setting
Fast or Slow Cycle SelectionFast or Slow Cycle Selection is fast cycle, which cycles 1st stage at approximately 1.2°F and 2nd stage 0.75°F. If you prefer slow cycle, press the temperature key to change to SL. The 1st stage and 2nd stage would be 1.5°F and 1.2°F respectively.
Select Compressor Lockout CL OFF or ONSelect Compressor Lockout CL OFF or ON
3)
Select Compressor Lockout CL OFF or ON – Selecting
Select Compressor Lockout CL OFF or ONSelect Compressor Lockout CL OFF or ON CL ON will cause the thermostat to wait 5 minutes before turning on the compressor if the heating and cooling system loses power. It will also wait 5 minutes minimum between cooling and heating cycles. This is intended to help protect the compressor from short cycling. Some newer compres­sors already have a time delay built in and do not require this feature. Your compressor manufacturer can tell you if the lockout feature is already present in their system. When the thermostat compressor time delay occurs it will flash the setpoint for about five minutes.
5
Page 6
CONFIGURATION MENUCONFIGURATION MENU
CONFIGURATION MENU
CONFIGURATION MENUCONFIGURATION MENU
StepStep
Step
StepStep
1
2 3
4
5
6 7
8 9
10
11
12 13
14
Press the System button until
INSTALLER/CONFIGURATION MENUINSTALLER/CONFIGURATION MENU
INSTALLER/CONFIGURATION MENU
INSTALLER/CONFIGURATION MENUINSTALLER/CONFIGURATION MENU
PressPress
Press
PressPress
Button(s)Button(s)
Button(s)
Button(s)Button(s)
SystemSystem
System
SystemSystem
SystemSystem
System
SystemSystem SystemSystem
System
SystemSystem
SystemSystem
System
SystemSystem
SystemSystem
System
SystemSystem
SystemSystem
System
SystemSystem SystemSystem
System
SystemSystem
SystemSystem
System
SystemSystem SystemSystem
System
SystemSystem
SystemSystem
System
SystemSystem
SystemSystem
System
SystemSystem
SystemSystem
System
SystemSystem
SystemSystem
System Returns to the OFF position
SystemSystem
DisplayedDisplayed
Displayed
DisplayedDisplayed
(Factory Default)(Factory Default)
(Factory Default)
(Factory Default)(Factory Default)
MS 2MS 2
MS 2
MS 2MS 2
FAFA
FA
FAFA
CLCL
CL
CLCL
(OFF)(OFF)
(OFF)
(OFF)(OFF)
CDLCDL
CDL
CDLCDL
(ON)(ON)
(ON)
(ON)(ON)
FAFA
FA
FAFA
(ON)(ON)
(ON)
(ON)(ON)
0 FLTR0 FLTR
0 FLTR
0 FLTR0 FLTR
0°F0°F
0°F
(Room Temperature)
0°F0°F
°F°F
°F
°F°F
LRLR
LR
LRLR
(90)(90)
(90)
(90)(90)
LRLR
LR
LRLR
(45)(45)
(45)
(45)(45)
CACA
CA
CACA
(OFF)(OFF)
(OFF)
(OFF)(OFF) (OFF)(OFF)
(OFF)
(OFF)(OFF)
00
0
00
OFF OFF
OFF is displayed, then press the and simultaneously
OFF OFF
Press Press
Press
Press Press
SS1, HP2, HP1SS1, HP2, HP1
SS1, HP2, HP1 Selects Single stage, Multi-stage, or Heat Pump
SS1, HP2, HP1SS1, HP2, HP1
50-195050-1950
50-1950 (increments of 50) Selects filter replacement run time
50-195050-1950
LR 62 to LR89LR 62 to LR89
LR 62 to LR89 Selects Limited
LR 62 to LR89LR 62 to LR89
LR 46 to LR 82LR 46 to LR 82
LR 46 to LR 82 Selects Limited COOL range
LR 46 to LR 82LR 46 to LR 82
or or
or
or or
to selectto select
to select
to selectto select
(Single stage or 2-stage) System Configuration
SLSL
SL Selects Fast or Slow Cycle Selection
SLSL CLCL
CL Selects Compressor Lockout
CLCL
(ON)(ON)
(ON)
(ON)(ON)
CDLCDL
CDL Selects Backlight Display
CDLCDL
(OFF)(OFF)
(OFF)
(OFF)(OFF)
FAFA
FA Selects Fast Second Stage
FAFA
(OFF)(OFF)
(OFF)
(OFF)(OFF)
4 LO to 4 HI4 LO to 4 HI
4 LO to 4 HI Selects Temperature Display Adjustment
4 LO to 4 HI4 LO to 4 HI
°C°C
°C For
°C°C
CACA
CA Feature Not Available
CACA
(ON)(ON)
(ON)
(ON)(ON) (ON)(ON)
(ON) Selects Keypad Lockout
(ON)(ON)
001 to 999001 to 999
001 to 999 Selects Keypad lockout combination number
001 to 999001 to 999
CommentsComments
Comments
CommentsComments
CL OFFCL OFF
CL OFF or
CL OFFCL OFF
ON ON
ON or
ON ON
°C°C
°C selection
°C°C
HEAT HEAT
HEAT range
HEAT HEAT
Press System to set code
ONON
ON
ONON
OFFOFF
OFF
OFFOFF
4 LO4 LO
4 LO to
4 LO4 LO
4 HI4 HI
4 HI
4 HI4 HI
Select Backlight DisplaySelect Backlight Display
4)
Select Backlight Display – The display backlight improves
Select Backlight DisplaySelect Backlight Display display contrast in low lighting conditions. When the "C" terminal is powered, selecting backlight CdL ON will keep the light on continuously. Select backlight OFF will keep the light on momentarily after any key is pressed. When the "C" terminal is not powered, the light will be on momentarily after any key is pressed no matter the backlight is selected ON or OFF.
Select (Fast) Second Stage ON or OFFSelect (Fast) Second Stage ON or OFF
5)
Select (Fast) Second Stage ON or OFF – In the run mode,
Select (Fast) Second Stage ON or OFFSelect (Fast) Second Stage ON or OFF if the setpoint temperature is manually raised by 3°F (2°C) or more above the actual temperature with the fast second stage feature is enabled, FA ON, the second stage will energize immediately. With FA OFF, second stage will not energize until the setpoint temperature is 1°F or more above actual temperature for more than ten min­utes.
Select filter replacement run timeSelect filter replacement run time
6)
Select filter replacement run time – The thermostat will
Select filter replacement run timeSelect filter replacement run time
FLTR FLTR
display
FLTR after a set time of operation. This is a remind-
FLTR FLTR er to change or clean your air filter. This time can be set from 0 to 1950 hours in 50 hour increments. will cancel this featurewill cancel this feature
will cancel this feature. When
will cancel this featurewill cancel this feature clear it by pressing
HOLD HOLD
HOLD and
HOLD HOLD
FLTR FLTR
FLTR is displayed, you can
FLTR FLTR
RUN RUN
RUN at the same time. This
RUN RUN
A selection of 000A selection of 000
A selection of 000
A selection of 000A selection of 000
resets the timer and starts counting the hours until the next filter change. Contact your system manufacturer for a specific replacement/maintenance interval.
, and the
Select Temperature Display Adjustment 4 LO to 4 HISelect Temperature Display Adjustment 4 LO to 4 HI
7)
Select Temperature Display Adjustment 4 LO to 4 HI –
Select Temperature Display Adjustment 4 LO to 4 HISelect Temperature Display Adjustment 4 LO to 4 HI Allows you to adjust the room temperature display up to 4° higher or lower. Your thermostat was accurately calibrated at the factory but you have the option to change the display temperature to match your previous thermostat. The cur­rent or adjusted room temperature will be displayed on the left side of the display.
Select F° or C° Readout Select F° or C° Readout
8)
Select F° or C° Readout – Changes the display readout
Select F° or C° Readout Select F° or C° Readout
to Centigrade or Fahrenheit as required.
Limited Heat Range Limited Heat Range
9)
Limited Heat Range – This feature provides a maximum
Limited Heat Range Limited Heat Range
setpoint temperature for heat. The default setting is 90°F. It can be changed between 62°F and 89°F by pressing the temperature uptemperature up
temperature up or
temperature uptemperature up
Limited Cool RangeLimited Cool Range
10)
Limited Cool Range – This feature provides a minimum
Limited Cool RangeLimited Cool Range
temperature downtemperature down
temperature down key.
temperature downtemperature down
setpoint temperature for cool. The default setting is 45°F. It can be changed between 46°F and 82°F by pressing the temperature up or temperature down key.
This feature not availableThis feature not available
11)
This feature not available.
This feature not availableThis feature not available
6
Page 7
CONFIGURATION MENUCONFIGURATION MENU
CONFIGURATION MENU
CONFIGURATION MENUCONFIGURATION MENU
12 & 13)
ELECTRICAL DATAELECTRICAL DATA
ELECTRICAL DATA
ELECTRICAL DATAELECTRICAL DATA
Electrical RatingElectrical Rating
Electrical Rating:
Electrical RatingElectrical Rating
Keypad LockoutKeypad Lockout
Keypad Lockout – This menu selection will display
Keypad LockoutKeypad Lockout
lock lock
lock icon. The
lock lock display the default) indicating in the time digits to the (keypad locked out). When the keypad lockout function is enabled ( display will indicate the number the time digits. The and are used to set the combina­tion number from If a combination of pressed the menu will be exited and keypad lockout will not be evoked. If pressed again, the combination is locked into non-volatile memory and the menu is exited. The keypad locked with a valid combination) will display when the menu is exited. The system key will operate for 10 seconds after the menu mode is exited to allow the user to change the mode from
20 to 30 VAC 50/60 Hz or DC
0.05 to 1.5 Amps (Load per terminal)
2.5 Amps Maximum Total Load (All terminals combined)
and are used to toggle the function and
lock lock
lock icon and
lock lock
ONON
ON), and the
ONON
00
0 to
00
1 to 9991 to 999
1 to 999 is selected and the
1 to 9991 to 999
OFF OFF
OFF (keypad not locked out,
OFF OFF
lock lock
lock icon and
lock lock
SYSTEM SYSTEM
SYSTEM key is pressed again, the
SYSTEM SYSTEM
0 0
0 (default, still disabled) in
0 0
999999
00
999. "
0" will not be a valid combination.
999999
00
00
0 is selected and the system key is
00
lock lock
lock icon (to designate
lock lock
OFF OFF
OFF to the desired system mode.
OFF OFF
SYSTEM SYSTEM
SYSTEM key is
SYSTEM SYSTEM
While the keypad is locked out, a simultaneous press of the temperature mode instead of only
ONON
ON
ONON
entered with the keypad lockout feature enabled, the menu item displayed is the combination code
keys are used to set the combination unlock number
00
from
0 to
00 combination lock number stored in memory when the SYSTEM SYSTEM
SYSTEM key is pressed, the keypad is unlocked and the
SYSTEM SYSTEM lock lock
lock icon is removed. If the unlock number does not match
lock lock when the keypad remains disabled.
To reset the combination code and unlock the keypad if the code is forgotten, see troubleshooting section.
THERMAL DATATHERMAL DATA
THERMAL DATA
THERMAL DATATHERMAL DATA
Setpoint Temperature RangeSetpoint Temperature Range
Setpoint Temperature Range:
Setpoint Temperature RangeSetpoint Temperature Range
45°F to 90°F (7°C to 32°C)
Operating Ambient Temperature RangeOperating Ambient Temperature Range
Operating Ambient Temperature Range:
Operating Ambient Temperature RangeOperating Ambient Temperature Range
32°F to 105°F
Operating Humidity RangeOperating Humidity Range
Operating Humidity Range:
Operating Humidity RangeOperating Humidity Range
0 to 90% RH (non-condensing)
Shipping Temperature RangeShipping Temperature Range
Shipping Temperature Range:
Shipping Temperature RangeShipping Temperature Range
-40°F to 150°F
and will enter the menu item from any
OFF modeOFF mode
OFF mode. When the menu is
OFF modeOFF mode
999999
99 9. If the unlock number matches exactly with the
999999
SYSTEM SYSTEM
SYSTEM key is pressed, menu is exited and the
SYSTEM SYSTEM
first
00
0. The or
00
SPECIFICATIONSSPECIFICATIONS
SPECIFICATIONS
SPECIFICATIONSSPECIFICATIONS
The system "mode" is selected by pressing the SYSTEM button. Icons on the bottom right corner of the display will indicate the mode:
OFFOFF
or
OFF. In any mode except
OFFOFF be shown on the right side of the display. In be blank. The current temperature will be displayed on the left side of the display.
To operate properly in the temperature cannot be the same as or higher than the cool setpoint temperature. The heat setpoint must be at least 1° lower than the cool setpoint.
Automatic System ChangeoverAutomatic System Changeover
Automatic System Changeover
Automatic System ChangeoverAutomatic System Changeover
When the thermostat is in the Snowflake Snowflake
Snowflake icons are displayed. The thermostat will call for heat
Snowflake Snowflake or cool depending on the room temperature. The setpoint temperature displayed will be that of the last mode called. If the last system cycle was heat, the If the room temperature raises above the COOL COOL
COOL setpoint and a call for cool is required, the temperature
COOL COOL displayed will change to be the
COOL COOL
COOL (
COOL COOL
AUTO AUTO
),
AUTO ( ),
AUTO AUTO
OFFOFF
OFF, the setpoint temperature will
OFFOFF
AUTO AUTO
AUTO mode, the heat setpoint
AUTO AUTO
AUTO AUTO
AUTO mode, both the
AUTO AUTO
HEAT HEAT
HEAT setpoint will be displayed.
HEAT HEAT
COOL COOL
COOL setpoint.
COOL COOL
HEAT HEAT
HEAT ( ),
HEAT HEAT
OFFOFF
OFF, this area will
OFFOFF
HEAT HEAT
HEAT setpoint and the
HEAT HEAT
EMEREMER
EMER,
EMEREMER
Flame Flame
Flame and
Flame Flame
OPERATIONOPERATION
OPERATION
OPERATIONOPERATION
Second Stage Time DelaySecond Stage Time Delay
Second Stage Time Delay
Second Stage Time DelaySecond Stage Time Delay
Your thermostat is designed to determine the optimum time to activate the second stage. Simply raising the temperature in heating or lowering it in cooling will not always force the thermostat to bring the second stage on quickly. There is a time delay from 0-30 minutes depending on the performance of the first stage of the system.
EXAMPLE: For the last 2 hours the thermostat is set on 70° and the room temperature is 70° with the equipment using only the first stage of heat. Since the equipment is keeping the tempera­ture within 1 degree of setpoint, the thermostat will delay second stage for a longer time if you manually raise the temperature or if the room temperature quickly changes. Once the second stage comes on, it will come on sooner the next time there is a difference between the setpoint and the room temperature. The net effect of the staging program is that when the first stage is capable of making temperature the second stage will delay longer. When the thermostat calculates that first stage cannot make temperature in a reasonable time, the second stage will come on sooner. This built in function automatically optimizes the use of additional stages of heat or cool.
7
Page 8
TROUBLESHOOTINGTROUBLESHOOTING
TROUBLESHOOTING
TROUBLESHOOTINGTROUBLESHOOTING
Reset OperationReset Operation
Reset Operation
Reset OperationReset Operation
If a voltage spike or static discharge blanks out the display or causes erratic thermostat operation, you can reset the thermostat by removing the wires from terminals R and C and removing batteries for 2 minutes. After resetting the thermo­stat, replace the wires and batteries. If the thermostat has been reset and still does not function correctly contact your heating/cooling service person or place of purchase.
SymptomSymptom
Symptom
SymptomSymptom
No Heat/No Cool/No FanNo Heat/No Cool/No Fan
No Heat/No Cool/No Fan
No Heat/No Cool/No FanNo Heat/No Cool/No Fan (common problems)(common problems)
(common problems)
(common problems)(common problems)
No HeatNo Heat
No Heat
No HeatNo Heat
Possible CausePossible Cause
Possible Cause
Possible CausePossible Cause
1. Blown fuse or tripped circuit breaker.
2. Furnace power switch to OFF.
3. Furnace blower compartment door or panel loose or not properly installed.
1. Pilot light not lit.
2. System Switch not set to HEAT.
3. Loose connection to thermostat or system.
4. Furnace Lock-Out Condition. Heat may also be intermittent.
5. Heating system requires service or thermostat requires replacement.
Corrective ActionCorrective Action
Corrective Action
Corrective ActionCorrective Action
Replace fuse or reset breaker. Turn switch to ON. Replace door panel in proper position to engage safety interlock or door switch.
Re-light pilot. Set System Switch to HEAT and raise setpoint above room temperature. Verify thermostat and system wires are securely attached. Many furnaces have safety devices that shut down when a lock-out condition occurs. If the heat works intermittently contact the furnace manufacturer or local service person for assistance. Diagnostic: Set System Switch to HEAT and raise the setpoint above room temperature. Within a few seconds the thermostat should make a soft click sound. This sound usually indicates the thermostat is operating properly. If the thermostat does not click, try the reset operation listed above. If the thermostat does not click after being reset contact your heating and cooling service person or place of purchase for a replacement. If the thermostat clicks, contact the furnace manufacturer or a service person to verify the heating is operating correctly.
No CoolNo Cool
No Cool
No CoolNo Cool
Heat, Cool or FanHeat, Cool or Fan
Heat, Cool or Fan
Heat, Cool or FanHeat, Cool or Fan Runs ConstantlyRuns Constantly
Runs Constantly
Runs ConstantlyRuns Constantly
FurnaceFurnace
Furnace
FurnaceFurnace (Air Conditioner)(Air Conditioner)
(Air Conditioner)
(Air Conditioner)(Air Conditioner) Cycles Too FastCycles Too Fast
Cycles Too Fast
Cycles Too FastCycles Too Fast or Too Slow (narrow oror Too Slow (narrow or
or Too Slow (narrow or
or Too Slow (narrow oror Too Slow (narrow or wide temperature swing)wide temperature swing)
wide temperature swing)
wide temperature swing)wide temperature swing)
1. System Switch not set to COOL.
2. Loose connection to thermostat or system.
3. Cooling system requires service or thermostat requires replacement.
1. Possible short in wiring.
2. Possible short in thermostat.
3. Possible short in heat/cool/fan system.
4. Fan Switch set to Fan On.
1. The location of the thermostat and/or the size of the Heating System may be influencing the cycle rate.
Set System Switch to COOL and lower setpoint below room temperature. Verify thermostat and system wires are securely attached. Same procedure as diagnostic for No Heat condi­tion except set the thermostat to COOL and lower the setpoint below the room temperature. There may be up to a five minute delay before the thermostat clicks in Cooling.
Check each wire connection to verify they are not shorted or touching together. No bare wire should stick out from under terminal screws. Try resetting the thermostat as described above. If the condition persists the manufacturer of your system or service person can instruct you on how to test the Heat/ Cool system for correct operation. If the system operates correctly, replace the thermostat.
Digital thermostats normally provide precise temperature control and may cycle faster than some older mechanical models. A faster cycle rate means the unit turns on and off more frequently but runs for a shorter time so there is no increase in energy use. If you would like to increase the cycle time, choose If an acceptable cycle rate is not achieved as received or by choosing slow cycle, contact a local service person for additional suggestions.
SL SL
SL for slow cycle in the menu, step 4.
SL SL
8
Page 9
TROUBLESHOOTINGTROUBLESHOOTING
TROUBLESHOOTING
TROUBLESHOOTINGTROUBLESHOOTING
SymptomSymptom
Symptom
SymptomSymptom
Thermostat Setting &Thermostat Setting &
Thermostat Setting &
Thermostat Setting &Thermostat Setting & Thermostat ThermometerThermostat Thermometer
Thermostat Thermometer
Thermostat ThermometerThermostat Thermometer DisagreeDisagree
Disagree
DisagreeDisagree
Blank Display and/orBlank Display and/or
Blank Display and/or
Blank Display and/orBlank Display and/or Keypad Not RespondingKeypad Not Responding
Keypad Not Responding
Keypad Not RespondingKeypad Not Responding
Heat Setpoint willHeat Setpoint will
Heat Setpoint will
Heat Setpoint willHeat Setpoint will not Respond to thenot Respond to the
not Respond to the
not Respond to thenot Respond to the Temperature Up KeyTemperature Up Key
Temperature Up Key
Temperature Up KeyTemperature Up Key
Cool Setpoint willCool Setpoint will
Cool Setpoint will
Cool Setpoint willCool Setpoint will not Respond to thenot Respond to the
not Respond to the
not Respond to thenot Respond to the Temperature Down KeyTemperature Down Key
Temperature Down Key
Temperature Down KeyTemperature Down Key
Forgot KeypadForgot Keypad
Forgot Keypad
Forgot KeypadForgot Keypad Lockout CodeLockout Code
Lockout Code
Lockout CodeLockout Code
Possible CausePossible Cause
Possible Cause
Possible CausePossible Cause
1. Thermostat thermometer setting requires adjustment.
1. Voltage spike or static discharge.
1. The desired setpoint conflicts with the setpoint of the COOL mode.
1. The desired setpoint conflicts with the setpoint of the HEAT mode.
Corrective ActionCorrective Action
Corrective Action
Corrective ActionCorrective Action
The thermometer can be adjusted +/- 3 degrees. See Temperature Display Adjustment in the Configuration Menu section.
Use the Reset Operation at top of previous page.
Change system mode to COOL. Raise the Cool setpoint. Return to HEAT mode and set desired temperature.
Change system mode to HEAT. Lower the Heat setpoint. Return to COOL mode and set desired temperature.
CAUTION: This resets the thermostat to factory default settings of the configuration menu. After performing this reset, the thermostat will require configuration again. Be sure that you know the required configuration settings before resetting.
With the thermostat in any mode, press at the same time to enter the configuration menu at the point where the lockout code is to be entered. Press time to reset the lockout code, unlock the keypad and reset all configuration menu settings.
and and SYSTEM button at the same
and
Why won't my 2nd orWhy won't my 2nd or
Why won't my 2nd or
Why won't my 2nd orWhy won't my 2nd or 3rd stage come on?3rd stage come on?
3rd stage come on?
3rd stage come on?3rd stage come on?
Your thermostat is designed to determine the optimum time to activate the second stage. Simply raising the temperature in heating or lowering it in cooling will not always force the thermostat to bring the second stage on quickly. There is a time delay from 0-30 minutes depending on the performance of the first stage of the system.
9
Page 10
The Emerson logo is a trademark and a service mark of Emerson Electric Co.
Loading...