FAILURE TO READ AND FOLLOW ALL INSTRUCTIONS CAREFULLY BE-FAILURE TO READ AND FOLLOW ALL INSTRUCTIONS CAREFULLY BE-
FAILURE TO READ AND FOLLOW ALL INSTRUCTIONS CAREFULLY BE-
FAILURE TO READ AND FOLLOW ALL INSTRUCTIONS CAREFULLY BE-FAILURE TO READ AND FOLLOW ALL INSTRUCTIONS CAREFULLY BEFORE INSTALLING OR OPERATING THIS CONTROL COULD CAUSE PER-FORE INSTALLING OR OPERATING THIS CONTROL COULD CAUSE PER-
FORE INSTALLING OR OPERATING THIS CONTROL COULD CAUSE PER-
FORE INSTALLING OR OPERATING THIS CONTROL COULD CAUSE PER-FORE INSTALLING OR OPERATING THIS CONTROL COULD CAUSE PERSONAL INJURY AND/OR PROPERTY DAMAGE.SONAL INJURY AND/OR PROPERTY DAMAGE.
To prevent electrical shock and/or equipment damage,
To prevent electrical shock and/or equipment damage,To prevent electrical shock and/or equipment damage,
disconnect electric power to system at main fuse ordisconnect electric power to system at main fuse or
disconnect electric power to system at main fuse or
disconnect electric power to system at main fuse ordisconnect electric power to system at main fuse or
circuit breaker box until installation is complete.circuit breaker box until installation is complete.
circuit breaker box until installation is complete.
circuit breaker box until installation is complete.circuit breaker box until installation is complete.
aa
tortor
::
a
tor
:
aa
tortor
::
CAUTION
Sa Sa
Sa
Sa Sa
vv
e these instre these instr
v
e these instr
vv
e these instre these instr
1F83-2771F83-277
1F83-277
1F83-2771F83-277
uctions fuctions f
uctions f
uctions fuctions f
Assemble tools required as shown below.
HAND OR POWER
DRILL WITH 3/16 INCH
DRILL BIT, IF NEEDED
REMOREMO
REMO
REMOREMO
or futuror futur
or futur
or futuror futur
FLAT BLADE SCREWDRIVER
VING OLD VING OLD
VING OLD
VING OLD VING OLD
e use!e use!
e use!
e use!e use!
PREPPREP
PREP
PREPPREP
ARAARA
TIONSTIONS
ARA
TIONS
ARAARA
TIONSTIONS
WIRE CUTTER/STRIPPER
THERMOSTTHERMOST
THERMOST
THERMOSTTHERMOST
AA
A
AA
TT
T
TT
Before removing wires from old thermostat's switching sub-
label each wirelabel each wire
base,
label each wire with the terminal designation it was
label each wirelabel each wire
removed from.
1. Shut off electricity at the main fuse box until installation is
complete. Ensure that electrical power is disconnected.
Remove Old ThermostatRemove Old Thermostat
2.
Remove Old Thermostat: A standard heat/cool
Remove Old ThermostatRemove Old Thermostat
thermostat consists of three basic parts:
a. The cover, which may be either a snap-on or
hinge type.
b. The base, which is removed by loosening all
captive screws.
c. The switching subbase, which is removed by
unscrewing the mounting screws that hold it on
the wall or adaptor plate.
3. Remove the front cover of the old thermostat.
wireswires
still attachedstill attached
wires
still attached, remove wall plate from the wall. If
wireswires
still attachedstill attached
the old thermostat has a wall mounting plate, remove the
thermostat and the wall mounting plate as an assembly.
4. Identify each wire attached to the old thermostat.
5. Disconnect the wires from the old thermostat one at a
DO NOT LET WIRES FALL BACK INTO THEDO NOT LET WIRES FALL BACK INTO THE
time.
DO NOT LET WIRES FALL BACK INTO THE
DO NOT LET WIRES FALL BACK INTO THEDO NOT LET WIRES FALL BACK INTO THE
WALLWALL
WALL.
WALLWALL
6. Install new thermostat using the following procedures.
WithWith
With
WithWith
Y2
C
R
E/W1
Y1
Mounting
Hole
Figure 1 – Thermostat baseFigure 1 – Thermostat base
Figure 1 – Thermostat base
Figure 1 – Thermostat baseFigure 1 – Thermostat base
ATTENTION!ATTENTION!
ATTENTION! This product does not contain mercury. How-
ATTENTION!ATTENTION!
ever, this product may replace a unit which contains mercury.
Do not open mercury cells. If a cell becomes damaged, do
touch any spilled mercury. Wearing non-absorbent gloves,
clean up the spilled mercury and place into a container which
can be sealed. If a cell becomes damaged, the unit should be
discarded.
Mercury must not be discarded in household trash. When the
unit this product is replacing is to be discarded, place in a
suitable container and refer to www.white-rodgers.com for the
location to send product containing mercury.
OBLW2G
ELEC.GAS
AUTOON
Mounting
Hole
Elec-Gas
Switch
notnot
not
notnot
White-Rodgers is a division
of Emerson Electric Co.
www.white-rodgers.com
PART NO. 37-6509EPART NO. 37-6509E
PART NO. 37-6509E
PART NO. 37-6509EPART NO. 37-6509E
Replaces 37-6509D
0818
Page 2
MOUNTING AND WIRINGMOUNTING AND WIRING
MOUNTING AND WIRING
MOUNTING AND WIRINGMOUNTING AND WIRING
CAUTION
WARNING
!
Do not use on circuits exceeding specified voltage.Do not use on circuits exceeding specified voltage.
Do not use on circuits exceeding specified voltage.
Do not use on circuits exceeding specified voltage.Do not use on circuits exceeding specified voltage.
Higher voltage will damage control and could causeHigher voltage will damage control and could cause
Higher voltage will damage control and could cause
Higher voltage will damage control and could causeHigher voltage will damage control and could cause
shock or fire hazard.shock or fire hazard.
shock or fire hazard.
shock or fire hazard.shock or fire hazard.
Take care when securing and routing wires so they doTake care when securing and routing wires so they do
Take care when securing and routing wires so they do
Take care when securing and routing wires so they doTake care when securing and routing wires so they do
not short to adjacent terminals or rear of thermostat.not short to adjacent terminals or rear of thermostat.
not short to adjacent terminals or rear of thermostat.
not short to adjacent terminals or rear of thermostat.not short to adjacent terminals or rear of thermostat.
Personal injury and/or property damage may occur.Personal injury and/or property damage may occur.
Personal injury and/or property damage may occur.
Personal injury and/or property damage may occur.Personal injury and/or property damage may occur.
!
Attach Thermostat Base to Wall
Do not short out terminals on gas valve or primaryDo not short out terminals on gas valve or primary
Do not short out terminals on gas valve or primary
Do not short out terminals on gas valve or primaryDo not short out terminals on gas valve or primary
control to test. Short or incorrect wiring will damagecontrol to test. Short or incorrect wiring will damage
control to test. Short or incorrect wiring will damage
control to test. Short or incorrect wiring will damagecontrol to test. Short or incorrect wiring will damage
thermostat and could cause personal injury and/orthermostat and could cause personal injury and/or
thermostat and could cause personal injury and/or
thermostat and could cause personal injury and/orthermostat and could cause personal injury and/or
property damage.property damage.
property damage.
property damage.property damage.
Thermostat installation and all components of the
system shall conform to Class II circuits per the NEC
code.
This thermostat is configured from the factory to operate a heat/
cool, fossil fuel (gas, oil, etc.), forced air system. It is configured
correctly for any system that DOES NOT require the thermostat
to energize the fan on a call for heat. If you system is an electric
heat or heat-pump system that REQUIRES the thermostat to
turn on the fan on a call for heat, locate the ELEC/GAS switch
on the back of the thermostat (see fig. 1) and switch it to the
ELEC position. This will allow the thermostat to energize the fan
immediately on a call for heat. If you are unsure if the heating/
cooling system requires the thermostat to control the fan,
contact a qualified heating and air conditioning service person.
When the thermostat is configured for Heat Pump, the thermostat will always power the circulator fan on a call for heat in the
HEAT mode. The ELEC/GAS switch must be set to match the
type of Auxiliary heat your system uses for proper operation in
the EMERgency mode.
All wiring diagrams are for typical systems only. Refer to
equipment manufacturers’ instructions for specific system wiring information.
O
Reversing Valve
Energized in Cool
Mode
B
Reversing Valve
Energized in Heat,
Off, Emergency
Mode
Y2
2nd Stage
Compressor
Compressor
Contactor
Figure 2. Typical wiring diagram for single transformer heat pump systems
*The 24 volt neutral connection to terminal C on the thermostat is not required if you replace the batteries once a year with fresh “AA” alkaline batteries.
If safety circuits are in only one of the systems, remove
the transformer of the system with NO safety circuits.
1. Remove the packing material from the thermostat. Gently
pull the cover straight off the base. Forcing or prying on
the thermostat will cause damage to the unit.
2. Connect wires beneath terminal screws on base using
appropriate wiring schematic (see figs. 2 through 4).
3. Place base over hole in wall and mark mounting hole
locations on wall using base as a template.
4. Move base out of the way. Drill mounting holes.
5. Fasten base loosely to wall, as shown in fig. 1, using two
mounting screws. Place a level against bottom of base,
adjust until level, and then tighten screws. (Leveling is for
appearance only and will not affect thermostat operation.)
If you are using existing mounting holes, or if holes drilled
are too large and do not allow you to tighten base snugly,
use plastic screw anchors to secure subbase.
6. Push excess wire into wall and plug hole with a fireresistant material (such as fiberglass insulation) to
prevent drafts from affecting thermostat operation.
Battery Location
2 “AA” alkaline batteries are included in the thermostat at the
factory with a battery tag to prevent power drainage. You
must remove the battery tag to engage the batteries.
If “BATT” is displayed, the batteries are low and should be
replaced. For best results, replace all batteries with new
premium brand alkaline batteries such as Duracell
Energizer
®
. To replace batteries, press system button to
OFF, install the batteries along the top of the base (see Fig.
1). The batteries must be installed with the positive (+) end to
the left.
GW2
Fan
Relay
NOTE
Aux
Heat
Relay
E/W1
Emergency
Heat
Relay
CY1
*
SYSTEM
MONITOR
SWITCH
24 VAC
(Class II Current Limited)
L
TRANSFORMER
®
or
THERMOSTAT
R
SYSTEM
Hot
120 VAC
Neutral
TAPE OFF!
HOT
120 VAC
NEUTRAL
CUT AND
24 VAC
O
Reversing
Val ve
Energized in
Cool Mode
B
Reversing
Val ve
Energized in
Heat, Off,
Emergency
Mode
Y2
2nd Stage
Compressor
Compressor
Contactor
GW2
Fan
Relay
E/W1
Emergency
Aux
Heat
Relay
Heat
Relay
TWO COMMONS MUST
BE JUMPERED TOGETHER!
CY1
*
SYSTEM
MONITOR
SWITCH
L
THERMOSTAT
R
SYSTEM
Limit or
Safety
Switches
24 VAC
TRANSFORMER
(Class II Current Limited)
Figure 3. Typical wiring diagram for two transformer heat pump systems with NO safety circuits
*The 24 volt neutral connection to terminal C on the thermostat is not required if you replace the batteries once a year with fresh “AA” alkaline batteries.
Hot
120 VAC
Neutral
Page 3
WIRING DIAWIRING DIA
WIRING DIA
WIRING DIAWIRING DIA
GRAMSGRAMS
GRAMS
GRAMSGRAMS
O
Reversing
Valve
Energized in
Cool Mode
B
Reversing
Valve
Energized in
Heat, Off,
Emergency
Mode
Y2
2nd Stage
Compressor
Compressor
Contactor
GW2
Fan
Relay
Polarity must be observed. If the HOT side of the second transformer
is jumpered to the COMMON side of the first transformer a short will
be made. Damage to equipment will occur when power is restored.
E/W1
Emergency
Heat
Relay
Aux
Heat
Relay
TWO COMMONS MUST
BE JUMPERED TOGETHER!
CY1
*
SYSTEM
MONITOR
SWITCH
NOTE
L
COMMON
R
Switches
Limit or
Safety
Switches
Limit or
Safety
24 VAC
24 VAC
ACCESSORY
RELAY N.O.
CONTACT
COMMON
24 VAC120 VAC
Heat Pump Transformer
(Class II Current Limited)
THERMOSTAT
SYSTEM
Auxiliary
Heating
Transformer
(Class II
Current Limited)
Limit or
Safety
HOT
Switches
120 VAC
The accessory relay scheme
is required when safety
circuits exist in both systems.
Limit or
Safety
Switches
NEUTRAL
NOTE
HOT
NEUTRAL
Figure 4. Typical wiring diagram for two transformer heat pump systems with safety circuits in BOTH systems
*The 24 volt neutral connection to terminal C on the thermostat is not required if you replace the batteries once a year with fresh “AA” alkaline batteries.
Refer to equipment manufacturers' instructions for specific
system wiring information.
You can configure the thermostat for use with the following
heat pump system types:
HEAT PUMP TYPE 1. Single stage compressor system; gas
or electric backup.
This thermostat is designed to operate a single-transformer
system. If you have a two-transformer system, cut and tape off
one transformer. If transformer safety circuits are in only one of
the systems, remove the transformer of the system with NO
safety circuits. If required, replace remaining transformer with a
75VA Class II transformer. After disconnecting one transformer,
the two commons must be jumpered together.
Use the terminal output information below to help you wire the
thermostat properly for your heat pump system. After wiring,
see CONFIGURATION section for proper thermostat configuration.
HeatMalfunctionMode 2nd2nd(compressor) Set GAS/ELEC switchEmergency
Pump 2Switch stagestagefor Emergency modemode
or SystemEmergency 1st stage1st stageand CoolModeOFF
Heat Modecompressor
3rd stage,
Emergency
Mode 2nd
stage
*The 24 volt neutral connection to terminal C on the thermostat is not required if you replace the batteries once a year with fresh “AA” alkaline batteries.
O
Reversing
Val ve
Energized in
Cool Mode
B
Reversing
Val ve
Energized in
Heat Mode
Off Emergency
Y1
Compressor
Contactor
Stage 1
Y2
Compressor
Contactor
Stage 2
G
Fan
Relay
E/W1
Heat
Relay
Stage 1
W2
Heat
Relay
Stage 2
*
CR
THERMOSTAT
SYSTEM
Hot
24 VAC120 VAC
Neutral
TRANSFORMER
(Class II, Current Limited)
Figure 5. Typical wiring diagram for single transformer multi-stage systems
*The 24 volt neutral connection to terminal C on the thermostat is not required if you replace the batteries once a year with fresh “AA” alkaline batteries.
Refer to equipment manufacturers' instructions for specific
system wiring information.
You can configure the thermostat for use with either multi-stage
electric heat systems or multi-stage gas systems. When configured for electric heat, the G terminal (blower/fan) will be
energized on a call for heat.
This thermostat is designed to operate a single-transformer
system. If you have a two-transformer system, cut and tape off
Multi-stage Malfunction 24 Volt 24 Volt Heat Mode Heat mode Cool Mode Cool Mode Blower/Fan Energized Energized Energized
*The 24 volt neutral connection to terminal C on the thermostat is not required if you replace the batteries once a year with fresh “AA” alkaline batteries.
LL
L
LL
Light (Common) (Hot) 2nd stage 1st stage 2nd stage 1st stageon call for Cool (andin Cool in Heat, Off,
C*C*
C*
C*C*
RR
R
RR
W2W2
W2
W2W2
E/W1E/W1
E/W1
E/W1E/W1
one transformer. If transformer safety circuits are in only one of
the systems, remove the transformer of the system with NO
safety circuits. If required, replace remaining transformer with a
75VA Class II transformer. After disconnecting one transformer,
the two commons must be jumpered together.
Use the terminal output information below to help you wire the
thermostat properly for your multi-stage system. After wiring,
see CONFIGURATION section for proper thermostat configuration.
Y2Y2
Y2
Y2Y2
Y1Y1
Y1
Y1Y1
GG
G
GG
Heat if configuredModeEmergency
to Electric Heat)Modes
OO
O
OO
BB
B
BB
CHECK CHECK
CHECK
CHECK CHECK
THERMOSTTHERMOST
THERMOST
THERMOSTTHERMOST
AA
T OPERAT OPERA
A
T OPERA
AA
T OPERAT OPERA
TIONTION
TION
TIONTION
NOTE
To prevent static discharge problems, touch side ofTo prevent static discharge problems, touch side of
To prevent static discharge problems, touch side of
To prevent static discharge problems, touch side ofTo prevent static discharge problems, touch side of
thermostat to release static build-up before touchingthermostat to release static build-up before touching
thermostat to release static build-up before touching
thermostat to release static build-up before touchingthermostat to release static build-up before touching
any keys.any keys.
any keys.
any keys.any keys.
If at any time during testing your system does not operate
properly, contact a qualified service person.
Fan Operation
If your system does not have a G terminal connection, skip to
Heating System.
1. Turn on power to system.
2. Move FAN switch to ON position. The blower should begin to operate.
3. Move FAN switch to AUTO position. The blower should
stop immediately.
CAUTION
!
Do not allow the compressor to run unless the com-Do not allow the compressor to run unless the com-
Do not allow the compressor to run unless the com-
Do not allow the compressor to run unless the com-Do not allow the compressor to run unless the compressor oil heaters have been operational for 6 hourspressor oil heaters have been operational for 6 hours
pressor oil heaters have been operational for 6 hours
pressor oil heaters have been operational for 6 hourspressor oil heaters have been operational for 6 hours
and the system has not been operational for at least 5and the system has not been operational for at least 5
and the system has not been operational for at least 5
and the system has not been operational for at least 5and the system has not been operational for at least 5
minutes.minutes.
minutes.
minutes.minutes.
Heating System
1. Press SYSTEM button to select the Flame icon ( ). If
the auxiliary heating system has a standing pilot, be sure
to light it.
2. Press
temperature. The heating system should begin to
operate. The display should show “STG1”. However, if
the setpoint temperature display is flashing, the compressor lockout feature is operating (see Configuration menu,
item 5).
3. Adjust temperature setting to 3° above room temperature.
If your system configuration is set at MS2, HP2 or HP1,
the auxiliary heat system should begin to operate and the
display should show “STG1+2”.
4. Press
ture. The heating system should stop operating.
to adjust thermostat setting to 1° above room
to adjust the thermostat below room tempera-
Emergency System
EMER bypasses the Heat Pump to use the heat source wired
to terminal E on the thermostat. EMER is typically used when
compressor operation is not desired, or you prefer back-up
heat only.
1. Press SYSTEM button to select EMER. “EMER” will flash
on the display.
2. Press
temperature. The Aux. heating system will begin to
operate. The display will show “STG1” flashing “EMER”
and Flame icon (
operating.
3. Adjust temperature setting to 3° above room temperature.
The auxiliary heat system should begin to operate and
the display should show “STG1+2”.
4. Press
ture. The Aux. heating system should stop operating.
To prevent compressor and/or property damage, if theTo prevent compressor and/or property damage, if the
To prevent compressor and/or property damage, if the
To prevent compressor and/or property damage, if theTo prevent compressor and/or property damage, if the
outdoor temperature is below 50°F, DO NOT operateoutdoor temperature is below 50°F, DO NOT operate
outdoor temperature is below 50°F, DO NOT operate
outdoor temperature is below 50°F, DO NOT operateoutdoor temperature is below 50°F, DO NOT operate
the cooling system.the cooling system.
the cooling system.
the cooling system.the cooling system.
to adjust thermostat setting above room
) to indicate that the Aux. system is
to adjust the thermostat below room tempera-
CAUTION
!
Cooling System
1. Press SYSTEM button to select the Snowflake icon ( ).
2. Press
temperature. The blower should come on immediately on
high speed, followed by cold air circulation. The display
should show “STG1”.
3. Adjust temperature setting to 3° below room temperature.
The second stage cooling should begin to operate and
the display should show “STG1+2”.
4. Press
temperature. The cooling system should stop operating.
to adjust thermostat setting below room
to adjust the temperature setting above room
4
Page 5
Before you begin programming your thermostat, you should be
EMER
FAULT
STG1+2
familiar with its features and with the display and the location
and operation of the thermostat buttons. Your thermostat consists of two parts: the thermostat cover and the base. To remove
the cover, pull it straight out from the base. To replace the cover,
line up the cover with the base and press until the cover snaps
onto the base.
The Thermostat Buttons and Switches
Raises temperature setting
1
Lowers temperature setting.
2
FAN switch (ON, AUTO)
3
SYSTEM button (COOL, AUTO, HEAT, EMER, OFF)
4
The Display
Flame icon ( ) is displayed when the system is in
5
HEAT mode. Snowflake icon (
the system is in COOL mode. Flame icon ( ) andSnowflake icon (
when thermostat is in AUTO mode.
Displays “BATT” when the 2 "AA" batteries are low
6
and should be replaced. Only “BATT” and “LO” in the
minutes field are displayed when batteries are low and
with no system power.
Displays current temperature or “LO” in the minutes
7
field when batteries are low.
Displays set temperature (this is blank when SYSTEM
8
is OFF).
Displays “FLTR” when the system has run for the
9
programmed filter time period as a reminder to change
or clean your filter.
Display ( ) when in keypad lockout mode.
10
) are displayed simultaneously
) is displayed when
OPERAOPERA
OPERA
OPERAOPERA
Figure 6 – Thermostat display, buttons and switchesFigure 6 – Thermostat display, buttons and switches
Figure 6 – Thermostat display, buttons and switches
Figure 6 – Thermostat display, buttons and switchesFigure 6 – Thermostat display, buttons and switches
“FAULT” will be displayed when there is a malfunction
12
in the HEAT/COOL system.
Display ( ) when limited HEAT/COOL range is activated.
13
” icon will flash if an attempt is made to adjust
The “
the temperature beyond the limited HEAT/COOL
temperature range.
Stage 1 & 2 indicators: The thermostat shall indicate
14
when the first and second stage is energized except
in emergency mode. The icon is “STG 1” for the first
stage energized. The icons for the first and second
stage energized are “STG1+2” located in the upper
right side of the display.
TIONTION
TION
TIONTION
“EMER” is displayed flashing when the system is in
11
EMER mode.
The configuration menu allows you to set certain thermostat
operating characteristics to your system or personal requirements.
Set SYSTEM button to OFF, then simultaneously press
and to enter configuration menu. The display will
show the first item in the configuration menu.
The configuration menu table summarizes the configuration
options. An explanation of each option follows.
Press SYSTEM to change to the next menu item. To exit the
menu and return to the program operation, press RUN. If no
keys are pressed within fifteen minutes, the thermostat will
revert to normal operation.
CONFIGURACONFIGURA
CONFIGURA
CONFIGURACONFIGURA
1) Single Stage, Multi-stage or Heat Pump System
Configuration – This control can be configured for Heat
Pump or two stage heat/two stage cool multi-stage operation. The display indicates “MS 2” (default for multi-stage
mode) in the display. The Multi-stage configuration can be
toggled to “SS1”, “HP2”, or “HP1” by pressing the
key. In Multi-stage configuration, SYSTEM button will not
have EMERgency mode.
2) Fast or Slow Cycle Selection – The factory default setting
is fast cycle, which cycles 1st stage at approximately 1.2°F
and 2nd stage 0.75°F. If you prefer slow cycle, press the
or key to change to SL. The 1st stage and 2nd
stage would be 1.5°F and 1.2°F respectively.
TION MENUTION MENU
TION MENU
TION MENUTION MENU
or
5
Page 6
CONFIGURACONFIGURA
CONFIGURA
CONFIGURACONFIGURA
TION MENUTION MENU
TION MENU
TION MENUTION MENU
Press the SYSTEM button until OFF is displayed, then press the and simultaneously
INSTALLER/CONFIGURATION MENU
PressDisplayedPress or
StepButton(s)(Factory Default)to selectComments
1SystemMS 2SS1, HP2, HP1Selects Single stage, Multi-stage, or Heat Pump
(Single stage or 2-stage) System Configuration
2SystemFASLSelects Fast or Slow Cycle Selection
3SystemCLCLSelects Compressor Lockout CL OFF or ON
(OFF)(ON)
4SystemCDLCDLSelects Backlight Display
(ON)(OFF)
5SystemFAFASelects Fast Second Stage ON or OFF
(ON)(OFF)
6System0 FLTR50-1950 (increments of 50)Selects filter replacement run time
7System0°F4 LO to 4 HISelects Temperature Display Adjustment 4 LO to 4 HI
(Room Temperature)
8System°F°CSelects temperature display F° or °C selection
9SystemAU OnOFFSelects AUTO Mode ON or OFF
(Not available on earlier models)
10SystemLRLR 62 to LR89Selects Limited HEAT range
(90)
11SystemLRLR 46 to LR 82Selects Limited COOL range
(45)
12SystemCACAFeature Not Available
(OFF)(ON)
13System(ON)Selects Keypad Lockout
(OFF)
14System0001 to 999Selects Keypad lockout combination number
Press System to set code
15SystemReturns to the OFF position
3) Select Compressor Lockout CL OFF or ON – Selecting
CL ON will cause the thermostat to wait 5 minutes before
turning on the compressor if the heating and cooling system
loses power. It will also wait 5 minutes minimum between
cooling and heating cycles. This is intended to help protect
the compressor from short cycling. Some newer compressors already have a time delay built in and do not require
this feature. Your compressor manufacturer can tell you if
the lockout feature is already present in their system. When
the thermostat compressor time delay occurs it will flash the
setpoint for about five minutes.
4) Select Backlight Display – The display backlight improves
display contrast in low lighting conditions. When the C
terminal is powered, selecting backlight CdL ON will turn
the light on continuously. Select backlight OFF will keep
the light on momentarily after any key is pressed. When the
C terminal is not powered, this selection has no effect.
5) Select (Fast) Second Stage ON or OFF – In the run mode,
if the setpoint temperature is manually raised by 3°F (2°C)
or more above the actual temperature with the , and the
fast second stage feature is enabled, FA ON, the second
stage will energize immediately. With FA OFF, second
stage will not energize until the setpoint temperature is 1°F
or more above actual temperature for more than ten minutes.
6
Page 7
CONFIGURACONFIGURA
CONFIGURA
CONFIGURACONFIGURA
TION MENUTION MENU
TION MENU
TION MENUTION MENU
6) Select filter replacement run time – The thermostat will
display FLTR after a set time of operation. This is a remind-
er to change or clean your air filter. This time can be set from
0 to 1950 hours in 50 hour increments. A selection of 000will cancel this feature. When “FLTR” is displayed, you
can clear it by pressing SYSTEM. This resets the timer and
starts counting the hours until the next filter change. Contact
your system manufacturer for a specific replacement/main
tenance interval.
7) Select Temperature Display Adjustment 4 LO to 4 HI –
Allows you to adjust the room temperature display up to 4°
higher or lower. Your thermostat was accurately calibrated
at the factory but you have the option to change the display
temperature to match your previous thermostat. The current or adjusted room temperature will be displayed on the
left side of the display.
8) Select F° or C° Readout – Changes the display readout
to Centigrade or Fahrenheit as required.
9) Selected Auto mode – This control will feature AUTO
changeover mode when AU on is selected (default). Press
or keys (not available on earlier models) to defeat
the
the auto changeover mode (OFF).
10)Limited Heat Range – This feature provides a maximum
setpoint temperature for heat. The default setting is 90°F. It
can be changed between 62°F and 89°F by pressing the
or key.
11)Limited Cool Range – This feature provides a minimum
setpoint temperature for cool. The default setting is 45°F. It
can be changed between 46°F and 82°F by pressing the
or key.
12)This Feature Not Available.
13 & 14) Keypad Lockout – This menu selection will display
lock icon ( ) and “OFF” (default, keypad not locked out).
The
and are used to toggle the selection between OFF
and ON (keypad locked out). When the keypad lockout
selection is enabled (ON), and the SYSTEM button is
pressed again, the display will indicate the number “0”
(default, still disabled) in the time digits. The and are
used to set the combination number from 0 to 999. If a
combination of 0 is selected and the SYSTEM button is
pressed, the menu will be exited and keypad will not be
locked. If 1 to 999 is selected and the SYSTEM button is
pressed, the combination is stored into memory and the
menu is exited. The ( ) will display designating keypad
locked with a valid combination. The SYSTEM button will
operate for 10 seconds after the menu mode is exited to
allow the user to change the mode from OFF to the desired
SYSTEM mode.
While the keypad is locked out, a simultaneous press of
and will enter the configuration menu from any
mode instead of only OFF mode. When the menu is
entered with the keypad lockout feature enabled, the
menu item displayed is the combination code 0. The
keys are used to set the combination unlock number
from 0 to 999. If the unlock number matches exactly with
the combination lock number stored in memory when the
SYSTEM button is pressed, the keypad is unlocked and
the (
) is removed. If the unlock number does not match
when the SYSTEM button is pressed, the menu is exited
and the keypad remains disabled.
To reset the combination code and unlock the keypad if
the code is forgotten, see troubleshooting section.
first
or
ELECTRICAL DATAELECTRICAL DATA
ELECTRICAL DATA
ELECTRICAL DATAELECTRICAL DATA
Electrical RatingElectrical Rating
Electrical Rating:
Electrical RatingElectrical Rating
20 to 30 VAC 50/60 Hz or DC
0.05 to 1.5 Amps (Load per terminal)
2.5 Amps Maximum Total Load (All terminals combined)
SPECIFICASPECIFICA
SPECIFICA
SPECIFICASPECIFICA
THERMAL DATATHERMAL DATA
THERMAL DATA
THERMAL DATATHERMAL DATA
Setpoint Temperature RangeSetpoint Temperature Range
Setpoint Temperature Range:
Setpoint Temperature RangeSetpoint Temperature Range
45°F to 90°F (7°C to 32°C)
Operating Ambient Temperature RangeOperating Ambient Temperature Range
Operating Ambient Temperature Range:
Operating Ambient Temperature RangeOperating Ambient Temperature Range
32°F to 105°F
Operating Humidity RangeOperating Humidity Range
Operating Humidity Range:
Operating Humidity RangeOperating Humidity Range
0 to 90% RH (non-condensing)
Shipping Temperature RangeShipping Temperature Range
Shipping Temperature Range:
Shipping Temperature RangeShipping Temperature Range
-40°F to 150°F
TIONSTIONS
TIONS
TIONSTIONS
7
Page 8
OPERAOPERA
OPERA
OPERAOPERA
TIONTION
TION
TIONTION
The system "mode" is selected by pressing the SYSTEM
button. Icons on the bottom right corner of the display will
indicate the mode:
OFFOFF
or
OFF. In any mode except
OFFOFF
be shown on the right side of the display. In
be blank. The current temperature will be displayed on the left
side of the display.
To operate properly in the
temperature cannot be the same as or higher than the cool
setpoint temperature. The heat setpoint must be at least 1°
lower than the cool setpoint.
Automatic System ChangeoverAutomatic System Changeover
Automatic System Changeover
Automatic System ChangeoverAutomatic System Changeover
When the thermostat is in the
Snowflake Snowflake
Snowflake icons are displayed. The thermostat will call for heat
Snowflake Snowflake
or cool depending on the room temperature. The setpoint
temperature displayed will be that of the last mode called. If the
last system cycle was heat, the
If the room temperature raises above the
COOL COOL
COOL setpoint and a call for cool is required, the temperature
COOL COOL
displayed will change to be the
Your thermostat is designed to determine the optimum time to
activate the second stage. Simply raising the temperature in
heating or lowering it in cooling will not always force the
thermostat to bring the second stage on quickly. There is a time
delay from 0-30 minutes depending on the performance of the
first stage of the system.
EXAMPLE: For the last 2 hours the thermostat is set on 70° and
COOL COOL
COOL (
COOL COOL
Second Stage Time DelaySecond Stage Time Delay
Second Stage Time Delay
Second Stage Time DelaySecond Stage Time Delay
AUTO AUTO
),
AUTO ( ),
AUTO AUTO
OFFOFF
OFF, the setpoint temperature will
OFFOFF
AUTO AUTO
AUTO mode, the heat setpoint
AUTO AUTO
AUTO AUTO
AUTO mode, both the
AUTO AUTO
HEAT HEAT
HEAT setpoint will be displayed.
HEAT HEAT
COOL COOL
COOL setpoint.
COOL COOL
HEAT HEAT
HEAT ( ),
HEAT HEAT
OFFOFF
OFF, this area will
OFFOFF
HEAT HEAT
HEAT setpoint and the
HEAT HEAT
EMEREMER
EMER,
EMEREMER
Flame Flame
Flame and
Flame Flame
the room temperature is 70° with the equipment using only the
first stage of heat. Since the equipment is keeping the temperature within 1° of setpoint, the thermostat will delay second stage
for a longer time if you manually raise the temperature or if the
room temperature quickly changes. Once the second stage
comes on, it will come on sooner the next time there is a
difference between the setpoint and the room temperature. The
net effect of the staging program is that when the first stage is
capable of making temperature the second stage will delay
longer. When the thermostat calculates that first stage cannot
make temperature in a reasonable time, the second stage will
come on sooner. This built in function automatically optimizes
the use of additional stages of heat or cool.
LOW BATTERY INDICATORLOW BATTERY INDICATOR
LOW BATTERY INDICATOR
LOW BATTERY INDICATORLOW BATTERY INDICATOR
If the 2 “AA” alkaline batteries are low and should be replaced,
the display will be blank except for “
mend replacing batteries every 2 years. If the home is going
to be unoccupied for an extended period (over 3 months),
the batteries should be replaced before leaving. When the
batteries are low, pressing any button will cause the display
to operated for ten seconds. After ten seconds, the display will
be blank except for “
batteries, but you can override setpoint temperature. After
LO BATTLO BATT
“
LO BATT” has been displayed for 4 weeks, the thermostat
LO BATTLO BATT
will raise the temperature 10 degrees above your setpoint in
COOL mode and will drop the temperature 10 degrees below
your setpoint in HEAT mode. If the “
continues, and when it reaches certain value, the thermostat
will turn off all the loads and “
LO BATTLO BATT
LO BATT”. You cannot program with low
LO BATTLO BATT
LO BATTLO BATT
LO BATT”. We recom-
LO BATTLO BATT
LO BATTLO BATT
LO BATT” condition
LO BATTLO BATT
LO BATTLO BATT
LO BATT” will flash.
LO BATTLO BATT
TRTR
OUBLESHOOOUBLESHOO
TR
OUBLESHOO
TRTR
OUBLESHOOOUBLESHOO
Reset OperationReset Operation
Reset Operation
Reset OperationReset Operation
If a voltage spike or static discharge blanks out the display or causes erratic thermostat operation, you can reset the thermostat by removing the wires from terminals
replace the wires and batteries. If the thermostat has been reset and still does not function correctly, contact your heating/
cooling service person or place of purchase.
SymptomSymptom
Symptom
SymptomSymptom
No Heat/No Cool/No FanNo Heat/No Cool/No Fan
No Heat/No Cool/No Fan
No Heat/No Cool/No FanNo Heat/No Cool/No Fan
(common problems)(common problems)
(common problems)
(common problems)(common problems)
No HeatNo Heat
No Heat
No HeatNo Heat
TINGTING
TING
TINGTING
RR
CC
R and
C and removing batteries for 2 minutes. After resetting the thermostat,
RR
CC
Possible CausePossible Cause
Possible Cause
Possible CausePossible Cause
1. Blown fuse or tripped circuit breaker.
2. Furnace power switch to OFF.
3. Furnace blower compartment door or
panel loose or not properly installed.
1. Pilot light not lit.
2. SYSTEM button not set to
3. Loose connection to thermostat or
system.
4. Furnace Lock-Out Condition. Heat
may also be intermittent.
HEATHEAT
HEAT.
HEATHEAT
Corrective ActionCorrective Action
Corrective Action
Corrective ActionCorrective Action
Replace fuse or reset breaker.
Turn switch to ON.
Replace door panel in proper position to engage
safety interlock or door switch.
Re-light pilot.
Press SYSTEM button to
above room temperature.
Verify thermostat and system wires are securely
attached.
Many furnaces have safety devices that shut down
when a lock-out condition occurs. If the heat works
intermittently contact the furnace manufacturer or
local service person for assistance.
HEATHEAT
HEAT and raise setpoint
HEATHEAT
Page 9
TRTR
OUBLESHOOOUBLESHOO
TR
OUBLESHOO
TRTR
OUBLESHOOOUBLESHOO
TINGTING
TING
TINGTING
Symptom
No Heat (continued)No Heat (continued)
No Heat (continued)
No Heat (continued)No Heat (continued)
No CoolNo Cool
No Cool
No CoolNo Cool
Heat, Cool or Fan
Runs Constantly
Possible Cause
5. Heating system requires service or
thermostat requires replacement.
1. SYSTEM button not pressed to COOL.
2. Loose connection to thermostat or
system.
3. Cooling system requires service or
thermostat requires replacement.
1. Possible short in wiring.
2. Possible short in thermostat.
3. Possible short in heat/cool/fan
system.
4. FAN Switch set to Fan On.
Corrective Action
Diagnostic: Press SYSTEM button to
raise the setpoint above room temperature. Within a
few seconds the thermostat should make a soft click
sound. This sound usually indicates the thermostat
is operating properly. If the thermostat does not
click, try the reset operation listed above. If the
thermostat does not click after being reset contact
your heating and cooling service person or place of
purchase for a replacement. If the thermostat clicks,
contact the furnace manufacturer or a service
person to verify the heating is operating correctly.
Press SYSTEM button to COOL and lower setpoint
below room temperature.
Verify thermostat and system wires are securely
attached.
Same procedure as diagnostic for No Heat condition
except set the thermostat to COOL and lower the
setpoint below the room temperature. There may be
up to a five minute delay before the thermostat
clicks in Cooling.
Check each wire connection to verify they are not
shorted or touching together. No bare wire should
stick out from under terminal screws. Try resetting
the thermostat as described above. If the condition
persists the manufacturer of your system or service
person can instruct you on how to test the Heat/Cool
system for correct operation. If the system operates
correctly, replace the thermostat.
HEATHEAT
HEAT and
HEATHEAT
Furnace
(Air Conditioner)
Cycles Too Fast
or Too Slow (narrow or
wide temperature swing)
1. The desired setpoint conflicts with the
setpoint of the COOL mode.
1. The desired setpoint conflicts with the
setpoint of the HEAT mode.
Digital thermostats normally provide precise
temperature control and may cycle faster than some
older mechanical models. A faster cycle rate means
the unit turns on and off more frequently but runs for
a shorter time so there is no increase in energy use.
If you would like to increase the cycle time, choose
SL for slow cycle in the menu, step 4. If an acceptable cycle rate is not achieved as received or by
choosing slow cycle, contact a local service person
for additional suggestions.
The thermometer can be adjusted +/- 4 degrees.
See Temperature Display Adjustment in the
Configuration Menu section.
Use the Reset Operation at top of previous page.
Change system mode to COOL. Raise the Cool
setpoint. Return to HEAT mode and set desired
temperature.
Change system mode to HEAT. Lower the Heat
setpoint. Return to COOL mode and set desired
temperature.
Page 10
TRTR
OUBLESHOOOUBLESHOO
TR
OUBLESHOO
TRTR
OUBLESHOOOUBLESHOO
TINGTING
TING
TINGTING
SymptomSymptom
Symptom
SymptomSymptom
Forgot Keypad
Lockout Code
Why won't my 2nd or 3rd
stage come on?
Possible CausePossible Cause
Possible Cause
Possible CausePossible Cause
First Stage is keeping up with
demand
Corrective ActionCorrective Action
Corrective Action
Corrective ActionCorrective Action
CAUTION: This resets the thermostat to factory
default settings of the configuration menu. After
performing this reset, the thermostat will require
configuration again. Be sure that you know the
required configuration settings before resetting.
With the thermostat in any mode, press
the same time to enter the configuration menu at the
point where the lockout code is to be entered. Press
and and SYSTEM button at the same time to
reset the lockout code, unlock the keypad and reset
all configuration menu settings.
Your thermostat is designed to determine the
optimum time to activate the second stage. Simply
raising the temperature in heating or lowering it in
cooling will not always force the thermostat to bring
the second stage on quickly. There is a time delay
from 0-30 minutes depending on the performance of
the first stage of the system.
and at
FF
AA
QQ
F
A
Q
FF
AA
QQ
Symptom
My thermostat is reading in Celsius.
How do I change it to Fahrenheit?
My display light does not work. Can it be
fixed or replaced?
My setpoint temperature is flashing.
What does that mean?
How can I get a copy of the Operating
Manual for my thermostat?
Corrective Action
Your thermostat display can be set to display temperature in Fahrenheit or
Celsius. This option can be set in the INSTALLER/CONFIGURATION MENU
of your thermostat. See page 6 step 12.
Because it is soldered to the circuit board it is not possible to repair or
replace.
When the thermostat compressor time delay occurs it will flash the setpoint
for about five minutes. This is intended to help protect the compressor from
short cycling.
Visit our website at www.white-rodgers.com for operating manuals.
10
Page 11
NONO
NO
NONO
TESTES
TES
TESTES
11
Page 12
The Emerson logo is a
trademark and service mark
of Emerson Electric Co.
HOMEOWNER HELP LINE: 1-800-284-2925
St. Louis, MissouriMarkham, Ontario
www.white-rodgers.com
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.