1F82-261
Programmable Electronic Digital
Heat Pump Thermostat
INSTALLATION AND
OPERATION INSTRUCTIONS
Operator: Save these instructions for future use!
FAILURE TO READ AND FOLLOW ALL INSTRUCTIONS CAREFULLY
BEFORE INSTALLING OR OPERATING THIS CONTROL COULD CAUSE
PERSONAL INJURY AND/OR PROPERTY DAMAGE.
DESCRIPTION
Your new White-Rodgers 5-Day/1-Day/1-Day Digital Thermostat uses the technology of a solid-state microcomputer to
provide precise time/temperature control. This thermostat offers
you the flexibility to design heating and cooling programs that fit
your needs.
Features:
• Separate 5-day (weekday) and 1-day/1-day (Saturday/Sunday)
programming with four separate time/temperature periods per day
• Simultaneous heat and cool program storage
• Preprogrammed temperature control
• Optional battery back-up for AC power loss
This thermostat is intended for use with a low voltage NEC
Class II system. Do not use this thermostat with a line voltage
system. If in doubt about whether your wiring is millivolt, line, or
low voltage, have it inspected by a qualified heating and air
conditioning contractor or electrician.
Do not exceed the specification ratings.
All wiring must conform to local and national electrical codes
and ordinances.
This control is a precision instrument, and should be handled
carefully. Rough handling or distorting components could cause
the control to malfunction.
! CAUTION
▲
To prevent electrical shock and/or equipment damage, disconnect electric power to system at main fuse
or circuit breaker box until installation is complete.
• LCD continuously displays set point, and alternately displays time and room temperature
• Continuous Backlit display option
• Temperature override until next program period
• Manual program override (HOLD temperature)
• Temporary HOLD
• °F/°C convertibility
• Temperature range 45° to 90°F
• R, C, Y, W2, G, O/B, E, and L terminals for single or twotransformer systems
PRECAUTIONS
! WARNING
▲
Do not use on circuits exceeding specified voltage.
Higher voltage will damage control and could cause
shock or fire hazard.
Do not short out terminals on gas valve or primary
control to test. Short or incorrect wiring will damage
thermostat and could cause personal injury and/or
property damage.
Thermostat installation and all components of the
system shall conform to Class II (current limited)
circuits per the NEC code. Failure to do so could cause
a fire hazard.
ELECTRICAL DATA
Electrical Rating:
20 to 30 VAC 50/60 Hz. or D.C.
0.05 to 1.0 Amps (Load per terminal)
1.5 Amps Maximum Total Load (All terminals combined)
THERMAL DATA
Setpoint Temperature Range:
45°F to 90°F (7°C to 32°C)
Operating Ambient Temperature Range:
32°F to 105°F
Operating Humidity Range:
0 to 90% RH (non-condensing)
Shipping Temperature Range:
-4°F to 149°F
WHITE-RODGERS
EMERSON ELECTRIC CO.
9797 REAVIS ROAD
ST. LOUIS, MISSOURI 63123-5398
www.white-rodgers.com
APPLICATIONS
For use with the following Class II systems:
• Standard heat pump systems with electric, gas or oil
Aux heat with 24VAC Hot and Common available
• Single-stage heat pump systems with no Aux heat with
24VAC Hot and Common available
DO NOT USE WITH:
• Millivolt systems
• Systems exceeding 30 VAC and 1.5 amps
• 3-wire zoned hydronic heating systems
Printed in U.S.A.
SPECIFICATIONS
PART NO. 37-6175D
Replaces 37-6175C
0225
INSTALLATION
REMOVE OLD THERMOSTAT
1. Shut off electricity at the main fuse box until installation is
complete. Ensure that electrical power is disconnected.
2. Remove the front cover of the old thermostat. With wires
still attached, remove wall plate from the wall. If the old
thermostat has a wall mounting plate, remove the thermostat
and the wall mounting plate as an assembly.
3. Identify each wire attached to the old thermostat using
the labels enclosed with the new thermostat.
4. Disconnect the wires from old thermostat one at a time. DO
NOT LET WIRES FALL BACK INTO THE WALL.
5. Install new thermostat using the following procedures.
ATTENTION!
This product does not contain mercury. However, this product
may replace a unit which contains mercury.
Do not open mercury cells. If a cell becomes damaged, do not
touch any spilled mercury. Wearing nonabsorbent gloves, take
up the spilled mercury and place into a container which can be
sealed. If a cell becomes damaged, the unit should be discarded.
Mercury must not be discarded in household trash. When the
unit this product is replacing is to be discarded, place in a
suitable container and return to White-Rodgers at 9797 Reavis
Road, St. Louis, MO, 63123-5398 for proper disposal.
ATTACH THERMOSTAT BASE TO WALL
1. Remove the packing material from the thermostat. Gently pull
the cover straight off the base. Forcing or prying on the
thermostat will cause damage to the unit.
2. Connect wires beneath terminal screws on base using
appropriate wiring schematic (see figs. 2 through 4).
3. Place base over hole in wall and mark mounting hole
locations on wall using base as a template.
4. Move base out of the way. Drill mounting holes.
5. Fasten base loosely to wall, as shown in fig. 1, using two
mounting screws. Place a level against bottom of base,
adjust until level, and then tighten screws. (Leveling is for
appearance only and will not affect thermostat operation.) If
you are using existing mounting holes, or if holes drilled are
too large and do not allow you to tighten base snugly, use
plastic screw anchors to secure subbase.
6. Push excess wire into wall and plug hole with a fire-resistant
material (such as fiberglass insulation) to prevent drafts from
affecting thermostat operation.
ELECTRIC/GAS JUMPER (Fan Option)
Read the following information before clipping the nonelectric
heat jumper. If you are unsure of your application, contact a
qualified service person.
If your emergency or auxiliary system will energize the blower,
then jumper, W904, on the thermostat base must be cut (see
fig. 1).
If your emergency or auxiliary heat system requires that the
thermostat energize the fan circuit, do not cut jumper W904.
OPTIONAL BATTERIES
With two "AA" batteries installed, your thermostat will maintain
time and continuously display the temperature during a loss
Optional (2) "AA" batteries
Screw anchors
O/B
0
4
Mounting
hole
switch
Mounting
hole
(below Fan switch)
Reset switch
W904
Electric/Gas
jumper
W
9
Figure 1. Thermostat Base
of AC power. Installed batteries will also allow programming
prior to installation.
ENERGY MANAGEMENT RECOVERY
(EMR)
When the EMR feature is activated the thermostat's microcomputer calculates the time it will take to change the room
temperature to the next heat or cool program setting. Then the
thermostat will start the system before the next programmed
period so that the desired temperature is reached at or near the
beginning of the period (the thermostat calculates 15 minutes
for every 1°F temperature change). This minimizes the use of
auxiliary stages during the transition period to reduce energy
costs.
For example: The thermostat is programmed to provide an
overnight heating temperature of 66°F, and during the next
program period, beginning at 6:00 AM, the programmed temperature is 70°F. With EMR activated, the thermostat will automatically start the heating system at 5:00 AM, so that the
programmed temperature of 70°F is reached by about 6:00 AM.
If the overnight room temperature drops only to 68F°, the
thermostat will start the system at 5:30 to reach the programmed
temperature of 70°F at 6:00.
The thermostat is shipped with the EMR feature active, which
means that the thermostat will start the heating system before
the beginning of the next program period. This feature provides
better efficiency by allowing gradual temperature changes using
only the first stage of heat.
To deactivate the EMR function, see the Configuration menu
on Page 5). The thermostat will then wait until the programmed
time to start the system for a temperature change.
O/B TERMINAL SWITCH SELECTION
The O/B switch on this thermostat is factory set to the “O”
position. This will accommodate the majority of heat pump
applications, which require the changeover relay to be energized in COOL. If the thermostat you are replacing or the heat
pump being installed with this thermostat requires a “B” terminal, to energize the changeover relay in HEAT, the O/B switch
must be moved to the “B” position.
2
G W2
Aux
Relay
See Note **
Emergency
Changeover
Relay*
Compressor
Contactor
* Changeover Relay is energized in COOL when O/B switch is in the “O” position
Changeover Relay is energized in HEAT when O/B switch is in the “B” position
Fan
Relay
(Stage 2)
** Jumper required to use a single Aux Heat for both Second Stage Heat and Emergency
Figure 2. Typical wiring diagram for single transformer systems
NOTE
If safety circuits are in
only one of the systems,
remove the transformer
of the system with NO
safety circuits.
CUT AND
TAPE OFF!
HOT
120 VAC
NEUTRAL
* Changeover Relay is energized in COOL when O/B switch is in the “O” position
Changeover Relay is energized in HEAT when O/B switch is in the “B” position
** Jumper required to use a single Aux Heat for both Second Stage Heat and Emergency
24 VAC
Changeover
Relay*
Compressor
Contactor
Figure 3. Typical wiring diagram for two transformer systems with NO safety circuits
G W2
Fan
Relay
See Note **
Emergency
Aux
Relay
(Stage 2)
TWO COMMONS MUST
BE JUMPERED TOGETHER!
E
Relay
E
Relay
CYO/B
CYO/B
SYSTEM
MONITOR
SWITCH
SYSTEM
MONITOR
SWITCH
L
THERMOSTAT
R
SYSTEM
24 VAC
TRANSFORMER
(Class II Current Limited)
L
THERMOSTAT
R
Limit or
Safety
Switches
24 VAC
(Class II Current Limited)
120 VAC
Neutral
SYSTEM
TRANSFORMER
Hot
Hot
120 VAC
Neutral
G W2
See Note **
Changeover
Relay*
Compressor
Contactor
* Changeover Relay is energized in COOL when O/B switch is in the “O” position
Changeover Relay is energized in HEAT when O/B switch is in the “B” position
** Jumper required to use a single Aux Heat for both Second Stage Heat and Emergency
Fan
Relay
Aux
Relay
(Stage 2)
E
CYO/B
Emergency
Relay
TWO COMMONS MUST
BE JUMPERED TOGETHER!
SYSTEM
MONITOR
SWITCH
Figure 4. Typical wiring diagram for two transformer systems with safety circuits in BOTH systems
L
R
COMMON
Limit or
Switches
Limit or
Safety
Switches
Polarity must be observed. If the HOT side of
NOTE
the second transformer is jumpered to the
COMMON side of the first transformer a short
will be made. Damage to equipment will occur
when power is restored.
THERMOSTAT
Safety
ACCESSORY
RELAY N.O.
24 VAC
24 VAC
CONTACT
COMMON
Current Limited)
24 VAC 120 VAC
Heat Pump Transformer
(Class II Current Limited)
SYSTEM
Auxiliary
Heating
Transformer
(Class II
120 VAC
Limit or
Safety
Switches
NOTE
The accessory relay scheme
is required when safety
circuits exist in both systems.
Limit or
Safety
Switches
NEUTRAL
HOT
NEUTRAL
HOT
3