White Rodgers 1F80-361 User Manual

Page 1
Operator: Save these instructions for future use!Operator: Save these instructions for future use!
Operator: Save these instructions for future use!
Operator: Save these instructions for future use!Operator: Save these instructions for future use!
FAILURE TO READ AND FOLLOW ALL INSTRUCTIONS CAREFULLYFAILURE TO READ AND FOLLOW ALL INSTRUCTIONS CAREFULLY
FAILURE TO READ AND FOLLOW ALL INSTRUCTIONS CAREFULLYFAILURE TO READ AND FOLLOW ALL INSTRUCTIONS CAREFULLY BEFORE INSTALLING OR OPERATING THIS CONTROL COULD CAUSEBEFORE INSTALLING OR OPERATING THIS CONTROL COULD CAUSE
BEFORE INSTALLING OR OPERATING THIS CONTROL COULD CAUSE
BEFORE INSTALLING OR OPERATING THIS CONTROL COULD CAUSEBEFORE INSTALLING OR OPERATING THIS CONTROL COULD CAUSE PERSONAL INJURY AND/OR PROPERTY DAMAGE.PERSONAL INJURY AND/OR PROPERTY DAMAGE.
PERSONAL INJURY AND/OR PROPERTY DAMAGE.
PERSONAL INJURY AND/OR PROPERTY DAMAGE.PERSONAL INJURY AND/OR PROPERTY DAMAGE.
Your new White-Rodgers 5-Day/1-Day/1-Day Digital Thermo­stat uses the technology of a solid-state microcomputer to provide precise time/temperature control. This thermostat offers you the flexibility to design heating and cooling programs that fit your needs.
Features:Features:
Features:
Features:Features:
• Separate 5-day (weekday), 1-day (Sat) and 1-day (Sun) pro­gramming with four separate time/temperature periods per day
• Simultaneous heat and cool program storage
• Preprogrammed temperature control
• Backlit display
• LCD continuously displays setpoint, and alternately dis­plays time and room temperature
1F80-3611F80-361
1F80-361
1F80-3611F80-361
Programmable Electronic Digital Thermostat
INSTALLATION ANDINSTALLATION AND
INSTALLATION AND
INSTALLATION ANDINSTALLATION AND
OPERATION INSTRUCTIONSOPERATION INSTRUCTIONS
OPERATION INSTRUCTIONS
OPERATION INSTRUCTIONSOPERATION INSTRUCTIONS
DESCRIPTIONDESCRIPTION
DESCRIPTION
DESCRIPTIONDESCRIPTION
• Temperature override until next program period
• Manual program override (HOLD temperature)
• Temporary HOLD
• °F/°C convertibility
• Temperature range 45° to 90°F
• RC, RH, C, W, Y, G , O and B terminals
• Optional C terminal (Dual Power option)
• B and O terminals for single stage heat pumps (no auxiliary heat) or damper operation
• Program storage in case of power loss
• 2 “AA” Energizer
®
alkaline batteries included
This thermostat is intended for use with a low voltage system; do not use this thermostat with a line voltage system. If in doubt about whether your wiring is millivolt, line, or low voltage, have it inspected by a qualified heating and air conditioning contractor or electrician.
Do not exceed the specification ratings. All wiring must conform to local and national electrical codes and
ordinances. This control is a precision instrument, and should be handled
carefully. Rough handling or distorting components could cause the control to malfunction.
CAUTIONCAUTION
!
CAUTION
CAUTIONCAUTION
To prevent electrical shock and/or equipment damage,To prevent electrical shock and/or equipment damage,
To prevent electrical shock and/or equipment damage,
To prevent electrical shock and/or equipment damage,To prevent electrical shock and/or equipment damage, disconnect electric power to system at main fuse ordisconnect electric power to system at main fuse or
disconnect electric power to system at main fuse or
disconnect electric power to system at main fuse ordisconnect electric power to system at main fuse or circuit breaker box until installation is complete.circuit breaker box until installation is complete.
circuit breaker box until installation is complete.
circuit breaker box until installation is complete.circuit breaker box until installation is complete.
ELECTRICAL DATAELECTRICAL DATA
ELECTRICAL DATA
ELECTRICAL DATAELECTRICAL DATA Electrical Rating:Electrical Rating:
Electrical Rating:
Electrical Rating:Electrical Rating:
8 to 30 VAC 50/60 Hz. or D.C.
0.05 to 1.0 Amps (Load per terminal)
1.5 Amps Maximum Total Load1.5 Amps Maximum Total Load
1.5 Amps Maximum Total Load (All terminals combined)
1.5 Amps Maximum Total Load1.5 Amps Maximum Total Load
THERMAL DATATHERMAL DATA
THERMAL DATA
THERMAL DATATHERMAL DATA Setpoint Temperature Range:Setpoint Temperature Range:
Setpoint Temperature Range:
Setpoint Temperature Range:Setpoint Temperature Range:
45°F to 90°F (7°C to 32°C)
Operating Ambient Temperature Range:Operating Ambient Temperature Range:
Operating Ambient Temperature Range:
Operating Ambient Temperature Range:Operating Ambient Temperature Range:
32°F to 105°F
Operating Humidity Range:Operating Humidity Range:
Operating Humidity Range:
Operating Humidity Range:Operating Humidity Range:
0 to 90% RH (non-condensing)
Shipping Temperature Range:Shipping Temperature Range:
Shipping Temperature Range:
Shipping Temperature Range:Shipping Temperature Range:
-4°F to 149°F
PRECAUTIONSPRECAUTIONS
PRECAUTIONS
PRECAUTIONSPRECAUTIONS
WARNINGWARNING
!
WARNING
WARNINGWARNING
Do not use on circuits exceeding specified voltage.Do not use on circuits exceeding specified voltage.
Do not use on circuits exceeding specified voltage.
Do not use on circuits exceeding specified voltage.Do not use on circuits exceeding specified voltage. Higher voltage will damage control and could causeHigher voltage will damage control and could cause
Higher voltage will damage control and could cause
Higher voltage will damage control and could causeHigher voltage will damage control and could cause shock or fire hazard.shock or fire hazard.
shock or fire hazard.
shock or fire hazard.shock or fire hazard.
Do not short out terminals on gas valve or primaryDo not short out terminals on gas valve or primary
Do not short out terminals on gas valve or primary
Do not short out terminals on gas valve or primaryDo not short out terminals on gas valve or primary control to test. Short or incorrect wiring will damagecontrol to test. Short or incorrect wiring will damage
control to test. Short or incorrect wiring will damage
control to test. Short or incorrect wiring will damagecontrol to test. Short or incorrect wiring will damage thermostat and could cause personal injury and/orthermostat and could cause personal injury and/or
thermostat and could cause personal injury and/or
thermostat and could cause personal injury and/orthermostat and could cause personal injury and/or property damage.property damage.
property damage.
property damage.property damage.
Thermostat installation and all components of theThermostat installation and all components of the
Thermostat installation and all components of the
Thermostat installation and all components of theThermostat installation and all components of the system shall conform to Class II circuits per the NECsystem shall conform to Class II circuits per the NEC
system shall conform to Class II circuits per the NEC
system shall conform to Class II circuits per the NECsystem shall conform to Class II circuits per the NEC code.code.
code.
code.code.
SPECIFICATIONSSPECIFICATIONS
SPECIFICATIONS
APPLICATIONSAPPLICATIONS
APPLICATIONS
APPLICATIONSAPPLICATIONS
For use with:
• Standard heat/cool or heat only systems
• Electric heat systems
• Gas or oil fired systems
• Gas systems with intermittent ignition devices (I.I.D.)
and/or vent dampers
• Hydronic (hot water or steam) systems
• Single-stage heat pump systems (no auxiliary heat)
• Millivolt systems
DO NOT USE WITH:DO NOT USE WITH:
DO NOT USE WITH:
DO NOT USE WITH:DO NOT USE WITH:
• Multi-stage systems
• Systems exceeding 30 VAC and 1.5 amps
• 3-wire zoned hydronic heating systems
SPECIFICATIONSSPECIFICATIONS
White-Rodgers is a division
of Emerson Electric Co.
www.white-rodgers.com
PART NO. 37-6621BPART NO. 37-6621B
PART NO. 37-6621B
PART NO. 37-6621BPART NO. 37-6621B
Replaces 37-6621A
0512
Page 2
INSTALLATIONINSTALLATION
INSTALLATION
INSTALLATIONINSTALLATION
REMOVE OLD THERMOSTATREMOVE OLD THERMOSTAT
REMOVE OLD THERMOSTAT
REMOVE OLD THERMOSTATREMOVE OLD THERMOSTAT
1. Shut off electricity at the main fuse box until installation is complete. Ensure that electrical power is disconnected.
2. Remove the front cover of the old thermostat. still attached, still attached,
still attached, remove wall plate from the wall. If the old
still attached, still attached, thermostat has a wall mounting plate, remove the thermo­stat and the wall mounting plate as an assembly.
Identify each wire attached to the old thermostat usingIdentify each wire attached to the old thermostat using
3.
Identify each wire attached to the old thermostat using
Identify each wire attached to the old thermostat usingIdentify each wire attached to the old thermostat using the labels enclosed with the new thermostat.the labels enclosed with the new thermostat.
the labels enclosed with the new thermostat.
the labels enclosed with the new thermostat.the labels enclosed with the new thermostat.
4. Disconnect the wires from old thermostat one at a time. NOT LET WIRES FALL BACK INTO THE WALL.NOT LET WIRES FALL BACK INTO THE WALL.
NOT LET WIRES FALL BACK INTO THE WALL.
NOT LET WIRES FALL BACK INTO THE WALL.NOT LET WIRES FALL BACK INTO THE WALL.
5. Install new thermostat using the following procedures.
With wiresWith wires
With wires
With wiresWith wires
DODO
DO
DODO
Screw anchors
ATTENTION!ATTENTION!
ATTENTION!
ATTENTION!ATTENTION!
This product does not contain mercury. However, this product may replace a unit which contains mercury.
Do not open mercury cells. If a cell becomes damaged, do not touch any spilled mercury. Wearing nonabsorbent gloves, take up the spilled mercury with sand or other absorbent material and place into a container which can be sealed. If a cell becomes damaged, the unit should be discarded.
Mercury must not be discarded in household trash. When the unit this product is replacing is to be discarded, place in a suitable container and return to White-Rodgers at 2895 Harrison Street, Batesville, AR 72501 for proper disposal.
ELECTRIC HEAT OR SINGLE-STAGEELECTRIC HEAT OR SINGLE-STAGE
ELECTRIC HEAT OR SINGLE-STAGE
ELECTRIC HEAT OR SINGLE-STAGEELECTRIC HEAT OR SINGLE-STAGE
HEAT PUMP SYSTEMSHEAT PUMP SYSTEMS
HEAT PUMP SYSTEMS
HEAT PUMP SYSTEMSHEAT PUMP SYSTEMS
This thermostat is configured from the factory to operate a heat/ cool, fossil fuel (gas, oil, etc.), forced air system. It is configured correctly for any system that DOES NOT require the thermostat to energize the fan on a call for heat. If your system is an electric heat or heat-pump system that REQUIRES the thermostat to turn on the fan on a call for heat, locate the switch switch
switch on the back of the thermostat (see fig. 1) and switch it to
switch switch
ELECTRIC ELECTRIC
the
ELECTRIC position. This will allow the thermostat to
ELECTRIC ELECTRIC energize the fan immediately on a call for heat. If you are unsure if the heating/cooling system requires the thermostat to control the fan, contact a qualified heating and air conditioning service person.
ATTACH THERMOSTAT BASE TO WALLATTACH THERMOSTAT BASE TO WALL
ATTACH THERMOSTAT BASE TO WALL
ATTACH THERMOSTAT BASE TO WALLATTACH THERMOSTAT BASE TO WALL
1. Remove the packing material from the thermostat. Gently
pull the cover straight off the base. Forcing or prying on the thermostat will cause damage to the unit. If necessary, move the electric heat switch (see above).
2. Connect wires beneath terminal screws on base using
appropriate wiring schematic (see figs. 2 through 7).
3. Place base over hole in wall and mark mounting hole
locations on wall using base as a template.
4. Move base out of the way. Drill mounting holes.
5. Fasten base loosely to wall, as shown in fig. 1, using two
mounting screws. Place a level against bottom of base, adjust until level, and then tighten screws. (Leveling is for appearance only and will not affect thermostat operation.) If you are using existing mounting holes, or if holes drilled are too large and do not allow you to tighten base snugly, use plastic screw anchors to secure subbase.
ELECTRIC HEAT SYSTEMSELECTRIC HEAT SYSTEMS
ELECTRIC HEAT SYSTEMS,
ELECTRIC HEAT SYSTEMSELECTRIC HEAT SYSTEMS
ELECTRIC/GASELECTRIC/GAS
ELECTRIC/GAS
ELECTRIC/GASELECTRIC/GAS
Mounting
holes
Electric/Gas
switch
Figure 1. Thermostat BaseFigure 1. Thermostat Base
Figure 1. Thermostat Base
Figure 1. Thermostat BaseFigure 1. Thermostat Base
6. Push excess wire into wall and plug hole with a fire-resistant material (such as fiberglass insulation) to prevent drafts from affecting thermostat operation.
BATTERY LOCATIONBATTERY LOCATION
BATTERY LOCATION
BATTERY LOCATIONBATTERY LOCATION
2 "AA" alkaline batteries are included in the thermostat at the factory with a battery tag to prevent power drainage. remove the battery tag to engage the batteriesremove the battery tag to engage the batteries
remove the battery tag to engage the batteries.
remove the battery tag to engage the batteriesremove the battery tag to engage the batteries
“BATT”“BATT”
If
“BATT” is displayed, the batteries are low and should be
“BATT”“BATT” replaced with fresh "AA" Energizer® alkaline batteries. To replace batteries, install the batteries along the top of the base (see Fig. 1). The batteries must be installed with the positive (+) end to the left.
HYDRONIC (HOT WATER OR STEAM)HYDRONIC (HOT WATER OR STEAM)
HYDRONIC (HOT WATER OR STEAM)
HYDRONIC (HOT WATER OR STEAM)HYDRONIC (HOT WATER OR STEAM)
HEATING SYSTEMSHEATING SYSTEMS
HEATING SYSTEMS
HEATING SYSTEMSHEATING SYSTEMS
This thermostat is set to operate properly with a forced-air heating system. If you have a hydronic heating system (a system that heats with hot water or steam), you must set the thermostat to operate properly with your system. Change the second option in the configuration menu to SL (see CONFIGU­RATION MENU, page 4).
CHECK THERMOSTAT OPERATIONCHECK THERMOSTAT OPERATION
CHECK THERMOSTAT OPERATION
CHECK THERMOSTAT OPERATIONCHECK THERMOSTAT OPERATION
If at any time during testing your system does not operate properly, contact a qualified service person.
Turn on power to the system.
Fan OperationFan Operation
Fan Operation
Fan OperationFan Operation
If your system Heating SystemHeating System
Heating System.
Heating SystemHeating System
1. Move FAN switch to ON position. The blower should begin
to operate.
2. Move FAN switch to
stop immediately.
does notdoes not
does not have a
does notdoes not
GG
G terminal connection, skip to
GG
AUTO AUTO
AUTO position. The blower should
AUTO AUTO
Mounting
holes
You mustYou must
You must
You mustYou must
2
Page 3
JUMPER
RH
Y
24 VAC
120 VAC
Hot
Neutral
THERMOSTAT
SYSTEM
G W
Figure 6. Typical wiring diagram for heat pump
with reversing valve energized in COOL
TRANSFORMER
Reversing
Valve*
RCOBC
JUMPER
WIRE
Compressor
Contactor
JUMPER
WIRE
* Reversing valve is energized when the system switch is in the COOL position
Fan
Relay
RH
Y
24 VAC
120 VAC
Hot
Neutral
THERMOSTAT
SYSTEM
G W
Figure 7. Typical wiring diagram for heat pump
with reversing valve energized in HEAT
TRANSFORMER
Reversing
Valve*
RCO
B
C
JUMPER
WIRE
Compressor
Contactor
JUMPER
WIRE
* Reversing valve is energized when the system switch is in the HEAT position
Fan
Relay
WIRE
YC
OB
G W
Fan
Relay
Heating System
RC
NOTE
For 2-wire Heat only, attach to RH and W
Figure 2. Typical wiring diagram for
heat only, 3-wire, single transformer systems
JUMPER
WIRE
C
Y
Cooling System
G W
Fan
Relay
RCOB
24 VAC
RH
TRANSFORMER
Figure 3. Typical wiring diagram for
cool only, 3-wire, single transformer systems
THERMOSTAT
RH
SYSTEM
24 VAC
TRANSFORMER
THERMOSTAT
SYSTEM
120 VAC
Hot
120 VAC
Neutral
Hot
Neutral
OBC
Y
Cooling System
G W
Fan
Relay
Heating
System
RC
24 VAC
24 VAC
COOLING TRANSFORMER
Figure 5. Typical wiring diagram for
heat/cool, 5-wire, two-transformer systems
THERMOSTAT
RH
SYSTEM
HEATING
TRANSFORMER
Hot
120 VAC
Neutral
Hot
120 VAC
Neutral
RED jumper wire (provided with thermostat) must be connected between thermostat RH and RC terminals for proper thermostat operation with this system.
Y
OC‡B
Cooling System
G W
Fan
Relay
Heating System
Figure 4. Typical wiring diagram for
heat/cool, 4-wire, single transformer systems
NOTE
The 24 Volt neutral connection to terminal C on the thermostat is not required if the batteries are replaced once a year with fresh "AA" Energizer® alkaline batteries.
Heating SystemHeating System
Heating System
Heating SystemHeating System
1. Move SYSTEM switch to system has a standing pilot, be sure to light it.
2. Press to adjust thermostat setting above room tempera­ture. The heating system should begin to operate.
3. Press
to adjust temperature setting below room tem-
perature. The heating system should stop operating.
HEATHEAT
HEAT position. If the heating
HEATHEAT
JUMPER
WIRE
RC
24 VAC
THERMOSTAT
RH
SYSTEM
TRANSFORMER
Hot
120 VAC
Neutral
Cooling SystemCooling System
Cooling System
Cooling SystemCooling System
CAUTIONCAUTION
!
CAUTION
CAUTIONCAUTION
To prevent compressor and/or property damage, if theTo prevent compressor and/or property damage, if the
To prevent compressor and/or property damage, if the
To prevent compressor and/or property damage, if theTo prevent compressor and/or property damage, if the outdoor temperature is below 50°F, DO NOT operateoutdoor temperature is below 50°F, DO NOT operate
outdoor temperature is below 50°F, DO NOT operate
outdoor temperature is below 50°F, DO NOT operateoutdoor temperature is below 50°F, DO NOT operate the cooling system.the cooling system.
the cooling system.
the cooling system.the cooling system.
1. Move SYSTEM switch to
2. Press
to adjust thermostat setting below room tempera-
COOLCOOL
COOL position.
COOLCOOL
ture. The blower should come on immediately on high speed, followed by cold air circulation
3. Press to adjust temperature setting above room tem­perature. The cooling system should stop operating.
3
Page 4
OPERATIONOPERATION
OPERATION
OPERATIONOPERATION
Before you begin programming your thermostat, you should be familiar with its features and with the display and the location and operation of the thermostat buttons. Your thermostat con­sists of two parts: the remove the cover, pull it straight out from the base. To replace the cover, line up the cover with the base and press until the cover snaps onto the base.
thermostat coverthermostat cover
thermostat cover and the
thermostat coverthermostat cover
basebase
base. To
basebase
The Thermostat Buttons The Thermostat Buttons
The Thermostat Buttons
The Thermostat Buttons The Thermostat Buttons
1
Raises temperature setting.
Lowers temperature setting.
2
TIME button.
3
PRGM (program) button.
4 5
RUN (run program) button.
6
HOLD temperature button.
7
FAN switch ( SYSTEM switch (
8
9
Indicates day of the week. Flame iconFlame icon
Flame icon ( ) is displayed when the SYSTEM switch is in
Flame iconFlame icon
10
the HEAT position. flashing) when the SYSTEM switch is in the COOL position. SnowflakeSnowflake
Snowflake is displayed (flashing) if the thermostat is in
SnowflakeSnowflake lockout mode to prevent the compressor from cycling too quickly.
11
Displays should be replaced. Only field are displayed when batteries are low with no system power.
Alternately displays current time and temperature. Dis-
12
plays
13
The word HOLD mode. thermostat is in a temporary HOLD Mode.
14
Displays currently programmed set temperature (this is blank when SYSTEM switch is in the
15
Displays grammed filter time period as a reminder to change or clean your air filter.
The configuration menu allows you to set certain thermostat operating characteristics to your system or personal require­ments.
Press RUN to make sure the thermostat is in the run program mode, then press PRGM and RUN at the same time to enter the configuration menu. The display will show the first item in the configuration menu.
The configuration menu table summarizes the configuration options. An explanation of each option follows.
ONON
AUTOAUTO
ON,
AUTO).
ONON
AUTOAUTO COOLCOOL
COOL,
COOLCOOL
“BATT”“BATT”
“BATT” when the 2 "AA" batteries are low and
“BATT”“BATT”
“LO”“LO”
“LO” in the minutes field when batteries are low.
“LO”“LO”
“HOLD”“HOLD”
“HOLD” is displayed when the thermostat is in the
“HOLD”“HOLD”
“HOLD”“HOLD”
“HOLD” is displayed flashing when the
“HOLD”“HOLD”
“FLTR”“FLTR”
“FLTR” when the system has run for the pro-
“FLTR”“FLTR”
CONFIGURATION MENUCONFIGURATION MENU
CONFIGURATION MENU
CONFIGURATION MENUCONFIGURATION MENU
OFFOFF
OFF,
OFFOFF
The DisplayThe Display
The Display
The DisplayThe Display
Snowflake iconSnowflake icon
Snowflake icon (
Snowflake iconSnowflake icon
“BATT”“BATT”
“BATT” and
“BATT”“BATT”
and Switchesand Switches
and Switches
and Switchesand Switches
HEATHEAT
HEAT).
HEATHEAT
)is displayed (non-
“LO”“LO”
“LO” in the minutes
“LO”“LO”
OFFOFF
OFF position).
OFFOFF
Press HOLD to change to the next menu item or press TIME to go backwards to the previous item in the menu. To exit the menu and return to the program operation, press RUN. If no keys are pressed within fifteen minutes, the thermostat will revert to normal operation.
1)1)
Select Temporary Hold Time Select Temporary Hold Time
1)
Select Temporary Hold Time - The thermostat can hold any
1)1)
Select Temporary Hold Time Select Temporary Hold Time temperature you set it to for the amount of time you select on this option. Your choices are 0:00 to 8:00 hours in 15 minute increments. 0:00 disables the function
Example:
1. You have selected 3:00 hours for the Temporary Hold time period.
2. With the thermostat set to Heat or Cool, press HOLD approximately five secondsapproximately five seconds
approximately five seconds until HOLD time (3:00
approximately five secondsapproximately five seconds indicating 3 hours) appears as a setting reminder.
3. After releasing the button, blink.
4. Use ence. The thermostat will maintain this temperature setting for 3 hours with it is in Temporary Hold. After 3 hours the thermostat will go back to the program temperature and longer blink or display.
2)2)
Select FA or SL (Fast or Slow) Heating Cycle RateSelect FA or SL (Fast or Slow) Heating Cycle Rate
2)
Select FA or SL (Fast or Slow) Heating Cycle Rate - The
2)2)
Select FA or SL (Fast or Slow) Heating Cycle RateSelect FA or SL (Fast or Slow) Heating Cycle Rate FA setting is frequently used for gas, oil or electric heat. The SL setting produces a longer heating cycle which is nor­mally for hot water or steam (hydronic) systems. Both settings produce very accurate temperature control and can be set to your personal preference. FA cycles the system just under 1°F and the SL setting cycles at approxi­mately 1.5°F.
3)3)
Select backlit displaySelect backlit display
3)
Select backlit display - The display backlight improves
3)3)
Select backlit displaySelect backlit display display contrast in low lighting conditions. Selecting back-
ONON
light
ON will keep the light on for a short period of time after
ONON
any key is pressed. Selecting
or to set the temperature to your prefer-
“HOLD”“HOLD”
“HOLD” on the display will
“HOLD”“HOLD”
“HOLD”“HOLD”
“HOLD” blinking to remind you
“HOLD”“HOLD”
“HOLD”“HOLD”
“HOLD” will no
“HOLD”“HOLD”
OFFOFF
OFF will keep the light off.
OFFOFF
forfor
for
forfor
4
Page 5
Configuration Menu
Step Press Button(s) Displayed (Factory Default) Press or to select: COMMENTS
1
2
3
4
5
6
7
8 9
* Press
4)4)
Select Energy Management Recovery OFF or ONSelect Energy Management Recovery OFF or ON
4)
Select Energy Management Recovery OFF or ON -
4)4)
Select Energy Management Recovery OFF or ONSelect Energy Management Recovery OFF or ON
PRGM
and RUN
*
HOLD
HOLD
*
HOLD
*
HOLD
*
HOLD
*
HOLD
*
HOLD
*
RUN
HOLD to advance to next item or TIME to move backwards to previous item
Energy Management Recovery (EMR) causes the thermo­stat to start heating or cooling early to make the building temperature reach the program setpoint at the time you specify. Heating will start 5 minutes early for every 1° of temperature required to reach setpoint.
Example:Example:
Example: You select EMR and have your heating pro-
Example:Example: grammed to 65° at night and 70° at 7 AM. If the building temperature is 65° the difference between 65° and 70° is 5°. Allowing 5 minutes per degree the thermostat setpoint will change to 70° at 6:35 AM. Cooling allows more time per degree because it takes longer to reach temperature.
5)5)
Select filter replacement run timeSelect filter replacement run time
5)
Select filter replacement run time - The thermostat will
5)5)
Select filter replacement run timeSelect filter replacement run time display
“FLTR” “FLTR”
“FLTR” after a set time of operation. This is a
“FLTR” “FLTR” reminder to change or clean your air filter. This time can be set from 0 to 1950 hours in 50 hour increments. of 000 will cancel this feature.of 000 will cancel this feature.
of 000 will cancel this feature. When
of 000 will cancel this feature.of 000 will cancel this feature. you can clear it by pressing HOLD and RUN at the same time. This resets the timer and starts counting the hours until the next filter change. Changing the time in the menu also resets the timer.
6)6)
Select Compressor Lockout LOC OFF or ONSelect Compressor Lockout LOC OFF or ON
6)
Select Compressor Lockout LOC OFF or ON - Selecting
6)6)
Select Compressor Lockout LOC OFF or ONSelect Compressor Lockout LOC OFF or ON LOC ON will cause the thermostat to wait 5 minutes before turning on the compressor if the heating and cooling sys­tem loses power. It will also wait 5 minutes minimum between cooling cycles. This is intended to help protect the compressor from short cycling. Some newer compressors already have a time delay built in and do not require this feature. Your compressor manufacturer can tell you if the feature is already present in their system. When the compressor time delay occurs it will flash the (snowflake icon) for about five minutes then turn on the compressor.
7)7)
Select Temperature Display Adjustment 4 LO to 4 HISelect Temperature Display Adjustment 4 LO to 4 HI
7)
Select Temperature Display Adjustment 4 LO to 4 HI -
7)7)
Select Temperature Display Adjustment 4 LO to 4 HISelect Temperature Display Adjustment 4 LO to 4 HI Allows you to adjust the room temperature display 4° higher or lower. Your thermostat was accurately calibrated at the factory but you have the option to change the display temperature to match your previous thermostat.
8)8)
Select F° or C° ReadoutSelect F° or C° Readout
8)
Select F° or C° Readout - Changes the display readout to
8)8)
Select F° or C° ReadoutSelect F° or C° Readout Centigrade or Fahrenheit as required.
HOLD
(0:00)
(FA)
d-L
(ON)
E
(ON) Filter
(000) LOC
(OFF)
0 HI
(0)
(F) C
A selectionA selection
A selection
A selectionA selection
“FLTR”“FLTR”
“FLTR” is displayed,
“FLTR”“FLTR”
0 to 8 hrs (in
15 minute increments)
0 to 1950 hours
(in 50 hour increments)
Select temporary Hold time
SL
OFF
OFF
ON
4 LO to
4 HI
Select FA or SL (Fast or Slow) heating cycle rate
Select display backlight OFF or ON
Select Energy Management Recovery OFF or ON
Select filter replacement run time
Select compressor lockout OFF or ON
Select temperature display adjustment higher or lower
Select temperature display to F or C Returns to normal operation
OPERATING FEATURESOPERATING FEATURES
OPERATING FEATURES
OPERATING FEATURESOPERATING FEATURES
Now that you are familiar with the thermostat buttons and display, read the following information to learn about the many features of the thermostat.
SIMULTANEOUS HEATING/COOLING PROGRAMSIMULTANEOUS HEATING/COOLING PROGRAM
SIMULTANEOUS HEATING/COOLING PROGRAM
SIMULTANEOUS HEATING/COOLING PROGRAMSIMULTANEOUS HEATING/COOLING PROGRAM STORAGE STORAGE
STORAGE — When programming, you can enter both
STORAGE STORAGE your heating and cooling programs at the same time. There is no need to reprogram the thermostat at the beginning of each season.
TEMPERATURE OVERRIDETEMPERATURE OVERRIDE
TEMPERATURE OVERRIDE — Press
TEMPERATURE OVERRIDETEMPERATURE OVERRIDE display shows the temperature you want. The thermostat will override current programming and keep the room temperature at the selected temperature until the next program period begins. Then the thermostat will automati­cally revert to the program.
HOLD TEMPERATUREHOLD TEMPERATURE
HOLD TEMPERATURE — The thermostat can hold any
HOLD TEMPERATUREHOLD TEMPERATURE temperature within its range for an indefinite period without reverting to the programmed temperature. Momentarily press HOLD button.
“HOLD”“HOLD”
“HOLD” will be displayed. Then choose
“HOLD”“HOLD” the desired temperature by pressing thermostat will hold the room temperature at the selected setting until you press RUN button to start program opera­tion again.
CONFIGURATION MENUCONFIGURATION MENU
CONFIGURATION MENU — Allows you to customize
CONFIGURATION MENUCONFIGURATION MENU certain thermostat options.
PROGRAMMING YOUR THERMOSTATPROGRAMMING YOUR THERMOSTAT
PROGRAMMING YOUR THERMOSTAT
PROGRAMMING YOUR THERMOSTATPROGRAMMING YOUR THERMOSTAT
This section will help you plan your thermostat’s program to meet your needs. For maximum comfort and efficiency, keep the following guidelines in mind when planning your program.
• When heating (cooling) your building, program the temperatures to be cooler (warmer) when the building is vacant or during periods of low activity.
• During early morning hours, the need for cooling is usually minimal.
or until the
or . The
5
Page 6
AM
MO TU WE TH FR
Planning Your ProgramPlanning Your Program
Planning Your Program
Planning Your ProgramPlanning Your Program
Look at the factory preprogrammed times and temperatures shown in the sample schedule. If this program will suit your needs, simply press the RUN button to begin running the factory preset program.
If you want to change the preprogrammed times and tempera­tures, follow these steps.
Determine the time periods and temperatures for your weekday and weekend programs. You must program four periods for both the weekday and weekend program. However, you may use the same heating and cooling temperatures for consecutive time periods. You can choose start times, heating tempera­tures, and cooling temperatures independently for both week­day and weekend programs (for example, you may select 5:00 AM and 70° as the weekday
1st period heating1st period heating
1st period heating start time and
1st period heating1st period heating temperature, and also choose 7:00 AM and 76° as the weekday 1st period cooling1st period cooling
1st period cooling start time and temperature).
1st period cooling1st period cooling Use the following table to plan your program time periods and
the temperatures you want during each period. Fill in the complete table to have a record of your programs.
Entering Your ProgramEntering Your Program
Entering Your Program
Entering Your ProgramEntering Your Program
Follow these steps to enter the heating and cooling programs you have selected.
Set Current Time and DaySet Current Time and Day
Set Current Time and Day
Set Current Time and DaySet Current Time and Day
1. Press TIME button once. The display will show the hour only.
EXAMPLE:
PM
2. Press and hold either or until you reach the correct
hour and AM/PM designation (
AMAM
AM begins at midnight;
AMAM
PMPM
PM
PMPM
begins at noon).
3. Press TIME once. The display window will show the minutes
only.
EXAMPLE:
4. Press and hold either or until you reach the correct
minutes.
5. Press TIME once. The display will show the day of the week.
6. Press or until you reach the current day of the week.
7. Press RUN once. The display will show the correct time and
room temperature alternately.
Enter Heating ProgramEnter Heating Program
Enter Heating Program
Enter Heating ProgramEnter Heating Program
1. Move the SYSTEM switch to
2. Press PRGM once. “
MO TU WE TH FRMO TU WE TH FR
MO TU WE TH FR” (indicating week-
MO TU WE TH FRMO TU WE TH FR
HEATHEAT
HEAT.
HEATHEAT
day program) will appear in the display. Also displayed are the currently programmed start time for the
1st heating1st heating
1st heating
1st heating1st heating period and the currently programmed temperature (flash­ing).
EXAMPLE:
This display window shows that for the 1st weekday period, the start time is 6:00 AM, and 68° is the programmed temperature (this example reflects factory preprogramming).
3. Press
or to change the displayed temperature to
your selected temperature for the 1st heating program period.
4. Press TIME once (the programmed time will flash). Press or until your selected time appears. The time will
change in 15 minute increments. When your selected time is displayed, press TIME again to return to the change temperature mode.
5. Press PRGM once. The currently programmed start time
and setpoint temperature for the
2nd heating2nd heating
2nd heating program
2nd heating2nd heating
period will appear.
6. Repeat steps 3 and 4 to select the start time and heating
temperature for the 2nd heating program period.
7. Repeat steps 3 through 5 for the 3rd and 4th heating
program periods. Weekday heating programs are now com­plete.
8. Press PRGM once. “
SASA
SA” (indicating Saturday program) will
SASA appear in the display, along with the start time for the 1st heating period and the currently programmed temperature.
9. Repeat steps 3 through 7 to complete Saturday heating programming.
10.Press PRGM once. “
SUSU
SU” (indicating Sunday program) will
SUSU appear in the display, along with the start time for the 1st heating period and the currently programmed temperature.
11.Repeat steps 3 through 7 to complete Sunday heating programming.
12.When you have completed entering your heating program, press RUN.
Heating/Cooling Schedule Plan (Factory Program)
WEEKDAY (5 DAY)
Period
1ST 6:00 AM 70˚F 6:00 AM 70˚F 6:00 AM 70˚F 2ND 8:00 AM 62˚F 8:00 AM 62˚F 8:00 AM 62˚F 3RD 5:00 PM 70˚F 5:00 PM 70˚F 5:00 PM 70˚F 4TH 10:00 PM 62˚F 10:00 PM 62˚F 10:00 PM 62˚F 1ST 6:00 AM 78˚F 6:00 AM 78˚F 6:00 AM 78˚F 2ND 8:00 AM 85˚F 8:00 AM 85˚F 8:00 AM 85˚F
COOL HEAT
3RD 5:00 PM 78˚F 5:00 PM 78˚F 5:00 PM 78˚F 4TH 10:00 PM 82˚F 10:00 PM 82˚F 10:00 PM 82˚F
Start Time Temperature
SAMPLE
SATURDAY (1 DAY)
Start Time Temperature
SUNDAY (1 DAY)
Start Time Temperature
Period
COOL HEAT
1ST 2ND 3RD 4TH 1ST 2ND 3RD 4TH
Heating/Cooling Schedule Plan
WEEKDAY (5 DAY)
Start Time Temperature
SATURDAY (1 DAY)
Start Time Temperature
SUNDAY (1 DAY)
Start
Time Temperature
6
Page 7
Enter Cooling ProgramEnter Cooling Program
Enter Cooling Program
Enter Cooling ProgramEnter Cooling Program
CAUTIONCAUTION
!
CAUTION
CAUTIONCAUTION
If the outside temperature is below 50°F, disconnectIf the outside temperature is below 50°F, disconnect
If the outside temperature is below 50°F, disconnect
If the outside temperature is below 50°F, disconnectIf the outside temperature is below 50°F, disconnect power to the cooling system before programming.power to the cooling system before programming.
power to the cooling system before programming.
power to the cooling system before programming.power to the cooling system before programming. Energizing the air conditioner compressor duringEnergizing the air conditioner compressor during
Energizing the air conditioner compressor during
Energizing the air conditioner compressor duringEnergizing the air conditioner compressor during cold weather may cause personal injury or propertycold weather may cause personal injury or property
cold weather may cause personal injury or property
cold weather may cause personal injury or propertycold weather may cause personal injury or property damage.damage.
damage.
damage.damage.
1. Move SYSTEM switch to
2. Follow the procedure for entering your cooling program, using your selected cooling times and temperatures.
Reset OperationReset Operation
Reset Operation
Reset OperationReset Operation If a voltage spike or static discharge blanks out the display or causes erratic thermostat operation you can reset the thermo-
stat by pressing resets the factory defaults to the configuration menu and
, and TIME at the same time. This also
COOLCOOL
COOL position.
COOLCOOL
CHECK YOUR PROGRAMMINGCHECK YOUR PROGRAMMING
CHECK YOUR PROGRAMMING
CHECK YOUR PROGRAMMINGCHECK YOUR PROGRAMMING
Follow these steps to check your thermostat programming one final time before beginning thermostat operation.
1. Move SYSTEM switch to
2. Press PRGM to view the 1st weekday heating period time and temperature. Each time you press PRGM, the next heating period time and temperature will be displayed in sequence for weekday, then weekend program periods (you may change any time or temperature during this procedure).
3. Press RUN.
4. Move SYSTEM switch to
5. Repeat step 2 to check cooling program.
6. Move SYSTEM switch to begin program operation.
YOUR THERMOSTAT IS NOW COMPLETELY PROGRAMMED ANDYOUR THERMOSTAT IS NOW COMPLETELY PROGRAMMED AND
YOUR THERMOSTAT IS NOW COMPLETELY PROGRAMMED AND
YOUR THERMOSTAT IS NOW COMPLETELY PROGRAMMED ANDYOUR THERMOSTAT IS NOW COMPLETELY PROGRAMMED AND READY TO PROVIDE MAXIMUM COMFORT AND EFFICIENCY!READY TO PROVIDE MAXIMUM COMFORT AND EFFICIENCY!
READY TO PROVIDE MAXIMUM COMFORT AND EFFICIENCY!
READY TO PROVIDE MAXIMUM COMFORT AND EFFICIENCY!READY TO PROVIDE MAXIMUM COMFORT AND EFFICIENCY!
program. If the thermostat has power, has been reset and still does not function correctly contact your heating/cooling ser­vice person or place of purchase.
BatteriesBatteries
Batteries
BatteriesBatteries For optimum performance, we recommend replacing batteries once a year with fresh "AA" Energizer® alkaline batteries.
HEATHEAT
HEAT position.
HEATHEAT
COOLCOOL
COOL position.
COOLCOOL
HEATHEAT
HEAT or
HEATHEAT
TROUBLESHOOTINGTROUBLESHOOTING
TROUBLESHOOTING
TROUBLESHOOTINGTROUBLESHOOTING
COOLCOOL
COOL and press RUN to
COOLCOOL
SymptomSymptom
Symptom
SymptomSymptom
No Heat/No Cool/No FanNo Heat/No Cool/No Fan
No Heat/No Cool/No Fan 1. Blown fuse or tripped circuit breaker. Replace fuse or reset breaker.
No Heat/No Cool/No FanNo Heat/No Cool/No Fan (common problems)(common problems)
(common problems) 2. Furnace power switch to OFF. Turn switch to ON.
(common problems)(common problems)
No HeatNo Heat
No Heat 1. Pilot light not lit. Re-light pilot.
No HeatNo Heat
No CoolNo Cool
No Cool 1. SYSTEM Switch not set to
No CoolNo Cool
PP
ossibossib
le Causele Cause
P
ossib
le Cause
PP
ossibossib
le Causele Cause
3. Furnace blower compartment door or Replace door panel in proper position to engage panel loose or not properly installed. safety interlock or door switch.
HEAHEA
2. SYSTEM Switch not set to
3. Loose connection to thermostat or system. Verify thermostat and system wires are securely
4. Furnace Lock-Out Condition. Heat may also Many furnaces have safety devices that shut the be intermittent. system down when a lock-out condition occurs.
5. Heating System requires service or Diagonistic: Set SYSTEM Switch to thermostat requires replacement. the setpoint above room temperature. Within a few
2. Loose connection to thermostat or system. Verify thermostat and system wires are securely
3. Cooling System requires service or thermostat Same procedure as diagnostic for No Heat requires replacement. condition except set the thermostat to
TT
HEA
T. Set SYSTEM Switch to
HEAHEA
TT
COOLCOOL
COOL Set SYSTEM Switch to
COOLCOOL
Corrective ActionCorrective Action
Corrective Action
Corrective ActionCorrective Action
Heat Heat
Heat and raise setpoint
Heat Heat
above room temperature.
attached.
If the heat works intermittently contact the furnace manufacturer or local service person for assistance.
seconds the thermostat should make a soft click sound. This sound usually indicates the thermostat is operating properly. If the thermostat does not click, try the reset operation listed above. If the thermostat does not click after being reset contact your heating and cooling service person or place of purchase for a replacement. If the thermostat clicks, contact the furnace manufacturer or a service person to verify the heating system is operating correctly.
COOLCOOL
COOL and lower setpoint
COOLCOOL
below room temperature.
attached.
lower the setpoint below the room temperature. There may be up to a five minute delay before the thermostat clicks in Cooling if the compressor lock-out option is selected in the configuration menu (Item 6).
HEAHEA
TT
HEA
T and raise
HEAHEA
TT
COOLCOOL
COOL and
COOLCOOL
7
Page 8
TROUBLESHOOTINGTROUBLESHOOTING
TROUBLESHOOTING
TROUBLESHOOTINGTROUBLESHOOTING
SymptomSymptom
Symptom
SymptomSymptom
Heat, Cool or Fan Runs Constantly.Heat, Cool or Fan Runs Constantly.
Heat, Cool or Fan Runs Constantly. 1. FAN Switch set to Fan ON. Check each wire connection to verify they are
Heat, Cool or Fan Runs Constantly.Heat, Cool or Fan Runs Constantly.
Furnace Cycles Too Fast or Too SlowFurnace Cycles Too Fast or Too Slow
Furnace Cycles Too Fast or Too Slow 1. The location of the thermostat and/or the size Item 2 in the Configuration Menu is the adjustment
Furnace Cycles Too Fast or Too SlowFurnace Cycles Too Fast or Too Slow (narrow or wide temperature swing)(narrow or wide temperature swing)
(narrow or wide temperature swing) of the Heating System may be influencing the that controls the cycle rate. If an acceptable cycle
(narrow or wide temperature swing)(narrow or wide temperature swing)
Cooling Cycles Too Fast or Too SlowCooling Cycles Too Fast or Too Slow
Cooling Cycles Too Fast or Too Slow 1. The location of the thermostat and/or the size The cycle rate for cooling is fixed and can not be
Cooling Cycles Too Fast or Too SlowCooling Cycles Too Fast or Too Slow (narrow or wide temperature swing)(narrow or wide temperature swing)
(narrow or wide temperature swing) of the Cooling System may be influencing the adjusted. Contact a local service person for
(narrow or wide temperature swing)(narrow or wide temperature swing)
Thermostat Setting and ThermometerThermostat Setting and Thermometer
Thermostat Setting and Thermometer 1. Thermostat thermometer setting requires The thermometer can be adjusted +/- 4 degrees as
Thermostat Setting and ThermometerThermostat Setting and Thermometer DisagreeDisagree
Disagree adjustment. listed in item 7 of the Configuration Menu. No other
DisagreeDisagree
Clock Loses or Gains TimeClock Loses or Gains Time
Clock Loses or Gains Time 1. Loss of power to thermostat and low batteries. The thermostat will maintain its program in memory
Clock Loses or Gains TimeClock Loses or Gains Time
Heat or Cool Starts EarlyHeat or Cool Starts Early
Heat or Cool Starts Early 1. EMR activated See Configuration Menu (Item 4).
Heat or Cool Starts EarlyHeat or Cool Starts Early Thermostat Does Not Follow ProgramThermostat Does Not Follow Program
Thermostat Does Not Follow Program 1. AM or PM set incorrectly in program. Check current clock and program settings including
Thermostat Does Not Follow ProgramThermostat Does Not Follow Program
Blank Display and/or Keypad NotBlank Display and/or Keypad Not
Blank Display and/or Keypad Not 1. Loss of power and dead batteries. Replace batteries and check heat/cool system for
Blank Display and/or Keypad NotBlank Display and/or Keypad Not RespondingResponding
Responding 2. Voltage Spike or Static Discharge. proper operation. If a voltage spike or static discharge
RespondingResponding
Possible CausePossible Cause
Possible Cause
Possible CausePossible Cause
2. Possible short in wiring. not shorted or touching together. No bare wire
3. Possible short in thermostat. should stick out from under terminal screws.
4. Possible short in Heat/Cool/Fan system. Try resetting the thermostat. If the condition
cycle rate. rate is not achieved using the FA (Fast) or SL
cycle rate. suggestions.
2. AM or PM set incorrectly on the clock. the AM or PM designations for each time period.
3. Voltage spike or static discharge. If a voltage spike or static discharge occurs use the
Corrective ActionCorrective Action
Corrective Action
Corrective ActionCorrective Action
persists the manufacturer of your system or service person can instruct you on how to test the Heat/Cool system for correct operation. If the system operates correctly, replace the thermostat.
(Slow) adjustment contact a local service person for additional suggestions.
adjustment is possible.
even with no power/no batteries but the clock time will be incorrect when power is restored. See No Heat/No Cool/No Fan (common problems) above for items to check in the system.
Reset Operation listed above.
occurs use the Reset Operation listed above.
The Emerson logo is a trademark and a service mark of Emerson Electric Co.
Loading...