White Rodgers 1F80-241 User Manual

Operator: Save these instructions for future use!
FAILURE TO READ AND FOLLOW ALL INSTRUCTIONS CAREFULLY BEFORE INSTALLING OR OPERATING THIS CONTROL COULD CAUSE PERSONAL INJURY AND/OR PROPERTY DAMAGE.
Your new White-Rodgers 5-Day/1-Day/1-Day Digital Thermo­stat uses the technology of a solid-state microcomputer to provide precise time/temperature control. This thermostat offers you the flexibility to design heating and cooling programs that fit your needs.
Features:
• 24 Volt System powered.
• Separate 5-day (weekday), 1-day (Sat) and 1-day (Sun) pro­gramming with four separate time/temperature settings per day
• Simultaneous heat and cool program storage
• Preprogrammed temperature control
• Backlit display
1F80-241
Programmable Electronic Digital Thermostat
INSTALLATION AND
OPERATION INSTRUCTIONS
DESCRIPTION
• LCD continuously displays set point, and alternately dis­plays time and room temperature
• Temperature override until next program period
• Manual program override (HOLD temperature)
• Temporary HOLD
°F/°C convertibility
• Temperature range 45° to 90°F
• RC, RH, C, W, Y, G , O and B terminals
• B and O terminals for single stage heat pumps (no auxiliary heat) or damper operation
• Program storage in case of power loss.
PRECAUTIONS
This thermostat is intended for use with a low voltage system; do not use this thermostat with a line voltage system. If in doubt about whether your wiring is millivolt, line, or low voltage, have it inspected by a qualified heating and air conditioning contractor or electrician.
Do not exceed the specification ratings.
All wiring must conform to local and national electrical codes and ordinances.
This control is a precision instrument, and should be handled carefully. Rough handling or distorting components could cause the control to malfunction.
CAUTION
!
To prevent electrical shock and/or equipment dam­age, disconnect electric power to system at main fuse or circuit breaker box until installation is complete.
ELECTRICAL DATA
Electrical Rating:
18 to 30 VAC 50/60 Hz. or D.C.
0.05 to 1.0 Amps (Load per terminal)
1.5 Amps Maximum Total Load (All terminals combined)
THERMAL DATA
Setpoint Temperature Range:
45°F to 90°F (7°C to 32°C)
Operating Ambient Temperature Range:
32°F to 105°F
Operating Humidity Range:
0 to 90% RH (non-condensing)
Shipping Temperature Range:
-4°F to 150°F
WARNING
!
Do not use on circuits exceeding specified voltage. Higher voltage will damage control and could cause shock or fire hazard.
Do not short out terminals on gas valve or primary control to test. Short or incorrect wiring will damage thermostat and could cause personal injury and/or property damage.
Thermostat installation and all components of the system shall conform to Class II circuits per the NEC code.
SPECIFICATIONS
APPLICATIONS
For use with:
Standard heat/cool or heat only systems
Electric heat systems
Gas or oil fired systems
Gas systems with intermittent ignition devices (I.I.D.)
and/or vent dampers
Hydronic (hot water or steam) systems
Single-stage heat pump systems (no auxiliary heat)
DO NOT USE WITH:
Millivolt systems
Multi-stage systems
Systems exceeding 30 VAC and 1.5 amps
3-wire zoned hydronic heating systems
WHITE-RODGERS
EMERSON ELECTRIC CO. 9797 REAVIS ROAD ST. LOUIS, MISSOURI 63123-5398 www.white-rodgers.com
Printed in U.S.A.
PART NO. 37-6313A
0144
INSTALLATION
REMOVE OLD THERMOSTAT
1. Shut off electricity at the main fuse box until installation is complete. Ensure that electrical power is disconnected.
2. Remove the front cover of the old thermostat. With wires still attached, remove wall plate from the wall. If the old thermostat has a wall mounting plate, remove the thermostat and the wall mounting plate as an assembly.
3. Identify each wire attached to the old thermostat using the
labels enclosed with the new thermostat.
4. Disconnect the wires from old thermostat one at a time. DO NOT LET WIRES FALL BACK INTO THE WALL.
5. Install new thermostat using the following procedures..
ATTENTION!
This product does not contain mercury. However, this product may replace a unit which contains mercury.
Do not open mercury cells. If a cell becomes damaged, do not touch any spilled mercury. Wearing non-absorbent gloves, take up the spilled mercury with sand or other absorbent material and place into a container which can be sealed. If a cell becomes damaged, the unit should be discarded.
Mercury must not be discarded in household trash. When the unit this product is replacing is to be discarded, place in a suitable container and return to White-Rodgers at 9797 Reavis Road, St. Louis, MO, 63123-5398 for proper disposal.
ELECTRIC HEAT OR SINGLE-STAGE
HEAT PUMP SYSTEMS
Read entire paragraph before setting electric heat switch. If you are unsure of your application, contact a qualified service person.
If you have a single-stage heat pump system, OR your system uses central electric heat, where the blower is energized by a separate circuit through the fan relay (meaning that the fan turns on immediately on call for heat), then the switch on the thermostat base must be moved to the “ELECTRIC” position (see fig 1). If the thermostat is energizing electric heat sequenc­ers, the switch MUST remain in the “GAS” position.
If you must move the switch to the “ELECTRIC” position (to the left), use a small screwdriver or pencil.
Screw anchors
Mounting
holes
6. Push excess wire into wall and plug hole with a fire-resistant material (such as fiberglass insulation) to prevent drafts from affecting thermostat operation.
Electric/Gas
switch
Mounting
holes
Figure 1. Thermostat Base
HYDRONIC (HOT WATER OR STEAM)
HEATING SYSTEMS
This thermostat is set to operate properly with a forced-air heating system. If you have a hydronic heating system (a system that heats with hot water or steam), you must set the thermostat to operate properly with your system. Change the second option in the configuration menu to SL (see CONFIGURATION MENU, page 4).
CHECK THERMOSTAT OPERATION
If at any time during testing your system does not operate properly, contact a qualified service person.
Turn on power to the system.
ATTACH THERMOSTAT BASE TO WALL
1. Remove the packing material from the thermostat. Gently pull the cover straight off the base. Forcing or prying on the thermostat will cause damage to the unit. If necessary, move the electric heat switch (see ELECTRIC HEAT SYSTEMS, above).
2. Connect wires beneath terminal screws on base using appropriate wiring schematic (see figs. 2 through 7).
3. Place base over hole in wall and mark mounting hole locations on wall using base as a template.
4. Move base out of the way. Drill mounting holes.
5. Fasten base loosely to wall, as shown in fig. 1, using two mounting screws. Place a level against bottom of base, adjust until level, and then tighten screws. (Leveling is for appearance only and will not affect thermostat operation.) If you are using existing mounting holes, or if holes drilled are too large and do not allow you to tighten base snugly, use plastic screw anchors to secure subbase.
Fan Operation
If your system does not have a G terminal connection, skip to Heating System.
1. Move fan switch to ON position. The blower should begin to operate.
2. Move fan switch to AUTO position. The blower should stop immediately.
Heating System
1. Move SYSTEM switch to HEAT position. If the heating system has a standing pilot, be sure to light it.
2. Press to adjust thermostat setting above room tempera­ture. The heating system should begin to operate.
3. Press perature. The heating system should stop operating.
2
to adjust temperature setting below room tem-