wheelock ET90-2415C-FR, ET90-24177C-FN, ET90-24177C-FW, ET90-2415C-FW, ET70-2430W INSTALLATION INSTRUCTIONS

...
0 (0)
273 Branchport Avenue Long Branch, NJ 07740 Thank you for using our products. (800) 631-2148 INSTALLATION INSTRUCTIONS www.wheelockinc.com SERIES ET70/90 LOW PROFILE SPEAKERS AND SPEAKER STROBES
Use this product according to this instruction manual. Please keep this instruction manual for future reference.
Wheelock’s Series ET70/90 Low Profile Speakers and Speaker Strobes are UL Listed under Standard 1971 for Signaling Devices for the Hearing Impaired and UL Standard 1480 for Speaker Appliances. They are designed for multiple power requirements with high dBA output at each power tap. All models offer a choice of field selectable taps, 1/8W to 8W for either 25.0VRMS or 70.0VRMS audio systems. The Low Profile design incorporates a high efficiency speaker for maximum output at minimum power across a frequency range of 400Hz to 4000Hz, and features a sealed back construction for extra protection and improved audibility. The Series ET appliances also incorporate a Speaker Mounting Plate attached to the speaker for ease of installation. The Low Profile Speaker Strobes can provide a non-synchronized strobe appliance when connected directly to a Fire Alarm Control Panel (FACP), or provide a synchronized strobe appliance when used in conjunction with a Sync Module (SM), Dual Sync Module (DSM), or Power Booster (PS-12/24-8). The Strobes use a Xenon flashtube with solid state circuitry enclosed in a rugged Lexan lens to provide maximum visibility and reliability for effective visible signaling. The 241575W candela wall mounted strobes are listed at 15 candela under UL Standard 1971 and meet 75 candela intensity on axis with low current draw. The ET70 Speaker Strobes for wall mounting only 241575W, 2430W, 2475W and 24110W. The ET90 Speaker Strobes for ceiling mounting only strobe options: 2415C, 2430C, 2475C, and 24100C. All models are Listed for indoor use only
are available with a choice of five UL Listed strobe options: 2415W,
are available with a choice of four UL Listed
with the backboxes specified in these
instructions (see Mounting Options).
All
NOTE:
WARNING: READ THESE INSTRUCTIONS CAREFULLY. FAILURE TO COMPLY WITH ANY OF THE FOLLOWING INSTRUCTIONS, CAUTIONS AND WARNINGS COULD RESULT IN IMPROPER APPLICATION, INSTALLATION AND/OR OPERATION OF THESE PRODUCTS IN AN EMERGENCY SITUATION, WHICH COULD RESULT IN PROPERTY DAMAGE AND SERIOUS INJURY OR DEATH TO YOU AND/OR OTHERS.
SPECIFICATIONS:
ET70 25/70 75 78 81 84 87 90 93 ---- ---- ---- ---- A,C ET70-2415W 25/70 75 78 81 84 87 90 93 16 24 33 15 B,D ET70-241575W 25/70 75 78 81 84 87 90 93 16 24 33 ET70-2430W 25/70 75 78 81 84 87 90 93 16 24 33 ET70-2475W 25/70 75 78 81 84 87 90 93 16 24 33 ET70-24110W 25/70 75 78 81 84 87 90 93 16 24 33 ET90 25/70 75 78 81 84 87 90 93 ---- ---- ---- ---- A ET90-2415C 25/70 75 78 81 84 87 90 93 16 24 33 ET90-2430C 25/70 75 78 81 84 87 90 93 16 24 33 ET90-2475C 25/70 75 78 81 84 87 90 93 16 24 33 ET90-24100C 25/70 75 78 81 84 87 90 93 16 24 33
CAUTIONS
Speaker Strobe dBA at 10 Feet Voltage Mounting
Models Voltage (Rated Watts) (VDC/VRMS) Candela Options
(VRMS) 1/8 1/4 1/2 1 2 4 8 Min Nom Max
and
WARNINGS
are identified by the symbol . All warnings are printed in bold capital letters.
Table 1: UL Listed Models and Ratings
15* B,D
30 B,D 75 B,D
110 B,D
15 B 30 B 75 B
100 B
*241575W models are UL Listed at 15cd and meet 75cd on axis.
NOTES:
1. Strobes will produce 1 flash per second over the “regulated voltage” range.
2. All models are UL Listed for indoor use with a temperature range of +32oF to +120oF (0oC to +49oC) and maximum humidity of 85% RH.
3. dBA is rated per UL Standard 1480 for Speaker Appliances.
WARNING: THESE APPLIANCES WERE TESTED TO THE OPERATING VOLTAGE LIMITS OF 16-33 VOLTS USING FILTERED (DC) OR UNFILTERED FULL-WAVE RECTIFIED (FWR). DO NOT APPLY 80% AND 110% OF THESE VOLTAGE VALUES FOR SYSTEM OPERATION.
WARNING: CHECK THE MINIMUM AND MAXIMUM OUTPUT OF THE POWER SUPPLY AND STANDBY BATTERY AND SUBTRACT THE VOLTAGE DROP FROM THE CIRCUIT WIRING RESISTANCE TO DETERMINE THE APPLIED VOLTAGE TO THE STROBES. NOTE: THE MAXIMUM WIRE IMPEDENCE BETWEEN STROBES SHALL NOT EXCEED 35 OHMS. THE MAXIMUM NUMBER OF STROBES ON A SINGLE NOTIFICATION APPLIANCE CIRCUIT SHALL NOT EXCEED 47.
Copyright 2000 Wheelock, Inc. All rights reserved.
P83567 C
Sheet 1 of 10
Table 2: Wall Mount Strobe Current Ratings (AMPS) for 24VDC Models
Rated Average Current
Voltage 2415W 241575W 2430W 2475W 24110W
MEAN RMS MEAN RMS MEAN RMS MEAN RMS MEAN RMS
16.0VDC 0.072 0.072 0.099 0.099 0.125 0.125 0.215 0.220 0.276 0.296
24.0VDC 0.053 0.053 0.068 0.076 0.085 0.089 0.140 0.176 0.169 0.232
33.0VDC 0.045 0.045 0.055 0.066 0.069 0.081 0.114 0.172 0.138 0.203
16.0VRMS ----- 0.105 ----- 0.125 ----- 0.131 ----- 0.217 ----- 0.274
24.0VRMS ----- 0.076 ----- 0.097 ----- 0.121 ----- 0.200 ----- 0.241
33.0VRMS ----- 0.069 ----- 0.084 ----- 0.105 ----- 0.176 ----- 0.217 Rated Peak Current *
Voltage 2415W 241575W 2430W 2475W 24110W
16.0VDC 0.155 0.205 0.240 0.440 0.584
24.0VDC 0.160 0.210 0.250 0.450 0.586
33.0VDC 0.165 0.215 0.255 0.460 0.590
16.0VRMS 0.160 0.210 0.250 0.450 0.586
24.0VRMS 0.165 0.215 0.255 0.460 0.590
33.0VRMS 0.170 0.220 0.265 0.470 0.595
Rated Inrush Current **
Voltage 2415W 241575W 2430W 2475W 24110W
16.0VDC 0.110 0.110 0.110 0.110 0.110
24.0VDC 0.165 0.165 0.165 0.165 0.165
33.0VDC 0.230 0.230 0.230 0.230 0.230
16.0VRMS 0.155 0.155 0.155 0.155 0.155
24.0VRMS 0.235 0.235 0.235 0.235 0.235
33.0VRMS 0.325 0.325 0.325 0.325 0.325
Table 2A: Ceiling Mount Strobe Current Ratings (AMPS)
Rated Average Current
Voltage 2415C 2430C 2475C 24100C
MEAN RMS MEAN RMS MEAN RMS MEAN RMS
16.0VDC 0.105 0.105 0.158 0.161 0.330 0.385 0.375 0.432
24.0VDC 0.075 0.081 0.107 0.132 0.215 0.310 0.250 0.364
33.0VDC 0.058 0.080 0.090 0.129 0.165 0.273 0.200 0.358
16.0VRMS ----- 0.085 ----- 0.165 ----- 0.338 ----- 0.480
24.0VRMS ----- 0.085 ----- 0.153 ----- 0.314 ----- 0.380
33.0VRMS ----- 0.085 ----- 0.139 ----- 0.289 ----- 0.340 Rated Peak Current *
Voltage 2415C 2430C 2475C 24100C
16.0VDC 0.215 0.335 0.755 0.855
24.0VDC 0.220 0.340 0.760 0.860
33.0VDC 0.225 0.345 0.765 0.865
16.0VRMS 0.220 0.340 0.760 0.860
24.0VRMS 0.225 0.345 0.765 0.865
33.0VRMS 0.230 0.350 0.770 0.870
Rated Inrush Current **
Voltage 2415C 2430C 2475C 24100C
16.0VDC 0.110 0.110 0.110 0.110
24.0VDC 0.165 0.165 0.165 0.165
33.0VDC 0.230 0.230 0.230 0.230
16.0VRMS 0.155 0.155 0.155 0.155
24.0VRMS 0.235 0.235 0.235 0.235
33.0VRMS 0.325 0.325 0.325 0.325
* The time duration for the peak current is 100 microseconds.
** The time duration for the inrush current is 4 milliseconds.
P83567 C
Sheet 2 of 10
WARNING: MAKE SURE THAT THE TOTAL AVERAGE CURRENT, TOTAL PEAK CURRENT AND TOTAL INRUSH CURRENT REQUIRED BY ALL APPLIANCES THAT ARE CONNECTED TO THE SYSTEM’S PRIMARY AND SECONDARY POWER SOURCES, NAC CIRCUITS, SM AND DSM SYNC MODULES DO NOT EXCEED THE POWER SOURCES’ RATED CAPACITY OR THE CURRENT RATINGS OF ANY FUSES ON THE CIRCUITS TO WHICH THESE APPLIANCES ARE WIRED. OVERLOADING POWER SOURCES OR EXCEEDING FUSE RATINGS COULD RESULT IN LOSS OF POWER AND FAILURE TO ALERT OCCUPANTS DURING AN EMERGENCY, WHICH COULD RESULT IN PROPERTY DAMAGE AND SERIOUS INJURY OR DEATH TO YOU AND/OR OTHERS.
When calculating the total average, peak and inrush currents: Use Table 2 (for wall mount) and 2A (for ceiling mount) to determine the highest value of “Rated Average Current” for an individual strobe (across the expected operating voltage range of the strobe), and the highest value of “Rated Inrush Current” or “Rated Peak Current” (whichever is higher) of an individual strobe (across the expected voltage range of the strobe), then multiply these values by the total number of strobes; be sure to add the currents for any other appliances, including audible signaling appliances, powered by the same source and include any required safety factors.
If the inrush current or peak current exceeds the power supplies’ inrush capacity, the output voltage provided by the power supplies may drop below the listed voltage range of the appliances connected to the supply and the voltage may not recover in some types of power supplies. For example, an auxiliary power supply that lacks filtering at its output stage (either via lack of capacitance and/or lack of battery backup across the output) may exhibit this characteristic.
CAUTION:
Strobes are not designed to be used on coded systems in which the applied voltage is cycled on and off.
LIGHT DISTRIBUTION:
Table 3: Horizontal Plane (Wall Mount)
Horizontal 15W 1575W* 30W 75W 110W
Angle
(in deg.)
0 15.0 24 94 30.0 46 75.0 103 110.0 149 5 13.5 24 93 27.0 46 67.5 103 99.0 152 10 13.5 24 88 27.0 45 67.5 104 99.0 151 15 13.5 24 87 27.0 46 67.5 100 99.0 151 20 13.5 23 85 27.0 43 67.5 101 99.0 148 25 13.5 23 80 27.0 43 67.5 98 99.0 140 30 11.3 21 75 22.5 41 56.3 94 82.5 135 35 11.3 20 71 22.5 40 56.3 89 82.5 129 40 11.3 19 62 22.5 39 56.3 83 82.5 124 45 11.3 18 52 22.5 41 56.3 81 82.5 133 50 8.3 18 35 16.5 36 41.3 77 60.5 121 55 6.8 12 32 13.5 27 33.8 60 49.5 85 60 6.0 11 34 12.0 30 30.0 59 44.0 95 65 5.3 13 27 10.5 35 26.3 71 38.5 113 70 5.3 17 19 10.5 29 26.3 73 38.5 81 75 4.5 13 11 9.0 22 22.5 53 33.0 72 80 4.5 8 9 9.0 17 22.5 35 33.0 50 85 3.8 7 10 7.5 15 18.8 30 27.5 38 90 3.8 6 10 7.5 15 18.8 30 27.5 43
UL
Min.
Typ. 15W
Typ.
1575W
UL
Min.
Typ. 30W
UL
Min.
Typ. 75W
UL
Min.
Typ.
110W
* 1575W models are UL Listed for 15cd and meet 75cd on axis.
P83567 C
Sheet 3 of 10