INSTALLATION INSTRUCTIONS |
|
SERIES Z 2-WIRE FIELD SELECTABLE HORN, |
|
STROBE, AND HORN/STROBE APPLIANCES |
|
(WALL AND CEILING MOUNT ) |
Use this product according to this instruction manual. Please keep this instruction manual for future reference.
GENERAL:
The Cooper Wheelock Series Z horn, strobe, and horn/strobe appliances are designed for easy installation. The ZNS horn/strobes and ZRS strobes are for 24V operation and the ZNH horn is for 12V or 24V operation. The appliance comes in two main parts. The universal mounting back plate allows the appliance to be mounted to a single-gang, double-gang, four square backbox, 4” octagon backbox, or a 3 ½” octagon backbox. Two wire appliance wiring is then connected to the mounting back plate. This allows a continuity check of the entire NAC circuit before any appliances are attached. It also allows the appliances to be installed after all finish work has been completed. The installer can snap or install the appliances when all other work is complete.
WARNING: PLEASE READ THESE INSTRUCTIONS CAREFULLY BEFORE USING THIS PRODUCT. FAILURE TO COMPLY WITH ANY OF THE FOLLOWING INSTRUCTIONS, CAUTIONS AND WARNINGS COULD RESULT IN IMPROPER APPLICATION, CANDELA SETTING, INSTALLATION AND/OR OPERATION OF THESE PRODUCTS IN AN EMERGENCY SITUATION, WHICH COULD RESULT IN PROPERTY DAMAGE AND SERIOUS INJURY OR DEATH TO YOU AND/OR OTHERS.
SPECIFICATIONS:
|
Regulated |
Voltage Range |
|
|
|
|
|
|
Limit per UL |
Strobe |
|
Current Draw |
|
||
Model |
Voltage |
Horn |
Mounting |
||||
1971 |
(cd) |
See Table |
|||||
|
(VDC/VRMS) |
|
|
||||
|
(VDC/VRMS) |
|
|
|
|
||
|
|
|
|
|
|
||
ZRS-MCW |
24 |
16-33 |
15/30/75/110 |
- |
3 |
Wall |
|
ZRS-MCWH |
24 |
16-33 |
135/185 |
- |
3 |
Wall |
|
ZRS-MCC |
24 |
16-33 |
15/30/75/95 |
- |
3 |
Ceiling |
|
ZRS-MCCH |
24 |
16-33 |
115/177 |
- |
3 |
Ceiling |
|
ZNS-MCW |
24 |
16-33 |
15/30/75/110 |
X |
4 |
Wall |
|
ZNS-MCWH |
24 |
16-33 |
135/185 |
X |
4 |
Wall |
|
ZNS-MCC |
24 |
16-33 |
15/30/75/95 |
X |
4 |
Ceiling |
|
ZNS-MCCH |
24 |
16-33 |
115/177 |
X |
4 |
Ceiling |
|
ZNH |
12 |
8-17.5 |
- |
X |
5 |
Wall or |
|
24 |
16-33 |
Ceiling |
|||||
|
|
|
|
Strobe and Horn Strobe Appliances
Cooper Wheelock’s Series Horn Appliances provide a selectable Continuous or Code 3 Horn tone when connected directly to the Fire Alarm Control Panel (FACP). They can also provide a synchronized Code 3 Horn tone when used in conjunction with an FACP that incorporates the Wheelock sync protocol, a Wheelock Sync Module, or the Wheelock Power Supply. The Horn Appliances can be field set for High (HI) or Low (LO) dBA sound output. The Horn Appliances are UL Listed under Standard 464 for Audible Signal Appliances. They are listed for indoor use only. These models are designed for use with either filtered DC (VDC) or unfiltered Full-Wave-Rectified (VRMS) input voltage. All inputs are polarized for compatibility with standard reverse polarity supervision of circuit wiring by a FACP. The ZNS Horn/Strobe is for 24V operation only. The ZNH Horn is for 12V or 24V operation.
NOTE: The ZRS, ZNS, and ZNH are electrically identical to the corresponding RSS, NS, and NH models. Therefore, they carry the existing UL compatibility listings.
NOTE: The Code 3 temporal pattern (1/2 second on, 1/2 second off, 1/2 second on, 1/2 second off, 1/2 second on, 1-1/2 off and repeat) is specified by ANSI and NFPA 72 for standard emergency evacuation signaling. The Code 3 Horn should be used only for fire evacuation signaling and not for any other purpose.
|
|
|
ZNH at 12V |
|
ZNS and ZNH at 24V |
|||
|
|
8.0V |
12V |
17.5V |
16.0V |
24V |
33.0V |
|
Continuous |
High |
78 |
83 |
86 |
83 |
87 |
90 |
|
Horn |
Low |
72 |
76 |
80 |
77 |
81 |
83 |
|
Code 3 Horn |
High |
75 |
79 |
82 |
79 |
82 |
86 |
|
Low |
67 |
72 |
74 |
72 |
76 |
79 |
||
|
Copyright 2007 Cooper Wheelock, Inc. All rights reserved. |
P84860 E |
|
Sheet 1 of 4 |
CURRENT DRAW:
|
|
|
|
|
|
|
Strobe Setting (cd) |
|
|
|
|
|
|
|
|
|
|
MCW |
|
MCWH |
|
|
MCC |
|
MCCH |
||||
|
15 |
30 |
|
75 |
110 |
135 |
185 |
15 |
30 |
|
75 |
95 |
115 |
177 |
DC |
0.060 |
0.092 |
|
0.165 |
0.220 |
0.300 |
0.420 |
0.065 |
0.105 |
|
0.189 |
0.249 |
0.300 |
0.420 |
FWR |
0.102 |
0.155 |
|
0.253 |
0.347 |
0.455 |
0.645 |
0.110 |
0.170 |
|
0.280 |
0.375 |
0.455 |
0.645 |
|
|
|
|
|
|
|
Strobe Setting (cd) |
|
|
|
|
|
|
|
|
Horn |
|
MCW |
|
MCWH |
|
|
MCC |
|
MCCH |
||||
|
Setting |
15 |
30 |
75 |
110 |
135 |
185 |
15 |
30 |
|
75 |
95 |
115 |
177 |
DC |
High* |
0.074 |
0.107 |
0.184 |
0.244 |
0.350 |
0.477 |
0.082 |
0.124 |
|
0.209 |
0.275 |
0.350 |
0.477 |
Low* |
0.066 |
0.101 |
0.177 |
0.232 |
0.306 |
0.429 |
0.071 |
0.114 |
|
0.201 |
0.261 |
0.306 |
0.429 |
|
|
|
|||||||||||||
FWR |
High* |
0.133 |
0.189 |
0.285 |
0.383 |
0.491 |
0.681 |
0.141 |
0.204 |
|
0.312 |
0.411 |
0.491 |
0.681 |
Low* |
0.116 |
0.169 |
0.274 |
0.369 |
0.469 |
0.659 |
0.124 |
0.184 |
|
0.301 |
0.397 |
0.469 |
0.659 |
|
|
|
* Current Draw is the same for the Continuous Horn and Code 3 Horn Settings.
Table 5: ZNH Horn Current Draw (Amps)
|
Horn |
8-17.5 Volts |
16-33 Volts |
|
|
Setting |
|||
|
|
|
||
DC |
High* |
0.021 |
0.044 |
|
Low* |
0.012 |
0.018 |
||
|
||||
FWR |
High* |
0.054 |
0.075 |
|
Low* |
0.030 |
0.045 |
||
|
* Current Draw is the same for the Continuous Horn and Code 3 Horn Settings.
NOTE: Candela and Horn Setting will determine the current draw of the product.
When calculating the total currents use Tables 3-5 to determine the highest value of RMS current for an individual appliance, then multiply these values by the total number of appliances. Be sure to add the currents for any other appliances, including audible signaling appliances powered by the same source, and to include any required safety factors.
NOTE: The maximum number of strobes on a single notification appliance circuit shall not exceed 50.
NOTE: These notification appliances are UL Listed as “Regulated”. They are intended to be used with FACPs whose notification circuits are UL Listed as “Regulated.” These appliances shall not be used on UL Listed “Special Application” notification circuits unless the appliances are identified to be compatible in the installation instructions of the FACP or unless the FACP is identified to be compatible in this instruction manual.
NOTE: THESE APPLIANCES WERE TESTED TO THE REGULATED VOLTAGE LIMITS OF 16.0-33.0 VOLTS FOR 24V MODELS AND 8-17.5 VOLTS FOR 12V MODELS USING FILTERED DC OR UNFILTERED FULL-WAVE-RECTIFIED VOLTAGE. DO NOT APPLY VOLTAGE OUTSIDE OF THIS RANGE.
NOTE: CHECK THE MINIMUM AND MAXIMUM OUTPUT OF THE POWER SUPPLY AND STANDBY BATTERY AND SUBTRACT THE VOLTAGE DROP FROM THE CIRCUIT WIRING RESISTANCE TO DETERMINE THE APPPLIED VOLTAGE TO THE STROBES. THE MAXIMUM WIRE IMPEDANCE BETWEEN STROBES SHALL NOT EXCEED 35 OHMS.
NOTE: Strobes are not designed to be used on coded systems in which the applied voltage is cycled on and off.
NOTE: MAKE SURE THAT THE TOTAL RMS CURRENT REQUIRED BY ALL APPLIANCES THAT ARE CONNECTED TO THE SYSTEM’S PRIMARY AND SECONDARY POWER SOURCES, NOTIFICATION APPLICIANCE CIRCUITS, SM, DSM SYNC MODULES, OR COOPER WHEELOCK POWER SUPPLIES DOES NOT EXCEED THE POWER SOURCES’ RATED CAPACITY OR THE CURRENT RATINGS OF ANY FUSES ON THE CIRCUITS TO WHICH THESE APPLIANCES ARE WIRED. OVERLOADING POWER SOURCES OR EXCEEDING FUSE RATINGS COULD RESULT IN LOSS OF POWER AND FAILURE TO ALERT OCCUPANTS DURING AN EMERGENCY, WHICH COULD RESULT IN PROPERTY DAMAGE AND SERIOUS INJURY OR DEATH TO YOU AND/OR OTHERS.
WIRING AND MOUNTING BASE:
|
|
|
|
• All strobe appliances have in-out wiring terminals that accepts |
|
FROM PRECEDING |
{ |
} |
TO NEXT APPLIANCE |
two #12 to #18 American Wire Gauge (AWG) wires at each |
|
screw terminal. Strip leads 3/8 inches and connect to screw |
|||||
APPLIANCE, FACP OR |
OR END OF LINE |
||||
SYNC MODULE |
RESISTOR (EOLR) |
terminals. |
|||
|
+ + - |
|
|
• Break all in-out wire runs on supervised circuits to ensure |
|
|
|
|
integrity of circuit supervision as shown in Figure 2. The |
||
|
|
|
polarity shown in the wiring diagrams is for the operation of |
||
|
Figure 1: |
|
Figure 2: |
the appliances. The polarity is reversed by the FACP during |
|
|
|
supervision. |
P84860 E
Sheet 2 of 4