West Penn 975BK1000, 975BL0500, 975GN0500, 975GN1000, 975GY1000 Specsheet

...
0 (0)
West Penn 975BK1000, 975BL0500, 975GN0500, 975GN1000, 975GY1000 Specsheet

Detailed Specification & Technical Data

975

18/2 Solid Shielded FPLR

Fire Alarm Signaling

Construction & Dimensions

CONSTRUCTION & DIMENSIONS

-

 

 

CONDUCTOR PARAMETER

-

 

 

• Number of Conductors

2

 

 

• AWG Size

18

 

 

• Conductor Stranding

Solid

• Conductor Type

Bare Copper

• Nominal DCR

6.5 Ohm/1000ft

• Cabling Lay Length

2.75 in

• Twists/Foot

4.4 twist/ft

INSULATION PARAMETER

-

 

 

• Insulation Type

Polypropylene - PP

• Insulation Thickness

0.008 in

• Insulation Color Code

1. Black 2.Red

SHIELDING PARAMETER

-

 

 

• Shield Type

Overall 100% Aluminum Foil

• Drain Wire Type

Tinned Copper

• Drain Wire AWG

24 AWG

ELECTRICAL CHARACTERISTICS

-

 

 

• Nom. Cap. Between Conductors

38 pF/ft

• Nom. Cap. Conductor to Shield

69 pF/ft

Overall Construction

 

 

 

 

 

 

 

OVERALL CONSTRUCTION PARAMETERS

 

-

 

Jacket Type

 

PVC

Jacket Thickness

 

0.017 in

Nominal Cable O.D.

 

0.15 in

Plenum

 

No

NEC UL Rating

 

FPLR

RoHS Compliant

 

Yes

Pull Tension

 

53 lbs

Bend Radius

 

1.349 in

Cable Weight

 

22 lbs

Overall Electrical & Optical Characteristics

 

 

 

OVERALL ELECTRICAL/OPTICAL CHARACTERISTICS

 

 

-

UL Flammability

 

 

UL1666 Vertical Shaft

Operating Range

 

 

-20 to 60 Deg C

UL Voltage Rating

 

 

300