Wavetek ACTERN ANT20 series/ant20-3035/english/operating manual/_start.pdf operating manual

Page 1
Conforming to the Maze of Network Standards
ITU-T Recommendations and Practical Applications in PDH/SDH Networks
Application Note 59
Page 2
Why Do Recommendations Exist for SDH/PDH Networks?
Telecommunications networks are not built from technologies that are individually specified by each service provider. If they were, imagine how hard it would be to connect from one service provider to the next! The logical solution is to have a universal organization (or organizations) specifying trans­mission methods that are universally applicable to all service providers. One of these bodies is the International Telecommunication Union  Tele­communication Standardization Sector (ITU-T) formally known as CCITT. The ITU-T is responsible
for studying technical, operating and tariff questions and issuing Recommendations on them with a view to standardizing telecommunications on a worldwide basis. Many telecommunication networks use network ele­ments that are specified by ITU-T Recommendations. The Advanced Network Tester (ANT-20) recognizes these Recommendations and carries out measure­ments to qualify them. This note will directly quote Recommendations from ITU-T and then apply them to practical applications performed on the ANT-20.
Recommendations Description Page
G.783 SDH equipment functional blocks 1
G.783 Section 10 Jitter and wander parameters at MUX and DEMUX ports 3
G.823 Jitter and wander parameters at PDH interfaces 5
G.825 Jitter parameters at SDH interfaces contained in a SDH network 6
G.958 Jitter parameters at SDH regenerator ports 8
G.813 Jitter and wander parameters of SDH equipment slave clocks 9
G.826 Error performance in SDH/PDH networks 12
M.2100 Performance levels for BIS of international PDH paths. 14
G.841 Types and characteristics of SDH network protection architecture 15
G.841 Linear Multiplex section protection (MSP) protocol, commands and operation 16 (G.783 Annex A)
Cross Connect Test
G.823
Jitter Test
G.958
G.813
Wander
G.841
G.825
Jitter Test
Error
Performance
G.821 G.826
M.2100
PDH
Network
Page 3
1
Recommendation G.783: Characteristics of Synchronous Digital Hierarchy (SDH) Equipment Functional Blocks
“This Recommendation defines a library of basic building blocks and a set of rules by which they may be combined in order to describe a digital transmission equipment. The library comprises the functional building blocks needed to specify completely the generic functional structure of the Synchronous Digital Hierarchy.” The Recommendation describes processes within the basic building blocks, the so called “atomic functions”, for example the generation and evaluation of overheads used for performance monitoring. The regenerator section termination and
adaptation function acts as a source and sink for the regenerator section overhead (RSOH). The RSOH contains bytes A1, A2, B1, J0, E1, F1, D1 to D3 and bytes reserved for national use. This section acts as a maintenance entity between and including two regenerator termination functions. The multiplex section termination and adaptation function acts as a source and sink for the multiplex section overhead (MSOH). The MSOH contains bytes B2, K1, K2, D4 to D12, S1, M1, E2 and bytes reserved for national use. This section acts as a maintenance entity between and including two multiplex termination functions.
G.783 APPLICATION MSOH Byte Functionality and BERT RSOH Byte Functionality and BERT
In Brief
PDH signals are transported over four main SDH layers all of which play critical parts in certifying SDH transmission. The physical layer is classified as the fifth layer. The section overhead (SOH) is mainly built up from the RSOH and MSOH, which guide the payload of the STM-N signal between multiplex and regenerator elements within a network. With this particular asset of the STM-N technology, the overhead of the STM-N signal can be tested and in turn test the MST and RST functions.
Figure 1 illustrates the different layers which are passed by a signal when it is transmitted through a network. The different layers are terminated depen­ding on the functions implemented in the network elements. For example, the regenerator layer guides the signal between the MUX and REG, then a new RSOH is generated at the output of the REG to guide the signal to the ADM, and so on. The lower path (LP) layer will come into play when the PDH tributaries are terminated at the DEMUX.
LP: Lower Order Path HP: Higher Order Path MS: Multiplex Section RS: Regenerator Section OS: Optical Section
Figure 1
Application
A suitable application for testing the RST and MST functions lies in the Anomaly/Defect generator and analyzer. SDH technology uses a maintenance interaction flow where different signals are trans­mitted through particular bytes of the overhead to indicate anomalies and defects. Messages are generated due to an interaction with corresponding
layer errors. For example, if a LOF is generated in the RS layer then an AIS defect will display in the PDH layer. Test can be performed with the ANT-20 by sending out defects in the different layers and looking at the reactions in the corresponding layers. Figure 2 a/b illustrates two general setups which will result in two different error alarms being generated. The black line setup will generate error alarms of a HP and MS layer nature if a RS defect was first generated. The red line setup will generate error alarms of PDH layer nature due to the fact that a PDH signal is examined.
Page 4
2
Recommendation G.783: Section 10 Specification of Jitter and Wander
This section of recommendation G.783 specifies input and output jitter/wander requirements which directly refer to recommendations G.958, G.825 and G.813 which will be explained later in this note. This recommendation also specifies wander and combined jitter caused by PDH tributary mapping and pointer adjustments. “The combined jitter arising from tributary mapping and pointer adjustments should be specified in terms of peak-to-peak amplitude over a given frequency band, under application of represen-
tative specified pointer adjustment test sequences, for a given measurement interval.” A major factor that must be realized in this specifi­cation of mapping and pointer jitter on PDH interfaces is the definition of the filter character­istics. Most important is the specification of the highpass filter characteristics due to the low frequency components of pointer jitter. Tables 1a/1b show the filter characteristics for mapping jitter generation and combined jitter generation.
Figure 3a: The user interface window for generating different anomalies and defects.
Figure 3b: Results in graphical format.
Figure 3b
Figure 3a
Figure 2bFigure 2a
Page 5
3
G.703 Maximum (PDH) Filter characteristics pk-pk
interfaces mapping jitter
kbit/s f
1
f
3
f
4
f1–f
4
f3–f
4
high pass high pass low pass 1,544 10 Hz 8 kHz 40 kHz (Note 1) 0.1 UI 2,048 20 Hz 18 kHz 100 kHz (Note 1) 0.075 UI
(700 Hz) 6,312 10 Hz 3 kHz 60 kHz (Note 1) 0.1 UI 34,368 100 Hz 10 kHz 800 kHz (Note 1) 0.075 UI 44,736 10 Hz 30 kHz 400 kHz 0.4 UI 0.1 UI 139,264 200 Hz 10 kHz 3,500 kHz (Note 1) (Note 2) Notes
1. These values are for further study
2. Avalue of 0.075 UI has been proposed
Table 1a: Mapping jitter
G.703 Maximum (PDH) Filter characteristics pk-pk combined
interfaces jitter
kbit/s f
1
f
3
f
4
f1–f
4
f3–f
4
high pass high pass low pass 1,544 10 Hz 8 kHz 40 kHz 1.5 UI (Note 1) 2,048 20 Hz 18 kHz 100 kHz 0.4 UI 0.075 UI
(700 Hz) 6,312 10 Hz 3 kHz 60 kHz 1.5 UI (Note 1) 34,368 100 Hz 10 kHz 800 kHz 0.4 UI 0.075 UI
0.75 UI 44,736 10 Hz 30 kHz 400 kHz (Note 1) (Note 1) 139,264 200 Hz 10 kHz 3 500 kHz (Note 1) (Note 1) Note 1
These values are for further study
Table 1b: Combined jitter
Mapping and combined jitter occurs when PDH signals are transported over a SDH network. PDH tributaries need to be contained in the virtual container (VC) of a SDH transport module (STM). Accommodation of the PDH bit rate to the SDH clock requires a bit stuffing procedure during the mapping process. These stuffing phase steps lead to additional mapping jitter. The same thing, but with higher amplitude occurs if pointer adjustments
are apparent. Both effects together result in combined jitter. The recommendation specifies values to which the MUX and DEMUX must adhere to ensure as little jitter in the system as possible. The recommendation also defines pointer test sequences which are used to test the performance of SDH equipment with regard to SDH tributary jitter. These pointer test sequences are illustrated in Figure 4.
In Brief
Page 6
4
The ANT-20 has the advantage of generating AU and TU pointers simultan­eously. The application is set up to test the DUT’s combined and mapped jitter limits. This is performed by inputting an STM-N signal and moni­toring the PDH tributaries, (i.e. 2,8,34,140 Mbit/s). The ANT-20 will analyze jitter as illustrated in Recommen­dation G.783, but with the pointer test sequences activated simultaneously.
G.783 Section 10 APPLICATION PDH interfaces Jitter with pointer simulation
Figure 5a: The pointer value in graphical format with the current value (shown ringed).
Figure 5b: The possible sequences
that the ANT-20 may generate
as specified by ITU-T Recom-
mendation G.783.
Figure 4: Pointer sequences acc. to G.783
Figure 5a
Figure 5c
Figure 5b
Tributary
ports
2,048 kHz
Pointer action
Application
Missing pointer action
Start of next sequence
4 missing pointer action
Start of next sequence
87-3 sequence
Additional pointer action
43-44 sequence
Start of next sequence
86-4 sequence
Page 7
5
Recommendation G.823: Control of JITTER and WANDER within Digital Networks Based on the 2,048 kbit/s Hierarchy
Parameter value Network limit Measurement filter bandwidth Digital rate B
1
unit interval B2unit interval Band-pass filter having a lower cut-off
(kbit/s) peak-peak peak-peak frequency f
1
or f3and an upper cut-off frequency f
4
f
1
f
3
f
4
64 0.25 0.05 20 Hz 3 kHz 20 kHz
(Note 1)
2,048 1.5 0.2 20 Hz 18 khz 100 kHz
(700 Hz)
8,448 1.5 0.2 20 Hz 3 kHz 400 kHz
(80 kHz)
34,368 1.5 0.15 100 Hz 10 kHz 800 kHz
139,264 1.5 00.75 200 Hz 10 kHz 3500 kHz
Notes
1. For the codirectional interface only.
2. The frequency values shown in parenthesis only apply to certain national interfaces.
3. UI = Unit Interval
for 64 kbit/s 1 UI = 15.60 ns for 2,048 kbit/s 1 UI = 488.00 ns B
1
is the permissible jitter with the band pass
for 8,448 kbit/s 1 UI = 118.00 ns filter cut-off f
1
and f4.
for 34,368 kbit/s 1 UI = 29.10 ns B
2
is the permissible jitter with the band pass
for 139,264 kbit/s 1 UI = 7.18 ns filter cut-off f
3
and f4.
“The scope of this Recommendation is to define the parameters and the relevant values that are able to control satisfactorily the amount of jitter and wander present at the plesiochronous digital hierarchy (PDH) network interface.” The limits set for the maximum permissible levels of jitter at PDH interfaces within digital networks are illustrated in Table 2. The recommendation points out that the limits should be met for all operating conditions regardless of
Table 2: Jitter limits for PDH interfaces defining the cor­responding filter bandwidth.
Figure 6: Permissible MTIE vs.
observation period s for the output
of a network node.
the amount of equipment preceding the interface. This recommendation covers also limits for wander influences that appear over the equip­ment interfaces of a PDH network. The Recommendation states that “magnitudes of wander, being largely dependent on the fundamental propagation characteristics of transmission media and the aging of clock circuitry, can be predicted.” For PDH interfaces the following limits apply.
Figure 6 illustrates the permissible maximum time interval error (MTIE) vs. observation period S for the output of a network node. MTIE is the maximum UI which was recorded at an instant of the period S. S can be a 10 sec observation time which makes up a 12 hour measuring period.
In Brief
This Recommendation focuses on networks containing equipment with PDH interfaces. When networks are designed, service providers need to take into account the values illustrated in Table 2 and Figure 6, ensuring that all network elements on line do not introduce any more jitter or wander into a PDH network system.
MTIE
(ns)
Observation Period (S)
Page 8
6
G.823 APPLICATION PDH interface Jitter and Maximum
Tolerable Jitter PDH interface Wander (MTIE) PDH regenerators Jitter Transfer Function
Figure 7 shows the setup to test the performance of the DUT’s jitter capabilities for PDH signals. Jitter transfer function and maximum tolerable jitter tests can also be performed under this Recommen­dation. These two measurements are explained in more detail in the sections for Recommendation G.958 and G.825. For wander refer to G.813. The jitter result window in Figure 8 is for manual mode. In this mode the user can set jitter ampli­tudes manually and observe the reaction of the DUT through errors and alarms. Phase hits occur when a specific jitter threshold is exceeded. The results are recorded using a counter. Limits of the hit threshold may be set via the SET button. The jitter generator/analyzer window allows the user to select the application measurement for maximum tolerable jitter (MTJ) or fast MTJ (FMTJ), jitter transfer function and wander analysis.
Recommendation G.825: Control of JITTER and WANDER within Digital Networks Based on the Synchronous Digital Hierarchy (SDH)
“The scope of this Recommendation is to define the parameters and the relevant values that are able to control satisfactorily the amount of jitter and wander present at the SDH network interface.” This Recommendation specifies the jitter limits
applied to the SDH network interfaces. Network interfaces (e.g. international boundaries) must meet interface limits regardless of the individual carrier’s choice of equipment. These limits are displayed in Table 3.
Figure 8: The results
window for jitter for a
PDH signal.
STM level f1(Hz) f3(kHz) f4(MHz) B1(UIpp) B2(UIpp) STM-1 optical 500 65 1.3 1.5 0.15 STM-1 electrical 500 65 1.3 1.5 0.075 STM-4 optical 1,000 250 5 1.5 0.15 STM-16 optical 5,000 under study 20 1.5 0.15
(Note 2)
Notes
1. UIpp = Unit interval 2. A value of 1 MHz has been suggested.
for STM-1 UI = 6.43 ns B1 is the permissable jitter with the band for STM-4 UI = 1.61 ns pass filter cut-off f
1
and f4.
for STM-16 UI = 0.40 ns B2 is the permissable jitter with the band
pass filter cut-off f
3
and f4.
Table 3
Figure 7
PDH
Interface
Application
DUT
Page 9
7
G.825 APPLICATION ALL SDH interface Jitter, Maximum Tolerable Jitter
In Brief
This Recommendation applies to SDH service providers who need to test the quality of the SDH interfaces where SDH networks span a large area. Table 3 illustrates limits which any interface in the network will need to meet to ensure a quality
The setup to test the performance of maximum tolerable jitter (MTJ) at SDH network interfaces is shown in Figure 9. MTJ measurements are generally performed by increasing jitter amplitudes at certain scan frequencies and evaluating the number of errors that the DUT produces. The ANT-20 performs this procedure in an auto­mated way, thus generating different jitter ampli­tudes at certain frequencies and recording the jitter amplitude when the DUT failed, then comparing these values against the Recommendation mask.
Figure 10: Different tolerance masks and scan frequencies can be user defined, by clicking on the “SET” button situated in the title bar.
Figure 9
STM-4
Interface
network. Jitter and Wander limits for network ele­ments without connection to the network are more stringend to meet the network interface require­ments. Such limits are defined in Recommendation G.783 and G.958 for SDH network elements.
Application
Figure 11: MTJ results recorded in tabular and graphical format against tolerance masks set by ITU-T.
DUT
Page 10
8
Recommendation G.958: Digital Line Systems Based on the Synchronous Digital Hierarchy for Use on Optical Fiber Cables
Interface Measuring filter Peak-to-peak amplitude STM-1 500 Hz to 1.3 MHz 0.30 UI
65 KHz to 1.3 MHz 0.10 UI
STM-4 1,000 Hz to 5 MHz 0.30 UI
250 kHz to 5 MHz 0.10 UI
STM-16 5,000 Hz to 20 MHz 0.30 UI
1 MHz to 20 MHz 0.10 UI
For STM-1 1 UI = 6.43 ns For STM-4 1 UI = 1.61 ns For STM-16 1 UI = 0.40 ns
“Jitter transfer function (JTF) is defined as the ratio of jitter on the output STM-N signal to the jitter ap­plied on the input STM-N signal vs. frequency.” This factor indicates the degree to which jitter is amplified or attenuated by a regenerator. If the jitter amplification of several regenerators is too high, the accumulated jitter amplitude at the end of the line system may exceed the network limits.
STM-N level (type) fc (kHz) P (dB) STM-1 (A) 130 0.1
STM-1 (B) 30 0.1 STM-4 (A) 500 0.1 STM-4 (B) 30 0.1 STM-16 (A) 2,000 0.1 STM-16 (B) 30 0.1
STM-M ft (kHz) fo (kHz) A1 (Uip-p) A2 (Uip-p) Level
STM-1 65 6.5 0.15 1.5 STM-4 250 25 0.15 1.5 STM-16 1,000 100 0.15 1.5
“This Recommendation specifies characteristics of digital synchronous line systems based on the synchronous digital hierarchy (SDH) to provide transverse compatibility.” This Recommendation will focus on jitter gener­ation, jitter transfer and jitter tolerance of regener­ators. “Jitter generation is defined as the amount of jitter at the STM-N output of SDH regenerators.” The amplitude of the jitter present at the output of each regenerator should not exceed a specified limit value. Table 4 displays the proposed figures from the revised draft of recommendation G.958 on STM-N jitter generation for output jitter at an STM-N inter­face assuming the absence of jitter at the input interface, thus intrinsic jitter.
In Brief
This recommendation focuses on the limits that SDH regenerators need to meet to be part of a quality network system. Each regenerator can introduce jitter resulting in jitter accumulation,
“Jitter tolerance is defined as the peak-to-peak amplitude of sinusoidal jitter applied on the input STM-N signal that causes a 1 dB optical penalty at the optical equipment.” Regenerators must be able to tolerate a specified jitter amplitude at the input without any errors occurring.
NOTE: Relevant parts of Recommendation G.958 including the jitter requirements of regenerators will in future be moved to section 10 of a revised version of Recommendation G.783.
Table 4: Intrinsic jitter limits
Table 6 illustrates the jitter tolerance parameters
Table 5 illustrates the jitter transfer parameters for two classes of regenerators with different frequency bandwidths
affecting greatly the purity of the transported signal. Regenerators need to be within the required limits to reassure the performance of a network.
Page 11
9
G.958 APPLICATION SDH regenerator Intrinsic Jitter, Jitter Transfer
interface Function, Jitter Tolerance SDH regenerator Wander
Application
JTF measurements are of particular importance when dealing with regenerators. Checks are carried out to demonstrate that the jitter gain of a regenerator is below the defined value of recom­mendation G.958. If this is not the case, then “jitter runaway” occurs after several regenerators. JTF is measured by applying a signal with defined jitter modulation over the frequency range of the DUT. The jitter amplitude is selected so that the DUT can handle it at any frequency. The ANT-20 meas­ures the resulting jitter amplitude at the output of the DUT at various TX jitter frequencies. The log of the ratio between input and output gives the jitter gain or attenuation. Jitter transfer function measurements are im­proved by compensating for intrinsic jitter of the DUT and the ANT-20 by carrying out calibration measurements first. This improves the measure­ment accuracy.
Recommendation G.813: Timing Characteristics of SDH Equipment Slave Clocks (SEC)
“This Recommendation outlines requirements for timing devices used in synchronizing network equipment that operates according to the principles governed by the Synchronous Digital Hierarchy (SDH).” In a normal SDH system, the SDH equipment clock (SEC) is synchronized to a primary reference clock (PRC). SECs have multiple reference inputs which the clock can refer to however, when links between the master and slave clocks fail, then the SEC’s frequency will start to drift from that of the PRC at a rate dependent on the quality of the oscillator in the slave clock. This is referred to as “holdover”. This Recommendation specifies requirements for two options. “Option 1”, applies to SDH networks optimized for the 2,048 kbit/s hierarchy. “Option 2” applies to SDH network optimized for the 1,544 kbit/s hierarchy, which will not be referred to in this note.
Figure 13: The results are displayed in graphical or tabular format.
“Noise generation of a SEC represents the amount of phase noise produced at the output when there is an ideal input reference signal or the clock is in holdover state.” This is commonly known as wan­der generation and is measured in maximum time interval error (MTIE) and time deviation (TDEV). Figure 14 illustrates MTIE versus observation interval for constant and variable temperatures,
Figure 14: MTIE vs. Observation Time for constant and variable temperatures
Figure 12: Jitter transfer function test of regenerators.
where the menasurement needs normally a large period of time. From time interval (TIE) measure­ments the time deviation TDEV can be calculated. TDEV values are a measure of the phase error variation versus the integration time. Put simply, the time deviation is calculated for each point within a measurement time (T) for an instant that travels through the entire measurement time T
Total
. Figure 15 shows TDEV versus observation interval for constant temperature.
STM-16
Regenerator
0.1 1.0 10 100 1,000 Observation interval τ (s)
(var. temp.)
1,000
150 100
63 40
10
0
(const. temp.)
MTIE (ns)
Page 12
10
“The noise tolerance of a SEC indicates the min­imum phase noise level at the input of the clock that should be accommodated whilst:
– Maintaining the clock within prescribed
performance limits. – Not causing any alarms. – Not causing the clock to switch reference. – Not causing the clock to go into holdover.”
Interface Measure filter Peak-to-peak amplitude STM-1 500 Hz to 1.3 MHz 0.50 UI
65 kHz to 1.3 MHz 0.10 UI
STM-4 1,000 Hz to 5 MHz 0.50 UI
250 kHz to 5 MHz 0.10 UI
STM-16 5,000 Hz to 20 MHz 0.50 UI
1 MHz to 20 MHz 0.10 UI
For STM-1 1 UI = 6.43 ns For STM-4 1 UI = 1.61 ns For STM-16 1 UI = 0.40 ns
The noise tolerance is also commonly known as wander tolerance and is characterized by MTIE and TDEV masks illustrated in Figures 16a/16b. Jitter tolerance limits are also specified in this recommendation for SDH network elements excluding regenerators, which G.958 covers. Figure 17 shows the maximum tolerable input jitter for 2,048 kHz and 2,048 kbits Synchronization interface.
Figures 16a/16b: The input wander tolerance mask (MTIE and TDEV).
Figure 17: The lower limit of the maximum tolerable input jitter of 2,048 kHz and 2,048 kbit/s signals carrying synchronization to a SEC.
“The noise transfer characteristics of the SEC determines its properties with regard to the transfer of excursions of the input phase relative to the carrier phase.” In the passband the phase gain of the SEC should be smaller than 0.2 dB (2.3%). The Recommendation states, “The minimum bandwidth requirement for a SEC is 1 Hz and the maximum bandwidth requirement is 10 Hz.”
Figure 16a
Figure 16b
Figure 15: TDEV vs. observation time for constant temperature
Table 7
0.1 1.0 10 20 100 1,000
0.1 1.0 7 10 100 1,000
0.1 1.0 2.5 10 20 100 400 1,000
Observation interval τ (s)
Observation interval τ (s)
Observation interval τ (s)
100
10
6.4
3.2
1.0
0.1
1,000
170 100
12 10
0.1
10
5.5
2.0
1.0
0.25
0.1
(const. temp.)
TDEV (ns)
TDEV (ns) MTIE (ns)
0.1 10 19 49 100 1,000 10,000 100,000 Observation interval τ (s)
250
100
Peak-to-peak
jitter amplitude
(ns)
This Recommendation also specifies limits for jitter generation on SDH output interfaces. The differ­ence between G.958 and this Recommendation is that this recommendation defines limits for all network elements, excluding regenerators. The limits defined in this part of the recommendation are less stringent than the limits defined in G.958, as Table 7 shows.
Page 13
11
In Brief
SDH network elements use internal clocks (SEC) as timing sources. These clock sources should be synchronized to a PRC via the SDH line inter­face or via a 2,048 MHz clock line.
G.813 APPLICATION SDH NE (SEC) Wander SDH interface Jitter
ANT-20 can perform measurements on the whole range of interfaces from PDH to SDH. Due to the instrument’s large storage capacity, long-term measurements can run up to 100,000 sec or longer. The measured values are displayed in the jitter generator/analyzer window as a graph of the time interval error (TIE) versus time. Numerical values of MTIE and TIE are shown above the graph, as illustrated in Figure 19.
Figure 20: The offline analyzer for MTIE and TDEV.
Figure 19: Result window illustrating ANT-20’s wander measurement.
Figure 18
DUT
PRC
2,048 kHz Ref.
To check the quality of the timing signal and inter­nal clock, the phase of the reference clock (PRC) is compared with that of the transmitted data signal or clock output signal. The long-term phase variation is referred to as wander.
Application
The wander generation setup consists of the ANT-20 connected as in Figure 18. Wander tolerance can be tested by generating wander over the DUT and then observing the output for any errors and alarms. The wander that is placed over the DUT is in the form of a sinusoidal wave, as defined in Recommendation G.813. The results of wander generation tests which are displayed in Figure 19 can be imported into the ANT-20’s offline analyzer software. In this program
the MTIE and TDEV are calculated as a function of the observation interval. These results are then compared to predefined standards and to user­defined tolerance masks which determine the clock quality.
Page 14
12
Recommendation G.826: Error Performance Parameters and Objectives for International, Constant Bit Rate Digital Paths at or above the Primary Rate:
Rate Mbit/s 1.5 to 5 >5 to 15 >15 to 55 >55 to 160 >160 to 3500 Bits/block 800–5,000 2,000–8,000 4,000–20,000 6,000–20,000 15,000–30,000 ESR 0.04 0.05 0.075 0.16 SESR 0.002 0.002 0.002 0.002 0.002 BBER 2 u 10
-4
2 u 10
-4
2 u 10
-4
2 u 10
-4
10
-4
“Recommendation G.826 specifies error perform­ance events, parameters and objectives for digital paths operating at bit rates at or above the primary rate. Paths are used to support services such as circuit switched, packet switched and leased line services.” Specifications that refer to bit rates that are n u 64 kbit/s (n < 24 or 32 resp.) are in Recommendation G.821. “Recommendation G.826 is based upon the error performance measurement of blocks. Ablock is a set of consecutive bits associated with the path, each bit belongs to one and only one block. Consecutive bits may not be contiguous in time.” These blocks can be monitored in two different modes. In-service monitoring or out-of-service monitoring. In-service monitoring allows measure­ment while the system is operational. Error detection codes e.g. BIP or CRC are evaluated to assess performance parameters. Out-of-service measurements are mainly used for aligning newly setup communications equipment. The parameters monitored are errored second, severely errored second and background block error.
Events
OErrored Second (ES): A one second period
with one or more errored blocks or at least one defect.
OSeverely Errored Second (SES): A one-
second period which contains M 30% errored blocks or least one defect. SES is a subset of ES.
OBackground Block Error (BBE): An errored
block not occurring as part of an SES.
Parameters
OErrored Second Ratio (ESR): The ratio of ES
to total seconds in available time during fixed measurement interval.
OSeverely Errored Second Ratio (SESR): The
ratio of SES to total seconds in available time during a fixed measurement interval.
OBackground Block Error Ratio (BBER): The
ratio of Background Block Errors (BBE) to total blocks in available time during a fixed measure­ment interval. The count of total blocks exclu­des all blocks during SESs.
G.821 G.826 M.2100
Purpose Error Error BIS
Performance Performance Limits
OOS ISM/OOS ISM/OOS Technology N-ISDN PDH/SDH/Cell-based PDH Min. bit rate 64 kbit/s 1.5 Mbit/s 64 kbit/s Max. bit rate <primary rate SDH rates 140 Mbit/s Evaluation 30 days 30 days specified in
period M.2110 Measurement Bit error based Block error based Bit/Block error based
Table 8: End-to-end error performance objectives for 27,500 km international digital HRP.
Table 9: Error performance Recommendation
Page 15
13
In Brief
Every SDH path has an embedded error perform­ance monitoring capability from which a number of standard parameters are calculated within the network element. The management needs these parameters for several reasons, as follows: – Verification of contracted performance of paths
with clients;
– Verification of the performance of manufac-
turer’s equipment over its lifetime;
Application
The G.826 measurement interface allows the user to view the EB at the near and far end of the trans­mission path. ES, EFS SES are also included as the parameters for the overall transmission perfor­mance results. The “VERDICT” box gives a direct indication as to whether the communications path meets the requirements of the recommendation depending on the path allocation.
IG is the international gateway that connects the national portion to the international portion which usually corresponds to a DXC, higher order MUX or a switch. The international portion of an end-to-
Out-of-Service In-Service
Figure 23a: Near end measurements (A to C) B1, B2, BIP2 are included.
Figure 21: The hypothetical reference path (HRP) for which error performance objectives are defined
Figure 22: Result display ANT-20 G.826 performance analysis
Figure 23b: Far end measurements (C to A ) RDI, RDI are included.
SDH network
Terminating
country
Terminating
country
PEP IG
National
portion
National
portion
International portion
Hypothetical reference path
27,500 km
Intermediate
countries
Intercountry
(e.g. path
carried over
a submarine
cable
IG IG IG IG PEP
Input signal
Output signal
end path begins in one terminating country and ends in the second terminating country. It is not possible to have less than or more than two terminating countries for an international path.
– Identification of performance degradations in
order to prompt remedial maintenance action;
– Provision of black spot analysis information for
network quality improvement programs.
The ANT-20 carries out a performance analysis for three recommendations: G.821, G.826 and M.2100. The ANT-20 can perform the G.826 test in out-of-service or in-service mode.
Page 16
14
Recommendation M.2100: Performance Limits for Bringing-into-Service and Maintenance of International PDH Paths, Sections and Transmission Systems
“Recommendation M.2100 provides limits for bring­ing-into-service and maintenance of international sections, paths and transmission systems at every level of the plesiochronous digital hierarchy from 64 kbit/s. Error timing and availability performance are considered.
“This recommendation uses certain principles which are the basis of the maintenance of a digital network:
– It is desirable to do in-service, continuous meas-
urements. In some cases (e.g. bringing-into­service), out-of-service measurements may be necessary.
– Asingle set of parameters must be used for
maintenance of every level of the hierarchy (this principle does not apply to limits).
– Error performance limits of transmission
systems are dependent on the medium used. However, due to the many possible network structures, error performance limits on paths are independent of the medium.”
Parameter (Note) End-to-end PRO
(maximum % of time)
Errored Seconds (ES) 4.0 Severly Errored Seconds (SES) 0.1
Network level Maximum Errored Maximum Severely Errored
Seconds (ES) % of time Seconds (SES) % of time
Primary 2 0.1 Secondary 2.5 0.1 Tertiary 3.75 0.1 Quaternary 8 0.1
Table 10 displays the values which are specified for 64 kbit/s. The RPO is based on 40 % of the end-to-end RPO taken from Recommendation G.821. RPO stands for the reference performance objective, upon which other performance objective values are based.
Primary, secondary, tertiary and quaternary stand for the relevant levels in the Plesiochronous Digital Hierarchy. The PRO figures given in the table are equal to 50% of the performance objectives given in Recommendation G.826.
In Brief
This Recommendation indicates the limits to quantify an international digital network and its
Application
The same setup can be used as illustrated in the figure below for out-of-service in Recommendation G.826. The analysis in general, including all G.826 meas­urements, provides separate results for the “NEAR END” and the “FAR END”. This simply means that errors occurring directly in the path are analyzed as well as errors occurring in the return path which are indicated by a remote error indicator message (e.g. E-bit at 2,048 Mbit/s) or remote defect indication. This allows both directions to be monitored at one end of a path.
Table 10: End-to-end error reference per­formance objectives at 64 kbit/s
Figure 24: Result display ANT-20, M.2100 performance analysis
Table 11: End-to-end error performance objectives at or above the primary rate
elements. These limits are to be used to indicate the need for actions during maintenance and bringing-into-service of network paths.
Page 17
15
Recommendation G.841: Types and Characteristics of SDH Network Protection Architectures
Keeping the downtimes of SDH paths to an abso­lute minimum is extremely important for network operators, since the quality of the services they offer is the main feature that distinguishes the many different providers.
1. MS dedicated protection ring
An MS dedicated protection ring consists of two counter-rotating rings, each transmitting in opposite directions relative to each other. In this case, only one ring carries normal traffic to be protected while to other is reserved for protection of this normal traffic (see Figure 26a). The normal traffic for example is carried only in the clockwise direction. It is protected by beeing simultaneously transported in the opposite direction. If the normal traffic is interrupted, the terminating network element switches to the protection channel (in the example shown here: failure between B and C -> network element E switches over to the protection channel). MS dedicated protection ring would also require using the APS bytes, K1 and K2, for protection switching.
2. MS shared protection ring
MS shared protection rings can be categorized into two types: two-fiber and four-fiber. The ring APS protocol accommodates both types. For MS shared protection rings, the working channels carry the normal traffic signals to be protected while the protection channels are reserved for protection of this service. Normal traffic signals are transported bidirectionally over spans: an incoming tributary travels in one direction of the working channels while its associated outgoing tributary travels in the opposite direction but over the same spans. – Two-fiber shared protection ring This protection architecture requires only two fibers for each span of the ring. Each fiber carries both working channels and protection channels. On each fiber, half the channels are defined as working channels and half are defined as protection channels. The normal traffic carried on working channels in one fiber are protected by the protection channels traveling in the opposite direction around the ring (see Figure 25a). This permits the bidirectional transport of normal traffic.
Figure 26a
Figure 26b
Figure 25a
Figure 25b
Traffic from A to E
Traffic from A to E
Traffic from E to A
Traffic from E to A
__ working channel __ protection channel
“This recommendation provides the necessary equipment-level specifications to implement different choices of protection architectures for
Synchronous Digital Hierarchy (SDH) networks. ...
Physical implementations of these protection architectures may include rings, or linear chains of nodes. Each protection classification includes guidelines on network objectives, architecture, application functionality, switching criteria, proto­cols, and algorithms.” A series of mechanisms, designed to prevent pro­longed transmission path downtimes in the event of a defect, is defined for SDH networks.
The generic term for these mechanisms is APS (Automatic Protection Switching). System resources which during normal operation are either not used at all or only for very low-priority traffic are made available for this purpose. If a defect occurs, the “normal” traffic is then diverted automatically to these spare paths. In addition to the correct sequence of this switchover procedure, which may involve more than 10 different network elements, the time from the interruption of traffic to when the connection is restored is a critical factor. According to ITU-T Recommendation G.841, this time should be less than 50 ms.
In Brief
Page 18
16
In the event of a cable cut, normal traffic transmit­ted toward the failed span is switched at one node to the protection channels trasmitted in the oppo­site direction (away from the failure). This bridged traffic travels the long way around the ring on the protection channels to the other node where the normal traffic from the protection channels is switched back onto the working channels. In the other direction, the normal traffic ist bridged and switched in the same manner. Figure 25b illustra­tes a ring switch in response to a cable cut. – Four-fiber shared protection ring Two out of the four glass fibers transport the work­ing channels and two the protection channels. One fiber pair (working + protection) travels clockwise
around the ring, while the other pair travels around it in the counterclockwise direction. Thus, bidirec­tional connections can be operated. There are two possible mechanisms if a defect occurs. One of them functions in the same way as with the two-fiber shared protection ring. The traffic is switched over in the network elements located closest to the fault and transported via the protection fiber for the opposite direction (“ring switching”). The second mechanism is known as “span switch­ing.” In the event of a defect the traffic is trans­ported via the protection fiber that operates in the same direction as the faulty working fiber. Conse­quently, only the link segment that is actually faulty is switched over to standby.
Section 7.1 of the revised Recommendation G.841 contains the protocol for the switchover procedure of the APS mechanisms compatible with 1: n operation.
1+1 operation:
The traffic is transported simultaneously via the working path and the protection path. The receiv­ing end then decides which of the two paths is to be used.
1:1 operation:
The spare path can only be used if a switchover takes place at both the transmitting end and the receiving end.
1:N operation:
A 1:N configuration represents a more cost-effect­ive solution than the other two mechanisms de­scribed above. N working channels are protected by one protection channel. If there are no defects in the network, this protection channel can be used to transport low-priority traffic.
Application
Proper interworking of the network elements re­quires the proper response on the part of the APS
Recommendation G.841 Section 7.1 (G.783 Annex A): Linear Multiplex Section Protection (MSP)
Annex B of G.841 describes the MSP protocol optimized for 1+1 operation. Linear MSP was specified in Annex A of G.783 which is now included in the new revised Recommendation G.841.
In Brief
signaling to changes in the signal status or to the appropriate switching commands from network management. The ANT-20 makes this test simple and reliable by interpreting the protocol elements in plain text. APS commands can also be generated in the descriptor directly from the menu, without complicated bit manipulations. The ANT-20 understands the K1/K2 codes for linear MSP conforming to ITU-T G.783 as well as those for MS SPRING to ITU-T G.841. We measure the switchover time out-of-service (OOS) on the PDH or SDH/SONET tributaries of the ADMs (add-drop multiplexers). Depending on the configuration, alarms and bit errors (Test Sequence Errors, TSE) appear on the tributary ports for the duration of the switchover procedure. What customers are interested in is the interruption time on the tributary and not just the K1/K2 switchover according to the APS protocol.
Figure 27:
ANT-20 interpreter
for ring switching
Page 19
The ANT-20Õs solution is flexible and lets you se­lect different events as your measurement criterion:  SDH: MS-AIS, AU-AIS, TU-AIS, TSE  SONET: AIS-L, AIS-P, AIS-V, TSE The switchover time is specified as 50 ms. The ANT-20 measures the duration of the event on the tributary with a resolution of 1 ms, even if the
-
signal has bit error ratios up to 2u10
4
. A second ANT-20 can be used to generate the APS. In through mode, the instrument generates
-
the alarm types SF (B2 >1u10
-
(B2 >1u10
6
), and in OOS mode also LOS, LOF,
3
) and SD
MS-AIS (AIS-L). The procedure is as follows:
1. Set the signal structure using the ANT-20Õs
signal structure editor. Start the APS time measurement.
2. Activate APS by manually interrupting the
working channel, by generating an event with a second ANT-20 in through mode, or using a network management setting.
3. Measure the interruption time. Compare it with
the expected value. Result interpretation is simple: ÒpassedÓ or ÒfailedÓ.
Figure 28: Result from the switch-over measurement
If the switch-over time is exceeded or communi­cation between the network elements is not reliable, we must find the reason. With its byte capture function, the ANT-20 enables detailed analysis of the SOH bytes. Up to 265 changes in the K1/K2 combination are recorded. The ANT-20 can be configured to measure in monitor mode or in through mode in the protection channel of the SDH ring.
APS time measurement. Event: AIS, TSE
Figure 29: Measuring switch-over time
Figure 30: Byte capture shows content of K1/K2 bytes in plain text
working channel
protection channel
SOH/TOH byte capture
Abbreviation list :
ADM Add & Drop Multiplexer AIS Alarm Indication Signal APS Automatic Protection Switching BBE Backround Block Error BBER Backround Block Error Ratio BIP Bit Interleaved Parity BIS Bringing Into Service CRC Cyclic Redundancy Check DEMUX Demultiplexer DXC Digital Cross Connect ES Errored Second ESR Errored Second Ratio EFS Error Free Second FMTJ Fast Maximum Tolerable Jitter IG International Gateway ISM In Service Monitoring JTF Jitter Transfer Function HP High Order Path LOF Loss Of Frame LP Low Order Path MS Multiplex Section MSOH Multiplex Section
Overhead
MSP Multiplex Section
Protection
MST Multiplex Section Termination
Function MTJ Maximum Tolerable Jitter MTIE Maximum Time Interval Error MUX Multiplex OOS Out of Service OS Optical Section PDH Plesiochronous Digital Hierarchy PEP Path End Point RDI Remote Defect Indication PRC Primary Reference Clock UI Unit Interval REG Regenerator RS Regenerator Section RST Regenerator Section Termination
Function RSOH Regenerator Section Overhead SES Severely Errored Second SESR Severely Errored Second Ratio SD Signal Degradation SDH Synchronous Digital Hierarchy SEC Synchronous Equipment Clock SF Signal Failure STM Synchronous Transport Module TDEV Time Deviation VC Virtual Container
Author
Ben Di-Lorenzo, Stephan Schultz, Frank Coenning, Wolfgang Miller State: December 1998
Page 20
Wandel&Goltermann Worldwide
Canada
Wandel & Goltermann Inc. 21 Rolark Drive Scarborough, Ontario M1R 3B1 Tel. +1-416 2917121 Fax +1-416 291 2638
USA
Wandel & Goltermann Inc. P. O. Box 13585 Research Triangle Park, NC 27709- 3585 Tel. +1-919 -941-5730 Fax +1-919-941-5751
Mexico
Wandel & Goltermann de Me xico S.A. de C.V. San Francisco No. 6 Col. Del Valle Me xico D.F. CP 03100 Me xico Tel. +52 -5 543 6644 Fax +52- 5 543 8660
Latin America
Argentina/Uruguay
Wandel & Goltermann S.A. MontanÄ eses 2599 1428 Buenos Aires Argentina Tel. +54 -114784 4700 Fax +54-11 4786 7917
Brazil/Chile/Peru/Bolivia/ Paraguay
Wandel & Goltermann InstrumentacËaÄ o Ltda. & Cia. Av. Eng. Luis Carlos Berrini, 936-9. andar 04571-000 SaÄ o Paulo, SP Brazil Tel. +55 -115505 3800 Fax +55-11 5505 1598
Colombia/Ecuador
Wandel & Goltermann Andina Ltda. A.P. 55052 Cra. 14 No. 85- 82, Oficina 401 Santafe de BogotaÂDC Colombia Tel. +57-1 2564001 Fax +57-1 616 3267
Guatemala/Central America/ Caribbean Islands
Wandel & Goltermann de Centroamerica y el Caribe 6a. Calle 6-48 zona 9 Edificio Tivoli Plaza, of. 507 Apartado Postal 2761 0100 9 Guatemala Ciudad Guatemala Tel. +502 -3 3180 65 Fax +502- 3 31 86 82
Venezuela
Wandel & Goltermann Venezuela Av. Eugenio Mendoza con 1era. Transversal Edif. Banco de Lara, Piso 7, Ofic. A-1 La Castellana Z.P. 1060 Caracas, Venezuela Tel. +58 -2 -2630605 Fax +58- 2-2636465
Europe
Austria CIS Countries, East and Southeast Europe, Iran, Turkey, Pakistan
Wandel & Goltermann GmbH Postfach 13 Elisabethstraûe 36 A-2500 Baden Tel. +43 -22 5285 521-0 Fax +43- 22 52 80 727
Belgium/Luxemburg
Wandel & Goltermann nv/sa Imperiastraat 10 B-1930 Zaventem Tel. +32 -2 725 18 19 Fax +32- 2 725 41 42
Finland
Wandel & Goltermann AB Tekniikantie 12 FIN- 02150 Espoo Tel. +358 -(0)9 -4354 3199 Fax +358- (0)9-455 1522
France
Wandel & Goltermann France 46 bis, rue Pierre Curie B.P. 10 Z.I. Les Gaà tines F-78373 Plaisir Ce dex TeÂl. + 33- (0)1 30 81 50 50 Fax +33- (0)1 30 55 87 75
Germany
Wandel &Goltermann GmbH & Co. Vertriebsgesellschaft P.O.Box 1155 D-72794 Eningen u.A. Tel. +49 -7121 862222 Fax +49-7121 861222 e-mail: vertrieb@wago.de
Italy
Wandel & Goltermann S.R.L. Tecnologie di Misura Elettroniche Via Pomponazzi 25 I-20 141 Milano Tel. +39 -02 895 12381 Fax +39- 02 89511780
Netherlands
Wandel & Goltermann bv Postbus 1575 NL-5602 BN Eindhoven Tel. +31- 40- 267 97 00 Fax +31-40 -267 97 11
Norway
Wandel & Goltermann AB Postboks 134, Skùyen Hovfaret 13 N-0212 Oslo Tel. +47- 22- 504090 Fax +47-22 -504025
Spain/Portugal
Wandel &Goltermann S.A. c/Arturo Soria n
o
343 - 3
o
E- 28033 Madrid Tel. +34 -91-383-9801 Fax +34-91-383- 2263
Sweden
Wandel & Goltermann AB Box 6044 Ellen Keys Gata 60 S-129 06 HaÈ gersten Tel. +46 -8 -449 48 00 Fax +46-8 -449 48 39
Switzerland
Wandel & Goltermann (Schweiz) AG Postfach 779 Morgenstrasse 83 CH- 3018 Bern 18 Tel. +41- 31 991 77 81 Fax +41-31 99147 07
United Kingdom
Wandel & Goltermann Sales Ltd. Portland House, Aldermaston Park Aldermaston, Berkshire RG7 4HR England Tel. +44 -1189 409200 Fax +44-1189 409210 e-mail: wguk.help@wago.de
East and South East Europe
see Austria
Africa
Wandel & Goltermann GmbH & Co. Vertriebsgesellschaft P.O.Box 1155 D-72794 Eningen u.A. Tel. +49-7121-8611 83 Fax +49-7121-86 21 55 e-mail: export.germany@wago.de
Asia
Middle East see Germany
South East Asia see Australia
India
Wandel & Goltermann Pvt. Ltd. R. K. Khanna Tennis Stadium Africa Avenue New Delhi 110029 Tel. +91-11-619 6420 Fax +91-11-619 6190
CIS Countries/Iran/Turkey/Pakistan
see Austria
China
Wandel & Goltermann Pty.Ltd. Beijing Office Suite 1902 Ever Bright Building 6, Fu Xing Men Wai Da Jie Beijing 100045 Peoples Republic of China Tel. +86 -10- 6856 1034 Fax +86-10- 6856 1031
Hong Kong
Wandel & Goltermann Ltd. Rm 1501, Fook Lee Commercial Centre Town Place, 33 Lockhart Road Wanchai, Hong Kong Tel. +852 -2528 -6283 Fax +852-2529 -5593
Japan
Wandel & Goltermann K.K. Kyoritsu Shin-Yokohama Bldg. 6F 2-15-12 Shin-Yokohama Kouhoku-ku Yokohama, 222 Japan Tel. +81- 45- 473- 9501 Fax +81-45- 473- 9812
Republic of Korea
Wandel & Goltermann Ltd. 1st Fl., Yehsung Bldg. 150-30 Samsung-dong, Kangnam-ku, Seoul 135-091, Korea Tel. +82 -2 -563 2236/7 Fax +82-2 -563 2239
Singapore
Wavetek Asia-Pacific Pte Ltd 438B Alexandra Road Alexandra Technopark Hex 06-07 Singapore 119968 Tel. +65 -377 -3003 Fax +65-377-3033
Australia and Pacific Region
Australia
Wandel & Goltermann Pty. Ltd. P. O. Box 419 World Trade Centre Melbourne, Victoria 3005 Australia Tel. +61- 3- 9690 6700 Fax +61-3-9690 6750
New Zealand
Wandel & Goltermann Pty. Ltd. P. O. Box 10 418 The Terrace Wellington New Zealand Tel. +64-4-4952290 Fax +64-4 -4952292
For all other countries
(not listed) please contact: Wandel &Goltermann GmbH&Co. Elektronische Meûtechnik Marketing International Postfach 12 62 D-72795 Eningen u.A. Tel. +49- 7121-86 16 16 Fax +49 -7121- 86 1333 e-mail: solutions@wg.com http://www.wg.com
Subject to change without notice ± Order no. E02.99/WG1/59/5.0
Printed in Germany ã
Subject to change without notice – Order no. E02.99/WG1/59/5.0
Printed in Germany ©
Loading...