LEROY-SOMER reserves the right to modify the characteristics of its products at any time in order to incorporate the latest
technological developments. The information contained in this document may therefore be changed without notice.
CAUTION
For the user’s own safety, this VARMECA 30 motor must be connected to an approved earth ( terminal).
If accidentally starting the installation is likely to cause a risk to p ersonnel or the machines being driven, it is essential to supply
the equipment via a circuit-breaking device (power contactor) which can be controlled via an external safety system (emergency
stop, detection of errors on the installation).
The VARMECA 30 motor is fitted with safety devices which, in the event of a fault, control stopping and thus stop the motor. The
motor itself can become jammed for mechanical reasons. Voltage fluctuations, and in particular power cuts, may al so cause the
motor to stop.
The removal of the causes of the shutdown can lead to restarting, which may be dangerous for certain machines or installations.
In such cases, it is essential that the user takes appropriate precautions against the motor restarting after an unscheduled stop.
The variable speed drive is designed to be able to supply a motor and the driven machine above its rated speed.
If the motor or the machine are not mechanically designed to withstand such speeds, the user may be exposed to serious danger
resulting from their mechanical deterioration. It is important that the user checks that the installation can withstand it, before
programming a high speed.
The variable speed drive which is the subject of this manual is designed to be integrated in an installation or an electrical machine,
and can under no circumstances be considered to be a safety device. It is therefore the responsibility of the machine manufacturer,
the designer of the installation or the user to take all necessary precautions to ensure that the system complies with current
standards, and to provide any devices required to ensure the safety of equipment and personnel.
LEROY-SOMER declines all responsibility in the event of th e above recommendations not being observed.
36
LEROY-SOMER
INSTALLATION AND MAINTENANCE
3776 en - 07.2007 / h
VARMECA 30
Variable speed motor or geared motor
SAFETY AND OPERATING INSTRUCTIONS FOR ELECTRICAL ACTUATORS
(In accordance with the low voltage directive 73/23/EEC modified by 93/68/EEC)
• Throughout the manual, this symbol warns of
consequences which may arise from inappropriate
use of the VARMECA 30, since electrical risks may lead
to material or physical damage as well as constituting a
fire hazard.
1 - General
Depending on their degree of protection, VARMECA 30
motors may contain moving parts, as well as hot surfaces,
during operation.
Unjustified removal of protection devices, incorrect use, faulty
installation or inappropriate operation could represent a
serious risk to personnel and equipment.
For further information, consult the manual.
All work relating to transportation, installation, commissioning
and maintenance must be performed by experienced,
qualified personnel (see IEC 364 or CENELEC HD 384, or
DIN VDE 0100 and national specifications for installation and
accident prevention).
In these basic safety instructions, qualified personnel means
persons competent to install, mount, commission and operate
the product and possessing the relevant qualifications.
2 - Use
VARMECA 30 motors are components designed for
integration in installations or electrical machines.
When integrated in a machine, commissioning must not take
place until it has been verified that the machine conforms with
directive 89/392/EEC (Machinery Directive).
It is also necessary to comply with standard EN 60204, which
stipulates in particular that electrical actuators (which include
VARMECA 30) cannot be regarded as circuit-breaking
devices and certainly not as isolating switches.
Commissioning can take place only if the requirements of the
Electromagnetic Compatibility Directive (89/336/EEC,
modified by 92/31/EEC) are met.
VARMECA 30 motors meet the requirements of the Low
Voltage Directive 73/23/EEC, modified by 93/68/EEC. The
harmonised standard of the DIN VDE 0160 series in
connection with standard VDE 0660, part 500 and EN 60146/
VDE 0558 are also applicable.
The technical characteristics and instructions concerning the
connection conditions specified on the nameplate and in the
documentation provided must be observed without fail.
4 - Installation
The installation and cooling of equipment must comply with
the specifications in the manual supplied with the product.
VARMECA 30 motors must be protected against excessive
stress. In particular, there must be no damage to parts and/or
modification of the clearance between components during
transportation and handling. Avoid touching the electronic
components and contact parts.
VARMECA 30 motors contain parts which are sensitive to
electrostatic stress and may be easily damaged if handled
incorrectly. Electrical components must not be exposed to
mechanical damage or destruction (risks to health!).
5 - Electrical connection
When work is performed on VARMECA 30 motors which are
powered up, national accident prevention specifications must
be respected.
The electrical installation must comply with the relevant
specifications (for example conductor cross-sections,
protection via fused circuit-breaker, connection of protective
conductor). More detailed information is given in the manual.
Instructions for an installation which meets the requirements
for electromagnetic compatibility, such as screening,
earthing, presence of filters and correct insertion of cabl es
and conductors, are given in the documentation supplied with
the VARMECA 30. These instructions must be followed in all
cases, even if the VARMECA 30 carries the CE mark.
Adherence to the limits given in the EMC legisl ation is the
responsibility of the manufacturer of the installation or the
machine.
6 - Operation
Installations incorporating VARMECA 30 motors must be
fitted with additional protection and monitoring devices as laid
down in the current relevant safety regulations: law on
technical equipment, accident prevention regulations, etc.
Modification of VARMECA 30 motors using control software
is permitted.
Active parts of the device and live power connections must
not be touched immediately after the VARMECA 30 is
powered down, as the capacitors may still be charged. In view
of this, the warnings fixed to VARMECA 30 motors must be
observed.
During operation, all protective covers must remain closed.
en
3 - Transportation, storage
All instructions concerning transportation, storage and correct
handling must be observed.
The climatic conditions sp ecified in the technica l manual must
be observed.
7 - Servicing and maintenance
Refer to the manufacturer’s documentation.
37
LEROY-SOMER
INSTALLATION AND MAINTENANCE
VARMECA 30
Variable speed motor or geared motor
Notes
3776 en - 07.2007 / h
38
LEROY-SOMER
INSTALLATION AND MAINTENANCE
3776 en - 07.2007 / h
VARMECA 30
Variable speed motor or geared motor
CONTENTS
1 - GENERAL INFORMATION.............................................................................................................................. 40
1.1 - General operating principle............................................................................................................................. 40
1.6 - Description of cables and protection devices................................................................................................. 46
1.7 - UL conformity................................................................................................................................................. 47
1.8 - Weights and dimensions................................................................................................................................ 48
4.1 - Starting with the power supply....................................................................................................................... 62
4.2 - Starting with remote volt-free contact ............................................................................................................ 62
4.3 - Starting with local run/stop control (BMA 31/32, BMA 33/34 or BMAVAR 31/32,
7.1 - Speed control knob option (B 31/32 or B 33/34)............................................................................................ 64
7.2 - Control knob with integrated run-stop control option (BMA31/32 or BMA 33/34) .......................................... 64
7.3 - Control knob with forward/reverse/stop control option (BMAVAR 31/32
or BMAVAR 33/34)........................................................................................................................................ 64
7.4 - Internal speed control option (CVI VMA 31/32 or CVI VMA 33/34) ............................................................... 64
ional I/O interface and sequential brake control option (ESFR VMA 33/34).......................................... 65
en
5
39
LEROY-SOMER
INSTALLATION AND MAINTENANCE
3776 en - 07.2007 / h
VARMECA 30
Variable speed motor or geared motor
GENERAL INFORMATION
1 - GENERAL INFORMATION
• This manual describes the characteristics and installation of the VARMECA 31ML, 31M, 31TL, 31T, 32M, 32TL, 32T,
33TL, 33T, 34TL, 34T.
• The VARMECA 30 is designed to operate in an industrial environment. When used with an e xternal EMC filter,
the VARMECA 30 complies with standards for residential environment.
• If the run command has been enabled, the motor starts as soon as it is switched on.
1.1 - General operating principle
The VARMECA 30 is the physical association of a 3-phase
induction motor and an integrated variable speed drive.
The motor allows all kinds of mounting arrangement (foot or
flange) and can be combined with standard gearboxes from
the LEROY-SOMER range.
In the standard version, the drive with integrated control does
not require any connection other than the power supply.
The options may be used to broaden the application range of
the VARMECA 30.
Thanks to the advanced technology of the IGBT power
module, very high efficiency and reduced noise levels are
possible.
1.2 - Product name
Single-phase power supply
115 V ±10% - 50/60 Hz
Rating
31 ML 0250.2531 M 0250.2531 TL 0250.2531 T 0250.25
31 ML 0370.3731 M 0370.3731 TL 0370.3731 T 0370.37
Power (kW)
Single-phase power supply
200/240 V ±10% - 50/60 Hz
RatingPower (kW)RatingPower (kW)RatingPower (kW)
31 M 0550.5531 TL 0550.5531 T 0550.55
31 M 0750.7531 TL 0750.7531 T 0750.75
32 M 0900.9032 TL 0900.9031 T 0900.90
32 M 1101.132 TL 1101.131 T 1101.1
32 M 1501.532 TL 1501.532 T 1501.5
3-phase power supply
200/240 V ±10% - 50/60 Hz
32 TL 1801.832 T 1801.8
32 TL 2202.232 T 2202.2
33 TL 300332 T 3003
33 TL 400432 T 400 4
34 TL 550 5.533 T 5505.5
34 TL 7507.533 T 7507.5
3-phase power supply
400/480 V ±10% - 50/60 Hz
34 T 9009
34 T 11111
40
LEROY-SOMER
INSTALLATION AND MAINTENANCE
3776 en - 07.2007 / h
VARMECA 30
Variable speed motor or geared motor
GENERAL INFORMATION
OPERA T ING EXTENSIONS
DesignationDescription
B 31/32 or B 33/34Integrated speed control knob
BMA 31/32 or BMA 33/34Speed control knob and integrated run-stop control knob
BMAVAR 31/32 or BMAVAR 33/34Speed control knob and integrated stop forward/reverse control knob
CVI VMA 31/32 or CVI VMA 33/34Integrated speed control
ESFR VMA 31/32 or ESFR VMA 33/34Brake control
RF100 – RF200 – RF600Braking resistor Power 100, 200 and 600 W
RF – BRR – 800 – 200Braking resistor Power 800 W – External mounting
PX LCDParameter-setting console
COD VMA 33/34Encoder feedback
SOFTVMA 30Parameter-setting software
PAD VMA 31/32 or PAD VMA 33/34Local display unit
PX KEYCopy key
SO VMA 31/32Fixed brake control and power supply (3-phase supply 400-480 V only)
VMA COM PB 31/32 or VMA COM PB 33/34Fieldbus: PROFIBUS DP
VMA COM IS 31/32 or VMA COM IS 33/34Fieldbus: INTERBUS S
VMA COM DT 31/32 or VMA COM DT 33/34Fieldbus: DEVICENET
VMA COM CN 31/32 or VMA COM CN 33/34Fieldbus: CAN OPEN
FLT VMA 31MEMC filter for residential environment – Internal mounting (for VMA 31M)
FLT VMA 31/32EMC filter for residential environment – Internal mounting (for VMA 31TL/T 32/TL/T)
FLT VMA 33EMC filter for industrial environment – Internal mounting (for VMA 33 TL/T)
FLT VMA 34EMC filter for industrial environment – Internal mounting (for VMA 34 TL/T)
en
1.3 - Characteristics
1.3.1 - Electrical data
Power supply
Phase voltage imbalance-3%
Output voltageFrom 0 V to input voltageFrom 0 V to input voltage
Power range (kW)0.25 - 0.37* - 0.55 - 0.75 - 0.9 - 1.1 - 1.5
Maximum number of power-
ups per hour
*0.37 kW max. for 115 V supply (0,75 kW with 310M rating)
**7.5 kW max. for 230 V supply
- 10 to 80 Hz at constant torque (factory setting can be modified with parameter-setting
Motor frequency variation
range
Efficiency97.5% motor efficiency
Overload
option)
- 10 to 50 Hz for general applications (factory setting can be modified with parameter-setting
option)
- 0 to Fmax depending on thermal and mechanical limits (Fmax = 400 Hz ; LEROY-SOMER to
be consulted anytime the applications requires the drive to run at more than 150 Hz)
- Analogue reference (0 V or 4 mA) = Minimum speed
(10 V or 20 mA) = Maximum speed
- 0 to 10 V with integrated potentiometer (B31/32 – B33/34 option)
Speed reference
Speed regulation
Run/Stop
Forward/Reverse
Stop mode
Ramps- Ramps adjustable from 0 to 600s
Fieldbus- PROFIBUS DP, INTERBUS S, DEVICENET, CAN OPEN, MODBUS RTU, LS NET
- 0 to 10 V with remote potentiometer
- 4 to 20 mA with external reference
- Reference with internal potentiometer
- Digital references
- Fieldbus
- Speed regulation with encoder feedback option for VMA 33 or 34 only
- Regulation of a reference with integrated PI loop
- With power supply
- With remote volt-free contact
- With fieldbus
- With local run/stop control
- With internal connection on the terminal block
- With remote volt-free contact
- With fieldbus
- With local run/stop control
- On ramps (using volt-free contact or integrated control)
- Freewheel
- With electromechanical brake
ProtectionVARMECA 30
- Undervoltage (see notice 3847)
- Overvoltage (see notice 3847)
- Overloads (see notice 3847)
Power
Control- Short-circuit on 0-10 V/24 V inputs or outputs
Drive reset
.thermal, drive and motor
.protection against locked rotor
- Short-circuit
.motor windings
- Overspeed (see notice 3847)
- By switching off the VARMECA 30 or by opening/closing the connection between the 24V
and ENA (VMA 31/32) terminals or SDI 1 and SDI 2 (VMA 33/34) terminals
42
LEROY-SOMER
INSTALLATION AND MAINTENANCE
VARMECA 30
Variable speed motor or geared motor
GENERAL INFORMATION
1.4 - Environmental characteristics
CharacteristicsLevel
Index of protectionIP 65
Storage temperature- 40 °C to + 70 °C Conforming to standard IEC 68-2-1.
Transport temperature- 40 °C to + 70 °C
Operating temperature- 20 °C to + 50 °C (with power derated by 1% per °C, above 40 °C)
< 1000 m without derating.
Altitude
Ambient humidity95% non condensing
Humidity during storage93%, 40 °C, 4 days
Vibration
Shocks
ImmunityConforming to EN61000-6-2
Radiated and conducted
emissions
UL standardsConforming to UL 508 C (E211799)
The maximum authorised altitude is 4000 m, but above 1000 m, the continuous output current
should be derated by 1% per additional 100 m over 1000 m (eg: for an altitude of 3000 m,
derate by 20%).
- Exposed product: 0.01 g
- Sinusoidal vibration:
• VMA 31/32 : 2-9 Hz 3,5 ms
• VMA 33/34 : 2-6 Hz 3,5 ms-2 - 6-100 Hz 5 ms
in accordance with standard IEC 68-2-6.
Packaged product: 15 g, 6 ms, 500 times/direction in all 6 directions in accordance with
standard
IEC 68-2-29.
Conforming to EN50081-2 with internal filter
2
/Hz 1 hr in accordance with standard IEC 68-2-34.
-2
- 9-100 Hz 10 ms
-2
-2
3776 en - 07.2007 / h
en
1.5 - Radio-frequency interference
1.5.1 - General
Variable speed drives use high-speed switches (transistors,
semi-conductors) which switch high voltages (around
550VDC for 3-phase drives) at high frequencies (several
kHz). This provides better efficiency and a low level of motor
noise.
As a result, they generate radio-frequency signals which may
disturb operation of other equipment or distort measurements
taken by sensors:
- due to high-frequency leakage currents which escape to
earth via the stray capacity of the drive/motor cable and that
of the motor via the metal structures which support the motor
- by conduction or feedback of R.F. signals on the power
supply cable: conducted emissions
- by direct radiation near to the mains supply power cabl e or
the drive/motor cable: radiated emissions
These phenomena are of direct interest to the user.
The frequency range concerned (radio frequency) does not
affect the energy distribution company.
Conformity of the drive is only assured when the
mechanical and electrical installation instructions
described in this manual are adhered to.
43
LEROY-SOMER
INSTALLATION AND MAINTENANCE
3776 en - 07.2007 / h
VARMECA 30
Variable speed motor or geared motor
GENERAL INFORMATION
1.5.2 - Standards (Emission)
The maximum emission level is set by the generic industrial (EN 50081-2) and residential (EN 50081-1) standards.
VARMECA 30 conforms to the following standards:
EN 50081-2, EN 61000-6-4 - EN 61800-3, IEC 61800-3.
Emission
Conformity conditions according to the
switching frequency
StandardDescriptionApplication
Second environment with
unrestricted distribution (DENR)
Second environment with
EN 61800-3Variable speed drive standards
EN 50081-1Generic emission standards for
EN61000-6-3
EN 50081-2Generic emission standards for
EN 61000-6-4
residential, commercial and light
industrial environments
the industrial environmentA.C. supply
restricted distribution (DER)
First environment with
unrestricted distribution (R)
First environment with restricted
distribution (I)
A.C. supply-
VMA 31/32 ≤ 10kHz
VMA 33/34 ≤ 11kHz
VMA 31/32 ≤ 10kHz
VMA 33/34 ≤ 11kHz
VMA 31/32 ≤ 4kHz
VMA 33/34 ≤ 4,5kHz
VMA 31 ≤ 8kHz
VMA 32 ≤ 4kHz
VMA 33/34 ≤ 4,5kHz
With EMC filter
InternalExternal
VMA 31/32 ≤ 10kHz
VMA 33/34 ≤ 11kHz
VMA 31/32 ≤ 10kHz
VMA 33/34 ≤ 11kHz
-
VMA 31/32 ≤ 4kHz
VMA 33/34 ≤ 4,5kHz
VMA 31/32 ≤ 10kHz
VMA 33/34 ≤ 11kHz
VMA 31/32 ≤ 4kHz
VMA 33/34 ≤ 11kHz
VMA 31/32 ≤ 10kHz
VMA 33/34 ≤ 11kHz
The second environment includes industrial networks supplied with low voltage but which do not serve buildings
for domestic use. Operation of a dr iv e with out an EMC filte r in this ty pe of e nvironment may resu lt in inte rference
on certain electronic appliances located near the drive whose immun ity level might not be compatible with industrial
conditions. If it proves impossible to filter the disturbed element, add an external EMC filter.
44
LEROY-SOMER
INSTALLATION AND MAINTENANCE
3776 en - 07.2007 / h
VARMECA 30
Variable speed motor or geared motor
GENERAL INFORMATION
1.5.3 - Standards (Immunity)
The minimum immunity level is set by the generic industrial (EN 51000-6-2) and residential (EN 51000-6-1) standards.
VARMECA 30 conforms to the following standards:
EN 61000-4-2, IEC 61000-4-2 - EN 61000-4-3, IEC 61000-4-3 - EN 61000-4-5, IEC 61000-4-5 - EN 61000-4-6, IEC 61000-4-6 EN
61000-4-11, IEC 61000-4-11 - EN 61000-6-2, IEC 61000-6-2 - EN 61000-3, IEC 61000-3.
Immunity
StandardDescriptionApplicationConformity
IEC 61000-4-3 Immunity standards for radiated
EN 61000-4-3
IEC 61000-4-6 Generic immunity standards for
EN 61000-4-6
EN 50082-1Generic immunity standards for
EN 61000-6-1
EN 50082-2
EN 61000-6-2
EN 61800-3
EN 61000-6-2
EN 61000-4-4 Bursts of fast transientsControl cableLevel 4 (hardened industrial)
EN 61000-4-5 Shock wavesPhase-earth power supply cableLevel 4
radio-frequency
conducted radio-frequency
residential, commercial and light
industrial environments
Generic immunity standards for the
industrial environment
Variable speed drive standardsConforms to the first and second environmentIEC 61000-6-2
shielded cables outside product
Product casingLevel 3 (industrial)
Control and power cables
-ConformsIEC 61000-6-1
-ConformsIEC 61000-6-2
Power cableLevel 3 (industrial)
Phase-to-phase power supply
cable
Earth signal circuits
(refer to section 1.5.5)
Level 3 (industrial)
Level 3
Level 2
en
1.5.4 - Earth leakage current
Earth leakage currents may depend on the type of EMC filter
used. The VARMECA 30 can be supplied with its filter
integrated and wired-up. The levels of leakage current also
depend on the voltage and/or the power supply frequency
and the size of the motor.
In all cases, for conformity with immunity standards, a voltage
limiting device is connected to earth. The shunt current is
negligible in normal circumstances.
1.5.4.1 - use of earth leakage detector (residual current
device)
1- Type AC: which detects AC faults. Not to be used with
variable speed drives.
2- Type A: which detects AC faults and pulsed DC faults
(provided that the DC is cancelled out at least once per cycle).
Only for use with single-phase drives.
3 - Type B: which detects AC faults, pulsed DC faults and
smoothed DC faults. Only this type is suitable for use with
all variable speed drives.
Note: If an external EMC filter is being used, a delay of 50 ms
should be incorporated to avoid spurious faults being taken
into account.
1.5.5 - Control cable immunity
Control cable immunity can be increased outside the
VARMECA 30 by one of the following 2 methods:
• Use of shielded twisted pair cable, with shielding connected
to earth around its circumference within 100 mm of the
VARMECA 30.
• Passing the cable through a ferrite ring at 100 mm maximum
distance from the VARMECA 30.
Note: Several control cables can pass through a single
ferrite.
1.5.6 - Control circuit immunity when
overvoltage occurs
Immunity to overvoltages in control circuits or in long cables
connected to the outside of a building.
The various drive input and output circuits conform to
standard EN61000-6-2 (1 kV) relating to overvoltages.
There are some exceptions, where the installation may be
exposed to overvoltage peaks which exceed the levels
determined by the standard. This may be the case in the
event of lightning strikes or earth faults associated with long
cable lengths (>30 m). To limit the risks of damage to the
drive, the following precautions could be taken:
45
LEROY-SOMER
30 V Zener diode
(eg: 2xBZW50-15
Signal
0V0V
to the drive
INSTALLATION AND MAINTENANCE
VARMECA 30
Variable speed motor or geared motor
GENERAL INFORMATION
3776 en - 07.2007 / h
- Galvanic isolation of the I/O.
- Duplication of the cable shielding with an earth wire of
2
10 mm
must be linked at both ends and connected to earth with the
shortest possible connection. This stratagem enables high
currents to pass into the earth wire, rather than into the
shielding
- Reinforcement of the logic and analogue I/O protection by
adding a zener diode or a peak limiter.
Elimination of uni-directional logic and analogue I/O
overvoltages
minimum. The cable shielding and the earth wire
These circuits are available in modules (DIN rail mounting).
These circuits are not suitable for encoder signals or for highspeed logic data networks, because the diodes may affect the
signal. The majority of encoders have galvanic isolation
between the motor casing and the encoder circuit, and in this
case, no precautions are necessary. For data networks,
follow the specific network recommendations.
If a logic output is subjected to significant overvoltages, the
drive trips on an "Old1" fault.
1.6 - Description of cables and protection devices
• It is the responsibility of the user to connect and provide protection for the VARMECA 30 in accordance with the
legislation and regulations in force in the country of use. This is particularly important as regards the size of cables,
the type and rating of fuses, the earth or ground connection, powering down, acknowledging faults, insulation and
protection against overcurrents.
• These tables are given for information only, and must under no circumstances be used in place of the current standards.
• When using a circuit-breaker, it must be a motor circuit-brea ker (D curve).
• The residual current device must be type B. Too many devices connected to a single residual current device can cause
it to trip. Check that the circuit-breaker is only protecting the VARMECA.
• Comply with the size of protection fuses.
Single-phase power supply 110V - 10 % to 120 V + 10 %Single-phase power supply 208V - 10 % to 240V + 10 %
P
(kW)
0.2531 ML 02586.81.5M16 + M2031 M 02583.51.5M16 + M20
0.3731 ML 037108.51.5M16 + M2031 M 0371041.5M16 + M20
0.5531 M 055104.51.5M16 + M20
0.7531 M 0751672.5M16 + M20
0.932 M 0901692.5M16 + M20
1.132 M 11020112.5M16 + M20
1.532 M 15025142.5M16 + M20
VMA
rating
Fuses
(gG)
I (A)
Cables
2
(mm
)
PE
VMA
rating
Fuses
(gG)
I (A)
Cables
(mm2)
PE
46
LEROY-SOMER
INSTALLATION AND MAINTENANCE
3776 en - 07.2007 / h
VARMECA 30
Variable speed motor or geared motor
GENERAL INFORMATION
Three-phase power supply 208V - 10 % to 240V + 10 %Three-phase power supply 380V - 10 % to 480V + 10 %
P
(kW)
0.2531 TL 025421.5M16 + M203 1 T 025411.5M16 + M20
0.3731 TL 037631.5M16 + M2031 T 03741.51.5M16 + M20
0.5531 TL 055641.5M16 + M203 1 T 055621.5M16 + M20
0.7531 TL 075851.5M16 + M203 1 T 075631.5M16 + M20
0.932 TL 090105.51.5M16 + M2031 T 09083.51.5M16 + M20
1.132 TL 1101062.5M16 + M2031 T 1101041.5M16 + M20
1.532 TL 1501672.5M16 + M2032 T 1501051.5M16 + M20
1.832 TL 180167.52.5M16 + M2032 T 180105.52.5M16 + M20
2.232 TL 2201682.5M16 + M2032 T 2201062.5M16 + M20
333 TL 30016122.5M20 + M2532 T 3001672.5M16 + M20
433 TL 40020154M20 + M2532 T 4001682.5M16 + M20
5.534 TL 55025204M20 + M2533 T 55016122.5M20 + M25
7.534 TL 75032244M20 + M2533 T 75020164M20 + M25
934 T 900 25194M20 + M25
1134 T 1113 2224M20 + M25
VMA
rating
Fuses
(gG)
I (A)
Cables
2
(mm
)
PE
VMA
rating
Fuses
(gG)
I (A)
Cables
(mm2)
PE
en
Note:
• The mains current value is a typical value which depends on t he source impedance. The high er the impedance, the lower the
current.
• The fuses (UL approved) are intended for installations capable of delivering 5000 A maximum at 480 V.
1.7 - UL conformity
1.7.1 - Specified mains supply
The drive can be incorporated in an installation which can deliver 5000 A rms maximum at a voltage of 264 VAC rms maximum
for 230 V (TL) drives or 528 VAC rms maximum for 400 V (T) drives.
1.7.2 - Cables
Only class 1 copper cables 60/75 °C (140/167 °F) should be used.
1.7.3 - Fuses
UL conformity is adhered to if the fuses used are UL-listed, fast-blow fuses (class CC up to 30 A) with a rating as indicated in the
above table, and if the short-circuit symmetrical current does not exceed 5 kA.
47
LEROY-SOMER
INSTALLATION AND MAINTENANCE
3776 en - 07.2007 / h
VARMECA 30
Variable speed motor or geared motor
GENERAL INFORMATION
1.8 - Weights and dimensions
Dimensions (mm)
TypeVMA rating
LS 7131ML-31M - 31TL - 31T17688821775944.2
LS 80 L
LS 90 S/L
LS 100 L
LS 112 M
LS 112 MG
LS 132 S
LS 132 M33T - 34TL - 34T3008883361151418.1
• It is the responsibility of the owner or user to
ensure that the installation, operation and
maintenance of the drive and its options comply with
legislation relating to the safety of people and equipment
and with the regulations in force in the country of use.
• Before carrying out any work, disconnect and lock the
drive power supply. For the single-phase range, wait 2
minutes to make sure that the capacitors have
discharged.
• After connection, ensure that the seals are firmly in
place, and that the screws and cable glands are
watertight to ensure IP 65 protection.
• Holes are provided at the lowest points of the
enclosure, depending on the operating position, to drain
off any moisture that may have accumulated inside
during cooling of the machine. In conditions which
encourage the formation of con de nsation, it is advisable
to leave the drain holes permanently open.
3 - CONNECTIONS
• All connection work must be performed in
accordance with the laws in force in the country
where the drive is installed. This includes earthing to
ensure that no directly accessible part of the drive can be
at the mains voltage or any other v oltage which may be
dangerous.
• The voltages on the cables or connections of the mains
supply, the motor, the braking resistor or the filter may
cause fatal electric shocks. Contact must be avoided in
all circumstances.
• The drive must be supplied via a circuit-breaking device
so that it can be powered down safely.
• The drive contains capacitors which remain charged at
a fatal voltage even after the power supply has be en cut
off.
• Wait 2 minutes after powering down the drive before
removing the protection devices.
• The drive power supply must be protected against
overloads and short-circuits.
• It is vital to respect the rating of protection devices.
• Connection with copper conductor only.
• Check that the voltage and current of the drive, the
motor and the mains supply are compa t ible.
• After the drive has been operating, the hea tsink or the
braking resistors may be very hot (avoid touching them).
• When the cover is open, the VARMECA 30 degree of
protection is IP10. Any work should only be carried out
by experienced, qualified personnel.
2.1 - General
The VARMECA 30 motor is fitted to the machine like a
standard motor, with flange or foot mounting.
The motor ventilation cools the whole assembly. Make sure
that the ventilation air inlet is free of obstruction.
The positions of the potentiometer/cable gland supports are
specified at the time of ordering. However they may be
reversed if necessary.
en
• Check that the different earth points are actually at the same
voltage.
• Incorporate a bend where the cables enter the cable glands
so that water cannot penetrate the terminal box.
• Tighten the cable gland firmly.
• The VARMECA 30 has a positive logic
configuration.
Using a drive with a control system which has a different
control logic may cause unwanted starting of the motor.
• The control circuits in the drive are isolated from the
power circuits by single insulation (IEC 664-1). The
installer must ensure that the external control circuits are
isolated against any human contact.
• If the control circuits need to be connected to circuits
conforming to SELV safety requirements, additional
insulation must be inserted to maintain the SELV
classification.
3.1 - Wiring precautions
• When the VARMECA 30 is controlled remotely, avoid
parallel routing of power cables and control cables.
• All remote control cables must be shielded and have a
cross-section between 0.22 mm
should be connected to earth at both ends.
2
and 1 mm2. The shielding
49
LEROY-SOMER
INSTALLATION AND MAINTENANCE
VARMECA 30
Variable speed motor or geared motor
CONNECTIONS
3776 en - 07.2007 / h
3.2 - Control terminal blocks
• Check that the terminal block has been removed
from its fixed holder (unplugged) before making
any connections, so as to avoid putting pressure on the
card.
• The VARMECA has a positive logic configuration. Using
a drive with a control system which has a different
control logic may cause unwanted starting of the motor.
• Th e control circuits in the drive are isolated from the
power circuits by single insulation (IEC 664-1).
VMA
terminal
33/34
1110V+10V analogue internal source
22ADI1
330VLogic circuit common 0V
44
5NA0VLogic circuit common 0V
VMA
terminal
31/32
DesignationFunctionCharacteristics
Analogue or logic
input 1
Assignment in standard
configuration: 0-10V speed
reference
Analogue or logic
input 2
ADI2
Assignment in standard
configuration: Motor PTC input
The installer must ensure that the external control
circuits are isolated against any human contact.
• If the control circuits need to be connected to circuits
conforming to SELV safety requirements, additional
insulation must be inserted to maintain the SELV
classification.
Removable screw terminal block:
- Tightening torque = 0.3 N.m
- Max. cross-section = 1.5 mm
Accuracy± 2%
Maximum output current30 mA
Voltage input
Full scale voltage10 V ± 2%
Input impedance95 k
Current input
Current range0 to 20 mA ± 5%
Input impedance500
Resolution10 bits
Sampling6 ms
Logic input (if connected to the +24V)
Thresholds"0": < 5 V – "1": > 10 V
Voltage range0 to +24 V
Load95 k
Input threshold7.5 V
Voltage input
Full scale voltage10 V ± 2%
Input impedance95 k
Current input
Current range0 to 20 mA ± 5%
Input impedance500
Resolution10 bits
Sampling6 ms
Logic input (if connected to the +24V)
Thresholds"0": < 5 V – "1": > 10 V
Voltage range0 to +24 V
Load95 k
Input threshold7.5 V
Input (PTC)
Trip
Cleared fault threshold< 1800
≥
3300
Ω
Ω
Ω
Ω
Ω
Ω
2
Ω
Ω
50
LEROY-SOMER
INSTALLATION AND MAINTENANCE
VARMECA 30
Variable speed motor or geared motor
CONNECTIONS
3776 en - 07.2007 / h
VMA
terminal
33/34
66ADIO3
77DIO1
85
1111
98 DI2
109DI3
1210DI4
13NASDI1+24V dedicated to the safety input
1412SDI2/ENASafety/unlocking input
1513COM/RL1
16NARL1C
1714RL1O/RL2- 2 A, inductive load
18NASDO1
19NASDO2
VMA
terminal
31/32
DesignationFunctionCharacteristics
CharacteristicsAnalogue voltage (common mode) or uni-directional
Voltage input
Full scale voltage10 V ± 2%
Analogue or logic input or analogue
output 3
Assignment in standard
configuration: Analogue output
(LED control option for VMA31 up
to 34)
Digital input or output 1
Assignment in standard
configuration:
External fault management
24V+24V internal source
Logic input 2
Assignment in standard
configuration: Run forward
Logic input 3
Assignment in standard
configuration: Run reverse
Logic input 4
Assignment in standard
configuration: Selection of ADI1
Fault relay output
Safety contact
Input impedance95 k
Current input
Current range0 to 20 mA ± 5%
Input impedance500
Resolution10 bits
Sampling6 ms
Logic input (if connected to the +24V)
Thresholds"0": < 5 V – "1": > 10 V
Voltage range0 to +24 V
Load95 k
Input threshold7.5 V
Voltage output
Voltage range0 to 10 V
Load resistor2 k
ProtectionShort-circuit (40 mA max)
Current output
Current range0 to 20 mA
Maximum voltage10 V
Load resistor500
CharacteristicsDigital input or output 1
Thresholds"0": < 5 V – "1": > 10 V
Voltage range0 to +24 V
Sampling/refreshment2 ms
Digital input
Absolute maximum voltage 0 to +35 V
Load15 k
Input threshold7.5 V
Logic output
Maximum output current50 mA
Overload current50 mA
Output current10 mA in total
Overload currentVMA 33/34: 150 mA - VMA 31/32: 50 mA
Accuracy± 5%
ProtectionCurrent limiting and setting to fault mode
CharacteristicsLogic input (positive logic)
Thresholds"0": < 5 V – "1": > 10 V
Voltage range0 to +24 V
Sampling/refreshment2 ms
Absolute maximum voltage
range
Load
Input threshold7.5 V
CharacteristicsLogic input (positive logic)
Thresholds"0": < 5 V – "1": > 18 V
Voltage range9 to +33 V
Impedance820
Characteristics
250 VAC maximum contact
current
CharacteristicsNO single-pole changeover contact
3.3.1 - Terminal block for power supply PB1
(marked L1, L2 and L3)
This terminal block is used to connect the 3-phase power
supply when the EMC filter is not supplied with the
VARMECA 30. Otherwise, the EMC filter output is screwed
onto this connector and the power supply should be attached
to the terminals located on top of the filter.
3.3.2 - Terminal block for braking resistor PB2
(marked R+ and R-)
This terminal block is used to connect a braking resistor when
this option is required. The resistor is mounted on the outside
and/or the rear of the VARMECA 30 casing.
Screw terminal block:VMA 33/34VMA 31/32
Tightening torque1.8 N.m0.8 Nm
Max. cross-section 4 mm
Note: For the VMA 31/32, PB1 and PB2 are both
located on the same terminal block.
The terminal block on the VARMECA 31/32 has a terminal
marked FI connected to the R- terminal which enables
use of the internal braking resistor. The jumper must be
removed when an external braking resistor is connected
or if the inertia is incompatible with the rated
deceleration ramp.
2
(AWG8)2.5 mm
2
(AWG8)2.5 mm
2
2
3.4 - Terminal blocks for options
3.4.1 - RS485 type serial link connector
This is an RJ 45 connector and is used to connect the PX LCD
console or a PC in order to use the PEGASE VMA 30
programming software.
For the VMA 31/32 it is also used to connect the fieldbus or the
PADVMA 31/32 option.
3.4.2 - Description of Slot 1
(VMA 33/34 only)
This slot is used to connect the encoder fee dback module
(option: COD VMA 30) when "closed loop" mode is selected.
3.4.3 - Description of Slot 2
(VMA 33/34 only)
This slot is used to connect one of the fieldbus modules
(protocols supported: PROFIBUS DP, INTERBUS S,
DEVICE NET and CAN OPEN).
3.4.4 - P2 connector (VMA 31/32 only)
This is used to connect the following options: Local
potentiometer (B 31/32), local potentiometer with integrated
Run/Stop (BMA 31/32), local potentiometer with integrated
Forward/Reverse/Stop (BMAVAR), Brake control
(ESFRVMA 30), etc.
52
LEROY-SOMER
QS
Indicator relay
Locking input
0-10 V/4-20 mA
speed reference
(local options or external ref.)
Local option indication
External fault input
Forward/Stop
Reverse/Stop
Selection of 0-10 V/4-20 mA
speed reference
Motor PTC input
Braking resistor
(optional)
Jumper to be removed if
optional Braking resistor
connected
Mains supply
10V
ADI1
0V
ADI2
24V
ADIO3
DI01
DI2
DI3
Dl4
+24V
ENA
RL1
RL2
L1
L2
L3
R+
R-
Fi
PE
2
3
4
5
6
1
8
9
10
11
12
7
13
14
VARMECA 31/32
QS
Indicator relay
0-10 V/4-20 mA
speed reference
(local options or external ref.)
Local option indication
External fault input
Forward/Stop
Reverse/Stop
Locking input
Safety contact
Selection of 0-10 V/4-20 mA
speed reference
Motor PTC input
Braking resistor
(optional)
Mains supply
10V
ADI1
0V
ADI2
0V
ADIO3
DI01
+24V
DI2
DI3
+24V
DI4
SDI1
SDI2
COM
RL1C
RL10
SD01
SD02
L1
L2
L3
R+
R-
PE
2
3
4
5
6
1
8
9
10
11
12
13
14
7
15
16
17
18
19
VARMECA 33/34
INSTALLATION AND MAINTENANCE
VARMECA 30
Variable speed motor or geared motor
CONNECTIONS
3.5 - Wiring diagrams
3.5.1 - Standard configuration connection diagram
3776 en - 07.2007 / h
en
Note:
For single-phase versions, the power supply is connected to terminals L and N.
53
LEROY-SOMER
INSTALLATION AND MAINTENANCE
VARMECA 30
Variable speed motor or geared motor
CONNECTIONS
3776 en - 07.2007 / h
3.5.2 - Connection diagram with safety input
3.5.2.1 - Safety input
This input, when opened, causes the drive to lock.
Independent of the microprocessor, it acts on several levels
of control from the power bridge. It is designed in such a way
that even if one or more circuit components were to fail, the
absence of torque on the motor shaft is guaranteed with a
very high level of integrity.
This input is used to create a safety function using the
principles of category 1 or 3 of standard EN954-1, depending
on the application diagram.
The design of the "freewheel stop" function using input SDI2
has been evaluated by CETIM.
The results of this examination are recorded in report no.
732773/47A.
This built-in functionality enables the drive to act as substitute
for a contactor in order to stop the motor in freewheel mode.
By using this safety input redundantly with another drive logic
input, a diagram can be used which is ca pable of resisting a
single fault. The drive will stop the motor in freewhee l mode
using two different control channels.
For correct use, the power connection diagrams described in
the following paragraphs must be adhered to.
To unlock the drive and provide the safety function , safety
input ENA (VMA 31/32) or SDI2 (VMA 33/34) must be
connected to the +24V source (SDI1 for VMA 33/34).
This +24V source should be reserved exclusively for the
safety input function (VMA33/34).
• The safety input is a safety component which
must be incorporated into the complete system
dedicated to machine safety. As for any installation, the
complete machine must be the subject of a risk analysis
by the integrator which will determine the safety category
with which the installation must comply.
• The safety input, when open, locks the drive, mean ing
the dynamic braking function i s no longer avai lable. If a
braking function is required before the drive safety lock
is applied, a time-delayed safety relay should be installed
to activate locking automatically after the end of braking.
If braking needs to be a machine safety function, it
should be provided by an electromechanical solution
since the dynamic braking by the drive function is not
considered to be a safety function.
• The safety input does not provide the electrical isolation
function. Before any work is carried out, the power
supply must be cut by an approved isolating device
(isolator, switch, etc).
• The safety function is not enabled when the drive is
controlled via the keypad or via a fieldbus.
54
LEROY-SOMER
AU
QS
QS
10V
ADI1
0V
ADI2
24V
ADIO3
DI01
DI2
DI3
DI4
+24V
ENA
RL1
RL2
L1
L2
L3
R+
R-
Fi
PE
2
3
4
5
6
1
8
9
10
11
12
7
13
14
Indicator relay
0-10 V/4-20 mA
speed reference
(local options or external ref.)
Local option indication
External fault input
Forward/Stop
Reverse/Stop
Selection of 0-10 V/4-20 mA
speed reference
Motor PTC input
Braking resistor
(optional)
Jumper to be removed if
optional Braking resistor
connected
Mains supply
VARMECA 31/32
QS
10V
ADI1
0V
ADI2
0V
ADIO3
DI01
+24V
DI2
DI3
+24V
DI4
SDI1
SDI2
COM
RL1C
RL10
SD01
SD02
L1
L2
L3
R+
R-
PE
2
3
4
5
6
1
8
9
10
11
12
13
14
7
15
16
17
18
19
AU
QS
Indicator relay
0-10 V/4-20 mA
speed reference
(local options or external ref.)
Local option indication
External fault input
Forward/Stop
Reverse/Stop
Safety contact
Selection of 0-10 V/4-20 mA
speed reference
Motor PTC input
Braking resistor
(optional)
Mains supply
VARMECA 33/34
INSTALLATION AND MAINTENANCE
3776 en - 07.2007 / h
VARMECA 30
Variable speed motor or geared motor
CONNECTIONS
3.5.2.2 - 3-phase AC power supply in accordance with safety standard EN954-1 - category 1 with use of safety input
en
Note:
For single-phase standards, the power supply is connected to terminals L and N.
QS: Fused isolator: QS must be opened before any intervention on the electrical parts of the drive or motor.
AU: Emergency stop button.
Optional braking resistor. Dissipates the active power returned by the motor onto the drive DC bus in the event of a driving
machine.
Using the safety input means the motor can be stopped in freewheel mode without using a l ine contactor. The drive’s internal
principles are sufficiently safe to perform a stop using the safety input directly (category 1 of EN954-1).
55
LEROY-SOMER
KA
KA
AU
QS
10V
ADI1
0V
ADIO3
0V
DI01
+24V
DI2
DI3
+24V
DI4
SDI1
SDI2
COM
RL10
SD01
SD02
L1
L2
L3
R+
R-
PE
KA
0-10 V/4-20 mA
speed reference
(local options or external ref.)
Motor PTC input
Local option
indication
External
fault input
Selection of
0-10 V/4-20 mA
speed reference
Forward/Stop
Reverse/Stop
Braking resistor
(optional)
Mains supply
VARMECA 33/34 (only)
INSTALLATION AND MAINTENANCE
3776 en - 07.2007 / h
VARMECA 30
Variable speed motor or geared motor
CONNECTIONS
3.5.2.3 - 3-phase AC power supply in accordance with safety standard EN954-1 - category 2 or 3 with use of safety input
SDI2 redundantly with logic input DI2
QS: Fused isolator: QS must be opened before any intervention on the electrical parts of the drive or motor.
AU: Emergency stop button.
KA: Relays
Optional braking resistor. Dissipates the active power returned by the motor onto the drive DC bus in the event of a driving
machine.
Using the safety input means the motor can be stopped in freewheel mode without using a l ine contactor. The drive’s internal
principles are sufficiently safe to perform a stop using the safety input directly (category 1 of EN954-1).
Duplication of the stop command on a logic input enables use of the internal drive redunda ncy to perform a freewheel stop
(application of category 3 principles in accordance with EN954 for the part relating to the drive).
56
LEROY-SOMER
INSTALLATION AND MAINTENANCE
VARMECA 30
Variable speed motor or geared motor
CONNECTIONS
3776 en - 07.2007 / h
3.6 - Power supply and control for
FCR brake motors
3.6.1 - Power supply for the built-in fixed
control brake (SO VMA option) VMA 31/32 only
- The brake is supplied via the rectifier fixed o n the SO VMA
connection card. This connection is made at the factory.
- The rectifier is supplied by a mains phase and the motor star
point.
- No parameters need to be set on the VARMECA.
- The brake is released as soon as the VARMECA run
command is enabled. The brake is released after a stop
command, at the end of the deceleration ramp or on
disconnection of the power supply.
3.6.2 - Power supply for the built-in
sequential control brake (VMA ESFR option)
- The brake is supplied via the rectifier and a solid state relay
fixed on the VMA ESFR connection card. This connectio n is
made at the factory.
- The rectifier is supplied by two mains phases.
- The brake is controlled according to a sequence which can
be adjusted using the VARMECA parameters.
en
3.6.3 - Separate power supply
The brake is supplied and controlled by an external source.
57
LEROY-SOMER
INSTALLATION AND MAINTENANCE
VARMECA 30
Variable speed motor or geared motor
CONNECTIONS
3.7 - Rectified brake voltage according to the mains supply
3776 en - 07.2007 / h
MainsVMA ratingPower (kW)
31M-0250.25
Single-phase power
supply
208V -10%
to 240V +10%
3-phase power
supply
208V -10%
to 240V +10%
3-phase power
supply
380V -10%
to 480V +10%
3-phase power supply
208V -10%
to 240V +10%
3-phase power supply
380V -10%
to 480V +10%
NA: Not available, provide a separate power supply.
3.8 - Example of supplying 2 motors
with or without brake in parallel with a
single VARMECA
3.8.1 - The VARMECA must be sized to take
account of the total motor power rating
- The flange with 4 cable glands option must be used to make
it easier to wire up the 2nd motor.
3.8.2 - The 2nd motor is designed to connect to
the terminals marked U, V, W and PE on the SO
VMA and VMA ESFR options for VMA 31/32 or
on the 2nd motor option for VMA 33/34
3.8.3 - Connecting the brake on the 2nd motor
- With the SO VMA option, the rectifier is supplied between
the motor star point and a mains phase from the F1 terminal
of the SO VMA 31/32 option.
- With the VMA ESFR option, the rectifier is supplied
between 2 mains phases and the solid state relay; connect it
from the F1 and F2 terminals of the VMA ESFR 31/32 to the
VMA ESFR 33/34.
en
F1 and F2 terminals of the VMA ESFR 31/32 option
F1 terminal of the SO VMA 31/32 option
59
LEROY-SOMER
INSTALLATION AND MAINTENANCE
VARMECA 30
Variable speed motor or geared motor
CONNECTIONS
3.9 - Wiring diagrams for the SO VMA and VMA ESFR options
3.9.1 - Connection of the SO VMA 31/32 option
L1 L2 L3
3-phase
mains supply 400V
L1
Motor/star
point
Coil
brake
Power supply to 2nd brake
(mains voltage output)
SO VMA
U
VW+-F2
F1
CG
Power supply to 2nd motor
(variable frequency and voltage output)
U
V
W
3776 en - 07.2007 / h
3.9.2 - Connection of the VMA ESFR 31/32 option
L1
Full-wave
(208-240VAC
mains supply)
Coil
brake
Half-wave
(380-480VAC mains
supply)
Power supply to 2nd brake
(mains voltage output)
ESFR
VW+-F2
F1
L3
Power supply to 2nd motor
(variable frequency and voltage output)
L1 L2 L3
U
S06
+–
230/400V
mains supply*
CG
Flex trip to connector
for options
CG
U
V
W
Brake
100 - 120VDC
*NOTA : With single
phase drive, connect
power supply
between L and N.
60
1
: 400/480V mains supply
2
: 230V mains supply
S06
1
+–
Brake
2
180VDC
LEROY-SOMER
Opto Triac
Fu
Brake (p.58)
Dedicated logic output
AC power supply output
for a 2nd brake
1.25 A
600 V
L1
L3
F1
F2
Brake connection
on + and - terminals
Dedicated logic
output connection
Power supply on the
L1 and L3 terminals
F1 and F2 output
for a 2nd brake
INSTALLATION AND MAINTENANCE
VARMECA 30
Variable speed motor or geared motor
CONNECTIONS
3.9.3 - Connection of the VMA ESFR 33/34 option
3776 en - 07.2007 / h
en
61
LEROY-SOMER
INSTALLATION AND MAINTENANCE
VARMECA 30
Variable speed motor or geared motor
COMMISSIONING
3776 en - 07.2007 / h
4 - COMMISSIONING
• Before switching on the VARMECA 30, check that
the electrical connections are correct, and that any
moving parts are mechanically protected.
• For the safety of personnel, the VARMECA 30 must not
be switched on with the protective cover removed.
4.1 - Starting with the power supply
Since the run command has been factory-enabled via a
jumper, the motor starts as soon as it is switched on.
The speed is adjusted with the local control knob (B 31/32 or
B 33/34 option) or a remote reference (0-10 V or 4-20 mA).
Power-up: the green indicator lamp is lit continuously.
The control terminals SDI1 and SDI2 (VMA 33/34) or 1 1 and
12 (VMA 31/32) are linked (unlocking).
4.1.1 - Automatic starting
By leaving the wire between control terminals 8 and 11 (VMA
31/32) or DI2 and +24V (VMA 33/34), the motor starts running
forward.
4.2 - Starting with remote volt-free
contact
Once it has been switched on, the motor starts in accordance
with the run command given by the closing of the vol t-free
contact corresponding to the desired direction of rotation.
The speed is adjusted with the local control knob (B 31/32 or
B 33/34 option) or a remote reference (0-10 V or 4-20 mA).
4.3 - Starting with local run/stop control
(BMA 31/32, BMA 33/34 or BMAVAR
31/32, BMAVAR 33/34 option)
Once it has been switched on, the motor starts after the
control knob corresponding to the desired direction of rotation
has been pressed for one second.
The speed is only adjusted with the local control knob.
4.4 - Setting the speed
4.4.1 - External reference
Adjust the speed reference using the chosen reference
(0/10 V or 4/20 mA).
4.4.2 - Control knob options (B 31/32 or B 33/34)
and remote potentiometer option
Adjust the speed reference using the control knob or the 10
kΩ remote potentiometer.
4.4.3 - Internal speed control option (CVI VMA
31/32 or CVI BMA 33/34)
Adjust the speed reference using the Int. Spd. potentiometer.
Adjust the Max. Spd. or Min. Spd. potentiometers if it is not
possible to reach the desired speed.
62
LEROY-SOMER
INSTALLATION AND MAINTENANCE
3776 en - 07.2007 / h
VARMECA 30
Variable speed motor or geared motor
FAULTS-DIAGNOSTICS
5 - FAULTS-DIAGNOSTICS
Information relating to the status of the VARMECA 30 is provided by two indicator lamps located on the local control opti ons (B 31/
32 or B 33/34, BMA 31/32 or BMA 33/34, BMAVAR 31/32 or BMAVAR 33/34, CVI VMA 31/32 or CVI VMA 33/34 options), or by
the internal LED in VMA 31/32.
Colour and state of indic. lampVARMECA statusChecks to be performed
Steady green
Flashing greenCurrent limiting
Flashing red
No trip
Mains present
IGBT temperature alarm
Motor overload
Braking resistor option overload
• Check that the motor is not
overloaded or stalled
• Check that air is able to circulate
around the motor fins and VARMECA
casing
• The motor is overloaded: check the
motor current using a clamp ammeter
• Check that the deceleration ramp is
long enough for applications with high
inertia
en
• Short-circuit of a motor winding
• Locked motor rotor
• Faulty insulation of a winding
Steady red
The fault is cleared by switching off the VARMECA 30 or by opening/closing the co nnection between terminals 12: ENA and 11: +24 V (VMA
31/32) or SDI1 and SDI2 (VMA 33/34).
6 - MAINTENANCE
• All work relating to installation, commissioning
and maintenance must be carried out by
experienced, qualified person nel.
• Before carrying out any work, disconnect an d lock the
VARMECA 30 power supply circuit and wait 2 minutes for
the capacitors to discharge.
6.1 - Care
No special care is required on the VARMECA 30, apart from the
regular removal of dust from the fan grille and the cooling fins
located at the bottom of the casing.
Do not dismantle the VARMECA 30 while it is still under
guarantee, as this would then imme diately become null and
void.
CAUTION:
Certain components which are sensitive to electrostatic
discharge may be destroyed simply by touching them.
Do not leave any metal object in the connection area, as this
could cause a short-circuit.
2
• I
t overheating
• Internal fault
• Undervoltage
• Overvoltage
The motor current IS NOT MEASURED ON THE VARMECA
30 POWER SUPPLY (L1, L2, L3).
It is measured using an ordinary clamp ammeter on one of the
wires which goes into the motor terminal block.
6.2.2 - Procedure for measuring the motor
current on VMA 31/32 (if the motor wire loop is
inaccessible)
- Open the VARMECA 30 power supply circuit and lock it.
- Wait 2 minutes for the capacitors to discharge (for the
single-phase range).
- Open the cover of the VARMECA 30.
- Open the connection between terminals SDI1 and SDI2
(VMA 33/34) or 11 and 12 (VMA 31/32).
- Remove the TORX + slot type screws from the protection
plate above the motor terminals.
- Pass the longest motor wire along the side of the protection
circuit.
- Replace the protection plate and fasten it.
- Pass the clamp ammeter through the motor wire loop.
- Remake the connection between terminals SDI1 and SDI2
(VMA 33/34) or 11 and 12 (VMA 31/32).
• Check that no incident has occurred
• Switch off and then on again to clear
the fault.
• Check the mains voltage
• Check that the deceleration ramp is
long enough for applications with high
inertia
• If the fault remains, consult LEROYSOMER
6.2 - Measurements
6.2.1 - General
The input voltages can be measured using ordinary
instruments.
63
LEROY-SOMER
1
2
3
INSTALLATION AND MAINTENANCE
VARMECA 30
Variable speed motor or geared motor
OPERATING EXTENSIONS
3776 en - 07.2007 / h
7 - OPERATING EXTENSIONS
7.1 - Speed control knob
option (B 31/32 or B 33/34)
The speed is set using a knob with graduations from 15 to
100%.
• With 2 indicator lamps.
• Connected on the P2 connector (VMA 31/32) or directly on
the control terminals (VMA 33/34)
7.2 - Control knob with integrated
run-stop control option
(BMA 31/32 or BMA 33/34)
In addition to speed control, a run button and a stop button
make it possible to control the VARMECA 30 locally, once it
has been switched on, as required. For a run command to be
taken into account, the button must be held down for onesecond.
• With 2 indicator lamps.
• Connected on the P2 connector (VMA 31/32) or directly on
the control terminals (VMA 33/34).
• Do not wire the shunt between terminals 8-11 and/or 9-11
(VMA 31/32).
7.3 - Control knob with
forward/reverse/stop control option
(BMAVAR 31/32 or BMAVAR 33/34)
In addition to speed control, a forward button, a reverse
button and a stop button make it possible to control the
VARMECA 30 locally, once it has been switched on, as
required. For a run command to be taken into account, the
button must be held down for one second.
• With 2 indicator lamps.
• Connected on the P2 connector (VMA 31/32) or directly on
the control terminals (VMA 33/34).
• Do not wire the shunt between terminals 8-11 and/or 9-11
(VMA 31/32).
7.4 - Internal speed control option
(CVI VMA 31/32 or CVI VMA 33/34)
The speeds are set on potentiometers which are accessible
once the cover has been removed.
c Min.Spd potentiometer: calibration of the minimum speed.
d Int.Spd potentiometer: speed control which replaces
control via the control knob.
e Max.Spd potentiometer: calibration of the maximum speed.
There are also 2 indicator lamps.
Note: With this option, do not wire up terminal ADI1.
External resistors with greater thermal power can be used,
provided that the minimum ohmic value of 180 Ω (RF 100 –
RF 200) or 50 Ω (RF 600) is respected.
12.80.650
Value
kW
0.1200
P
Value
kW
P
peak
Ω
kW
3.2
Ω
200 (2x100 in parallel)
P
thermal
kW
0.2
Value
Ω
200
(2x100
in
series)
7.7 - Power supply and
electromechanical brake control option
(SO VMA 31/32)
The motor must be fitted with an FCR brake adapted for the
VARMECA 31/32.
The brake has a built-in power supply. The brake is released
as soon as the run command is enabled. The brake is
engaged after a stop command, at the end of the deceleration
ramp or on disconnection of the power supply.
7.8 - Additional I/O interface and
sequential brake control option
(ESFR VMA 31/32)
The brake has a built-in power supply. The brake is controlled
according to a sequence which can be adjusted using the
VARMECA parameters.
7.9 - Additional I/O interface and
sequential brake control option
(ESFR VMA 33/34)
The brake has a built-in power supply. The brake is controlled
according to a sequence which can be adjusted using the
VARMECA parameters. See VARMECA 30 parametersetting manual.
7.10 - Fieldbus options (not available
for VMA32 M)
The interface card is mounted inside the VARMECA casing.
Protocols supported:
PROFIBUS DP - INTERBUS S
DEVICENET - CAN OPEN
7.11 - Encoder feedback option
(COD VMA 33/34)
VMA33/34 only: Please contact Leroy-Somer.
65
LEROY-SOMER
INSTALLATION AND MAINTENANCE
VARMECA 30
Variable speed motor or geared motor
OPERATING EXTENSIONS
3776 en - 07.2007 / h
7.12 - Parameter-setting
console option (PX LCD)
The console option provides access to the drive internal
settings (terminal block configuration, ramp, speed and PI
settings, etc).
See VARMECA 30 parameter-setting manual.
This option provides access to the drive internal settings from
a PC. The software is compatible with WINDOWS 95, 98, NT,
2000, XP and subsequent versions.
See VARMECA 30 parameter-setting manual.
Description of the option:
1 CD ROM
1 cable, L = 3 m
7.14 - Operator display option
(PAD VMA 30)
The VARMECA 30 operator display consists of a display unit,
three control buttons and three parameter-setting keys.
Please contact Leroy-Somer.
7.15 - XPress Key (PX Key)
7.15.1 - General
The XPress Key option is used to save a copy of all the
VARMECA 30 parameters so that they can be duplicated very
simply in another drive.
7.15.2 - Setting drive parameters with XPress
Key
• Connect XPress Key to the serial port via a RJ45 connector.
• With the drive locked, press the "Key" button for a first time.
Confirm the transfer of parameters into the drive by pressing
the "Key" button a second time.
CAUTION:
If confirmation is not received within 10 seconds, the
procedure is cancelled.
66
LEROY-SOMER
INSTALLATION AND MAINTENANCE
VARMECA 30
Variable speed motor or geared motor
OPERATING EXTENSIONS
3776 en - 07.2007 / h
7.16 - EMC filter (FLT VMA33/FLT VMA34)
VARMECA 33/34 drives conform to drive standard EN
61800-3 because of the EMC filter which can be
integrated in the front of the VARMECA 30 casing.
7.16.1 - Dimensions
7.17 - EMC filter option (FLT VMA 31M)
The filter is mounted in the VMA 31M casing.
The VARMECA then conforms to the requirements for
residential environments.
7.18 - EMC filter option (FLT VMA 31/32)
The filter is mounted in the VMA 31/32 TL/T casing.
The VARMECA then conforms to the requirements for
residential environments.
en
7.16.2 - Connection
L1 L2 L3
Filter
option
Mains supply
67
LEROY-SOMER
INSTALLATION AND MAINTENANCE
VARMECA 30
Variable speed motor or geared motor
NOTES
3776 en - 07.2007 / h
68
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.