VEGA SON83 User Manual

VEGASON 83 … 87
ECHOFOX
®
TIB • Technical Information • Operating Instructions
Pulse-echo sensors
Digital transmission of measuring data
Approvals for
- hazardous areas acc. to
- CENELEC
- ElexV Zone 0
Compact instrument
Current output 0 … 20 mA Approval for
VEGA Grieshaber KG
Am Hohenstein 113 D-77761 Schiltach Phone 0 78 36 / 50 - 0 Fax 0 78 36 / 50 201
2
VEGASON 83 … 87
Contents
Contents
1 Introduction
1.1 Contents of the instruction manual .....................................................................................................................4
1.2 Safety information ...............................................................................................................................................4
2 Product description
2.1 Function and configuration ..................................................................................................................................4
2.2 Types and versions .............................................................................................................................................5
2.3 Configuration of a measuring system, sensor in not-Ex-area .............................................................................8
2.4 Configuration of a measuring system, sensor in Ex-area ................................................................................... 9
2.5 Order code for sensors .....................................................................................................................................10
2.6 Technical data of the sensors............................................................................................................................11
2.7 Configuration with compact instrument .............................................................................................................14
2.8 Order code for compact instrument...................................................................................................................15
2.9 Technical data of compact instruments .............................................................................................................16
2.10 Dimensional drawings .......................................................................................................................................18
2.11 Approvals ..........................................................................................................................................................22
3 Environment
3.1 Installation recommendations relating to liquid tank / vessels ..........................................................................23
3.2 Installation recommendations relating to solid silos ..........................................................................................25
4 Electrical connection
4.1 Connection example of sensors ........................................................................................................................26
4.2 Connection example of Ex-sensors ..................................................................................................................27
4.3 Connection example of compact instruments ...................................................................................................29
5 Set-up
5.1 Sensor and signal conditioning instrument (e.g. VEGAMET) ...........................................................................30
5.2 Sensor and processing system (VEGALOG 571) .............................................................................................30
5.3 Compact instrument.......................................................................................................................................... 30
VEGASON 83 … 87
3
1 Introduction / 2 Product description
1 Introduction
1.1 Contents of the instruction manual
The Technical Information / Operating Instructions is called TIB. It contains all necessary information for correct
- installation
- connection
- set-up
- optimization of the pulse-echo-sensors VEGASON …. V… or pulse­echo compact instrument VEGASON … K….
VEGA regularly revises the contents of TIBs as technical improvements are made to the instruments.
1.2 Safety information
The described module must only be inserted and operated as described in this TIB. Please note that other action can cause damage for which VEGA does not take responsibility.
2 Product description
2.1 Function and configuration
Function
The VEGASON … sensor systems or compact instruments are used for continuous and non-contact level measurement.
Short sound impulse packets are emitted by the transducer of the pulse-echo sensor. The combined emitter and receiver system detects the pulses reflected by the product.
The running period of the ultrasonic pulses is directly pro­portional to the distance between sensor and measured product.
The signal processing ECHOFOX of signal analysis to process the reflected ultrasonic pulses.
®
uses modern methods
The signal-to noise ratio is optimized by digital signal processing methods with mathematic algorithms (DSP).
The automatic configuration of a user specific data base enables an optimum adaption to the respective application.
The use of fuzzy-logic for echo evaluation ensures a reliable determination of the level. False echoes, e.g. from stirrers or other installations are detected and are not included in the generation of the measured value.
These measuring data are transmitted digitally to respective signal conditioning instruments or processing systems and processed.
The operation of the sensors is made via the signal conditioning instrument VEGAMET or via a PC (VEGACONNECT necessary).
Compact instruments are additionally equipped with an integral output of the measuring data and make a current output 0 … 20 mA available.
The operation of the compact instrument is only possible with PC via VEGACONNECT.
Configuration
Flange version
The sensor or compact instruments consist of a housing, integrated therein the above electronics and all required terminals, a mounting flange and a transducer.
Housing, flange and transducer are designed acc. to the type.
Separate version
The separate version consists of a housing with integral electronics and all necessary terminal and mounting plate.
Transducer with mounting tube and connection cable as separate modular unit. The transducers differ acc. to the various types.
4
VEGASON 83 … 87
2 Product description
2.2 Types and versions
VEGASON 83 FK VEGASON 83 FV
Flange version with flange size DN 100, transducer inte­gral in flange, plastic housing with integral ECHOFOX sensor electronics.
Suitable for a number of applications and mounting positions,
- mounting directly on the vessel ceiling (tank, silo) or on existing sockets
- positioning on fix points above the vessels etc.
Measuring range 0,7 m … 10 m (see section 3 Evironment).
VEGASON 83 FV Ex, 83 FV Ex 0
®
-
VEGASON 84 FK VEGASON 84 FV
Flange version with flange size DN 150, transducer below the flanges, plastic housing with integral ECHOFOX sensor electronics.
Suitable for a number of applications and mounting positions,
- mounting directly on the vessel ceiling (tank, silo) or on existing sockets
- positioning on fix points above the vessel etc.
Measuring range 0,7 m … 20 m (see section 3 Environment).
®
-
VEGASON 84 FK StEx VEGASON 84 FV StEx
as VEGASON 83 FV, however housing of sensor electronics and transducer made of stainless steel 1.4305
Suitable for the use in hazardous areas (see section 2.11 Approvals).
VEGASON 83 FV Ex B, 83 FV Ex0 B
as VEGASON 83 FV Ex or FV Ex 0, however with integral overvoltage arrester of sensor electronics.
as VEGASON 84 FK or FV , however additionally approved for the use in dust-Ex areas StEx (see section 2.11 Approvals).
VEGASON 84 FV Ex, 84 FV Ex 0
Flange version with flange size DN 150, transducer inte­gral in flange, housing of sensor electronics and transducer made of stainless steel 1.4305.
Suitable for the use in hazardous areas (see section 2.11 Approvals).
VEGASON 83 … 87
5
2 Product description
VEGASON 84 FV Ex B, 84 FV Ex0 B
as VEGASON 84 FV Ex or FV Ex 0, however with integral overvoltage arrester of sensor electronics.
Compact instrument VEGASON 85 FK
VEGASON 85 FV
VEGASON 87 FK VEGASON 87 FV
Flange version, flange size ø 450 mm, triple transducer divided into emission and receipt unit, reset as described under VEGASON 85 FV . Measuring range 0,4 m … 60 m (see section 3 Environment).
VEGASON 87 FK StEx VEGASON 87 FV StEx
Flange version with flange size DN 150, transducer below the flanges, plastic housing with integral ECHOFOX sensor electronics.
Suitable for a number of applications and mounting positions,
- mounting directly on the vessel ceiling (tank, silo) or on existing sockets
- positioning on fix points above the vessels etc.
Measuring range 1,0 m … 30 m (see section 3 Environment).
®
-
VEGASON 85 FK StEx VEGASON 85 FV StEx
as VEGASON 85 FK or FV , however additionally approved for the use in dust-Ex areas StEx (see section 2.11 Approvals).
as VEGASON 87 FK or FV , however additionally approved for the use in dust-Ex areas StEx (see section 2.11 Approvals).
6
VEGASON 83 … 87
2 Product description
VEGASON 83 GK VEGASON 83 GV
Separate version, transducer and housing are separated. An ECHOFOX housing. The transducer is provided with a fixing tube (thread G 1). It can be mounted in a small hole (ø 35 mm) at the vessel ceiling (tank/silo). As option the transducer can be screwed with a swivelling holder (DN 150) and can be optimally adapted to the installation conditions. Measuring range 0,7 m … 10 m (see section 3 Environment).
®
-sensor electronics is integrated in the
VEGASON 84 GK VEGASON 84 GV
as VEGASON 83 GKor GV, however measuring range 0,7 m … 20 m
VEGASON 84 GK StEx VEGASON 84 GV StEx
as above, however additionally approved for the use in dust-Ex areas StEx (see section 2.11 Approvals).
VEGASON 85 GK VEGASON 85 GV
as VEGASON 83 GK or GV , however measuring range 1,0 m … 30 m
VEGASON 85 GK StEx VEGASON 85 GV StEx
as above, however additionally approved for the use in dust-Ex areas StEx (see section 2.11 Approvals).
VEGASON 87 GK VEGASON 87 GV
as VEGASON 83 GK or GV, however triple transducer divided into emission and receipt unit, rest as described under measuring range 0,4 m … 60 m
VEGASON 87 GK StEx VEGASON 87 GV StEx
as above, however additionally approved for the use in dust-Ex areas StEx (see section 2.11 Approvals).
6
VEGASON 83 … 87
7
2 Product description
11
11 … 15
6 … 10
1 … 5
4
2.3 Configuration of a measuring system, sensor in not-Ex-area
Generally a measuring system consists of two components
- a local sensor and
- a signal conditioning instrument or processing system
The kind of signal conditioning instrument or processing system depends on the installation conditions.
Sensor(s) VEGASON 83 … 87
Signal conditioning instrument e.g. VEGAMET 514 V (VEGAMET 407 V)
Processing system VEGALOG 571
VEGACONNECT
RS 232
PC
EV -input card (via additionally EV-input cards max. 3 x 5 = 15 sensors each can be connected)
CPU-central unit
Sensor(s) and signal conditioning instrument or processing system are connected via a two-wire line. The power supply of the sensor or the sensors is ensured via this line and the measuring data are transmitted digitally to the signal conditioning instrument or processing system.
The indicating and operating surface VEGA Visual Operating, installed on a PC ensures a simple and comfortable configuration and parameter adjustment of the respective measuring system.
VEGACONNECT can be connected to respective sockets of the signal conditioning instrument or the sensor. If neces­sary, it is possible to connect VEGACONNECT directly to the two-wire line (signal conditioning instrument … sensor).
8
VEGASON 83 … 87
2 Product description
2.4 Configuration of a measuring system, sensor in Ex-area
In this application a measuring system consists of three components
- a local Ex-sensor in the Ex-area
- a safety barrier and
- a signal conditioning instrument or processing system in the not-Ex-area
The kind of signal conditioning instrument or processing system mainly depends on the control and process technical requirements.
Sensor(s) VEGASON 83 und 84
Separator Type 146 or VEGATRENN 546
Signal conditioning instrument e.g. VEGAMET 514 V (VEGAMET 407 V)
4
1
1
1
Not-Ex-area
Ex-area
Processing system VEGALOG 571
RS 232
1 … 5
4
1 … 5
6 … 10
4
4 4
6 … 10
usw.
etc.
etc.
1. EV-input card 2. EV-input card
VEGACONNECT
(via additionally EV-input card 5 sensors each can be connected)
CPU-central unit
4
PC
Each sensor is connected to the respective signal conditioning instrument or processing system via a separator type 146 or VEGATRENN 546. The separator provides two intrinsically safe circuits. These circuits provide the power supply of the sensor and the digital transmission of measuring data to the signal conditioning instrument or processing system.
The indicating and operating surface VEGA Visual Operating, installed on a PC ensures a simple and comfortable configuration and parameter adjustment of the respective measuring system.
VEGASON 83 … 87
9
2.5 Order code for sensors
2.5.1 VEGASON …V / …V StEx
Type Measuring range
8 3 .................. 0,7 … 10 m
8 4 .................. 0,7 … 20 m
8 5 .................. 1,0 … 30 m
8 7 .................. 0,4 … 60 m
Version
F Flange version G Separate version
Approvals
. X without
EXS. XStEx for Zone 10 (only for VEGASON 84 … 87)
2 Product description
Flange size
E DN 100 PN 16 (for VEGASON 83) F DN 150 PN 16 (for VEGASON 84 and 85) U ø 450 (for VEGASON 87) Y Others
Flange material
A Aluminium (for StEx-version) P PPh Y Others
S O N V E Z Order no. for VEGASON … V
2.5.2 VEGASON … FV Ex…
Type Measuring range
8 3 F V E X CENELEC EEx d e ia IIB T6 .......... 0,7 … 10 m
8 3 F V E X 0 PTB Zone 0 EEx d e ia IIB T6 ........ 0,7 … 10 m
8 4 F V E X CENELEC EEx d e ia IIB T6 .......... 1,1 … 20 m
8 4 F V E X 0 PTB Zone 0 EEx d e ia IIB T6 ........ 1,1 … 20 m
Options
X without B with overvoltage arrester
S O N . X V V V Order no. for VEGASON … FV Ex…
10
VEGASON 83 … 87
2 Product description
2.6 Technical data of the sensors
2.6.1 VEGASON 83 … 87 FV, 84 … 87 FV StEx
VEGASON 83 … 87 GV , 84 … 87 GV StEx
Approvals
see section 2.11 Approvals
Power supply
via signal conditioning instrument VEGAMET … with digital transmission of measuring data via processing system VEGALOG 571 with EV-input cards Operating voltage max. 36 V DC Power consumption max. 200 mA
Measuring range
VEGASON 83 FV 83 GV 84 … 85 … 87 … Min. distance for liquids and
solids granulation 5 mm 0,7 m 0,5 m 0,7 m 1,0 m 0,4 m
granulation 5 mm 0,8 m 0,6 m 1,0 m 1,2 m 0,4 m
Max. distance dependent on product and process 10 m 10 m 20 m 30 m 60 m
Measuring data
Measuring resolution 1 mm 1 mm 1 mm 1 mm 1 mm Measuring frequency 33 kHz 33 kHz 22 kHz 16 kHz 16 kHz Measuring rate 0,6 sec. 0,6 sec. 0,7 sec. 1,0 sec. 1,5 sec. Radiation angle related to –3 dB 12° 12° 12° 15° 3,5°
Error limits
Linearity error relating to the adjustment < 0,1 % of measuring range Temperature error of the electronics 0,015 %/10 K of measuring range
Materials
VEGASON FV GV StEx Housing and cover of electronics PBT PBT PBT Flange PPh ––– St 37 galv. or Alu Transducer housing PVDF PVDF PVDF Impedance adapter PE PE PE Transducer fixing tube
- Type83 ––– PVDF St 37 galvanized
- T ype 84 and 85 ––– RCH 1000 St 37 galvanized
- T ype 87 ––– St 37 galvanized St 37 galvanized
Dimensions and weights
Flange size - Type 83 DN 100 PN 16 ––– DN 100 PN 16
- Type 84 and 85 DN 150 PN 16 ––– DN 150 PN 16
- Type 87 ø 450 ––– ø 450 Thread of the fixing tube ––– G 1 A ––– Total weight of sensors
- Type 83 … 85 appr. 6 kg appr. 6 kg appr. 6 kg
- Type 87 appr. 12 kg appr. 12 kg appr. 12 kg
Temperature reaction
VEGASON … StEx-version At an ambient temperature 40°C the max. temperature to be adjusted
- on the transducer in Zone 10 45°C is reached and
- on the housing (electronics) in Zone 11 55°C is reached
VEGASON 83 … 87
11
2 Product description
Ambient conditions
VEGASON FV GV StEx Ambient temperature related to
- transducer in Zone 10 -20°C … +80°C -20°C … +80°C -20°C … +75°C
- housing (electronics) in Zone 11 -20°C … +60°C -20°C … +60°C -20°C … +60°C Storage and transport temperature -20°C … +80°C -20°C … +80°C -20°C … +80°C Protection
- of transducer IP 67 IP 67 IP 65
- the housing (electronics) generally IP 67 IP 67 IP 65 certified
- transducer ––– ––– IP 65
- housing ––– ––– IP 54 Overvoltage class III III III Protection class II II II Max. vessel pressure related to
- Type 83 0,5 bar 1,0 bar –––
- T ype 84 and 85 0,5 bar 0,5 bar 0,5 bar
- Type 87 0,3 bar 0,5 bar 0,5 bar
Connection line
VEGASON … FV-version Sensor to signal conditioning instrument / processing system 2 pole, maximal 20 Ohm/line
VEGASON … GV-version Transducer to sensor electronics
- Type 83 … 85 standard coax cable type RG 58
standard length 5 m max. length 300 m
- Type 87 4 x 0,38 mm
2
, 1 screened wire standard length 5 m, max. length 35 m cable diameter 8 mm
Sensor electronics to signal conditioning instrument / processing system 2 pole, max. 20 Ohm/line
Temperature sensor each integrated in the transmitter
with GV-version via connected connection line above connection line
Electrical connection
Terminals for the connection lines for max. 1,5 mm Terminals for the earth connection for max. 4,0 mm
2 2
Cable entry 1 x Pg 13,5 for all FV-versions
2 x Pg 13,5 for all GV-versions
12
VEGASON 83 … 87
2 Product description
2.6.2 VEGASON 83 and 84 Ex, Ex0 VEGASON 83 and 84 Ex B, Ex0 B
Approvals
see section 2.11 Approvals
Power supply
via separator Type 146 or VEGATRENN 546 Supply via 2 intrinsically safe circuits of category ib IIB
Flame proofing EEx de ia IIB T6 (see also section 2.11)
Measuring range
VEGASON 83 84 Min. distance of liquids 0,7 m 1,1 m Max. distance dependent on product and process 10 m 20 m
Measuring data
Measuring resolution 1 mm 1 mm Measuring frequency 33 kHz 22 kHz Measuring rate 1,1 sec. 1,5 sec Radiation angle related to –3 dB 12° 12°
Error limits
Linearity error relating to the adjustment < 0,1 % of measuring range Temperature error of the electronics 0,015 %/10 K of measuring range
Materials
Housing of electronics 1.4305 Flange 1.4305 Diaphragm 1.4531 Flange sealing Viton
Dimensions and weights
Flange size - Type 83 DN 100 PN 16
- Type 84 DN 150 PN 16
Total weight of the sensors at DN 100 approx. 17 kg
at DN 150 approx. 21 kg
Ambient conditions
Max. permissible ambient temperature
- on the transducer +80°C
- on the housing (electronics) +60°C Storage and transport temperature -20°C … +80°C Protection IP 67 Max. vessel pressure
- Type 83 2 bar
- Type 84 1 bar Vessel pressures and ambient temperature under Ex-conditions see respective conformity certificate
Connection line
Sensor … separator 2 x 2 pole Resistance per conductor max. 7,5 Ohm Temperature sensor and its connection integrated int he respective sensor
Electrical connection
Terminals for the connection line max. 1,5 mm Terminals for earth connection max. 4,0 mm Cable entry 1 x Pg 13,5
VEGASON 83 … 87
2 2
13
2 Product description
2.7 Configuration with compact instrument
As described under "2 Product description" the compact instruments are equipped with an integral processing of measuring data. A current output 0 … 20 mA is available.
First of all each compact instrument must have a voltage supply. The current output can be directly connected to indicators or process control systems.
VEGASON 83 … 87
Power supply
VEGACONNECT
11
2
Ri
during the adjustment Ri = min. 100 Ohm
3 4
usw.
Processing one current output 0 … 20 mA each (e.g. for consumers with low inner resistance)
PC
The indicating and operating surface VEGA Visual Operating, installed on a PC ensures a simple and comfortable configuration as well as operator supporting parameter adjustment of the compact instruments.
Therefore it is necessary to connect the computer via VEGACONNECT directly with the respective compact instruments. A digital signal is superimposed to the current output. The adjustment of the sensor can be also carried out via the
current output. For indication and processing systems with an inner resistance of less than 100 Ohm a respective series resistor must be connected for the time of adjustment.
14
VEGASON 83 … 87
2 Product description
2.8 Order code for compact instrument
2.8.1 VEGASON …K / …K StEx
Type Measuring range
8 3 .................. 0,7 … 10 m
8 4 .................. 0,7 … 20 m
8 5 .................. 1,0 … 30 m
8 7 .................. 0,4 … 60 m
Version
F Flange version G Separate version
Approvals
. X without
E X S . X StEx for Zone 10 (only for VEGASON 84 … 87)
Power supply
E 110 V AC A 230 V AC I 24 V AC, 16 … 36 V DC X Others
Flange size
E DN 100 PN 16 (for VEGASON 83) F DN 150 PN 16 (for VEGASON 84 and 85) U ø 450 (for VEGASON 87) Y Others
Flange material
A Aluminium (for StEx-version) P PPh Y Others
S O N K E Order no. for VEGASON … K
VEGASON 83 … 87
15
2 Product description
2.9 Technical data of compact instruments
2.9.1 VEGASON 83 … 87 FK, 84 … 87 FK StEx VEGASON 83 … 87 GK, 84 … 87 GK StEx
Approvals
see section 2.11 Approvals
Power supply
Standard U Option U
Measuring range
VEGASON 83 FK 83 GK 84 … 85 … 87 … Min. distance of liquids and solids granulation 5 mm 0,7 m 0,5 m 0,7 m 1,0 m 0,4 m
granulation 5 mm 0,8 m 0,6 m 1,0 m 1,2 m 0,4 m
Max. distance dependent on product and process 10 m 10 m 20 m 30 m 60 m
Measuring data
Measuring resolution 1 mm 1 mm 1 mm 1 mm 1 mm Measuring frequency 33 kHz 33 kHz 22 kHz 16 kHz 16 kHz Measuring rate 0,6 sec. 0,6 sec. 0,7 sec. 1,0 sec. 1,5 sec. Radiation angle related to –3 dB 12° 12° 12° 15° 3,5°
24 V AC (–15 %, +10 %), 50/60 Hz, 10 VA
nenn
24 V DC (16 … 36 V), 8 W 230 V AC, (–10 %, +5 %), 50/60 Hz, 10 VA
nenn
110 V, 130 V, 240 V AC (–15 %, +10 %), 50/60 Hz, 10 VA
Current output
Range 0 … 20 mA Load max. 400 Ohm Resolution of D/A-conversion 0,025 % of adjustment
Error limits
Linearity error relating to the adjustment < 0,1 % of measuring range Temperature error of the electronics 0,015 %/10 K of measuring range
Materials
VEGASON FK GK StEx Housing and cover of the electronics PBTP PBTP PBTP Flange PPh ––– St 37 galv. or Alu Transducer housing PVDF PVDF PVDF Impedance adapter PE PE PE Transducer fixing tube
- Type 83 ––– PVDF St 37 galvanized
- T ype 84 and 85 ––– RCH 1000 St 37 galvanized
- Type 87 ––– St 37 galvanized St 37 galvanized
Dimensions and weights
Flange size - Type 83 DN 100 PN 16 ––– DN 100 PN 16
- Type 84 and 85 DN 150 PN 16 ––– DN 150 PN 16
- Type 87 ø 450 ––– ø 450 Thread of the fixing tube ––– G 1 A ––– Total weight of the sensor
- Type 83 … 85 appr. 6 kg appr. 6 kg appr. 6 kg
- Type 87 appr. 12 kg appr. 12 kg appr. 12 kg
Temperature reaction
VEGASON … StEx-version At an ambient temperature of 40°C the max. temperature to be adjusted
- transducer in Zone 10 of 45°C is reached and
- housing (electronics) in Zone 11 of 55°C is reached
16
VEGASON 83 … 87
2 Product description
Ambient conditions
VEGASON FK GK StEx Ambient temperatures related to
- transducer in Zone 10 -20°C … +80°C -20°C … +80°C -20°C … +75°C
- housing (electronics) in Zone 11 -20°C … +60°C -20°C … +60°C -20°C … +60°C Storage and transport temperature -20°C … +80°C -20°C … +80°C -20°C … +80°C Protection
- of the transducer IP 67 IP 67 IP 65
- of the housing (electronics) generally IP 67 IP 67 IP 65 certified
- transducer ––– ––– IP 65
- housing ––– ––– IP 54 Overvoltage class III III III Protection class II II II Max. vessel pressure related to
- Type 83 0,5 bar 1,0 bar –––
- T ype 84 and 85 0,5 bar 0,5 bar 0,5 bar
- Type 87 0,3 bar 0,5 bar 0,5 bar
Connection line
VEGASON … FK-versions Power supply 2/3 pole, standard cable
VEGASON … GK-versions Transducer to sensor electronics
- Type 83 … 85 standard coax cable type RG 58
standard length 5 m max. length 300 m
- Type 87 4 x 0,38 mm
2
, 1 screened wire standard length 5 m, max. length 35 m cable diameter 8 mm
Temperature sensor each integrated in the transmitter
with GK-version connected via above connection line
Electrical connection
Terminals for the connection lines for max. 1,5 mm Terminals for earth connection for max. 4,0 mm
2 2
Cable entry 2 x Pg 13,5 for all FK-versions
3 x Pg 13,5 for all GK-versions
VEGASON 83 … 87
17
2.10 Dimensional drawings
Standard- and StEx-versions
(Dimensions in mm)
2 Product description
VEGASON 83 FV VEGASON 83 FK
Min. distance Flange acc. to DIN - DN 100 PN 16 (ANSI 31/2" 150 psi)
VEGASON 84 and 85 FV… VEGASON 84 and 85 FK…
0,7…0,8 m
260 x 150
ø110
ø220
260 x 150
45˚
ø18
24730
2
ø22
247
ø180
45˚
Min. distance
VEGASON 87 FV… VEGASON 87 FK…
0,4 m
0,7…1,2 m
20
95
ø145 ø285
Flange acc. to DIN - DN 150 PN 16 (ANSI 6" 150 psi)
260 x 150
272
20
95
ø240
45˚
ø22
Min. distance
18
ø450
Installation approx. 320
ø410
VEGASON 83 … 87
2 Product description

Standard- and StEx-versions
(Dimensions in mm)
Electronics unit
260 x 150
90
253
VEGASON 83 GV VEGASON 83 GK
28
~155
138
ø162
Swivelling holder
Flange DN 150 PN 16
Standard version
Thread G 1 A
45
ø140
ø6,4
VEGASON 83 … 87
ø95
Transducer SW 73 SW 73 R Ex
90
Min. distance
0,5…0,6 m
19
Standard- or StEx-versions
(Dimensions in mm)
VEGASON 84 and 85 GV…, 84 and 85 GK…
28
2 Product description
Swivelling holder
VEGASON 87 GV… VEGASON 87 GK…
~155
138
28
~155
138
Flange DN 150 PN 16
Swivelling holder
Flange DN 150 PN 16
Standard version
Thread G 1 A
ø145
Transducer SW 74 SW 75
Standard version
Thread G 1 A
StEx-version
Thread G 1 A
28
82
138
Transducer SW 74 R Ex SW 75 R Ex
Min. distance
0,7…1,2 m
StEx-version
Thread G 1 A
28
60
20
Installation approx. 320
176
Min. distance
0,4 m
VEGASON 83 … 87
2 Product description
Ex-version
(Dimensions in mm)
VEGASON 83 FV Ex, Ex B VEGASON 83 FV Ex 0, Ex 0 B
Flange DN 100 PN 16
0,7 m
Min. distance
VEGASON 84 FV Ex, Ex B VEGASON 84 FV Ex 0, Ex 0 B
ø154
ø220
Pg 16
335
80
20
ø18
45˚
ø180
Flange DN 150 PN 16
1,1 m
Min. distance
ø154
ø285
Pg 16
335
60
22
ø22
45˚
ø240
VEGASON 83 … 87
21
2 Product description
2.11 Approvals
If measuring systems acc. to the following approvals are installed, the respective legal documents have to be observed. The documents are enclosed to the respecitve measuring system.
StEx-approval
For measuring systems in dust-Ex areas.
- pulse-echo sensor VEGASON 84 … 87 FK StEx and GK StEx VEGASON 84 … 87 FV StEx and GV StEx
defined in the type approval BVS 93.Y.8005
- signal conditioning instrument VEGAMET … with digital transmission of measuring data
- processing system VEGALOG 571 with EV-input cards
- auxiliary level switch all VEGASEL with current input 0/4 … 20 mA
Ex-approval
For measuring system in hazardous areas, certificated acc. to - CENELEC
- ElexV Zone 0 (Germany)
- pulse-echo sensor VEGASON 83 and 84 FV Ex VEGASON 83 and 84 FV Ex B
- power supply via separator type 146 or VEGATRENN 546 acc. to conformity certificate PTB-no. Ex-93.C.4025
defined in the conformity certificate PTB-no. Ex-93.C.4092 (CENELEC-certificate)
- signal conditioning instrument VEGAMET … with digital transmission of measuring data
- processing system VEGALOG 571 with EV-input cards
- auxiliary level switch all VEGASEL with current input 0/4 … 20 mA
- pulse-echo sensor VEGASON 83 and 84 FV Ex 0 VEGASON 83 and 84 FV Ex 0 B
- power supply via separator type 146 or VEGATRENN 546 acc. to conformity certificate PTB-no. Ex-93.C.4025
defined in the conformity certificate PTB-no. Ex-94.C.4041 (CENELEC and ElexV, Zone 0, Germany)
- signal conditioning instrument VEGAMET … with digital transmission of measuring data
- processing system VEGALOG 571 with EV-input cards
- auxiliary level switch all VEGASEL with current input 0/4 … 20 mA
Ex-technical data of sensors
Signal current circuit in flame proofing intrinsic safe EEx ia IIB Terminals 1 (+) und 2 (–) bzw. 3 (+) und 4 (–) Effective inner inductance each current circuit L
Effective inner capacitance not important
22
i
VEGASON 8. FV Ex, Ex0 not important VEGASON 8. FV Ex B, Ex 0 B 65 µH
VEGASON 83 … 87
3 Environment
3 Environment
3.1 Installation recommendations
relating to liquid tank / vessels
Installation under normal conditions
Flange version
Mounting on a very short, generally on a DIN-socket piece available on the tank.
The max. filling of the tank depends on the min. distance of the respective sensor or compact instrument.
Min. distance
Separate version
Mounting of the transducer in a very small hole (ø 35 mm) in the tank ceiling. The mounting procedure can be provided via an available access hatch.
Installation under special conditions
If the min. distance of the sensor is decreased, mounting on a socket piece is necessary .
Generally the diameter of the socket piece should be as large as possible and the socket length should be as short as possible.
~45°
Min. distance
See the following schedule as general tube relating to the dimensioning of the socket piece length to socket piece diameter.
Tube length L to tube diameter ø
VEGASON 83 84 85 87
The max. filling of the tank depends on the min. distance of the respective sensor or compact instrument.
Min. distance
Socket piece-ø 100 400 ––– ––– ––– 150 400 300 300 ––– 200 500 400 400 ––– 250 600 500 500 ––– 300 ––– 600 600 ––– 350 ––– 700 700 350
L
Length of socket piece
ø
ø socket piece
VEGASON 83 … 87
23
3 Environment
Installation in open vessels
In most applications a separate version is recommended for open vessels, i.e. mounting of the transducer to a fastening bracket or in another fix position above the vessel opening.
The max. filling of the vessel depends on the min. distance of the respective sensor or compact instrument.
Due to variation possibilities of the transducer position, the requested filling height can be ensured.
Information to socket piece / mounting
- In case of round top the sensor or the compact instrument should be mounted on a socket piece outside the center (mounting on half the range).
Radius
1
/
2
- The emitted sound impulse packets must not be influenced by the filling stream.
Min. distance
Min. distance
- The socket piece must not be flooded by the measured product.
24
- Chamfer the edges of the socket piece.
- There must be no weldment joints inside the socket piece.
VEGASON 83 … 87
3 Environment
3.2 Installation recommendations relating to solid silos
Installation under normal conditions
Flange version
Mounting on a very short, generally on a DIN-socket piece. The socket piece must be directed to the center of the silo outlet to ensure sufficient reflection in case of different material angles of repose. The max. filling on the silo depends on the min. distance of the respective sensor or compact instrument.
Min. distance
Installation under special conditions
If the min. distance of the sensor is decreased, mounting on a conical socket piece extension is necessary.
Information to socket piece / mounting
- Conical socket pieces acc. to drawing, i.e. conus
2x15°.
15° ≥15°
Min. distance
Separate version
In case of horizontal silo top the transducer of the separate version in conjunction with a swivelling holder can be easily and optimally directed to the center of the silo outlet. The max. filling of the silo depends on the min. distance of the respective sensor or compact instrument.
Min. distance
- Cylindrical socket pieces acc. to the values in the schedule (see page 23) should only be used in silos after consultance.
- Chamfer the edges of the socket piece.
- There must be no weldment joints inside the socket piece.
Important:
The distance from the mounting position to the filling and suction openings should be as large as possible.
VEGASON 83 … 87
25
4 Electrical connection
4 Electrical connection
4.1 Connection example of sensors
VEGASON 83 … 87 FV und 84 … 87 FV StEx
Connection for VEGACONNECT
R
ECHOFOX
VEGASON 8 FV
VBUS
4
+ -
5 6
+
VEGASON 83 … 85 GV VEGASON 84 and 85 GV StEx
R
ECHOFOX
VEGASON 8 GV
VBUS
4
+ -
5 6
+
VEGACONNECT
Synchronisation
8 9
7
in
out
Synchronization
VEGACONNECT
Synchronisation
8 9
7
in out
10
SW
10
The connection between echo sensor and signal conditioning instrument or processing system can be made with standard two-wire cable.
For installation with strong interference, screened cable is recommended. Screening must only be earthed at one end.
The two terminals marked with " " are connected in the housing. Connect screening as marked and carry out screening on the upper large terminal. Potential equalization to the outer terminals.
VEGAMET 407 V
18 17 16 15 14 13
9 8 7 6 5
-
-
2
+
+
1
VEGAMET 514 V
d b z
COM 02
t
!
MOD
+
-
STO
VEGAMET
407 V
SIM
Connection as above
Connection cable of transducers SW 73 … SW 75 (max. line length 300 m)
VEGASON 87 GV und GV StEx
R
ECHOFOX
VEGASON 8 GV
VBUS
+
-
synchronisation
in
4
5
out
7
6
+
Connection as above
Connection cable of transducers SW 7 (max. line length 35 m)
26
VEGACONNECT
SW7
8
10 13
9 ws
gn
+
30
­32
+ 
-
+ 
-
+ 
-
d b z
16
26
32
11 12
ge
br
Further connection possibilities. Max. 3 x 5 = 15 sensors
VEGALOG 571 EV-input card
VEGASON 83 … 87
4 Electrical connection
4.2 Connection example of Ex-sensors
VEGASON 83 and 84 FV Ex, FV Ex B VEGASON 83 and 84 FV Ex 0, FV Ex 0 B
2
3
1
4
Separator Type 146
11
Ex-area
Not-Ex-area
12
Information concerning safety and installation see following page.
In case of strong interferences, screened cable is recommended. Screening must only be earthed at one end.
18 17 16 15 14
13
9 8 7 6 5
2
-
1
+
COM 02
t
!
MOD
+
-
STO
VEGAMET
407 V
SIM
VEGAMET 407 V
1
1
2
+ +
2
-
3
3
4
4
-
VEGATRENN 546
d b z
20
+
22
-
+
30
-
+
32
-
Max. 5 sensors can be connected via 5 VEGATRENN 546 to the EV-input card
+
-
+
-
d b z
30
32
d b z
16
24
32
VEGAMET 514 V
VEGALOG 571 EV -input card
VEGASON 83 … 87
27
Connection example of Ex-sensors
4 Electrical connection
V essel with cathodic protection
External earth terminal
Zone 1 VEGASON 83 a. 84 Ex, ExB
Zone 0 VEGASON 83 a. 84 Ex0, Ex0B
Cathodic tank protection 2 … 24 V (object voltage)
V essel without cathodic protection
External earth terminal
Zone 1 VEGASON 83 a. 84 Ex, ExB
Zone 0 VEGASON 83 a.. 84 Ex0, Ex0B
to potential equalization line (PAL)
Furthermore all installations must be carried out acc. to local regulations.
Furthermore all installations must be carried out acc. to local regulations.
28
VEGASON 83 … 87
4 Electrical connection
4.3 Connection example of compact instruments
VEGASON 83 … 87 FK and 84 … 87 FK StEx
Anschluß für VEGACONNECT
R
ECHOFOX
+(L1) -(N)
power supply
VEGASON 8 FK
I out
3
4
+ - 0/4…20 mA
5 6
in
VEGACONNECT
Synchronisation
7
out
Synchronization
8 9
10
The two terminals marked " " are connected in the housing.
Potential equalization at the outer terminals.
Evaluation, current output 0 … 20 mA The current output can be directly connected to the indicators or the processors.
Power supply , Supply voltage see 2.9.1 Technical data
VEGASON 83 … 85 GK and 84 and 85 GK StEx
R
ECHOFOX
+(L1) -(N)
power supply
Connection as above
VEGASON 8 GK
4
3
+ - 0/4…20 mA
5 6
in
SynchronisationI out
VEGACONNECT
SW
7
out
8 9
10
Connection cable of transducers SW 73 … SW 75 (max. line length 300 m)
VEGASON 87 GK and GK StEx
R
ECHOFOX
+(L1) -(N)
power supply
Connection as above
VEGASON 8 GV
synchronisation SW7
I out
IN
3
2
+ - 0/4…20 mA
VEGACONNECT
5 6
8
out
7
10 13
9 ws
gn
Connection cable of transducers SW 7 (max. line length 35 m)
11 12
ge
br
VEGASON 83 … 87
29
5 Set-up
5 Set-up
Set-up can be realized in different ways. Observe the separate instruction for ECHOFOX
®
-sensors.
5.1 Sensor and signal conditioning instrument (e.g. VEGAMET)
The set-up can be made directly via the operating elements of the signal conditioning instrument or via a PC (equipped with VVO-Software).
In this case the computer can be connected via VEGACONNECT with the signal conditioning instrument or directly with the sensor.
Attention, in case of Ex-sensors in the Ex-area, VEGACONNECT must only be connected in the Ex-area (e.g. signal conditioning instrument).
5.2 Sensor and processing system (VEGALOG 571)
The set-up can be only made via PC (equipped with VVO­Software).
The PC must be connected with a suitable central unit (CPU) with the processing system VEGALOG 571 (interface RS 232).
5.3 Compact instrument
The PC (equipped with VVO-Software) must be directly connected via VEGACONNECT with the compact instrument or the current output.
30
VEGASON 83 … 87
Notices
VEGASON 83 … 87
31
VEGA Grieshaber KG
Am Hohenstein 113 D-77761 Schiltach Phone 0 78 36 / 50 - 0 Fax 0 78 36 / 50 201
Technical data subject to alterations 2.19 303 / July 1995