VEGA MET515V User Manual

Page 1
Operating Instructions
VEGAMET 515V
Level and Pressure
%
100
-
12
on
OKESC
CONNECT
CONNECT
12
on
out
in
Page 2
Contents
1 Product description
1.1 Function and configuration ................................................ 4
1.2 Approvals ........................................................................... 5
1.3 Features ............................................................................. 5
1.4 Technical data .................................................................... 6
1.5 Dimensions......................................................................... 9
2 Mounting................................................................................... 10
3 Electrical connection
3.1 Connection instructions ................................................... 11
3.2 Wiring plan ........................................................................ 11
4 Adjustment
4.1 Indicating and adjustment elements ............................... 12
4.2 Adjustment system .......................................................... 13
4.3 Adju stment via PC ........................................................... 14
4.4 Configuration and parameter adjustment....................... 15
Contents
5 Setup .......................................................................................... 16
6 Configuration
6.1 Configuration measurement loop, two independent
single measurements ...................................................... 17
6.2 Configuration measurement loop, linked applications ... 20
6.3 Measurement loop name................................................. 25
6.4 Fault signal........................................................................ 25
6.5 Tare ................................................................................... 26
6.6 Monitoring ......................................................................... 27
6.7 Configuration of inputs..................................................... 28
6.8 Conf iguration o f outputs .................................................. 30
2 VEGAMET 515V
Page 3
Contents
7 Parameter adjustment
7.1 Adju stm ent wit h me diu m .................................................. 32
7.2 Adjustment without medium ............................................ 33
7.3 Adjustment with linked measurements ........................... 34
7.4 Scaling .............................................................................. 36
7.5 Choose linearisation curve ............................................. 37
7.6 Inte gration ti me ................................................................ 37
7.7 Meas. value limitation ....... .. .. .. .. .. .. ... .. .. .. .. .. .. .. .. ... .. ............ 38
7.8 Adjustment of output parameters ................................... 39
7.9 Simulation ......................................................................... 45
7.10 Special function: Reset .................................................... 45
7.11 Special function: Manual and automatic correction ....... 46
8 Additional functions
8.1 Lin earisat ion curv es ........................................................ 47
8.2 Info .................................................................................... 50
8.3 Password ......................................................................... 51
8.4 Language.......................................................................... 51
8.5 Reset VEGAMET ............................................................. 52
8 Measuring results and units ................................................. 53
9 Diagnosis
9.1 Maintenance ..................................................................... 54
9.2 Simulation ......................................................................... 54
9.3 Fault signal........................................................................ 54
9.4 Repair ............................................................................... 54
9.5 Error codes ...................................................................... 55
10 Menu schematic ....................................................................... 58
Safety i nformation ...................................................................... 64
Note Ex a rea .............................................................................. 64
VEGAMET 515V 3
Page 4

1 Product description

Product description

1.1 Function and configuration

VEGAMET 515V is a signal conditioning in­strument for a number of applications, e.g.:
- level measurement
- gauge measurement
- gauge difference measurement
- process pressure measurement
- density measurement
- measurement with automatic correction
-etc.
Software configuration
Input components
- continuous current inputs
- contact inputs
Function
The signal conditioning instruments power the connected sensors and process their measuring data. The conditioning is carried out by a special software consisting of func­tional components (FB), input components (EB), output components (AB) as well as DCS components (PB).
Configuration
The VEGAMET 515V signal conditioning instrument is constructed as a module card in European size with 5 TE (= 25.4 mm) width. The front plate contains an adjustment module with LC display and keys. The front plate of VEGAMET 515VN does not contain an adjustment module.
Output components
- current outputs
- voltage outputs
- DISBUS outputs
- failure output
- MET display
- relay outputs
AB
EB FB
PC/DCS components
- PC/DCS outputs
Functional components
- measurement loop TAG 1
- measurement loop TAG 2
- measurement loop TAG 3
4 VEGAMET 515V
PB
Page 5
Product description

1.2 Approvals

VEGAMET 515V is suitable for measurements in Ex areas in conjunction with the following safety barriers:
- Safety barrier type 146 Conformity certificate PTB no. Ex-93.C.4025
- Safety barrier type 546 Conformity certificate PTB no. Ex-97.D.2098 X EC type approval certificate TÜV 97 ATEX 1186 X
- Safety barrier VEGATRENN 547 V Ex Conformity certificate PTB no. Ex-97.D.2098 X
- Safety barrier VEGATRENN 548 V Ex Conformity certificate PTB no. Ex-96.D.2137
For such applications, please note the appro­priate official documents (general type ap­proval, test and conformity certificates). They come with the respective instrument.

1.3 Features

- microcomputer-controlled signal condition­ing instrument for continuous measurement
- adjustment module with LC display and 6 keys (not with VEGAMET 515VN)
- adjustable integration time
- two fixed and three user-programmable linearisation curves
- fault monitoring
- fault signal and failure diagnosis via dis­play
Inputs:
- 2 sensor inputs for digital transmission of measured data (VBUS) (pressure transmit­ters, ultrasonic and radar sensors)
- 2 correction inputs (for key, switch or level switch)
Outputs:
- 3 current output 0/4 … 20 mA
- 3 voltage outputs 0/2 … 10 V
- 2 relay outputs (spdt)
- 1 DISBUS output for digital wiring and for connection of VEGADIS 174
- 1 fail safe relay
- adjustment also via PC with adjustment software VVO; connection via the interface adapter of the VEGACONNECT series
VEGAMET 515V 5
Page 6
Product description

1.4 Technical data

Power supply
Operating voltage Unom = 20 … 53 V AC, 50/60 Hz
Power consumption approx. 20 VA or approx. 15 W
Meas. data input
Number 2 inputs Input type active two-wire input, digital (VBUS) (sensor is
Possible sensors (loop powered) pressure transmitters, ultrasonic sensors,
Voltage approx. 25 V DC Current limitation at approx. 7 W, short-circuit proof Min. adjustment delta 2 % of sensor range (hydrostatic)
Connection cable 2-wire standard cable (screening recommen-
max. cable length 1000 m max. resistance per wire 20
Correction signal input
Number 2 inputs Function switching signal to trigger corrections
Voltage 5 V (from instrument) Current 5 mA External cable resistance ≤150 Ω
= 20 … 72 V DC
powered by VEGAMET)
radar sensors
5 mm (ultrasonic, radar)
ded)
or special relay modes via external switching contact
Current output
Number 3 outputs Function analogue output of the processing results Range individually adjustable in the range of 0 … 20 mA Load max. 500 Resolution 1 µA Linearity error 0.05 % (relating to 20 mA) Temperature error 0.05 %/10 K (relating to 20 mA)
Voltage output
Number 3 outputs Function analogue output of the processing results Range individually adjustable in the range of 0 … 10 V Current max. 1 mA Resolution 0.5 mV Linearity error 0.05 % (relating to 10 V) Temperature error 0.06 %/10 K (relating to 10 V)
6 VEGAMET 515V
Page 7
Product description
Relay outputs
Number 2 operating relays
1 fail safe relay Contact floating spdt Contact material AgNi, hard gold plated Turn-on voltage min. 10 mV DC
max. 250 V AC/DC Switching current min. 10 µA
max. 3 A AC, 1 A DC Breaking capacitance max. 500 VA, 54 W Min. switching hysteresis (Low-/High-Delta) 0.5 %
DISBUS output
Function for linking signal conditioning instruments with
another and for connecting digital indicating
instruments Connection cable 2-wire standard cable (screening is
recommended) max. cable length 1000 m max. resistance per wire 15
Indicating elements
Clear text indication LC display (not available with 515VN) - 4-line, 6 digits each
- background lighting Analogue indication LED chain consisting of: (not available with 515VN) - 11 segments 0 % … 100 %
- shows the actual value of the measurement
loop
LEDs in front plate green: operating voltage on
red: fault signal (LED lights with deenergised relay) yellow: relay status (standard setting: LED lights with energised relay)
Adjustment elements
Front plate 6 keys for configuration and parameter
adjustment (not available with 515VN)
Circuit board rotary switch for adjustment of the instrument
address on DISBUS
Ambient conditions
Permissible ambient temperature -20°C … +60°C Storage and transport temperature -40°C … +80°C
Electrical connection
Multiple plug component acc. to DIN 41 612, series F, 33-pole, 3 rows
d, b, z (partly equipped) Carrier BGT 596 (Ex) connection to the appropriate module Housing type 505 or type 506 connection to screw terminals (max. 2.5 mm2)
VEGAMET 515V 7
Page 8
Product description
Electrical protective measures
Protection
- unassembled IP 00
- mounted into carrier BGT 596
- front side completely equipped IP 40
- upper and lower side IP 20
- wiring side IP 00
- mounted into housing type 505 or type 506
- terminal side IP 20
- housing general IP 30
Protection class II (in housing type 505) Overvoltage category II
Electrical separating measures
Reliable separation acc. to VDE 0106, part 1 between power supply, fail safe and level relay
and measuring data inputs
- reference voltage 250 V
- isolation resistance 2.3 kV
Galvanic isolation between the relay outputs
- reference voltage 250 V
- isolation resistance 1.4 kV
Potential separation between DISBUS and outputs
- reference voltage 50 V
- isolation resistance 0.5 kV
Common reference potential at voltage and current output,
correction signal output
Mechanical data
Series module unit for carrier BGT 596
or housing type 505
Dimensions B = 25.4 mm (5 TE), H = 128.4 mm, T = 162 mm
CE conformity
VEGAMET 515V signal conditioning instrument meets the protective regulations of EMC (89/336/EWG) and NSR (73/23/EWG). Conformity has been judged acc. to the following standards: EMC Emission EN 50 081 - 2: 1993
Susceptibility EN 50 082 - 2: 1995
NSR EN 61 010 - 1: 1993
8 VEGAMET 515V
Page 9
Product description

1.5 Dimensions

Circuit board 100 x 160 x 1.5 European size
Multiple plug
5 TE
15
5,5
162
100
128,4
25,4
VEGAMET 515V 9
Page 10

2 Mounting

Mounting
VEGAMET 515V signal conditioning instru­ment can be either mounted with a socket module in a carrier BGT 596 or BGT 596 Ex.M or in a single housing type 505 or 506 .
Mounting in carrier
Mount the respective socket module (stand­ard or Ex version) in your carrier. Wire the connection of the multipoint connector ac­cording to the wiring plan.
Module
Multipoint connector DIN 41 612, series F, 33­pole (d, b, z) with coded pins and mounting material for mounting in carrier BGT 596 or BGT 596 Ex.M.
The multipoint connector is available in the following versions:
- Wire-Wrap standard connection
1.0 x 1.0 mm
- Plug connection 2.8 x 0.8 mm
- Termi-Point standard connection
1.6 x 0.8 mm
- Soldering connection
- Screw terminals 2 x 0.5 mm
2
For further mounting information, see the operating instructions of the carrier.
Mounting in single housing
Either screw the housing socket directly to the mounting plate or plug onto a carrier rail (35 x 15 acc. to EN 50 022 or 32 acc. to EN 50 035). Connect the terminals according to the wiring plans on the following pages. For further mounting information, see the operating instructions of the housing.
Transparent cover
To protect the instrument against unauthor­ised adjustment, the front plate of VEGAMET can be provided with a lockable transparent cover (supplied with the instrument).
Coding
To prevent an interchanging of the different signal conditioning instruments, the multipoint connector of the carrier or the housing can be equipped with coded pins.
The multiple plug of the signal conditioning instrument is equipped with corresponding holes (mechanical coding). An instrument coding ensures that the different signal con­ditioning instruments are not interchanged. The appropriate coded pins are supplied with each module or housing. Equip the multipoint connector with these coded pins acc. to the following table.
Instrument coding
VEGAMET 515V(N) a7 / c5
z b d
a c
o 1 o o 3 o o 5 o o 7 o
a7
o 9 o o11o o13o o15o o17o o19o o21o o23o o25o o27o o29o o31o
c5
10 VEGAMET 515V
Page 11
Electrical connection

3 Electrical connection

3.1 Connection instructions

Note the following instructions for electrical connection:
- The connection must be made acc. to the local installation standards (e.g. in Ger­many acc. to the VDE-regulations).
- The wiring between VEGAMET and sensor can be done with standard two-wire cable.
- If strong electromagnetic interference is expected, screened cable is recom­mended. The screening must be earthed on both ends.
- The line resistances stated in the technical data must not be exceeded.
- If overvoltages are expected, we recom­mend a sensor electronics with integrated overvoltage protection or the installation of VEGA overvoltage arresters.
- The voltage supply of VEGAMET must provide extra-low voltage to ensure pro­tection class II. When using VEGASTAB 593, a reliable separation from the mains circuits acc. to DIN VDE 0106, part 101 is ensured.

3.2 Wiring plan

d b z
+–
2
6
10 12
16 18
20 22 24
28 30 32
2
1 +
++
– +
+
+ –
–+–
+ –
3
– + +
+ –
Fail safe relay
Level relay 1 Level relay 2
DISBUS output
+ –
Sensor 2
Sensor 1
L (+) N (–)
+ –
Supply voltage
Current outputs 1 … 3
Voltage outputs 1 … 3
Correction signal Input 4
Correction signal Input 5
Note:
Terminals d30 and z30 or d32 and z32 are switched in parallel in the signal conditioning instrument.
VEGAMET 515V 11
Page 12

4 Adjustment

Adjustment

4.1 Indicating and adjustment elements

A rotary switch is located on the circuit board. It is used for adjustment of the instru­ment address on DISBUS. This setting is necessary if measured values are to be transmitted via the DISBUS cable to external instruments, e.g. VEGADIS 174 indicating instrument, VEGACOM 557 interface con­verter or other VEGAMETs. With these exter­nal instruments, a received measured value can be associated with a specific measure­ment loop by means of the address.
The adjustment range 1 … F corresponds to the DISBUS addresses 1 … 15. Factory setting: 1
Note:
With address 0, the VEGAMET does not participate in the DISBUS communication.
Rotary switch
8
9
7
6
5
4
33
The set instrument address on the DISBUS can be indicated via the LC display.
Note
If several VEGAMET are linked via the DISBUS, each address must be assigned only once!
A
B
C
D
2
E
F
1
0
10 11 12
13 14 15
Position of the rotary switch
Rotary switch
Front plate VEGAMET 515V
without adjustment with adjustment module 515VN module 515V
1 2
%
%
100
100
+
+
-
-
33
OKESC
CONNECT
12
on
515V
1 LCD (4 lines with 6 figures each, illuminated) for clear text
indication
2 LED chain (yellow) for quasianalogue indication of the
measured value 3 Keys for menu adjustment 4 Connection socket for VEGACONNECT 5 LED (yellow) lights if the relay is energised (standard
setting) 6 LED (red), lights if fail safe relay is deenergised 7 LED (green), lights if operating voltage is on
4 5 6
7
OKESC
CONNECT
CONNECT
12
12
on
on
514
515V
12 VEGAMET 515V
Page 13
Adjustment

4.2 Adjustment system

Indicating and adjustment module
Branching point, i.e. jump to the next lower menu with [OK]
Indication of
- measured value
- menu item
- parameter
Depending on the menu item, interrupt adjustment or change to the next higher menu
Adjustment structure
The adjustment is made via 6 keys in con­junction with the text display. The jump from the measured value display to the lower menu item is made with [OK]. Use [–>] or [<–] to change within this menu level from one menu item to the other. A branching point is indicated by the symbol and enables with [OK] a jump to the next lower menu item. Parameters are indicated when the symbol is missing. The value of the parameters can be modified with [+] or [–] or chosen out of a list. The modified value can be saved with [OK]. To interrupt a setting (without saving the modification), you have to push [ESC]. A jump to the next higher menu item is made with [ESC]. 15 minutes after pushing the key for the last time, an automatic reset to the measured value display is triggered. A jump to the next higher menu level with [ESC] is possible from each menu item, even if no connection is shown in the menu schematics.
Depending on the menu item, change value or choose out of a list
Choose menu item
Depending on the menu item, save the set value or change to the lower menu
ESC
ESC
Info
ESC
Lang­uage
Eng­lish
ESC
Reset VEGA­MET
Ser­vice
-
100
Add’l func­tions
ESC
Pass­word
on
%
+
OKESC
Edit lin. curve
If you are in the utmost right menu item of a menu row and push the [–>] key, you will immediately reach the utmost left menu item of this row. You also reach immediately the utmost right menu item from the left one, if you push the [<–] key. The connections (shown with a broken line) are not shown in the menu schematics in order to provide a better overview.
Volt output 1
ESC
prop. to
Per­cent
Unit
0,0%
Volt­output
0/10V
Failure mode
0V
Volt limita­tion
on
VEGAMET 515V 13
Page 14
Adjustment
Illustrations in the menu schematic
Lang-
White letters represent the param-
uage
eters which can be modified with the
Eng­lish
[+] or [–] key and saved with the
Examples:
- In the menu item "Language“ you can
Param.
TAG­No. 1
configuration of the measurement loop. In the menu schematics you see the factory setting.
Volt at 0%
0,000
[OK] key.
change from German to English.
Bolt print/italic entries, e.g. the meas­urement loop name "TAG-No. 1" can differ if you have made a corre-
sponding parameter adjustment or
Light grey menu items are only dis­played when necessary (depending on the adjustments in the other menu items).

4.3 Adjustment via PC

Signal conditioning instrument with ad­justment module
Setup
- directly via the keys of the adjustment
module
- or with a PC, equipped with VVO software
(VEGA Visual Operating) and the interface
adapter VEGACONNECT.
Signal conditioning instrument without adjustment module
Setup
- with a PC, equipped with VVO software
(VEGA Visual Operating) and the interface
adapter VEGACONNECT.
%
100
+
-
OKESC
CONNECT
12
on
515
VEGACONNECT
PC with VVO software
14 VEGAMET 515V
Page 15
Adjustment
4.4 Configuration and parameter ad­justment
No matter whether you set up your VEGAMET via the keys of the adjustment module or via a PC with the software VVO, the procedure is always the same.
Proceed in the following sequence:
- configuration (if not already configured as
factory setting)
- parameter adjustment.
In this operating instructions manual, the adjustment steps are described which are carried out directly on the keys of VEGAMET. The adjustment via the software VVO is de­scribed in a separate manual.
Configuration
Configuring means assigning or setting func­tions (once). VEGAMET requires a basic configuration (usually once) that determines the applications and the assignments of the inputs and outputs. Choices can be made from existing functions and options. This procedure is called configuration. The signal conditioning instruments are delivered with a configuration which only needs to be changed in special cases.
The basic configuration includes the following steps:
1 Configuration measurement loop
• Choose the kind of application (level,
gauge…)
• Choose sensor type (capacitive, hydro-
static…)
• Determine application (standard, level
difference…)
• Determine options (no option, correc-
tions…)
2 Configuration inputs
• Specify from where your VEGAMET re­ceives the input data (sensor, other VEGAMET)
• Enter sensor characteristics values (meas. range, current range)
3 Configuration outputs
• All outputs (except fail safe relay) can be assigned to one sensor or can be switched off.
After basic configuration, VEGAMET goes into operating mode and indicates the actual measured value. The other configurations should be carried out after the parameter adjustment.
Parameter adjustment
Parameter adjustment means changing the values. Signal conditioning instruments have many parameters, the values of which can be modified, such as, for example, the integra­tion time of 0 … 600 s. The modification of these values is called parameter adjustment. The parameter adjustment does not influence the configuration. Take notice that parameter adjustment is only possible after a configura­tion has been carried out (e.g. set values of the current input after the current output has been assigned).
Note:
The measurement loop configuration can only be modified if a "Reset to single measure­ment“ or "Reset to linked measurement“ has been carried out before (under "Additional functions“).
VEGAMET 515V 15
Page 16

5 Setup

• Adjust the VEGAMET instrument address with the rotary switch on the circuit board (if measured values are to be transferred via the DISBUS cable to external instru­ments, e.g. to VEGADIS 174 indicating instrument, VEGACOM 557 interface con­verter or other VEGAMETs).
• Install VEGAMET.
• Connect sensor and power supply.
• After switching on, the display indicates for approx. 10 secs the instrument type and the software version, e.g. "MET 515V V1.12“.
• If no measurement loop has yet been configured, the display shows "Configura­tion“, the red fault indicator LED also lights. In this case, proceed as described under "6.1 Configuration measurement loop“.
• If a measurement loop has already been configured, the display shows a value, e.g. "TAG-No. 1 21.8 %“.You can now carry out the settings, e.g. adjustment settings.
Setup
16 VEGAMET 515V
Page 17
Configuration

6 Configuration

6.1 Configuration measurement loop, two independent single measurements

TAG ­No. 1
%
xx,x
Param.
Confi-
TAG-
gura-
No. 1
tion
Config inputs
Config meas. loop
TAG 1
Level
1)
Appli­cation
Level
Gauge Distance
TAG 2
Level
like TAG1
1)
Sensor type
Hydro­static
Pulse-echo Pulse-radar
Mode
Stan­dard
1)
Option
no option
Offset cor. Real value cor. Density cor.
1)
The measurement loop configuration is usu­ally provided as a factory setting. Should a general modification of the measurement loop configuration be necessary, "Reset to single measurement“ or "Reset to linked application“ should be carried out first (with "Reset to single measurement“ the VEGAMET is pre­pared for configuration of two independent single measurements. With "Reset to linked application“ it is prepared for configuration of linked applications). Only then can setting in the menu items Application, Sensor type, Mode and Option be modified. Proceed in the menu items in the given sequence. The adjustment or selection options always de­pend on what was set in the previous menu item. When e.g. in the menu item Application "Level“ is set, only one sensor type suitable for level detection can be selected in the menu item "Sensor type“.
1)
The settings in these menu items can only be modified if a "Reset to single measurement“ was carried out beforehand (under menu item "Addi­tional functions“).
Sensor coordi­nation
Posi­tion A
Input no.1
Input 2
TAG­name
TAG ­No. 1
Posi­tion D
Input no.4
Input5
Fault signal
on
off
Posi­tionE
Input no.4
Input5
Tar e
Input from
undef­ined
Input 4
Fault signal
on
Input from
undef­ined
Input 4
As soon as you have made an adjustment in the menu item "Option“ and confirmed it, the display shows the message: "TAG being created!“.
In the following illustrations, different types of applications are shown. In addition, you will see which adjustments you have to carry out in the menu items "Sensor type“ and "Mode“.
The menu item "Position D“ only appears when in the menu item "Option“ either "Offset correction“ or "Real value correction“ has been set. The menu item "Position E“ only appears when in the menu item "Option“ "Density correction“ has been set.
VEGAMET 515V 17
Page 18
Configuration
In the menu items "Pos. D“ and "Pos. E“ you can determine if "Correction input 4“ or "Cor­rection input 5“ is to be used for one of the stated corrections. You then have to enter under "Parameter adjustment“ – "Special functions“ in the menu items "Real value cor­rection at…“ or "Density correction at…“ a value at which the correction should be car­ried out.
Note!
For tare and monitoring it is also possible to assign input 4. However, a correction input must not be used for tare, monitoring and e.g. density correction at the same time!
In the menu item "TAG-Name“ you can enter an individual name for the measurement loop.
If you choose "Fault signal off“, the fail safe relay and the fault indicator LED in the front plate do not function. For a description of the correction modes, see the following pages.
Two independent single measurements
Pos. A Pos. A
Pos. A
Pos. A
Level measurement
Pos. A Pos. A Pos. A
Gauge measurement
Pos. A Pos. A
Distance measurement
18 VEGAMET 515V
Page 19
Configuration
Offset correction
- with unpressurized sensor
- parallel shift of the adjust-
ment characteristics
Real value correction
- with available percentage
value
- parallel shift of the adjust-
ment characteristics
Density correction
- only in conjunction with
hydrostatic pressure transmitters
- slope correction of the
adjustment characteristics
actual measured value in %
100%
Pos. A
Pos. D
Offset correction
actual measured value in %
100%
Pos. D
Pos. A
Real value correction
actual measured value in %
100%
Pos. E
incorrect course of measured values
Measured value too low
Measured value too high
0
0 100%
corrected measured value e.g. 0 %
incorrect course of measured values
Measured value too low
Measured value too high
20
0
0 20 100%
corrected measured value e.g. 20 %
incorrect course of measured values
lower density, measured value too low
higher density,
40
measured value too high
0
Pos. A
0 40 100%
corrected measured value e.g. 40 %
Density correction
VEGAMET 515V 19
Page 20
Configuration

6.2 Configuration measurement loop, linked applications

(note the explanations under "6.1 Configuration measurement loop, two independent single measurements“)
Level measurement in pressurised vessels
Pos. B
Pos. A
Level measurement in pressurised vessels
TAG ­No. 1 % xx,x
Param.
TAG­No. 1
Confi­gura­tion
Config inputs
Config meas. loop
Appli­cation
Level
1) 1)1)
1)
The adjustments in these menu items can only be modified if a "Reset to linked measurement“ was carried out beforehand (under menu item "Addi­tional functions“).
Sensor type
Hydro­static
Mode
Pressu­rized
1)
Option
no option
Sensor coordi­nation
Posi­tion A
Input no.1
TAG 1
Level
TAG­name
TAG ­No. 1
Posi­tion B
Input no.2
TAG 2
Gauge pres­sure
Fault signal
on
off
Posi­tion D
Input no.4
like TAG 1
Tar e
Posi­tion E
Input no.5
TAG 3
Total pres­sure
Input from
unde­fined
Moni­toring
Input from
unde­fined
20 VEGAMET 515V
Page 21
Configuration
Product with variable density
Pos. C
Pos. A
Level measurement, product with variable density (density compensa­tion)
TAG ­No. 1 % xx,x
Param.
TAG­No. 1
Confi­gura­tion
Config inputs
1)
The adjustments in these menu items can only be
Config meas. loop
Appli­cation
Level
1)
Sensor type
Hydro­static
1)
Mode
varia­ble density
1)
modified if a "Reset to linked measurement“ was carried out beforehand (under menu item "Addi­tional functions“).
Option
no option
1)
Offset cor. Real value cor. Density cor.
Sensor coordi­nation
Posi­tion A
Input no.1
TAG 1
Level
TAG­name
TAG ­No. 1
Posi­tion C
Input no.2
TAG 2
Den­sity
Fault signal
on
off
Posi­tion D
Input no.4
like TAG 1
Tar e
Posi­tion E
Input no.5
TAG 3
incor. level
Input from
unde­fined
Moni­toring
Input from
unde­fined
VEGAMET 515V 21
Page 22
Density measurement
Pos. C
Pos. A
Density measurement
TAG ­No. 1 % xx,x
Param.
TAG­No. 1
Confi­gura­tion
Config inputs
Config meas. loop
Configuration
Appli­cation
Den­sity
1)
1)
The adjustments in these menu items can only be modified if a "Reset to linked measurement“ was carried out beforehand (under menu item "Addi­tional functions“).
Sensor type
Hydro­static
1)
Mode
Stan­dard
1)
1)
Option
no option
Offset cor.
Sensor coordi­nation
Posi­tion A
Input no.1
TAG 1
Den­sity
TAG­name
TAG ­No. 1
Posi­tion C
Input no.2
TAG 2
Level
Fault signal
on
off
Posi­tion D
unde­fined
like TAG 1
Tar e
Posi­tion E
unde­fined
TAG 3
incor. level
Input from
unde­fined
Moni­toring
Input from
unde­fined
22 VEGAMET 515V
Page 23
Configuration
Gauge difference
Pos. A Pos. B Pos. A Pos. B
Gauge difference
TAG ­No. 1 % xx,x
Confi-
Param.
gura-
TAG-
tion
No. 1
Config inputs
1)
The adjustments in these menu items can only be
Config meas. loop
Appli­cation
Gauge
1)
1)
Sensor type
Hydro­static
Pulse-echo Pulse-radar
Mode
Differ­ence
1)
modified if a "Reset to linked measurement“ was carried out beforehand (under menu item "Addi­tional functions“).
1)
Option
no option
Real value cor.
Sensor coordi­nation
Posi­tion A
Input no.1
TAG 1
Up­stream water
TAG­name
TAG ­No. 1
Posi­tion B
Input no.2
TAG 2
Down­stream water
Fault signal
on
off
Posi­tion D
Input no.4
like TAG 1
TAG 3
Gauge diff.
Tar e
Input from
unde­fined
Posi­tion E
Input no.5
Moni­toring
Input from
unde­fined
VEGAMET 515V 23
Page 24
Level difference
Pos. A Pos. B Pos. A Pos. B
Level measurement, level differ­ence
TAG ­No. 1 % xx,x
Param.
TAG­No. 1
Confi­gura­tion
Config inputs
Config meas. loop
Configuration
Appli­cation
Level
1)
The adjustments in these menu items can only be modified if a "Reset to linked measurement“ was carried out beforehand (under menu item "Addi­tional functions“).
1)
Sensor type
Hydro­static
Pulse-echo Pulse-radar
Mode
Differ­ence
1)1)
1)
Option
no option
Real value cor.
Sensor coordi­nation
Posi­tion A
Input no.1
TAG 1
Level1
TAG­name
TAG ­No. 1
Posi­tion B
Input no.2
TAG 2
Level2
Fault signal
on
off
Posi­tion D
Input no.4
like TAG 1
Tar e
Posi­tion E
Input no.5
TAG 3
Level diff.
Input from
unde­fined
Moni­toring
Input from
unde­fined
24 VEGAMET 515V
Page 25
Configuration

6.3 Measurement loop name

Naming the measurement loop
You can modify the measurement loop name "TAG-No. 1“, if you want a more meaningful designation. Two lines with six figures each are available. To do this, move to the menu item "TAG name …“.
TAG­Name
TAG -
No. 1
pushing the [+] or [–] key, by doing this you scroll through the alphabet, through the row of numbers and through a list of characters.
[–] to the requested character. With [–>] you move to the next character.
Push [+] or [–] once. The first char­acter of the measurement loop name, in this example the letter T, flashes (editing mode). Continue
TAG-
When you have reached the re-
Name
quested character, push [–>]. The
TAG ­No. 1
next character is activated and be­gins to flash. Scroll again with [+] and

6.4 Fault signal

If you choose "Fault signal off“ for a certain measurement loop, the fail safe relay and the fault indicator LED in the front plate will not react when a failure occurs on this measure­ment loop, e.g. in case of short-circuit. Fail­ures on other measurement loops, however, will be signalled.
Only if on all measurement loops "Fault signal off“ is selected will the fail safe relay and the fault indicator LED be completely out of op­eration.
TAG-
When you have finished the last posi-
Name
tion of the name and "written" the
Ves.4 Hall3
name of the measurement loop in this
way, you have to push [OK] to save the setting. If you quit the menu item without saving, the name of the measurement loop will be still "TAG-No. 1“.
Ves.4
In the display of measured value and
Hall3
all other menu items in which the
% 27,8
measurement loop name is stated,
you will now find the new designation.
VEGAMET 515V 25
Page 26
Configuration

6.5 T a re

With the function "Tare“, a measured value beginning at 0 % is created from the actual measured value. The tare function can be started via a key connected to correction signal input 4.
Meas. values in %
100%
Taster
40
0
tared measured values
The following steps are necessary to activate the tare function:
• Connect a key (closer) to input 4.
TAG ­No. 1
%
xx,x
Param.
TAG­No. 1
Confi­gura­tion
Config inputs
Config meas. loop
tared course
actual course
40 100%
actual measured values
• Choose in the menu item "Input from“ (un- der the menu item "Tare“) input 4.
TAG ­No. 1 % xx,x
Param.
TAG­No. 1
Signal condit­ioning
Out­puts
Curr. out­puts
Volt out­puts
Volt output 1
prop. to
Per­cent
Volume Tare
Unit
Tare %
V%
Adjust­ment
• Assign the tared value in the menu item "Unit“ to the requested output (e.g. current, volt, DIS, PC/DCS output, MET indication).
If you want to deactivate the tare function, you first have to cancel taring in the menu item "Unit“. Then you have to cancel the allo­cation of the correction input (input 4) under the menu item "Tare“.
TAG 1
Level
Appli­cation
Level
Tar e
Input from
Input no.4
26 VEGAMET 515V
Page 27
Configuration

6.6 Monitoring

To activate the monitoring, the following prerequirements must be met:
TAG ­No. 1
%
xx,x
Param.
Confi-
TAG-
gura-
No. 1
tion
Config inputs
• Choose in the menu item "Input from “ (un- der the menu item "Monitoring“) input 4.
• Connect a key switch (opener) to input 4.
Config meas. loop
TAG 1
Level
Appli­cation
Level
Moni­toring
Input from
Input no.4
TAG ­No. 1 % xx,x
Param.
TAG­No. 1
Adjust-
Signal condit­ioning
Unit
0,0%
Out­puts
Curr. out­puts
Mode
(moni­toring)
Volt outputs
Monit. to
Low & High
Relay outputs
Low %
5,0
High %
5,0
ment
Relay output 1
prop. to
Per­cent
• Choose in the menu range "Parameter adjustment relay outputs“ in the menu item
"Mode“ the mode "Monitoring“ for the se­lected relay.
The selected relay becomes energised. By pushing the key switch (opener opens) the actual measured value is first of all frozen and, derived from this, the relay deenergises if this value is underrun (Low) or exceeded (High). After a reset and repeated push of the key switch, the actual measured value is again frozen.
Meas. value 50 %
High 5 % Low –5 %
>55 %
<45%
Relay deenergises
If the monitoring function has to be deacti­vated, monitoring must first be cancelled in the menu item "Mode“. Then the allocation of the correction input (input 4) must be can­celled under the menu item "Monitoring“.
VEGAMET 515V 27
Page 28

6.7 Configuration of inputs

TAG ­No. 1 % xx,x
Param.
TAG­No. 1
Confi­gura­tion
Configuration
Config inputs
Input no. 1
Input from
local Met
MET02 MET03 MET04 ….
Input no. 2
like input no. 1
Serial no.
XXXX XXXX
Inputs no. 1 and 2: VBUS input (measured value) Inputs no. 4 and 5: Correction input
Input no. 4
Input from
local Met
Edit ser. no.
0000 0000
Input no. 5
like input no. 4
Channel no.
K1
Input
undef­ined
Input1 Input 2 Input 3
Input local MET:
Here you can enquire another VEGAMET (e.g. Met 04) and thereby specify that the input signal will not be received from a di­rectly connected sensor, but from a VEGAMET connected via DISBUS. The en­quired VEGAMET number corresponds to the DISBUS address of the instrument (see chapter 4.1).
Autom. sensor search
Input
undef­ined
Sensor charac­terist­ics
Min. meas. range 0,00
Max. meas. range 1,00
Sensor optimise
For radar/ultrasonic sensors: see
MINICOM menu schematic in
VEGASON/VEGAPULS operating
instruction manual under chapter
"Adjustment with VEGAMET or
MINICOM“.
Sensor search
OK ?
Sensor search Now ! OK ?
The sensor characteristics values are pro­vided by the connected sensor and cannot be modified here.
The sensor menu is also provided by the connected sensor. It allows the sensor to be configured from VEGAMET.
If another VEGAMET has been chosen, the menu item "Input undefined" appears in which you can set the input number of the other VEGAMET (see example "Weir control“).
28 VEGAMET 515V
Page 29
Configuration
Example weir control
Sensor 1
Weir 2
Upstream water
Sensor 2B
In the example illustrating weir control, two linked measurements are shown. The gauge difference is measured on each weir with one VEGAMET 515V. Normally, two sensors would be required for each VEGAMET. How­ever, since the gauge value of the upstream water is valid for both VEGAMETs, one sen­sor is sufficient for the upstream water. The input signal of sensor 1 (upstream water) is transmitted via the DISBUS cable from one VEGAMET (MET04) to the other VEGAMET. The value of sensor 1 is therefore available to both signal conditioning instruments.
Weir 1
Sensor 2A
%
100
+
-
OKESC
CONNECT
12
on
515V
"local MET“
Input2
DISBUS
%
100
+
-
OKESC
CONNECT
12
on
515V
"MET04“
Input1
VEGAMET 515V 29
Page 30

6.8 Configuration of outputs

TAG ­No. 1 % xx,x
Param.
TAG­No. 1
Confi­gura­tion
Configuration
Config inputs
Config meas. loop
Config outputs
Config curr. output
mA1 to
TAG ­No. 1
Config volt output
Volt1 to
TAG ­No. 1
mA2 to
TAG ­No. 2
Config relay output
Opera ting relay
Rel. 1 to
TAG ­No. 1
TAG 2 TAG 3
Volt2 to
TAG ­No. 2
mA3 to
TAG ­No. 3
Fail safe relay
Relay
Stan­dard
Rel. 1
Stan­dard
Hold function Reset of alarm functions
Volt3 to
TAG ­No. 3
Config PC/ DCS output
PC/DCS meas. values
DCS 1 to
TAG ­No. 1
TAG 2/ 3
Input
unde­fined
Input 4 Input 5
Config VEGA­DIS
DIS 1 to
TAG ­No. 1
TAG 2/ 3
PC/DCS relay status
off
Rel. 2 to
TAG ­No. 2
TAG 1 TAG 3
PC/DCS input status
off
DCS 7 to
----
Rel. 2
Stan­dard
Hold function Reset of alarm functions
DIS 7 to
----
Input
unde­fined
Input4 Input5
30 VEGAMET 515V
Page 31
Configuration
PC/PLC output and DIS output:
The PC/PLC signal as well as the DIS signal are transmitted via the DISBUS. The PC/PLC output delivers output signals from VEGAMET to the interface converter VEGACOM 557. This interface converter transfers the signals of VEGAMET via differ­ent standard protocols to connected sys­tems (DCS/PLC). In the menu items "DCS 1 to“ up to "DCS 7 to…“ the measurement loop can either be allocated or switched off.
In the menu items "PC/DCS relay status“ and "PC/DCS input status“ you can order the switching conditions of the relays and the conditions of the correction inputs to be transmitted via the DISBUS.
Up to seven external indicating instruments (VEGADIS 174) can be connected to DISBUS. In the menu items "DIS 1 to…“ up to "DIS 7 to–“ the measurement loop can either be allocated or switched off.
Relay outputs
A hold function or a function for reset of alarm functions can be allocated to each operating relay. If this is done, the menu item "Input undefined“ appears. There, "Input 4“ or "Input 5“ (correction inputs) can be assigned to the relay. For a description of the relay functions, see drawing.
Hold function
Parameter
High Low
Taster
Relay output
Reset of alarm functions
Parameter
High Low
Taster
Relay output
t
bz
d
t
bz
d
The relay modes "Hold function“ and "Reset of alarm functions“ are configured as de­scribed above and activated each by an external signal (correction signal input).
VEGAMET 515V 31
Page 32

7 Parameter adjustment

Parameter adjustment

7.1 Adjustment with medium

You can either carry out the adjustment with medium or without medium. To carry out an adjustment with medium, it is necessary that you know the percentage values of the ves­sel for the actual filling.
TAG­No. 1 % xx,x
Param.
TAG­No. 1
Ad­just­ment
with medium
Min­adjust at % 0,0
For this procedure, percentage values must be entered for min. and max. values that correspond to the actual fillings. The se­quence of the min. or max. value is not impor­tant. For example, if you know that your filling is presently 80 %, you can enter in the menu item Max. adjustment the value "80“. Then if your filling is, for example, 10 %, you enter in the menu item Min. adjustment the value "10“.
The larger the difference between the two adjustment points, the more exact the meas­urement over the whole measuring curve. It would be ideal if the adjustment could be carried out at 0 % and 100 %. For practical reasons, however, it is not always possible to completely fill or empty a vessel. The dis­tance between the two adjustment points however, should be at least 10 % of the sen­sor range.
Signal condit­ioning
Scaling
Max­adjust at % 100,0
Lin. curve
linear
Integr ation time s 0
Density in kg/dm3
1.000
Adjustment example
Max-
You know that your vessel is pres-
adjust
ently filled up to 80%. Move to the
at % 100,0
menu item "Max-adjust at % 100.0“.
Briefly push the [–] key, so that the
figure 100.0 flashes (editing mode).
Max-
Continue pushing [–] until the figure
adjust
80.0 appears on the display. Now
at % 80,0
push [OK] to save the adjustment.
Min-
Then, if your filling is for example
adjust
10 %, move to the menu item "Min-
at % 0,0
adjust at % 0.0“. Briefly push the [+] key until the figure 0,0 flashes (edit-
ing mode).
Min-
Continue pushing [+] until "10“ ap-
adjust
pears on the display. Now push [OK]
at % 10,0
to save the adjustment.
Of course, you can carry out the adjustment with medium also at 0 % and 100 % filling. Please note: The figures 0 % and 100 % must flash (editing mode) before they can be saved with the [OK] key.
Note:
If the medium is later changed (medium with another density value or dielectric constant) and no new adjustment is possible or when the MET indication and the DIS outputs refer to height in metres, note the following: For applications with hydrostatic pressure trans­mitters, the adjusted density value must correspond to the value of the medium.
The menu item "Density…“ is displayed if the appropriate sensor type was selected under "Configuration measurement loop“.
32 VEGAMET 515V
Page 33
Parameter adjustment

7.2 Adjustment without medium

Meas.
TAG-
value
No. 1
indication
% xx,x
Param.
TAG­No. 1
Ad­just­ment
with
w.o.
medium
medium
Ad­just­ment
bar
m
For the "
Adjustment without medium
anticipated values (pressure or distance) that correspond to 0 % and 100 % must be entered.
Offset correc­tion
Sensor unpres sur’d? OK?
Offset corr. Now! OK?
0% at mA 4,000
100% at mA 20,000
“, two
Adjustment example
You know the data of the vessel, i.e. you know that at 0 % filling the distance of the liquid to the sensor is 3.5 m and at 100 % filling 0.3 m.
Radar sensor
d1
0.3 m at 100 %
d2
3.5 m at 0 %
In this menu item you choose the
Adjust­ment
adjustment unit, e.g. m (d), if you use a radar sensor [m (d) = distance in
m(d)
m]. Use the [+] and [–] key, to choose the unit and [OK] to save the se­lected unit.
Depending on the sensor type used, the adjustment can be carried out in bar or m.
The menu item "Offset correction“ is activated when connecting hydrostatic pressure trans­mitters. The offset correction should be car­ried out after installation of the sensors, because the outputted sensor values can differ slightly with various installation posi-
0%
Enter in these two menu items the
at
distance values (d1 and d2). With the
m (d)
[+] and [–] keys you set the values,
3,50
with [OK] you save them.
100% at
Note that in this example, a lower
m (d)
distance value exists at 100 % filling
0,30
than at 0 % filling!
tions (vertical or horizontal mounting). With offset correction, the measured data of an unpressurized sensor (vessel empty) are detected as a corrective value and taken into account in all subsequent measurements.
VEGAMET 515V 33
Page 34
Parameter adjustment
7.3 Adjustment with linked measure­ments
Linked measurements are possible with VEGAMET 515V. For this, two sensors are connected which carry out one measurement each (TAG1 and TAG2). VEGAMET 515V calculate from the two sensor values a third value, e.g. a gauge difference (TAG3). When adjusting linked measurements, factors other than those associated with single measure­ments will possibly have to be taken into account.
Adjustment gauge difference
TAG1 TAG2
TAG3
Upstream water
Gauge difference
The adjustment of the individual measure­ment loops TAG1 and TAG3 is the same as the adjustment of single measurement loops, see under "7.1 Adjustment with medium“ and "7.2 Adjustment without medium“. It is also possible to carry out the adjustment only for measurement loop TAG3. If you want to ad­just all three measurement loops, the se­quence is not important.
Downstream water
Adjustment with medium
Ad­just­ment
with medium
Min­adjust at % 0,0
Max­adjust at % 100,0
• Make sure the gauge (level) is the same (difference = 0 %).
• Enter in the menu item "Min-adjust at %“ the figure "0.0“ (push the "+“ or "-“ key until the figure "0.0“ flashes, then push the "OK“ key).
• Mark the position of the sensor in the up­stream water.
• Suspend the sensor 30 cm higher (if 30 cm should correspond to 100 %). A 30 cm lower gauge is now simulated.
• Enter in the menu item "Max-adjust at %“ the figure "100.0“ (push the "+“ or "-“ key until the figure "100.0“ flashes, then push the "OK“ key).
• Suspend the sensor in the original position.
Note:
You can also suspend the sensor in up­stream water in a lower position in order to carry out the max. adjustment.
Adjustment of the gauge difference measurement loop (TAG3)
Suspend the sensors to the same level. Note that a difference of 30 cm (e.g. with weir control) can correspond to 100 %.
34 VEGAMET 515V
Page 35
Parameter adjustment
Adjustment without medium
The easiest way to carry out the adjustment without medium is to do it using the adjust­ment unit "m“.
Param.
TAG­No. 1
Ad­just­ment
with
w.o.
medium
medium
Offset
Adjust­ment
m
bar
correc­tion
Sensor unpres sur’d? OK?
Offset corr. Now! OK?
0% at m 0,00
100% at m 0,300
• Adjust in the menu item "Adjustment“ the unit "m“.
• Enter in the menu item "0 % at m…“ and "100 % at m…“ the values 0.00 and 0.30 (if 30 cm should correspond to 100 %).
Only carry out the offset correction at this point if both sensors are unpressurised.
If you want to carry out the adjustment in bar, you have to enter the differential values of the pressures.
If you want that the gauge difference of 30 cm is shown in the meas. value indication in cm, you can carry out a scaling (see "7.4 Scaling“).
Param.
TAG­No. 3
Ad-
Sig-
just-
nal
ment
condit­ioning
Scal­ing
0% corres ponds 0
100% corres ponds
300
Deci­mal point
888,8
prop. to
Height
Unit
cm
Adjustment with level difference and pres­sure difference
The adjustment of this linked measurement corresponds to the adjustment of gauge difference and is therefore not described separately.
Adjustment with level measurement in pressurized vessels
For the adjustment of measurement loop TAG1 (level), you can proceed in the same manner as with the adjustment of a single measurement loop. The adjustment can be either carried out with or without medium (product).
Measurement loop TAG2 (gauge pressure) is adjusted without medium, preferably in "bar“. For level measurement (TAG1), an adjust­ment of TAG2 is not necessary.
Also, the adjustment of measurement loop TAG3 (total pressure) must not be carried out if you only want to know level of TAG1. Often, the total pressure is the requested measured value, e.g. if, in a filling system, the filling pressure must be measured and controlled. In this case, carry out the adjustment without medium in "bar“.
VEGAMET 515V 35
Page 36
Parameter adjustment

7.4 Scaling

TAG-
Meas.
No. 1
value
%
indication
xx,x
Param.
TAG­No. 1
Ad-
Sig-
just-
nal
ment
condi­tioning
Scal­ing
0% corres ponds 0
100% corres ponds
1000
Deci­mal point
888,8
prop. to
unde fined
The adjustments under scaling determine which number values and which unit will actu­ally be displayed on the measured value indication (upper menu item). In the menu items "0 % corresponds…“ and "100 % cor­responds…“ you can enter with [+] or [–] and [OK] values which should be displayed at 0 % and at 100 % filling. In the menu item "Decimal point…“ you determine the position of the decimal point. In the next menu item "prop. to…“ you get a choice of parameters: push [+] or [–] to select percent, mass, vol­ume, pressure etc. and save with [OK]. The menu item "Unit…“ then serves up a corre­sponding new choice, e.g. m, dm, cm, mm, ft, yd and in, if you have selected the param­eter "Height“ (compare chapter "8 Measuring results and units“).
Unit
– –
Scaling example
You have a raised tank and you want the level to be indicated in meters with three places after the decimal point.
100 %
h=4.5 m
0 %
2.341 m
Set the number 1500 (with keys [+],
0% corres
[–] and [OK]) in this menu item. This
ponds
corresponds to the level at 0 % (if
1500
h=1.5 m
you want to have a lower resolution of the meas. value indication, you can also set 150 or 15).
100%
Set the number 4500 (with keys [+],
corres
[–] and [OK]) in this menu item. This
ponds
corresponds to the level at 100 %.
4500
Deci-
Adjust the decimal point as shown
mal
(with keys [+], [–] and [OK]).
point
8,888
prop.
Choose the term "Height“ in this
to
menu item (with keys [+], [–] and
Height
[OK]).
Percent Pressure Mass
After a scaling, the requested output can be assigned to the scaled value in the menu range "Parameter adjustment outputs“ (menu items "prop. to…“ and "Unit…“).
If you have chosen "Height“ in the
Unit
previous menu item, you get a
m
choice of several units (mm, dm, cm, m, yard…). Choose m (with the keys
dm cm
[+], [–] and [OK]).
….
The scaled value is now shown in the
TAG ­No. 1
meas. value indication.
m
2,341
36 VEGAMET 515V
Page 37
Parameter adjustment

7.5 Choose linearisation curve

Meas.
TAG-
value
No. 1 %
indication
xx,x
Param.
TAG­No. 1
Ad­just­ment
VEGAMET's evaluation routines can be adapted to different vessel forms. For this purpose, you can choose between different linearisation curves:
- linear (factory setting)
- cylindrical tank
- spherical tank
- Lin-curve 1
- Lin-curve 2
- Lin-curve 3 You can edit your modify lin. curves 1 … 3 yourself (see appropriate chapter).
Sig­nal condi­tioning
Scal­ing
Lin. curve
linear
Cylindrical tank Spherical tank Lin. curve1 Lin. curve2 Lin. curve3

7.6 Integration time

Meas.
TAG-
value
No. 1 %
indication
xx,x
Param.
TAG­No. 1
Ad­just­ment
If the integration time is set to 0 s (factory setting), each quick change of the product surface (e.g. waves) will be immediately detected and interpreted as level change. All output values of VEGAMET will follow the wave movements. To avoid this, the integra­tion time can be increased (a max. of 600 s is possible with VEGAMET). The higher the time setting, the slower the measurement reacts.
Signal condi­tioning
Scal­ing
Lin. curve
linear
Integr ation time s 0
After a linearisation, the requested output can be assigned to the linearised value in the menu range "Parameter adjustment outputs“ (menu items "prop. to…“ and "Unit…“).
VEGAMET 515V 37
Page 38

7.7 Meas. value limitation

Meas.
TAG-
value
No. 1 %
indication
xx,x
Param.
TAG­No. 1
Parameter adjustment
Ad­just­ment
Under
Signal condi­tioning
Lin.
Scal­ing
curve
linear
Integr ation time s 0
"Meas. value limitation“
Density in kg/dm3
1.000
you can ex-
Meas. value limita­tion
nega­tive values yes
no
clude negative values on the display (and on the outputs).
Failure mode standard
means that the fail safe relay responds at a sensor current of 3.6 mA or 21 mA.
Failure mode > 110 %
generates an additional fault signal at a measured value of more than 110 % or less than -10 %.
Failure mode
Stan­dard
>110 %
38 VEGAMET 515V
Page 39
Parameter adjustment

7.8 Adjustment of output parameters

Current outputs/Volt outputs
TAG ­No. 1 % xx,x
Param.
TAG­No. 1
Signal condi­tioning
Out­puts
Adjust­ment
Curr. out­puts
Curr. output 1
Volume TARE%
prop. to
Per­cent
Volt out­puts
Volt output 1
prop. to
Per­cent
Volume TARE%
Curr. output 2
like current output1 Unit
0,0%
Volt output 2
like Volt output 1 Unit
0,0%
Curr. output 3
Range
0% +100%
Volt output 3
Range
0% +100%
Curr. output
0/20mA 20/4mA 20/0mA free
Volt output
0/10V
10/2V 10/0V 2/10V free
Curr. at 0%
4,000
0,0 ..20,0
Volt at 0%
0,000
0,0 ..10,0
Curr. at 100%
20,000
0,0 ..20,0
Volt at 100%
10,000
0,0 ..10,0
Failure mode
0mA
22mA
- ­0% 100%
Failure mode
0V
11V
- ­0% 100%
Curr. limita­tion
on
off
Volt limita­tion
on
off
VEGAMET 515V 39
Page 40
Parameter adjustment
In the menu item "
prop. to“,
you can choose between percent and volume. "Prop. to vol­ume“ is then useful when you have chosen spherical tank or user programmable curve under "Conditioning - Linearisation curves“. The output current or the output voltage then assumes a value proportional to the volume of the tank contents.
Unit:
Selection list dependent on the choice in the previous menu item "prop. to“ (see chapter "8 Measuring results and units“).
The menu item range
"0%…100%“
only ap­pears with measurement loop TAG-No. 3 (with gauge difference, level difference measurement). The measured value can be here -100 %.
Therefore, the range can be adjusted to "
-100 % to +100 %“
. The correlation between output current and output voltage can be seen in the diagram below.
+100%
Range
0% +100%
0%
4mA 0V
20mA 10V
Volt output/Current output:
If "free“ is chosen, the following (light grey) menu items appear:
- Volt at 0 %/100 %: Individual voltage values between 0 V and +10 V can be set.
- Current at 0 %/100 %: Individual current values between 0 mA and +20 mA can be set.
In failure mode:
The height of the output current/output volt­age in case of failure is set here. If "--“ is chosen, the existing value is maintained.
Volt limitation/Current limitation on:
Voltage or current of the output remain within the values which were set in the menu item Voltage output/Current output, even if a level of more than 100 % or less than 0 % is meas­ured.
-100%
+100%
Range
-100%
0%
4mA 0V
20mA 10V
-100% +100%
40 VEGAMET 515V
Page 41
Parameter adjustment
Relay outputs
TAG ­No. 1 % xx,x
Param.
TAG­No. 1
Adjust-
Signal condi­tioning
Relay output 1
prop. to
Per­cent
Volume Height Pressure
Out­puts
Curr. out­puts
Relay output 2
like relay output 1
Unit
0,0%
0,00 % Tare %
ment
Volt
Relay
outputs
outputs
Monit.
Mode
on
Over-
Low &
fill
High
protec-
Dry run protec. Switching window on Switching window off Rising tendency Falling tendency (monitoring)
Low %
0,0
High %
100,0
Deviat­ion s 1,0
Devia­tion period
Scan time s 1
Failure mode
off
hold
No. of scans 10
Add’l func­tions
Switch­ing delay
t on s
0
t off s
0
In the menu item " parameter (meas. quantity) to which the relay reacts. You can choose between percent and volume ("Prop. to volume“ is then useful if under "Conditioning - Linearisation curves“, e.g. a spherical tank or a user-programmable curve was chosen). In the next menu item you can choose a suitable item "
Mode
prop. to
“, you choose a
"Unit“
. In the menu
“, you can choose the mode of the
In all other modes, the menu items "Low“ and "High“ appear. There, the switching points for the relay can be set. The menu item "
Failure mode
“ always ap­pears. "Failure mode off“ causes the relay to deenergize in case of failure (e.g. short­circuit). "Failure mode hold“ causes the exist­ing relay status to remain unchanged in case of failure.
relay. The individual relay modes are de­scribed on the following pages.
Under "Additional functions“, you can adjust a switch on (t on) and switch off delay (t off) of
If mode "Rising tendency“ or "Falling ten­dency“ was chosen, the menu items "Devia­tion“, "Deviation period“, "Scan time“ and "No.
the relay of max. 600 s (with the relay modes "Rising tendency“ or "Falling tendency“, no switching delay can be set).
of scans“ appear.
VEGAMET 515V 41
Page 42
Parameter adjustment
d
t
bz
Relay mode "Overfill protection"
The relay deenergises at switching point "High“ (safe condition).
Relay mode "Dry run protection"
The relay deenergises at switching point "Low“ (safe condition).
Relay mode "Switching window on"
The relay is energised within the switching window.
Relay mode "Switching window off"
High Low
Relay output
High Low
Relay output
High Low
Relay output
Parameter
Parameter
Parameter
Parameter
bz
d
t
bz
d
t
The relay is deenergised within the switching window.
High Low
Relay output
d
t
Relay mode "Monitoring"
The enquired relay energises. By pushing the key switch (opener), the actual measured
Meas. value 50 %
High 5 % Low –5 %
>55 %
<45%
Relay deenergised
value is first of all frozen and, derived from this, the relay deenergises if this value is underrun (LOW) or exceeded (High). After a reset and a repeated push of the key switch, the actual measured value is frozen again.
42 VEGAMET 515V
bz
Page 43
Parameter adjustment
Tendency determination
The level change within the cycle time (ta) is determined and after all cycles (n) an average value is generated out of the sum of the level changes. If this average value exceeds a previ­ously defined % value, the tendency determination responds, i.e. an energised relay deenergises. After the selection of "Tendency rising“ or "Tendency falling“ the menu items "Deviation in %“ and "Deviation per time“ are activated.
%
t
ges.
t
a
–– Mode Tendency rising
The relay deenergises when the rising average value of "t tot.“ exceeds the previously defined % value.
Tendency falling
Relay output
ta = cycle time n = number of cycles
%
4 n=4
321
t ges.
t
a
same dependence, however with falling average value
4 n=4
321
Relay output
ta = cycle time n = number of cycles
–– Deviation in % 2 If the level change exceeds the % value set
here, the tendency determination responds. 0 … 110 % Example 2 % (change) per t tot.
–– Deviation per time
t
bz
d
t
bz
d
–– Cycle time
in s 60 Adjustment range 0 … 999 s
Example 60 s correspond to 1 minute
–– Number of
cycles 4 Adjustment range 0 … 99 cycles
Example: t tot = ta • n = 60 • 4 = 240 s = 4 min, i.e. after every 4 minutes, the average value of the deviation is generated and the result is compared with the given deviation in %, here in the example = 2 %
VEGAMET 515V 43
Page 44
MET indication/PC/DCS outputs/DIS outputs
TAG ­No. 1 % xx,x
Param.
TAG­No. 1
Adjust-
Signal condit­ioning
Out­puts
Curr. out­puts
Volt out­puts
Relay out­puts
MET display
ment
PC/ DCS outputs
DIS outputs
Parameter adjustment
prop. to
Per­cent
scaled Height …
MET indication/Unit:
In the menu item "prop. to“, you choose the parameter to which the VEGAMET display reacts (if you have carried out a scaling un­der the menu item "Signal conditioning“, "prop. to scaled“ will have been automatically adjusted, i.e. the display will indicate the scaled value). "Prop. to volume“ is then useful if you have selected, for example, a spherical tank or a user-programmable lin. curve under "Signal conditioning - Linearisation curves“. The indicated value on the VEGAMET display then correlates proportionally to the volume of the tank contents.
Unit
0,0%
PC/ DCS output 1
prop. to
Per­cent
scaled Height …
DIS output 1
prop. to
Per­cent
scaled Height …
Unit
0,0%
DIS output 2
like DIS output 1
Unit
0,0%
DCS output 2
like DCS output 1
DIS output 7
DCS output 7
PC/DCS outputs and DIS outputs:
Adjustment according to the same procedure as the MET indication.
44 VEGAMET 515V
Page 45
Parameter adjustment

7.9 Simulation 7.10 Special function: Reset

TAG ­No. 1 % xx,x
Param.
TAG­No. 1
Adjust-
Signal
Out-
ment
condit­ioning
puts
Simu­lation
Simu­lation Now! OK?
Simu­lation %
XX,X
To check the outputs and connected instru­ments, you can adjust in this menu item any individual percentage value with the keys [+] and [–]. The initial point is always the actual measured value. The indicated value flashes when the simulation is activated. 15 minutes after adjustment of the simulated value, the simulation is automatically terminated and the display reset to measured value indication.
TAG ­No. 1 % xx,x
Param.
TAG­No. 1
Adjust-
Signal
Out-
Simu-
ment
condit­ioning
puts
lation
Spe­cial funct.
Reset
Level
Reset OK ?
Reset Now!
OK ?
With this reset, all parameter values of the measurement loop are reset to factory setting (empty and full adjustment, relay outputs, current output, volt output and scaling of the meas. value indication are reset).
VEGAMET 515V 45
Page 46

7.11 Special function: Manual and automatic correction

TAG ­Nr. 1 % xx,x
Param.
TAG­Nr. 1
Adjust­ment
Signal condit­ioning
Out­puts
Simu­lation
Spe­cal funct.
Parameter adjustment
Simu­lation Now! OK?
Simu­lation %
XX,X
Automatic correction:
1)
This menu item only appears if in the measurement
Reset
Level
Reset OK ?
Reset Now!
OK ?
Real value corr. at % 0
1)
loop configuration a correction mode was set. You then enter here the percentage value to which the automatic correction should respond (triggered by the level sensor on the correction input).
Manual offset correction
(only with hydrostatic pressure transmitters) This correction can be carried out to com­pensate deviations of the sensor values due to ageing. In order to do this, the sensor must be in an unpressurized condition (empty vessel).
Density corr. at %
50,0
Manu­al corr.
1)
Offset correc­tion
Offset correc­tion OK?
Correc­tion Now ! OK ?
Real value corr.
Real value corr. OK?
Correc­tion %
0,0
Correc­tion Now ! OK ?
Manual real value correction
In the menu item "Correction % 0.0“ you can enter a percentage value which corresponds to the actual existing level.
46 VEGAMET 515V
Page 47
Additional functions

8 Additional functions

8.1 Linearisation curves

TAG ­No. 1 % xx,x
Param.
Confi­gura­tion
Add’l funct.
Pass­word
off
Edit lin. curve
Lin. curve1
Add lin. point
TAG­No. 1
Lin.
Lin.
curve2
curve3
like LIN curve 1
Edit lin. curve 1
Delete lin. point
x % 0,0 y V% 0,0
x 0 %
0,0
y 0 V% 0,0
x 1 %
100,0
y 1 V% 100,0
Index marker number (0…32)
Linearisation curve 1 … 3
A linearisation curve is generated by a cer­tain number of index markers and their value pairs. A value pair consists of a value for level percent (X %) and a value for volume percent (Y V %). Up to max. 32 index mark­ers can be included. A linearisation curve can be terminated after any individual number of index markers. The signal conditioning instru­ment terminates the linearisation curve auto­matically with the values X = 100 % and Y = 100 %.
The data for the value pairs can be deter­mined by incremental filling or can be taken from value tables provided by vessel manu­facturer.
Example of incremental filling
Initial situation:
- the adjustment 0 % and 100 % has already been carried out by you
- the total volume of the vessel is known to you, for example 300 m
- the gauging volume (increment) in this example was set at 15 m³
3
x 2 %
100,0
y 2 V% 100,0
x 32 %
100,0
y 32V% 100,0
x 0,0 y 0,0
delete
Delete Now?
x 100,0 y 100,0
delete
Delete Now?
1st index marker
- fill the vessel with the liquid quantity of the gauging volume (increment) of 15 m
3
- the value for level percent is indicated on VEGAMET, transfer this value into the lin­earity protocol, column X %
- the value for volume percent must be cal­culated acc. to the following formula
100 % x gauging volume
Y 1 V = ––––––––––––––––––––––––
total volume
100 % x 15 m
= ––––––––––––––– = 5 %
300 m
3
3
Transfer this value also into the linearity protocol, column Y V %.
2nd index marker etc.
See also the following illustration.
VEGAMET 515V 47
Page 48
Illustration of a linearisation curve
Additional functions
X (in %)
100
80
60
40
20
Add lin. point
x % 0,0 y V% 0,0
With [OK] the new value pair is automatically added to the correct position in the linearisation curve. The exist­ing index markers are re­sorted.
0
X1 %
12,0
Y1 V %
5,0
Edit lin. curve 1
x 0 %
x 1 %
100,0
y 1 V% 100,0
x 2 %
100,0
y 2 V% 100,0
0,0
y 0 V% 0,0
Selection of an index marker 1 … 32 with [–>] or [<–], editing of the Y value with [+] or [–], accept with [OK].
40 60 80 100
De­lete lin. point
x 0,0 y 0,0
delete
De­lete Now?
X32 %
100,0
Y32V %
100,0
x100,0 y100,0
delete
De­lete Now?
To delete an index marker, select the value pair with [–>] or [<–]. With [OK] the value pair and the respective index marker are deleted in the lin. curve. The remaining index markers move up.
V (in %)20
48 VEGAMET 515V
Page 49
Additional functions
Linearity protocol
A linearisation curve is entered in the menu item "Add. lin. point“.
Linearisation curve 1
Index Value pair marker no. X % Y V %
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 29 30 31 32
Linearisation curve 2
Index Value pair marker no. X % Y V %
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 29 30 31 32
Linearisation curve 3
Index Value pair marker no. X % Y V %
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 29 30 31 32
Note
Date Name
VEGAMET 515V 49
Page 50

8.2 Info

TAG ­No. 1 % xx,x
Param.
TAG­No. 1
Confi­gura­tion
Add’l funct.
Additional functions
Pass­word
off
Lin. curve
For radar/ultrasonic sensors: see MINICOM menu schematic in the VEGASON/VEGAPULS operating instruction manual under chapter
"Adjustment with VEGAMET or
Info
Input info
Input1
MINICOM“.
VEGA­MET info
Type MET515V
like input1
Pro­gram info
Pro­gram info
xxxxxx
Serial number
xxxx
xxxx
Input 4
Sensor type
Vibra­tion
Meas. loop info
TAG 1
TAG ­No. 1
Min­adjust at %
0,0
Instr. addr.
Input5Input2
like input 4
Input from
local MET
TAG 2
TAG 3
TAG -
TAG -
No. 2
No. 3
Min-
Max-
adjust
adjust
bar
at %
0,000
Softw.
Softw.
vers.
date
V1.13
1
06
47/97
Chan-
Input
nel no.
undef-
K1
ined
100,0
Act. switch status
Max­adjust
bar
1,000
Param. vers.
5
Para­meter
Level
All menu items under "Info“ have only a dis­play (readout) function.
50 VEGAMET 515V
Page 51
Additional functions

8.3 Password

TAG­No. 1 % xx,x
Param.
TAG­No. 1
Param.
TAG­No. 2
Param.
TAG­No. 3
Confi­gura­tion
You have the option of protecting VEGAMET 515V against unauthorised or incorrect ad­justment. Activate in the menu "Password“ the option "on“ (with keys [+], [–] and [OK]). Now, you can only check the meas. value on the display. You can still reach any menu item with the arrow and OK keys, but as soon as you want to modify a setting, you are asked for the password. Enter the number "515“ (with the keys [+], [–] and [OK]), to carry out the adjustment. Entering the password once is sufficient to open all protected menu items.
Add’l funct.
Pass­word
on
off

8.4 Language

TAG­No. 1 % xx,x
Confi-
Param.
Param.
TAG­No. 1
TAG­No. 2
Param.
TAG­No. 3
Pass­word
on
off
In the menu item "Language“ you can choose a language other than German, such as English, French etc., as menu language (with keys [+], [–] and [OK]).
gura­tion
Edit lin. curve
Add’l funct.
Info
Lang­uage
Eng­lish
German French etc.
VEGAMET 515V 51
Page 52

8.5 Reset VEGAMET

TAG ­No. 1 % xx,x
Param.
Confi­gura­tion
Add’l funct.
Pass­word
off
Lin. curve
TAG­No. 1
Info
Lang­uage
Eng­lish
Reset VEGA­MET
Additional functions
Reset confi­gura­tion
TAG 1
to linked appli­cation
Delete all TAGs?
Reset
OK?
Reset Now!
OK?
to single meas.
Reset TAG1
Delete TAG1?
Reset
OK?
Reset Now!
OK?
Reset TAG2
Delete TAG2?
Reset
OK?
Reset Now!
OK?
“, you reset
to de fault
Reset
OK?
Reset Now!
OK?
With the function "
TAG 1 to default
the whole configuration and parameter ad­justment to factory setting. However, the basic configuration remains, e.g. "Level measurement/Hydrostatic“.
With the function "
Reset TAG 1
“, the basic configuration is also deleted. Then, the meas­urement loop must be completely re-created (config. meas. loop).
With "
Reset sensor values
“ the adjusted sensor data of the connected sensor are deleted.
Reset all inputs
Delete all sen­sor val­ues
Reset
OK?
Reset Now!
OK?
Reset lin. curves
Reset
Reset lin. curve2
Reset
OK?
Reset Now!
OK?
Reset lin. curve3
Reset
OK?
Reset Now!
OK?
lin. curve1
Reset
OK?
Reset Now!
OK?
Reset Lin-curves
Reset sensor values
Reset
Reset
input2
input1
Reset
Reset
OK?
OK?
Reset
Reset
Now!
Now!
OK?
OK?
With the function " delete your manually-edited linearisation curves.
With "Reset all curves“, you delete all to­gether, with "Reset lin-curve 1“, you always delete only one curve.
The three pre-programmed lin-curves "linear, horiz. cylindrical tank, spherical tank“ cannot be deleted.
Reset all curves
Delete all curves?
Reset
OK?
Reset Now!
OK?
“, you can
52 VEGAMET 515V
Page 53
Measuring results and units

8 Measuring results and units

With all outputs and with scaling you will find the menu items "prop. to“ and "Unit“. Here you can choose the meas. result and the suitable unit. The list of the units depends on the selected meas. result (physical quantity). The available units of measurement are listed in the table.
Current/Volt output
prop. to Unit
Percent 0,0 %
Tare %
Volum e V %
Tare V %
VEGADIS/DCS/MET indication
prop. to Unit
Percent 0,0 %
0,00 % Tare %
Volum e V %
Tare V %
Height m
Pressure bar
scaled scaled
Tare scaled
Relay outputs
prop. to Unit
Percent 0,0 %
Volum e V %
Height m
Pressure bar
Scaling
prop. to Unit
Percent %
Volum e m
Height m
Tare %
Tare V %
3
hl l gal V %
3
ft
3
in
dm cm mm yd ft in
Distance m (d)
Pressure bar
mbar psi hPa
Mass kg
t lb
Density kg/dm
g/cm
3
3
Distance m (d)
VEGAMET 515V 53
Page 54

9 Diagnosis

Diagnosis

9.1 Maintenance

The instrument is maintenance-free.

9.2 Simulation

Note
With activated simulation, the entire display flashes. The measured data delivered by the sensors are not released for processing ­you should, therefore, quit this menu item as soon as possible. After 15 minutes, there is an automatic reset to meas. value indication.

9.3 Fault signal

The signal conditioning instrument and the connected sensor are continuously moni­tored during operation. During the parameter adjustment, the set values are checked for plausibility. In both cases, a fault signal can be triggered by irregularities.
In case of failure, an error code is displayed (only within the meas. value indication), the fail safe relay deenergises, the signal lamp lights and the outputs react according to their preadjusted control behaviour.
Configuration
For each individual measurement loop, you can determine if a fault signal should be trig­gered or not. See menu range "Configuration measurement loop“, menu item "Fault signal“.
Parameter adjustment
In the menu item "Failure mode“, you can determine individually for each measurement loop whether and how a measuring range overrun should trigger a fault signal.

9.4 Repair

For safety and warranty reasons repair on the instrument must only be carried out by VEGA staff.
In case of defect, please return the impaired instrument with a short description of the fault to our repair department.
The error codes are listed in section "9.5 Error codes“ on the following pages.
The diagnosis info is transmitted as a running text tape.
54 VEGAMET 515V
Page 55
Diagnosis

9.5 Error codes

Error code Meaning
E004 This operation is not supported by the instrument (different software versions).
E007 Sensor type does not match.
E008 VBUS sensor not found. Sensor cannot be found.
E010 The serial numbers of the connected VBUS sensors are not yet assigned to an
E013 VBUS sensor signals failure; however the communication with the sensor is
You have tried to activate a function with a newer software version of VEGA Visual Operating in an instrument with an older software version. However, the instrument cannot support this operation. Have the software of your instrument updated.
A VBUS sensor with the serial number given by you was found, however the sensor type does not match the settings. Check the entered serial number and modify the configuration.
Probable reasons:
- no sensor connected
- no sensor with this serial number connected
- line break (VBUS)
- short-circuit (VBUS)
- sensor is defective
- interfered communication (VBUS) Also possible:
- failure on the VBUS transmitter/receiver part of VEGAMET Check the serial number, the connection cable, the sensor and if necessary VEGAMET.
input component.
okay. Probable reasons:
- failure on the VBUS sensor Check the VBUS sensor.
E016 Empty/full adjustment reversed. The values for the empty adjustment are
E017 Adjustment span too small. The adjustment values are too close together or are
E021 Span of the scaling values too small or values reversed. The scaling values are
E022 Scaling span too big.
E027 Actual measured value is less than -10 %.
E028 Actual measured value is more than 110 %.
VEGAMET 515V 55
above the values for the full adjustment. Carry out the adjustment again.
identical. Carry out the adjustment again. Also possible:
- an incorrect measuring range has been set on the capacitive electrode. Adjust a higher range.
too close together or are identical. Please check the scaling.
Page 56
Error code Meaning
Diagnosis
E031 Same DISBUS address. At least one other instrument with the same DISBUS
address is connected to the DISBUS. Please check the DISBUS address.
E032 Instrument address 0. Instrument address 0 is adjusted on VEGAMET. With
this address, VEGAMET does not participate in the DISBUS communication, even if the DISBUS is wired. If necessary, modify the instrument address.
E034 Instrument error. A considerable error was detected on the instrument (possi-
bly defective EEPROM). Disconnect voltage and then connect again (cold start). If the error is not eliminated, please contact your VEGA agency.
E035 Instrument error. A considerable error was detected on the instrument (check
sum error in EPROM). Disconnect voltage and then connect again (cold start). If the error is not eliminated, please contact your VEGA agency.
E050 Remote VEGAMET not found. The VEGAMET from which a measured value is
expected cannot be found. Reasons:
- the remote VEGAMET is not connected
- no VEGAMET with this instrument address connected
- line break (DISBUS)
- short-circuit (DISBUS)
- the remote VEGAMET is defective
- interfered communication (DISBUS) Also possible:
- failure on the DISBUS transmitter/receiver part of VEGAMET Please check the instrument address on both VEGAMETs, the connection cable, the remote VEGAMET and, if necessary, this VEGAMET.
E051 Failure during transmission of measured values via DISBUS. It is not possible
to receive a valid measured value via DISBUS from the remote VEGAMET; the communication with the remote VEGAMET, however, is okay. Reason:
- failure on remote VEGAMET
- the input on the remote VEGAMET which should be transmitted is not yet configured Please check the remote VEGAMET and, if necessary, its input configuration.
E052 The input number of the VEGAMET from which a measured value is expected
has not yet been assigned.
56 VEGAMET 515V
Page 57
Diagnosis
Error code Meaning
E060 Span of the current output values too small. The values for the current output
are too close together or are identical. Please check the adjustment of the current output.
E061 Span of the voltage output values too small. The values for the voltage output
are too close together or are identical. Please check the adjustment of the voltage output.
E063 Wrong sensor characteristics values. Please check the sensor characteristics
values
E102 A reset of the configuration was carried out on this VEGAMET via the key-
board.
E110 Switching hysteresis too small. The switching points are too close together or
are identical.
E111 Relay switching points reversed. The relay switching points are reversed with
regard to the selected relay mode.
VEGAMET 515V 57
Page 58
Menu schematic
TAG1-3 xx,x
xx,x
xx,x
3
TAG ­No. 1
%
xx,x
Param.
TAG­No. 1
Adjust­ment
TAG ­No. 2
%
xx,x
Param.
TAG­No. 2
like TAG- No .1
Signal condit­ioning
4
TAG ­No. 3
%
xx,x
Param.
TAG­No. 3
Out­puts
Curr. out­puts
Curr. output 1
prop. to
Per­cent
Meas. value indication
Volt out­puts
Volt output 1
prop. to
Per­cent
Curr. output 2
Unit
0,0%
Volt output 2
like Volt output1
Unit
0,0%
Curr. output 3
like current output 1
Range
0% +100%
10 Menu schematic
Volt output 3
Range
0% +100%
Curr. output
4/20mA
Add’l funct.
Volt output
0/10V
Current at 0%
4,000
Volt at 0%
0,000
Current at 100%
20,000
Confi­gura­tion
see following pages
Volt at 100%
10,000
Failure mode
0mA
Failure mode
0V
Curr. limit­ation
on
Volt limit­ation
on
with medium
Min­adjust at % 0,0
Scaling Lin.
0% corres ponds 0
Max­adjust at % 100,0
curve
linear
100% corres ponds 1000
Integr ation time s 0
Deci­mal point
888,8
w.o. medium
Adjust­ment
bar
Density in Kg/dm3
1,000
prop. to
unde­fined
Offset correc­tion
Sensor unpres sur’d ? OK ?
Offset corr. Now! OK ?
Unit
– –
0% at
bar
0,000
100% at
bar
1,000
Meas. value limit­ation
nega­tive values yes
Failure mode
Stan­dard
ESC
OK
With these keys you move in the menu field
58 VEGAMET 515V
Page 59
Menu schematic
Lang­uage
Eng­lish
1
Relay outputs
In white letters you can see the parameters which can be modified with the [+] or [–] key and saved with the [OK] key.
2
3
… setup sequence
MET display
prop.
Unit
to
Per­cent
0,0%
PC/DCS outputs
DIS out­puts
DIS output 1
prop. to
Per­cent
Sensor type
hydro­static
Bold print/italic is the sensor or measured value information which cannot be modified in this posi­tion.
Simu-
Spe-
lation
cial funct.
Reset
Simu-
Level
lation Now! OK?
Simu­lation %
XX,X
Unit
0,0%
Reset OK ?
Reset Now!
OK ?
DIS output 7
like DIS output 1
Real value corr. at % 0
Density corr. at % 0
Curr. at 100%
20,000
Light grey menu items are only displayed if necessary (depending on the adjustment in other menu items).
Manual corr.
Offset correc­tion
Offset correc­tion OK?
Correc­tion Now ! OK ?
Real value corr.
Real value corr. OK?
Correc­tion % 0,0
Correc­tion Now ! OK ?
Unit
0,00%
PC/DCS output 7
Low %
0,0
like PC/DCS output 1
High
Deviat­ion
%
%
100,0
1,0
Deviat­ion period
Scan time s 1
Failure mode
off
No. of scans
10
Add’l funct.
Switch­ing delay
t on s
0
t off s
0
Relay output 1
prop. to
Per­cent
Relay output 2
like relay output 1
Unit
0,0%
Mode
Overfill protec­tion
PC/DCS output 1
prop. to
Per­cent
Monit. on
Low& High
VEGAMET 515V 59
Page 60
Menu schematic
TAG1-3 xx,x
xx,x
xx,x
Config inputs
2
TAG ­No. 2
%
xx,x
Param.
TAG­No. 2
TAG -
Meas. value
No. 3
indication
%
xx,x
Param.
TAG­No. 3
with linked applications
Appli­cation
Level
1)
1) The settings in these menu
TAG ­No. 1
%
xx,x
Param.
TAG­No. 1
see previous pages
Config meas. loop
1
with two independent single meas­urements
items can only be modified if a "Reset to linked application“ was carried out beforehand
2) The settings in these menu
items can only be modified if a
TAG 1
Level
Appli­cation
Level
2) 2) 2) 2)
TAG 2
Level
Sensor type
Hydro­static
"Reset to single measurement“ was carried out beforehand
like TAG 1
Mode
Stan­dard
Sensor type
Hydro­static
1)
Option
no option
Confi­gura­tion
Mode
Pressu­rized
1) 1)
Sensor coor­dination
Posi­tion A
Input no.1
Add’l func­tions
see following pages
Option
no option
TAG­Name
TAG ­No. 1
Posi­tion D
undef­ined
Sensor coor­dination
Posi­tion A
Input no.1
Fault signal
on
Posi­tion E
undef­ined
TAG 1
Level
TAG­Name
TAG ­No. 1
Posi­tion B
Input no.2
Tar e
Input from
undef­ined
TAG 2
Gauge pres.
Fault signal
on
Posi­tion C
Input no.3
TAG 3
Total pres.
like TAG1
Moni­toring
Input from
undef­ined
Tar e
Input from
undef­ined
Posi­tion D
Input no.4
Moni­toring
Input from
undef­ined
Posi­tion E
Input no.5
Input no. 1
Input from
local Met
Input no. 2
like input no.1
Serial no.
XXXX XXXX
Input no. 4
Input from
local Met
Edit ser.no.
0000 0000
Input no. 5
like input no.4
Chan­nel no.
K1
Input
undef­ined
Input
undef­ined
Sensor charac­teris­tics
Min. meas. range 0,00
Max. meas. range 1,00
Autom. sensor search
Sensor search
OK ?
Sensor optimize
For radar/ultrasonic sensors: see MINICOM menu
schematic in the VEGASON/VEGAPULS operating
instruction manual under chapter "Adjustment with
VEGAMET or MINICOM“.
Sensor search Now ! OK ?
5 … 10
60 VEGAMET 515V
Page 61
Menu schematic
Config out­puts
Config curr. output
Curr.1 to
TAG ­No. 1
Config Volt output
Volt 1 to
TAG ­No. 1
Curr.2 to
TAG ­No. 2
Config relay outp.
Ope­rating relay
Rel. 1 to
TAG ­No. 1
Volt 2 to
TAG ­No. 2
Curr.3 to
TAG ­No. 3
Fail safe relay
Relay
Stan­dard
Rel. 1
Stan­dard
Volt 3 to
TAG ­No. 3
ESC
OK
Config PC/ DCS output
PC/ DCS meas. values
DCS 1 to
TAG ­No. 1
Input
undef­ined
PC/DCS relay status
off
Rel. 2 to
TAG ­No. 2
DCS 2 to
----
PC/DCS input status
off
Rel. 2
Stan­dard
Config VEGA­DIS
DIS 1 to
TAG ­No. 1
Input
undef­ined
1
Lang­uage
Eng­lish
Sensor type
Hydro­static
DIS 7 to
----
2
3
… setup sequence
In white letters you can see the parameters which can be modified with the [+] or [–] key and saved with the [OK] key.
Bold print/italic is the sensor or measured value information which cannot be modified in this position.
Light grey menu items are only displayed if necessary (depend­ing on the adjustment in other menu items).
With these keys you
move in the menu field
Cur­rent at 100%
20,000
VEGAMET 515V 61
Page 62
Menu schematic
TAG1-3 xx,x
xx,x
xx,x
Pass­word
on
TAG ­No. 1
%
xx,x
Param.
TAG­No. 1
see previous pages
Edit lin. curve
For radar/ultrasonic sensors: see MINICOM
under chapter "Adjustment with VEGAMET
Lin. curve1
TAG -
TAG ­No. 2
%
xx,x
Param.
TAG­No. 2
Info Lang-
Input info
Input 1 Typ e
menu schematic in the VEGASON/
VEGAPULS operating instruction manual
Lin. curve2
Meas. value
No. 3
indication
%
xx,x
Param.
TAG­No. 3
Input 4
Input 2 Input 5
like input1 like input4
Sensor type
Vibra­tion
or MINICOM“.
Lin. curve3
Confi­gura­tion
see previous pages
Input from
local MET
VEGA­MET info
MET515V
Chan­nel no.
K1
Add’l func­tions
Pro­gram info
Pro­gram info
xxxxxx
Serial number
xxxx
xxxx
Input
undef­ined
Meas. loop info
TAG 1
TAG ­No. 1
Min­adjust at %
0,0
Instr. addr.
1
Actual switch status
TAG 2
TAG ­No. 2
Min­adjust
mA
4,000
Softw. vers.
1.13
uage
Eng­lish
like TAG 1
Max­adjust at %
100,0
Softw. date
47/97
TAG 3
TAG ­No. 3
Max­adjust
mA
20,000
Param. vers.
5
Param­eter
Level
Add lin. point
x % 0,0 y V% 0,0
like LIN-curve 1
Edit lin. curve 1
x 0 %
0,0
y 0 V% 0,0
x 1 %
x 2 %
100,0
y 1 V% 100,0
100,0
y 2 V% 100,0
Index marker number (0…32)
x32 %
100,0
y32V% 100,0
Delete lin. point
x 0,0 y 0,0
delete
Delete Now?
x100,0 y100,0
delete
Delete Now?
62 VEGAMET 515V
Page 63
Menu schematic
Reset VEGA­MET
Reset confi­gura­tion
TAG1 to de­fault
Reset
OK?
Reset Now!
OK?
TAG2 to de­fault
Reset
OK?
Reset Now!
OK?
to linked applica­tion
Delete all TAGs ?
Reset
OK?
Reset Now!
OK?
to single meas.
Reset TAG 1
Delete TAG 1 ?
Reset
OK?
Reset Now !
OK?
Reset sensor value
Reset TAG 2
Delete TAG 2 ?
Reset
OK?
Reset Now !
OK?
Ser­vice
only accessible with password
Reset lin. curves
Reset lin. curve1
Reset
OK?
Reset Now !
OK?
Reset lin. curve2
Reset
OK?
Reset Now !
OK?
Reset lin. curve3
Reset
OK?
Reset Now !
OK?
Reset all curves
Delete all curves?
Reset
OK?
Reset Now !
OK?
In white letters you can see the parameters which can be modified with the [+] or [–] key and saved with the [OK] key.
Bold print/italic is the sensor or measured value information which cannot be modified in this position.
Light grey menu items are only displayed if necessary (depend­ing on the adjustment in other menu items).
ESC
OK
With these keys you
move in the menu field
Lang­uage
Eng­lish
Sensor type
Hydro­static
Cur­rent at 100%
20,000
VEGAMET 515V 63
Page 64
VEGA Grieshaber KG Am Hohenstein 113 D-77761 Schiltach Phone (07836) 50-0 Fax (07836) 50-201 E-Mail info@de.vega.com
www.vega.com

Safety information

Please read this manual carefully, and also take note of country-specific installation standards (e.g. the VDE regulations in Germany) as well as all prevailing safety regulations and acci­dent prevention rules. For safety and warranty reasons, any internal work on the instruments, apart from that in­volved in normal installation and electrical con­nection, must be carried out only by qualified VEGA personnel.

Note Ex area

Please note the attached safety instructions containing important information on installation and operation in Ex areas. These safety instructions are part of the oper­ating instructions and come with the Ex ap­proved instruments.
ISO 9001
All statements concerning scope of delivery, application, practical use and operating conditions of the sensors and processing sys­tems correspond to the latest information at the time of printing.
Technical data to subject to alterations
2.22 709 / February 2001
Loading...