VEGA MET513 User Manual

Operating Instructions
VEGAMET 513
Level and Pressure
%
100
-
OKESC
CONNECT
on
513
out
in
Contents
1 Product description
1.1 Function and configuration ................................................ 4
1.2 Approvals ........................................................................... 5
1.3 Features............................................................................. 5
1.4 Technical data .................................................................... 6
1.5 Dimensions......................................................................... 9
2 Mounting ................................................................................... 10
3 Electrical connection
3.1 Connection instructions ................................................... 11
3.2 Connection instructions for Ex approved applications . 11
3.3 Wiring plan ........................................................................ 12
4 Adjustment
4.1 Indicating and adjustment elements ............................... 13
4.2 Adjustment system .......................................................... 14
4.3 Adj ustmen t via PC ........................................................... 15
4.4 Configuration and parameter adjustment ....................... 16
4.5 Comparison: reduced menu – extended menu .............. 17
Contents
5Setup.......................................................................................... 18
6 Settings in the "reduced menu"
6.1 Con figurati on of mea surement loop ............................... 19
6.2 Adj ust men t wi th med ium.................................................. 20
6.3 Adjustment without medium ............................................ 21
6.4 Scaling .............................................................................. 22
6.5 Inte gration ti me ................................................................ 23
6.6 Outputs............................................................................. 23
6.7 Simulation ......................................................................... 23
6.8 Password, language, default, reset, menu mode .......... 24
2 VEGAMET 513
Contents
7 Settings in the "extended menu"
7.1 Config uration o f measur ement loo p ............................... 25
7.2 Configuration of inputs ..................................................... 27
7.3 Configu ration of ou tputs .................................................. 2 8
7.4 Adjustment........................................................................ 29
7.5 Conditioning...................................................................... 30
7.6 Paramet er adjustm ent of outp uts ................................... 31
7.7 Simulation ......................................................................... 33
7.9 Password, language, menu mode .................................. 33
7.8 Special function: Reset .................................................... 33
7.10 Special function: Manual correction ................................ 34
7.11 Li nearisa tion cur ves ........................................................ 35
7.12 Info .................................................................................... 38
7.13 Reset VEGAMET ............................................................. 39
8 Measured quantity and units ................................................ 40
9 Diagnostics
9.1 Maintenance..................................................................... 41
9.2 Simulation ......................................................................... 41
9.3 Fault signal........................................................................ 41
9.4 Repair............................................................................... 41
9.5 Error codes ...................................................................... 42
10 Menu schematics
10.1 Menu schematic "reduced menu" .................................. 45
10.2 Menu schematic "extended menu" ................................. 46
Safety informatio n ...................................................................... 52
Note Ex area .............................................................................. 52
VEGAMET 513 3

1 Product description

Product description

1.1 Function and configuration

VEGAMET 513 is a signal conditioning instru­ment for a number of applications, e.g.:
- level measurement
- density measurement
- gauge measurement
- process pressure measurement
-etc.
Software configuration
Input component
- continuous current input
Function
The signal conditioning instruments power the connected sensors and process their analogue measuring data. The conditioning is done via a special software consisting of functional components (FB), input compo­nents (EB), output components (AB) as well as DCS components (PB).
Configuration
The VEGAMET 513 signal conditioning instru­ment is constructed as module card in Euro­pean size with 5 TE (= 25.4 mm) width. It consists of a circuit board, a multiple plug as well as a front plate. The front plate contains an adjustment module with LC display and keys.
Output components
- current output
- voltage output
- DISBUS outputs
- failure output
- MET display
AB
EB FB
PC/DCS components
- PC/DCS outputs
Functional component
- measurement loop TAG 1
4 VEGAMET 513
PB
Product description

1.2 Approvals

VEGAMET are available with the following approvals:
- explosion protection: appropriate operating instrument with intrinsically safe circuit (VEGAMET 513 Ex)
- overfill protection acc. to WHG
For such applications, please note the appro­priate official documents (general type ap­proval, test and conformity certificates). They come with the respective instrument
Ex approval
For hazardous areas, certification acc. to CENELEC defined in the conformity certificate PTB no. Ex-95.D.2145 X for VEGAMET 513 Ex.
WHG approval
Signal conditioning instrument as part of an overfill protection system acc. to WHG (test certificate number see table).

1.3 Features

- microcomputer-controlled signal condition­ing instrument for continuous measurement
- adjustment module with LC display and 6 keys
- adjustable integration time
- two fixed and three user-programmable linearisation curves
- fault monitoring
- 1 sensor input (capacitive electrode or pressure transmitter)
- fault signal and failure diagnosis via dis­play
- 1 current output 0/4 … 20 mA (floating)
- 1 voltage output 0/2 … 10 V
- 1 DISBUS output for digital wiring and for connection of VEGADIS 174
- 1 fail-safe relay
- adjustment also via PC with adjustment software VVO; connection via the interface adapter of the VEGACONNECT series
Instrument Oscillator VEGAMET Test cer tificate Auxiliary level switch
Capacitive electrodes E17 EX 513 EX Z-65.13-123 543 … 547 EL 11 EX0, EL 21 EX0, E18 EX 643 EL 24 EX0, EL 29 EX, EL 31 EX0, EL 42 EX0
Pressure transmitters E23, 513 Z-65.11-130 543 … 547 D80, D81, D84, D86, E23 Ex 513 EX 643 D84 EX, D86 EX
Pressure transmitters E22, 513 Z-65.11-130 543 … 547 D77, D85, D87, E22 Ex 513 Ex 643 D77 EX, D85 EX, D87 EX
VEGAMET 513 5
no. VEGASEL
Product description

1.4 Technical data

Power supply
Operating voltage U
Power consumption approx. 6 VA or approx. 4 W
Meas. data input
Number 1 input Input type active two-wire input, analogue (sensor is
Range 4 … 20 mA Sensor capacitive electrodes, pressure transmitters,
Voltage
- at 4 mA approx. 18 V DC
- at 20 mA approx. 15 V DC Current limitation at approx. 26 mA, shortcircuit-proof Detection line break < 3.6 mA Detection shortcircuit > 21 mA Min. adjustment delta 2 % of the entered sensor values Connection cable 2-wire standard cable (screening
max. resistance per wire 35 Resolution 1 µA Linearity error 0.025 % at 4 … 20 mA Temperature error 0.04 %/10 K at 4 … 20 mA
= 24 V AC (20 … 53 V), 50/60 Hz
nom
= 24 V DC (20 … 72 V)
powered by VEGAMET)
process pressure transmitters, differential pressure transmitters
recommended)
Current output
Number 1 output Function analogue output of the processing results Range adjustable between 0 … 20 mA Load max. 500 Resolution 1 µA Linearity error 0.05 % of the adjusted range Temperature error 0.05 %/10 K (relating to 20 mA)
Voltage output
Number 1 output Function analogue output of the processing results Range adjustable between 0 … 10 V Current max. 1 mA Resolution 0.5 mV Linearity error 0.05 % (relating to 10 V) Temperature error 0.06 %/10 K (relating to 10 V)
6 VEGAMET 513
Product description
Relay output
Numbe r 1 fail-safe relay Contact floating spdt Contact material AgNi, hard gold plated Turn-on voltage min. 10 mV DC
max. 250 V AC/DC
Switching current min. 10 µA
max. 3 A AC, 1 A DC
Breaking capacitance max. 500 VA, 54 W
DISBUS output
Function for linking the signal conditioning instruments
and for connection of digital indicating instruments
Connection cable 2-wire standard cable (screening is
recommended)
max. cable length 1000 m
Indicating elements
Clear text indication LC display
4- line, 6 digits each background lighting
Analogue indication LED chain consisting of:
11 segments 0 % … 100 % shows the actual value of the measurement loop
LEDs in front plate green: operating voltage on
red: fault signal (LED lights with deenergised relay)
Adjustment elements
Front plate 6 keys for configuration and parameter
adjustment
Circuit board rotary switch for adjustment of the instrument
address on DISBUS
Ambient conditions
Permissible ambient temperature -20°C … +60°C Storage and transport temperature -40°C … +80°C
Electrical connection
Multiple plug component acc. to DIN 41 612, series F, 33-pole, 3 lines
d, b, z (partly equipped) Carrier BGT 596 (Ex) connection to the appropriate module Housing type 505 connection to screw terminals (max. 2.5 mm
VEGAMET 513 7
2
)
Product description
Electrical protective measures
Protection
- not mounted IP 00
- mounted in carrier BGT 596
- front side completely equipped IP 40
- upper and lower side IP 20
- wiring side IP 00
- mounted in housing type 505 or type 506
- terminal side IP 20
- housing in general IP 30
Protection class II (in housing type 505) Overvoltage category II
Electrical separating measures
between
- power supply and all other potentials reliable separation acc. to VDE 0106, part 1
- reference voltage 250 V
- isolation resistance 2.5 kV/AC
Between
- meas. data input and all other potentials reliable separation acc. to VDE 0106, part 1
- reference voltage 250 V
- isolation resistance 2.5 kV/AC
Between
- DISBUS and all other potentials potential separation
- reference voltage 50 V
- isolation resistance 0.5 kV/AC
Mechanical data
Series module unit for carrier BGT 596
or housing type 505
Dimensions B = 25.4 mm (5 TE), H = 128.4 mm, T = 162 mm
CE conformity
The VEGAMET signal conditioning instrument meets the protective regulations of EMC (89/336/EWG) and NSR (73/23/EWG). Conformity has been judged acc. to the following standards: EMC Susceptibility EN 50 081 - 2: 1993
Immission EN 50 082 - 2: 1995
NSR EN 61 010 - 1: 1993
8 VEGAMET 513
Product description
Ex technical data
Power supply
Operating voltage U Reference voltage U
Meas. data input (intrinsically safe circuit) on VEGAMET 513 Ex 2-times available
Flame proofing [EEx ia] IIC, [EEx ia] IIB, [EEx ib] IIC or
Max. values
- voltage U
- current I
- power P Characteristics linear Effective inner inductance L Effective inner capacitance C
Max. permissible outer inductance LO (mH) 0.5 1 1.5 2 2 9
Max. permissible outer capacitance CO (nF) 97 78 68 486 200 1000
I
I
The intrinsically safe circuits are reliably separated from the non-intrinsically safe circuits up to a peak value of the nominal voltage of 375 V. The max. voltage on the non-intrinsically safe circuits should not exceed 250 V
eff
corresponds to non-Ex version
nom
= 250 V AC or 125 V DC
m
[EEx ib] IIB
= 20 V
O
= 128 mA
O
= 640 mW
O
negligible negligible
EEx ia IIC EEx ia IIB EEx ib IIC EEx ib IIB
in case of failure.

1.5 Dimensions

Circuit board 100 x 160 x 1.5 European size
15
5,5
VEGAMET 513 9
162
Multipoint connector
100
5 TE
128,4
25,4

2 Mounting

Mounting
VEGAMET 513 signal conditioning instruments can be either mounted with a module in a carrier BGT 596 or BGT 596 Ex.M or in a single housing type 505.
Mounting in carrier
Mount the respective module (standard or Ex version) in your carrier. Wire the terminals of the multipoint connector according to the wiring plan.
Module
Multipoint connector DIN 41 612, series F, 33­pole (d, b, z) with coded pins and mounting material for mounting in carrier BGT 596 or BGT 596 Ex.M.
Module Ex
Multipoint connector DIN 41 612, series F, 33­pole (d, b, z) with coded pins, Ex separating chamber and mounting material for mounting in carrier BGT 596 Ex.M.
The multipoint connector is available in the following versions:
- Wire-Wrap standard connection
1.0 x 1.0 mm
- Plug connection 2.8 x 0.8 mm
- Termi-Point standard connection
1.6 x 0.8 mm
- Soldering connection
- Screw terminals 0.5 mm
2
For further mounting information, see the operating instructions of the carrier.
Mounting in single housing
Either screw the housing socket directly to the mounting plate or plug it onto a carrier rail (35 x 15 acc. to EN 50 022 or 32 acc. to EN 50 035). Connect the terminals according to the wiring plans on the following pages. For further mounting information see the oper­ating instructions of the housing.
Transparent cover
To protect the instrument against unauthor­ised adjustment, the front plate of VEGAMET can be provided with a lockable transparent cover.
Coding
To prevent an interchanging of the different signal conditioning instruments, the multipoint connector of carrier or the housing can be provided with coded pins.
Note:
The coding is absolutely necessary for Ex instruments!
The multiple plug of the signal conditioning instrument is equipped with respective holes (mechanical coding). Instrument coding ensures that the different signal conditioning instruments cannot be interchanged. The appropriate coded pins are supplied with each module or housing. Equip the multipoint connector with these coded pins acc. to the following table.
Instrument Ex
coding coding
VEGAMET 513 a1 / c5
VEGAMET 513 Ex a1 / c5 c23
z b d
a c
o 1 o o 3 o o 5 o
a5
o 7 o o 9 o o11o o13o o15o o17o o19o o21o o23o o25o o27o o29o o31o
c5
c23
10 VEGAMET 513
Electrical connection

3 Electrical connection

3.1 Connection instructions

Note the following instructions for electrical connection:
- The connection must be made acc. to the
local installation standards (e.g. in Ger­many acc. to the VDE-regulations).
- The wiring between VEGAMET and sensor
can be done with standard two-wire cable.
- If strong electromagnetic interferences are
expected, screened cable is recom­mended. The screening must be earthed on both ends.
- The line resistances stated in the technical
data must not be exceeded.
- If overvoltages are expected, we recom-
mend a sensor electronics with integrated overvoltage protection or the installation of VEGA overvoltage arresters.
- The voltage supply of VEGAMET must
provide extra-low voltage to ensure protection class II. When using VEGASTAB 593, a reliable separation from the mains circuits acc. to DIN VDE 0106, part 101 is ensured.

3.2 Connection instructions for Ex approved applications

The signal conditioning instruments must be generally mounted outside the hazardous areas, or special Ex protective measures must be taken.
Ex separating chamber
To ensure sufficient "air and creep distance", an Ex separating chamber must be mounted to the connections of VEGAMET. Lead the cables through the Ex separating chamber and connect them. Fasten the Ex separating chamber with the lower screw. Note the operating instructions of the carrier BGT 596 Ex.M.
Protection in Ex applications
In Ex applications, a protection class of IP 20 must be maintained. To accomplish this, cover the gaps or free modules from the front with suitable blind covers.
Mounting in carriers
If you mount your VEGAMET with Ex ap­proval in a carrier, you have to use a VEGA­Ex module. Keep a distance of at least 10 mm (2 TE) to module cards of other manufac­turers. If you want to mount VEGAMET at the utmost left position in the carrier, you have to mount a blind cover with at least 20 mm (4 TE) in front of the module of the instrument.
%
100
+
-
OKESC
CONNECT
12
on
Blind cover 4 TE
VEGAMET 513 11

3.3 Wiring plan

d b z
+–
Supply voltage
L (+) N (–)
Current output
Voltage output
Sensor
+ –
Ex version
For connection of Ex certified instruments, please note the instructions in the attached official documents as well as the valid mount­ing regulations. Make sure that the Ex sepa­rating chamber is mounted to the multipoint connector. Always lead the cables through the Ex separating chamber. Also note the operating instructions of the carrier BGT 596 Ex.M and the Ex instructions.
2
6
10 12
+
16 18
– +
20
22 24
28 30 32
Fail safe
relay
+
DISBUS
output
+ –
Electrical connection
12 VEGAMET 513
Adjustment

4 Adjustment

4.1 Indicating and adjustment ele­ments
Circuit board
A rotary switch is located on the circuit board. It is used for adjustment of the instru­ment address on DISBUS. This setting is necessary if several VEGAMET signal condi­tioning instruments are linked via the DISBUS.
The adjustment range 1 … F corresponds to the DISBUS addresses 1 … 15. Factory setting: 1
Note:
With address 0 the VEGAMET does not par­ticipate in the DISBUS communication.
Rotary switch
8
9
7
6
5
4
33
The set DISBUS address can be displayed via the LC display without removing the in­strument.
Note
If several VEGAMET are linked via the DISBUS, each address must only be assigned once!
A
B
C
D
E
2
F
1
0
10 11 12
13 14 15
Position of the rotary switch
Rotary switch
Front plate
1 2
%
100
+
-
33
OKESC
4 5 6
1 LCD (4 lines with 6 figures each, illuminated) for clear text
indication
2 LED chain (yellow) for quasi-analogue indication of the
measured value 3 Keys for menu adjustment 4 Connection socket for VEGACONNECT 5 LED (red), lights if fail safe relay is deenergised 6 LED (green), lights if operating voltage is on
CONNECT
on
513
VEGAMET 513 13

4.2 Adjustment system

Adjustment
Indicating and adjustment module
Branching point, i.e. jump to the next lower menu with [OK]
Depending on the menu item, interrupt adjustment or change to the next higher menu
Reduced menu - extended menu
Two menu modes are available: the mode "reduced menu" and the mode "extended menu".
Note:
VEGAMET 513 is preset to automatically place you in the menu mode "reduced menu"!
In the majority of all applications, you can carry out the necessary settings in this menu mode (see also chapter 4.5 Comparison of the menu modes).
Adjustment structure
The adjustment is made via 6 keys in con­junction with the text display. The jump from the measured value display to the underlying menu is made with [OK]. Use [–>] or [<–] to change within this menu level from one menu item to the other. A branching point is indicated by the symbol and enables with [OK] a jump to the underlying menu item. Parameters can be recognised by the absence of the symbol . The value of the parameters can be modified with [+] or [–] or chosen out of a list. The modified value can be saved with [OK]. To interrupt a setting (without saving the modification), you have to push [ESC]. A jump back to the next higher menu item is made with [ESC]. 15 minutes
Indication of
- measured value
- menu item
- parameter
%
100
+
-
OKESC
Depending on the menu item, change value or choose out of a list
Choose menu item
Depending on the menu item, save the set value or change to the underlying menu
after pushing a key for the last time, an auto­matic reset to the measured value display is triggered. A jump back to the next higher menu level (with ESC) is possible from each menu item, even if no connecting line is shown in the menu schematics.
Add’l func­tion
ESC ESC
Pass­word
on
Lang uage
Eng­lish
ESC
TAG 1 to de fault
ESC
Menu mode
Redu­ced
If you are in the utmost right menu item of a menu row and push the [–>] key, you will immediately reach the utmost left menu item of this row. You also reach immediately the right menu item from the left one, if you push the [<–] key. These shortcuts (shown with a broken line) are not shown in the menu schematics in order to give a better overview.
Volt out­put 1
Prop. to
Per­cent
Unit
0,0%
Volt out­put
0/10V
Fail­ure mode
0V
Volt limita tion
on
14 VEGAMET 513
Adjustment
Format examples of the menu schematic
In white letters you see the param-
Lang­uage
eters which can be modified with the
Eng-
[+] or [–] key and saved with the
lish
[OK] key.
Examples:
- In the menu item "Language" you can change from German to English.
Param.
Bold print/italic entries, e.g. the
TAG-
measurement loop name "TAG-No. 1"
No. 1
can differ if you have made a
corresponding parameter adjust­ment or configuration of the measurement loop. In the menu schematics you will see the factory settings.
Volt at
Light grey menu items are only dis-
0%
0,000
played if necessary (depending on the adjustments made in the other
menu items).
Change of the menu mode:
Move from the display of measured value (TAG-No.1) to the menu item "Menu mode Reduced". Now push [+] twice until "Menu mode Extended" appears, then push [OK] to save the setting. You can now return to the display of measured value by pushing [ESC] twice.
TAG­No. 1 % xx,x

4.3 Adjustment via PC

Signal conditioning instrument with ad­justment module
Setup
- directly via the keys of the adjustment module
- or with a PC, equipped with VVO software (VEGA Visual Operating) and an interface adapter VEGACONNECT.
%
100
+
-
OKESC
CONNECT
12
on
515
VEGACONNECT
PC with VVO software
Param.
TAG­No. 1
gura­tion
func­tions
Pass­word
off
Lang­uage
Eng­lish
TAG 1 to de fault
Reset TAG 1
Menu mode
Redu­ced
Ex­tended
Add’l
Confi-
VEGAMET 513 15
Adjustment
4.4 Configuration and parameter ad­justment
Independent of whether you set up your VEGAMET via the keys of the adjustment module or via a PC with the software VVO, the procedure is always the same.
Proceed in the following sequence:
- configuration (if not already configured as
factory setting)
- parameter adjustment.
In this operating instruction manual, the ad­justment steps are described which are directly carried out on the keys of VEGAMET. The adjustment via the software VVO is de­scribed in a separate manual.
Configuration
Configuring means assigning or setting (once) functions. VEGAMET requires a (mostly once) basic co-ordination, determin­ing the applications and the assignments of the inputs and outputs. Choises can be made from existing functions and options. This procedure is called configuration. The signal conditioning instruments are delivered with a configuration which only needs to be changed in special cases.
The basic configuration includes the following steps:
1 Configuration measurement loop
• Choose the kind of application (level,
gauge…)
• Choose sensor type (capacitive, hydro-
static…)
• Specify application (standard, level
difference…)
• Determine options (no option, correc-
tions…)
Note:
The measurement loop configuration can only be modified if a "Reset to single measure­ment" or a "Reset to linked application" has been carried out previously (under "Additional functions" in the extended menu). If you only want to modify the sensor type, you first have to carry out "Reset TAG 1" (under "Additional functions" in the reduced menu).
2 Configuration, inputs
• Determine from where your VEGAMET receives the input data (sensor, other VEGAMET)
• Enter sensor characteristics values (meas. range, current range)
3 Configuration, outputs
• All outputs (except fail-safe relay) can be assigned to a sensor or can be switched off.
After basic configuration, VEGAMET starts operating and indicates the actual measured value. The other configurations should be carried out after the parameter adjustment.
Parameter adjustment
Parameter adjustment means changing the values. Signal conditioning instruments have many parameters, the values of which can be modified, such as for example the integration time of 0 … 600 s. The modification of these values is called parameter adjustment. The parameter adjustment does not influence the configuration. Take notice that parameter adjustment is only possible after a configura­tion has been done (e.g. set values of the current input when the current output has been assigned).
16 VEGAMET 513
Adjustment
4.5 Comparison: reduced menu – extended menu
In the table the most important functions of VEGAMET 513 are listed – each with a mark indi­cating in which menu mode the functions are available.
Function Reduc. Ext.
Adjustment with medium x x
Adjustment without medium x x
Set integration time x x
Simulation xx
Switch over current output (4/20 mA, 0/20 mA, 20/4 mA, 20/0 mA) x x
Switch over voltage output (2/10 V, 0/10 V, 10/2 V, 10/0 V) x x
Scaling (display) x x
Change menu mode (reduced – extended) x x
Change menu language x x
Activate/deactivate password x x
Change sensor type x x
Change measurement loop name x x
Reset measurement loop (Reset TAG) x x
Reset measurement loop to default (TAG to default) x x
Edit linearisation curves x
Change application mode (e.g. level – gauge) x
Select different reference values for outputs x
Define output behaviour (current/voltage output) in case of failure x
Adapt VEGAMET to sensor characteristics values x
Offset correction during adjustment x
Reset level –x
Assign inputs (from another VEGAMET) x
Switch on/off current/voltage limitation x
Individual setting of current/voltage ouput values between 0 … 20 mA/0 … 10 V x
Manual offset correction x
Manual real value correction x
Info indication x
menu menu
VEGAMET 513 17

5 Setup

• Adjust the VEGAMET instrument address on the circuit board by means of the rotary switch (if the measured values should be transmitted via the DISBUS cable to exter­nal instruments, e.g. to VEGADIS 174 indi­cating instrument, VEGACOM 557 interface converter or other VEGAMET).
• Install VEGAMET.
• Connect sensor and power supply.
• After switching on, the display indicates for approx. 10 secs the instrument type and the software version, e.g. "MET 513 V1.12".
• If a measurement loop has not yet been configured, the display shows "Configura­tion", the red failure LED also lights. In this case, proceed as described under "6.1 Configuration of measurement loop".
• If a measurement loop is already configured, the display shows a value, e.g. "TAG-No. 1 21.8 %". You can now carry out the settings, e.g. adjustment.
Setup
18 VEGAMET 513
Settings in the "reduced menu"

6 Settings in the "reduced menu"

6.1 Configuration of measurement loop

Choose sensor type
Meas. value
TAG-
indication
No. 1 % xx,x
Param.
TAG­No. 1
By default, VEGAMET 513 is configured for connection to a hydrostatic sensor. If, for example, you use a capacitive electrode, you have to proceed as follows: Move to the menu item "Sensor type Hydrostatic". Push [+] or [–] once. The word "Hydrostatic" flashes. You are now in the editing mode. Continue pushing [+] or [–] until the display shows "Sensor type capacitive". You are still in the editing mode. Now push the [OK] key. By doing this, you save the settings and quit the editing mode.
Add’l
Confi-
func-
gura-
tions
tion
Pass­word
off
Sensor type
It is only possible to
Hydro-
modify the sensor type,
static
when a "Reset TAG 1" was
capa-
carried out before.
citive VEGADIF
Lang uage
Eng­lish
TAG 1 to de­fault
Reset TAG 1
Delete TAG 1?
Reset OK ?
Reset Now ! OK ?
Name measurement loop
TAG­No. 1 % xx,x
You can modify the meas­urement loop name "TAG­No. 1", if you want a more useful designation.
Param.
TAG­No. 1
Confi­gura­tion
Two lines with six figures each are available. To do this, move to the menu item "TAG name …".
TAG name
TAG ­No. 1
TAG
Push [+] or [–] once. The first char-
name
acter of the measurement loop name,
TAG -
No. 1
in this example the letter T, flashes
(editing mode). Continue pushing the [+] or [–] key, by doing this you scroll through the alphabet, through the row of numbers and through a list of characters.
TAG
When you have reached the re-
name
quested character, push [–>]. The
TAG ­No. 1
next character is activated and
begins flashing. Scroll again with [+] and [–] to the requested character. With [–>] you again move to the next character.
When you have finished the last
TAG name
position of the name and you have
Ves.4
"written" the name of the measure-
Hall3
ment loop in this way, you have to push [OK] to save the setting. If you quit the menu item without saving, the name of the measurement loop is again "TAG-No. 1".
In the display of measured value and
Ves.4 Hall3
all other menu items in which the
%
measurement loop name is shown,
27,8
you will now see the new designation.
VEGAMET 513 19
Settings in the "reduced menu"

6.2 Adjustment with medium

You can either carry out the adjustment with medium or without medium. Adjustment with medium means that you carry out the adjust­ment taking the actual level into account. To carry out an adjustment with medium, it is necessary to know the percentage value of the actual vessel filling.
TAG­No. 1 % xx,x
Param.
TAG­No. 1
Adjust ment
with me­dium
Min.
M ax.
adjust
adjust
at %
at % 100,0
0,0
In this procedure, the percentage values which correspond to the actual min. and max. fillings are entered. The adjustment sequence of the min. and max. value is unimportant. When you know, for example, that your filling is actually 80 %, you can enter in the menu max. adjustment the value "80". Later when your filling is, for example, 10 %, you enter in the menu min. adjustment the value "10".
Adjustment example
You know that your vessel is actually
Max. adjust
filled up to 80%. Move to the menu
at %
item "Max. adjust at % 100.0". Push
100,0
the [–] key briefly, so that the figure
100.0 flashes (editing mode).
Continue pushing [–] until the figure
M ax. adjust
80.0 appears on the display. Now
at %
push [OK] to save the adjustment.
80,0
Later, when your filling is, for exam-
Min. adjust
ple, 10 %, go to the menu item
at %
"Min. adjust at % 0.0". Briefly push
0,0
[+], until the figure 0.0 flashes (edit­ing mode).
Continue pushing [+] until "10" ap-
Min. adjust
pears on the display. Now push [OK]
at %
to save the adjustment.
10,0
You can of course carry out the adjustment with medium at 0 % and 100 % filling. Note: The figures 0 % and 100 % must flash (edit­ing mode), before they can be saved with the [OK] key.
The bigger the difference between the two adjustment points, the more precise the measurement over the whole measuring curve. An adjustment at 0 % and 100 % would be ideal. For practical reasons, it is not always possible to completely empty or fill a vessel. The distance between the two adjust­ment points, however, should be at least 10 % of the sensor range.
20 VEGAMET 513
Settings in the "reduced menu"

6.3 Adjustment without medium

Meas. value
TAG-
indication
No. 1 % xx,x
Param.
TAG­No. 1
Adjust ment
with
without
medium
medium
0%
100%
at
at
mA
mA
4,000
20,000
Adjustment without medium means that you carry out the adjustment independent of the actual level. For this adjustment procedure you have to enter two sensor current values (4 … 20 mA) corresponding to the levels 0 % and 100 %.
Adjustment example
You know the data of the sensor, i.e. you know that at 0 % filling the sensor delivers a current of 4.2 mA and at 100 % filling a cur­rent of 15.5 mA. Enter these values in the menu items.
15.5 mA at 100 %
4.2 mA at 0 %
0% at mA
4,200
100% at mA
15,500
Enter in these two menu items the values of the senor. Use the [+] and [–] keys to set the values and [OK] to save the values.
VEGAMET 513 21
Settings in the "reduced menu"

6.4 Scaling

TAG-
Meas. value
No. 1
indication
% xx,x
Param.
TAG­No. 1
Adjust
Signal
ment
condit ioning
Integr
Sca-
ation
ling
time s
0
0%
100%
Deci­corres ponds
corres ponds
1000
0
mal-
point
888,8
prop. to
unde fined
The adjustments under scaling determine which number values and which unit will be actually displayed in the measured value indication (upper menu item). In the menu items "0 % corresponds…" and "100 % corresponds…" you can enter with [+] or [–] and [OK] values which should be displayed at 0 % and at 100 % filling. In the menu item "Decimal point…" you determine the position of the decimal point. In the next menu item "prop. to…" you can select from a list of parameters: percent, mass, volume, pressure etc., by pushing [+] or [–] and saving with [OK]. According to this adjustment, the menu item "Unit…" provides a new choice, e.g. m, dm, cm, mm, ft, yd and in, if you have selected the parameter "Height" (compare chapter "8 Measured quantity and units").
Unit
– –
Scaling example
You have a raised tank and you want the level (relative to the reference level) to be indicated in meters with three digits after the decimal point.
100 %
h=4.5 m
0 %
2.341 m
Set the number 1500 (with keys [+],
0% corres
[–] and [OK]) in this menu item. This
ponds
corresponds to the level at 0 % (if
1500
you want to have a lower resolution of
h=1.5 m
Reference level
the meas. value indication, you can also set to 150 or 15).
Set the number 4500 (with keys [+],
100% corres
[–] and [OK]) in this menu item. This
ponds
corresponds to the level at 100 %.
4500
Adjust the decimal point as shown
Deci­mal-
(with keys [+], [–] and [OK]).
point
8,888
prop.
Choose the term "Height" in this
to
menu item (with keys [+], [–] and
High
[OK]).
Percent Pressure Mass
Because you have chosen "Height" in
Unit
the previous menu item, you get a
m
choice of several units (mm, dm, cm, m, yard…). Choose m (with the keys
dm
[+], [–] and [OK]).
cm ….
TAG -
In the meas. value indication the
No. 1
scaled value is shown.
m
2,341
22 VEGAMET 513
Settings in the "reduced menu"

6.5 Integration time

Meas. value
TAG-
indication
No. 1 % xx,x
Param.
TAG­No. 1
Signal-
Adjust
condit
ment
ioning
Sca­ling
Integr ation time s
0
If the integration time is set to 0 s (factory setting), each quick change of the product surface (e.g. waves) will be immediately detected and interpreted as level change. All output values of VEGAMET will react immediately to the wave movements. To avoid this, the integration time can be increased (max. 600 s are possible with VEGAMET). The higher the time adjustment, the slower the measurement reacts.

6.6 Outputs

The current output of VEGAMET is adjusted to 4 … 20 mA. By pushing [+] or [–] and [OK] the outputs can be adjusted to the following values: 0/20 mA, 20/4 mA and 20/0 mA.
For voltage output, the following options are available apart from the preadjustment (0/10 V): 10/2 V, 10/0 V and 2/10 V.

6.7 Simulation

Meas. value
TAG-
indication
No. 1 % xx,x
Param.
TAG­No. 1
Ad­just ment
Signal­condit­ioning
Out­puts
Simu­lation
Simu­lation Now ! OK ?
Simu­lation %
xx,x
TAG­No. 1 % xx,x
Param.
TAG­No. 1
Adjust ment
Meas. value indication
Signal­condit ioning
Out­puts
Current out­put 1
4/20mA
0/20mA 20/4mA 20/0mA
Volt out­put 1
0/10V
10/2V 10/0V 2/10V
To check outputs and connected instru­ments, you can adjust any individual percentage value with the keys [+] and [–] in this menu item. Initial point is always the actual measured value. The indicated value flashes when simulation is activated. 15 minutes after setting the simulated value, the simulation automatically terminates and resets to meas. value indication.
VEGAMET 513 23

6.8 Password, language, default, reset, menu mode

Meas. value
TAG-
indication
No. 1 % xx,x
Confi­gura­tion
Add’l func­tions
Param.
TAG­No. 1
Settings in the "reduced menu"
Pass­word
off
on
Lang­uage
Eng­lish
French German etc.
to de fault
Reset OK ?
Reset Now ! OK ?
Reset TAG 1
Delete TAG 1 ?
Reset OK ?
Reset Now ! OK ?
TAG 1
Password
You have the possibility to protect VEGAMET 513 against unauthorised adjustment or adjustment by mistake. Activate in the menu "Password" the option "on" (with keys [+], [–] and [OK]). Now you can only check the meas. value on the display. You can still reach any menu item with the arrow and OK keys, but as soon as you want to modify an adjustment, you are asked for the password. Enter the figure "513" (with the keys [+], [–] and [OK]), to carry out the adjustment. One single input of the password is sufficient to open all protected menu items.
Language
In the menu item "Language" you can choose a language other than German, such as English, French etc. as menu language (with keys [+], [–] and [OK]).
Menu mode
Redu­ced
Ex­tended
Default
In the menu item "TAG 1 to default" you reset all settings concerning measurement loop 1 to default. If, for example, you have changed the name of the measurement loop to "Silo 5", after the reset the name is again "TAG-No. 1". Also all adjustment values that you have entered for measurement loop 1 are now reset to default.
Reset TAG 1
With "Reset TAG 1" the measurement loop configuration will be deleted. This function must be carried out if you want to change the applied measuring technology (e.g. capaci­tive instead of hydrostatic).
Menu mode
The menu modes "Reduced" and "Extended" are available. With the keys [+], [–] and [OK] you choose the required menu mode. The menu schematics of the reduced menu and the extended menu are shown later in this operating instruction manual. The factory setting is "Reduced menu".
24 VEGAMET 513
Settings in the "extended menu"

7 Settings in the "extended menu"

7.1 Configuration of measurement loop

TAG ­No. 1
%
xx,x
Param.
Confi-
TAG-
gura-
No. 1
tion
Config in­puts
Config meas. loop
TAG 1
level
Appli­cation
level
0/4-20mA Gauge Pressure
Sensor type
Hydro­static
capacitive VEGADIF VEGABAR
Mode
Stan­dard
Option
no option
The measurement loop configuration is nor­mally already done at the factory. Should a fundamental modification of the measurement loop configuration be necessary, a "Reset to single measurement" must first be carried out (in the menu "Additional functions", "Reset VEGAMET"). Only then can you modify the adjustments in the menu items Application, Sensor type, Mode and Option. You should, therefore, work on the individual menu items in the given sequence. The selection or ad­justment possibilities always depend on the adjustment in the previous menu item. If, for example, in the menu item Application "Level" is adjusted, only the sensor mode that is suitable for level detection can be selected in the menu item "Sensor type". As soon as you have carried out and con­firmed an adjustment in the menu item "Op­tion", the following message appears on the display "TAG being created!".
Sensor coordi­nation
Posi­tion A
In­put 1
TAG­name
T AG ­No. 1
You choose the application 4/20 mA when you want to connect a sensor of another manufacturer to the VEGAMET.
In the following illustrations, further applica­tion modes are shown. In addition, you will see there which adjustments you have to carry out in the menu items "Sensor type" and "Mode".
VEGAMET 513 25
Level measurement
TAG 1
level
Settings in the "extended menu"
Pos. A
Applic­ation
Level
Sensor type
Hydro­static
Capacitive VEGABAR VEGADIF
Mode
Stan­dard
Option
no option
Sensor coordi nation
Posi­tion A
In­put1
Gauge measurement
TAG 1
Gauge
Applic­ation
Gauge
Sensor type
Hydro­static
Mode
Stan­dard
Option
no option
Sensor coordi nation
Posi­tion A
In­put1
Process pressure measurement
TAG 1
Process pres­sure
Applic­ation
Pres­sure
Sensor type
VEGA­BAR
VEGADIF
Mode
Stan­dard
Option
no option
Sensor coordi nation
Posi­tion A
In­put1
Pos. A
Level measurement
Pos. A
Gauge measurement
Pos. A
Pos. A
Process pressure measurement
Differential pressure measurement
TAG 1
Pressu­re diff.
Appli­cation
Pres­sure
Sensor type
VEGA­DIF
VEGABAR
Mode
Diffe­rence
Option
no option
Sensor coordi nation
Posi­tion A
In­put1
Differential pressure measurement
26 VEGAMET 513
Pos. A
Settings in the "extended menu"

7.2 Configuration of inputs

TAG ­No. 1 % xx,x
Confi-
Param.
gura-
TAG-
tion
No. 1
Config In puts
In­put no. 1
Input of
local Met
MET02 MET03 MET04 ….
Chan­nel no.
S1
In­put
unde­fined
Input1 Input2 Input3
Sensor charac­teri­stics
Min. meas. range 0,00
Max. meas. range 1,00
Input local MET:
Here you can select another VEGAMET (e.g. Met 04) and hence determine that the input signal should not be taken from a directly connected sensor, but from a VEGAMET connected over the DISBUS. The selected VEGAMET number corresponds to the DISBUS address of the instrument (see chapter 4.1).
Max.
Min.
sensor
sensor
value
value
20,000
4,000
If another VEGAMET has been chosen, the menu item "Input undefined" appears in which you can adjust the input number of the other VEGAMET (see illustration).
The menu items "Min. meas. range" and "Max. meas. range" are only visible with hydrostatic pressure transmitters. Sensor values are stated in the test certificate of the hydrostatic pressure transmitter.
DISBUS
100
100
on
MET 04 Input 1
CONNECT
OKESC
514Ex
OKESC
CONNECT
on
514Ex
"local MET"
VEGAMET 513 27

7.3 Configuration of outputs

TAG ­No. 1 % xx,x
Param.
TAG­No. 1
Confi­gura­tion
Settings in the "extended menu"
Config inputs
Config meas. loop
Config outputs
Config current output
Current1 to
T AG ­No. 1
----
Config Volt output
Volt1 to
T AG ­No. 1
----
PC/PLC output and DIS output:
The PC/PLC signal as well as the DIS signal are transmitted via the DISBUS. The PC/PLC output delivers output signals of VEGAMET to an interface converter VEGACOM 557. This interface converter transfers the signals from VEGAMET via different standard protocols to connected systems (DCS/PLC). In the menu items "PLC 1 to" up to "PLC C to…" the measurement loop can be allocated or switched off.
Config relay output
Fail safe relay
Relay
Stan­dard
Config PC/ PLC­output
PC/PLC meas. values
PLC 1 to
TAG ­No. 1
----
Config VEGA­DIS
DIS 1 to
TAG ­No. 1
----
PLC 2 to
----
DIS 2 to
----
PLC 3 to
----
DIS 3 to
----
Up to three external indicating elements (VEGADIS 174) can be connected to DISBUS. In the menu items "DIS 1 to…" up to "DIS 3 to–" the measurement loop can be allocated or switched off.
The current, volt and relay outputs are allocated as factory setting to measurement loop "TAG-No. 1". All outputs can be switched off individually (----), i.e. they will no longer access a measurement loop.
In the menu items "PC/PLC relay status" and "PC/PLC input status" it can be determined that the relay mode and input status are transmitted via the DISBUS.
28 VEGAMET 513
Settings in the "extended menu"

7.4 Adjustment

TAG ­No. 1 % xx,x
Param.
TAG­No. 1
Adjust­ment
with medium
Min­adjust at % 0,0
Max­adjust at % 100,0
without medium
Adjust­ment
mA
Offset cor­rection
Sensor unpres­sur'd ? OK ?
Offset corr. Now! OK ?
0% at
mA
0,000
100% at
mA
1,000
The adjustment with medium corresponds to the procedure in the reduced menu (see appropriate chapter).
- if the medium is changed later on (medium with another density value or DK value) and no new adjustment can be made or
- if the MET indication and the DIS outputs relate to height in meters,
Please note the following: In applications with hydrostatic pressure transmitters, the adjusted density value (see menu Parameter - Conditioning - Scaling ­Density) must correspond to the value of the medium. In applications with capacitive elec­trodes, the adjusted DK value must corre­spond to the value of the medium.
For the adjustment without medium, two anticipated values for level, gauge, etc. corresponding to 0 % and 100 % must be entered.
The menu item "Offset correction" is opened when hydrostatic pressure transmitters are connected. The offset correction should be carried out after installation of the sensor as the sensor values can differ slightly due to different installation positions (vertical or horizontal installations). With the offset cor­rection, the meas. data of the unpressurised sensor (vessel empty) are detected as cor­rection values and taken into account in all subsequent measurements.
VEGAMET 513 29

7.5 Conditioning

T AG ­No. 1 % xx,x
Param.
TAG­No. 1
Adjust-
Signal
ment
condi­tioning
Scaling
Lin. curve
linear
spherical tank etc.
100%
0%
corre-
corre-
sponds
sponds
1000
0
Integr ation time s 0
Deci­mal point
888,8
Dichte in Kg / d m
1,000
prop. to
unde­fined
Settings in the "extended menu"
Meas.
DK
value
value
limita-
(Er)
3
81,00
Unit
– –
tion
nega­tive values yes
Failure mode
Stan dard
>110%
The menu items "Scaling" and "Integration time" correspond to the menu items in the
"reduced menu" (see appropriate chapter).
The menu items "Density…" or "DK value…" are optionally displayed when under "Con­figuration measurement loop" the appropriate sensor type has been selected. The density or DK value must, before adjustment with medium, be so adjusted that it corresponds to the value of the medium (see also chapter "6.4 Adjustment").
The conditioning of VEGAMET can be adapted to different vessel forms. The follow­ing linearisation curves are available:
- linear (factory setting)
- horiz. cylindrical tank
- sperical tank
- Lin-curve 1
- Lin-curve 2
- Lin-curve 3 Lin-curves 1 … 3 can be edited by the user (see appropriate chapter).
After a scaling or linearisation, the required output must be assigned to the scaled or linearised value (menu item "prop. to..." and "Unit...") under the menu "Parameter adjust­ment outputs".
Under Meas. value limitation you can ex­clude negative values.
Failure mode Standard
means that at a sensor current of 3.6 mA or 21 mA the fail safe relay responds.
Failure mode >110%
also generates a fault signal when a meas. value of more than 110 % or less than -10 % reached.
30 VEGAMET 513
Settings in the "extended menu"

7.6 Parameter adjustment of outputs

Current outputs/voltage outputs
T AG ­No. 1 % xx,x
Param.
TAG­No. 1
Signal condi­tioning
Out­puts
Adjust­ment
Cur­rent out­puts
Cur­rent output 1
Volume T ARE%
prop. to
Per­cent
Volt out­puts
Volt output 1
prop. to
Per­cent
Volume TARE%
Unit
0,0%
Unit
0,0%
Current output
0/20mA 20/4mA 20/0mA free
Volt output
0/10V
10/2V 10/0V 2/10V free
Cur­rent at 0%
4,000
0,0 ..20,0
In the menu item "prop. to" you can choose between percent and volume. "Prop. to vol­ume" is then useful when under "Signal condi­tioning - Linearisation curves", for example, a spherical tank or an individually defined linearisation curve is selected. The output current or the output voltage is then propor­tional to the volume of the tank contents.
Unit:
Selection list dependent on the choice in the previous menu item "prop. to" (see chapter "8 Measuring results and units").
Volt output/Current output:
If "free" is chosen, the following (light grey) menu items appear:
- Volt at 0 %/100 %:
Volt at 0%
0,000
0,0 ..10,0
Current at 100%
20,000
0,0 ..20,0
Volt at 100%
10,000
0,0 ..10,0
Failure mode
0mA
22mA
- ­0% 100%
Failure mode
0V
11V
- ­0% 100%
Current limita­tion
on
off
Volt limita­tion
on
off
Individual voltage values between 0 V and +10 V can be adjusted.
- Current at 0 %/100 %: Individual current values between 0 mA and +20 mA can be adjusted.
Failure mode:
The height of the output current/output volt­age in case of failure is set here. If "--" is chosen, the actual value is maintained.
Volt limitation/Current limitation on:
Voltage/current remain within the values which are given in the menu item voltage output/current output.
VEGAMET 513 31
MET indication/PC/PLC outputs/DIS outputs
TAG ­No. 1 % xx,x
Param.
TAG­No. 1
Settings in the "extended menu"
Signal condi­tioning
Out­puts
Cur­rent out­puts
Volt out­puts
Relay out­puts
MET display
prop. to
Per­cent
scaled Height …
Adjust­ment
MET indication/Unit:
In the menu item "prop. to" you choose the parameter to which the VEGAMET display reacts (if you have carried out a scaling un­der the menu item "Signal conditioning", "prop. to scaled" will have been automatically adjusted, i.e. the display will indicate the scaled value). "Prop. to volume" is then useful if you have selected, for example, a spherical tank or a user-programmable lin. curve under "Signal conditioning - Linearisation curves". The indicated value of the VEGAMET display then reacts proportionally to the volume of the tank contents.
PC/PLC
DIS
outputs
outputs
Unit
0,0%
PC/PLC output 1
prop. to
Per­cent
scaled Height …
DIS output 1
prop. to
Per­cent
scaled Height …
Unit
0,0%
DIS output 2
as DIS output 1
Unit
0,0%
PC/ PLC output 2
as PLC output 1
DIS output 3
PC/ PLC output 3
PC/PLC outputs and DIS outputs:
Are adjusted according to the same procedure as the MET indication.
32 VEGAMET 513
Settings in the "extended menu"

7.7 Simulation 7 .8 Special function: Reset

T AG ­No. 1 % xx,x
Param.
TAG­No. 1
Out-
Adjust­ment
Signal condi­tioning
puts
Simu­lation
Simu­lation now! OK?
Simu­lation %
XX,X
To check the outputs and connected instru­ments, you can adjust in this menu item any individual percentage value with the keys [+] and [–]. Initial point is always the actual measured value. The indicated value flashes when the simulation is activated. 15 minutes after setting the simulated value, the simulation is automatically terminated and the measured value indication switched back on.
T AG ­No. 1 % xx,x
Param.
TAG­No. 1
Out-
Adjust­ment
Signal condi­tioning
puts
Simu­lation
Special func­tions
Reset
Level
Reset OK ?
Reset Now!
OK ?
With this reset, all parameter values of the measurement loop TAG-No. 1 are reset to factory setting (empty and full adjustment, relay outputs, current output, volt output and scaling of the meas. value indication are reset).

7.9 Password, language, menu mode

See chapter "6 Settings in the reduced menu".
TAG ­No. 1 %
Param.
Confi­gura­tion
Add'l func­tions
Pass­word
off
lin. curve
Ser-
InfoEdit
Lan-
Reset
guage
VEGA-
Eng-
MET
lish
vice
Menu mode
Exten­ded
Redu­ced
TAG­No. 1
VEGAMET 513 33

7.10 Special function: Manual correction

T AG ­No. 1 % xx,x
Param.
TAG­No. 1
Adjust-
Signal
ment
condi­tioning
Out­puts
Simu­lation
Special functions
Settings in the "extended menu"
Simu­lation now! OK?
Simu­lation %
XX,X
Reset
Level
Reset OK ?
Reset now!
OK ?
Manual corr.
Offset cor­rec­tion
Offset correc­tion OK?
Cor­rection now ! OK ?
Manual offset correction
(only with hydrostatic pressure transmitters) This correction can be carried out to com­pensate changes of the sensor values due to ageing. In oder to do this, the sensor must be in an unpressurized condition (empty vessel).
Real value corr.
Real value corr. OK?
Correc­tion %
0,0
Cor­rection now ! OK ?
Manual real value correction
In the menu item "Correction % 0.0" you can enter a percentage value which corresponds to the actual level.
34 VEGAMET 513
Settings in the "extended menu"

7.11 Linearisation curves

TAG ­No. 1 % xx,x
Param.
Confi-
Add'l gura­tion
func-
tions
Pass­word
off
Edit lin. curve
Lin. curve1
TAG­No. 1
Lin. curve2
Lin. curve3
Add lin. point
x % 0,0 y V% 0,0
as LIN-curve 1
Edit lin. curve 1
x 0 %
0,0
y 0 V% 0,0
x 1 %
100,0
y 1 V% 100,0
Index marker number (0…32)
Linearisation curve 1 … 3
A linearisation curve is created with a number of index markers and their value pairs. A value pair consists of a value for level percent (X %) and a value for volume percent (Y V %). Up to max. 32 index mark­ers can be included. A linearisation curve can be terminated after any individual number of index markers. The signal conditioning instru­ment terminates the linearisation curve auto­matically with the values X = 100 % and Y = 100 %.
The data for the value pairs can be deter­mined by incremental filling or can be taken from a table of values provided by the vessel manufacturer.
An example of incremental filling
Initial situation:
- you have already carried out the 0 % and 100 % adjustment
- the total volume of the vessel is known to you, for example 300 m
- the increment or gauging volume in this example was determined at 15 m
3
3
Delete lin. point
x 2 %
100,0
y 2 V% 100,0
x 32 %
100,0
y 32V% 100,0
x 0,0 y 0,0
delete
De­lete now?
x 100,0 y 100,0
delete
De­lete now?
1st index marker
- fill the vessel with the liquid quantity of the gauging volume of 15 m
3
- the value for level percent is indicated on VEGAMET, transfer this value into the lin­earity protocol, column X %
- the value for volume percent must be cal­culated acc. to the following formula
100 % x gauging volume
Y 1 V = ––––––––––––––––––––––––
total volume
100 % x 15 m
= ––––––––––––––– = 5 %
300 m
3
3
Transfer this value also into the linearity protocol, column Y V %.
2nd Index marker etc.
In addition, see the following illustration.
VEGAMET 513 35
Illustration of a linearisation curve
Settings in the "extended menu"
X (in %)
100
80
60
40
20
Add lin. point
x % 0,0 y V% 0,0
With [OK] the new value pair is automatically added to the correct position in the linearisation curve. The al­ready present index markers are re-sorted.
0
X1 %
12,0
Y1 V %
5,0
Edit lin. curve 1
x 0 %
x 1 %
100,0
y 1 V% 100,0
x 2 %
100,0
y 2 V% 100,0
0,0
y 0 V% 0,0
Select the index markers 1 … 32 with [–>] or [<–], edit the Y value with [+] or [–], accept with [OK].
40 60 80 100
Delete lin. point
x 0,0 y 0,0
delete
De­lete now?
X32 %
100,0
Y32V %
100,0
x100,0 y100,0
delete
De­lete now?
To delete the index markers, select value pairs with [–>] or [<–]. With [OK] the value pair and the corresponding index marker are deleted from the lin. curve. The re­maining index markers move up.
V (in %)20
36 VEGAMET 513
Settings in the "extended menu"
Linearity measurement protocol
A linearisation curve is entered in the menu item "Add. lin. point".
Linearisation curve 1
Index marker Value pair
no. X % Y V %
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
29
30
31
32
Linearisation curve 2
Index marker Value pair
no. X % Y V %
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
29
30
31
32
Linearisation curve 3
Index marker Value pair
no. X % Y V %
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
29
30
31
32
Note
Date
Name
VEGAMET 513 37

7.12 Info

TAG ­No. 1 % xx,x
Param.
Confi­gura-
TAG-
tion
No. 1
Add'l func­tions
Settings in the "extended menu"
Pass word
off
Lin. curve
Info
Input info
Input1
Sensor type
Hydro­static
VEGA­MET info
Type MET513
Input from
local MET
Pro­gram info
Pro­gram info
xxxxxx
Serial number
xxxx
xxxx
Channel No.
S1
Meas. loop info
TAG 1
T AG ­No. 1
Min­adjust at %
0,0
Instr. addr.
Input
In­put1
Min­adjust
0,000
1
Sensor char­acter­istics
Min. meas. range
bar
Softw. vers.
V1.13 06
0,00
Max­adjust at %
100,0
Softw. date
47/97
act. sensor value
xx,xxx
Max. meas. range
1,00
Max­adjust
bar
1,000
Param. vers.
5
Min. sensor value
4,000
Param­eter
Level
Max. sensor value
20,000
All menu items under "Info" only have display function.
38 VEGAMET 513
Settings in the "extended menu"

7.13 Reset VEGAMET

T AG ­No. 1 % xx,x
Param.
Confi-
Add'l gura­tion
func-
tions
Pass­word
off
Lin. curve
TAG­No. 1
Info
Lan­guage
Eng­lish
Reset VEGA­MET
Reset confi­gura­tion
TAG 1 to de fault
Reset
OK?
Reset now!
OK?
to single meas.
Reset TAG1
Delete TAG1?
Reset
OK?
Reset sensor values
Reset input1
Reset
OK?
Reset now!
OK?
Reset lin. curves
Reset lin. curve1
Reset
OK?
Reset now!
OK?
Reset lin. curve2
Reset
OK?
Reset now!
OK?
Reset lin. curve3
Reset
OK?
Reset now!
OK?
Reset all curves
Delete all curves?
Reset
OK?
Reset now!
OK?
Reset now!
OK?
With the function "TAG 1 to default" you reset the whole configuration and parameter ad­justment to factory setting. However, the
With the function "Reset lin-curves" you can delete your manually edited linearisation
curves. basic configuration remains, e.g. "Level measurement/Hydrostatic".
With "Reset all curves" you delete all together,
with "Reset lin-curve 1" you always delete With the function "Reset TAG 1" the basic
only one curve. configuration is also deleted. Then the meas­urement loop must be created completely anew (config. meas. loop).
The three pre-programmed lin-curves "linear,
horiz. cylindrical tank, spherical tank" cannot
be deleted. With "Reset sensor values", the adjusted sensor data of the connected sensor are deleted.
VEGAMET 513 39

8 Measured quantity and units

Measuring results and units
With all outputs and with scaling, you find the menu items "prop. to"
and "Unit". Here you can choose the measured quantity and the suitable unit. The list of the units depends on the selected measured quantity. In the table, the available units are listed.
Current/Volt output
prop. to Unit
Percent 0.0 %
Vol ume V %
VEGADIS/PLC/MET indication
prop. to Unit
Percent 0.0 %
0.00 %
Vol ume V %
Height m
Pressure bar
scaled (as with
scaling)
Scaling
prop. to Unit
Percent %
Vol ume m
Height m
Pressure bar
Mass kg
Density kg/dm
3
hl l gal V %
3
ft
3
in
dm cm mm yd ft in
mbar psi hPa
t lb
g/cm
3
3
40 VEGAMET 513
Diagnostics

9 Diagnostics

9.1 Maintenance

The instrument is maintenance-free.

9.2 Simulation

Note
When the simulation is activated, the entire display flashes. The measured data delivered by the sensors are not released for processing; you should, therefore, quit this menu item as soon as possible. After 60 minutes there is an automatic reset to meas. value indication.

9.3 Fault signal

The signal conditioning instrument and the connected sensor are permanently moni­tored during operation. During the parameter adjustment, the adjusted values are checked for plausibility. In both cases a fault signal can be triggered by irregularities.
In case of failure, an error code is displayed (only within the meas. value indication), the fail-safe relay deenergises, the signal lamp lights and the outputs react according to the preadjusted condition.
Configuration
For each individual measurement loop, you can determine if a fault signal should be trig­gered or not. See menu "Configuration meas­urement loop", menu item "Fault signal".
Parameter adjustment
In the menu item "Failure mode" you can de­termine individually for each measurement loop whether and how an exceeding of the measuring range should trigger a fault signal.

9.4 Repair

For safety and guarantee reasons, repair on the instrument must only be carried out by VEGA staff.
In case of defect, please return the affected instrument with a short description of the fault to our repair department.
The error codes are listed in section 9.5 on the following pages.
The diagnosis info is transmitted as a scrolling text info.
VEGAMET 513 41

9.5 Error codes

Error code Meaning
Diagnostics
E004 This operation is not supported by the instrument (different software versions).
E014 Possible short-circuit
E015 Possible line break
E016 Empty/full adjustment reversed. The values for the empty adjustment are
E017 Adjustment span too small. The adjustment values are too close together or are
You have tried to activate a function with a newer software version of VEGA Visual Operating in an instrument with older software version. However, the instrument cannot support this operation. Have the software of your instrument updated.
Probable reasons:
- short-circuit
- sensor is defective Check the connection cable and, if necessary, the sensor. Probably
- an incorrect measuring range has been set on the capacitive electrode. Adjust a smaller range.
Probable reasons:
- no sensor connected
- line break
- sensor is defective Check the connection cable and, if necessary, the sensor.
above the values for the full adjustment. Carry out the adjustment again.
identical. Carry out the adjustment again. Probably
- an incorrect measuring range has been set on the capacitive electrode. Adjust a higher range.
E021 Span of the scaling values too small or values reversed. The scaling values are
E022 Scaling span too big.
E027 Actual measured value is less than -10 %.
E028 Actual measured value is more than 110 %.
E031 Same DISBUS address. At least one other instrument with the same DISBUS
42 VEGAMET 513
too close together or are identical. Please check the scaling.
address is connected to the DISBUS. Please check the DISBUS address.
Diagnostics
Error code Meaning
E032 Instrument address 0. Instrument address 0 has been set on VEGAMET. With
this address, VEGAMET does not participate in the DISBUS communication, even if the DISBUS is wired. If necessary, modify the instrument address.
E034 Instrument error. A considerable error was detected on the instrument (possi-
bly defective EEPROM). Disconnect voltage and then reconnect (cold start). If the error is not eliminated, please contact your VEGA agency.
E035 Instrument error. A serious error was detected on the instrument (check sum
error in EPROM). Disconnect voltage and then reconnect (cold start). If the error is not eliminated, please contact your VEGA agency.
E050 Remote VEGAMET not found. The VEGAMET from which a measured value is
expected cannot be found. Reasons:
- the remote VEGAMET is not connected
- no VEGAMET with this instrument address connected
- line break (DISBUS)
- shortcircuit (DISBUS)
- the remote VEGAMET is defective
- interfered communication (DISBUS) Probably
- failure in the DISBUS transmitter/receiver part of VEGAMET Please check the instrument address on both VEGAMETs, the connection cable, the remote VEGAMET and, if necessary, this VEGAMET.
E051 Failure during transmission of measured values via DISBUS. It is not possible
to receive a valid measured value via DISBUS from the remote VEGAMET; the communication to the remote VEGAMET, however, is okay. Reason:
- failure on remote VEGAMET
- the input of the remote VEGAMET, which should be transmitted to, is not yet configured Please check the remote VEGAMET and, if necessary, its input configuration.
E052 The input number of the VEGAMET from which a measured value is expected
has not yet been assigned.
E053 Span of the sensor characteristics values too small. The sensor characteristics
values are too close together or are identical.
E054 Sensor characteristics values reversed. The min. sensor characteristics value
is higher than the max. sensor characteristics value.
E060 Span of the current output values too small. The values for the current output
are too close togehter or are identical. Please check the adjustment of the current output.
VEGAMET 513 43
Diagnostics
Error code Meaning
E061 Span of the voltage output values too small. The values for the voltage output
are too close togehter or are identical. Please check the adjustment of the voltage output.
E063 Incorrect sensor characteristics values. Please check the sensor
characteristics values
44 VEGAMET 513
Menu schematic "reduced menu"

10 Menu schematics

10. 1 Menu schematic "reduced menu"

TAG­No. 1 % xx,x
actual measured value
Param.
TAG­No. 1
Adjust­ment
with medium
Confi­gura­tion
Sensor
Hydro­static
Signal condi­tioning
Scal­ing
0% corre­sponds
Add'l func­tions
Pass­word
off
TAG­name
T AG ­No. 1
The sensor type can only be modified, when a "Reset TAG 1" has been carried out first.
Out­puts
Integr ation time s
0
Current output 1
4/20mA
100% corre­sponds
1000
0
without medium
Lan­guage
Eng­lish
Deci­mal point
888,8
Volt output 1
0/10V
TAG 1 to de fault
Reset
OK ?
Reset now!
OK ?
prop. to
unde­fined
Reset TAG 1
Delete TAG 1?
Reset OK ?
Reset now! OK ?
Simu­lation
Simu­lation now! OK ?
Simula­tion %
xx,x
Unit
– –
Menu mode
Redu­ced
With these keys you move in the menu field
Sensor type
Hydro­static
Lang­uage
Eng­lish
Bold print/italic is the sensor or measured value information which cannot be modified in this position.
In white letters you can see the parameters which can be modi­fied with the [+] or [–] key and saved with the [OK] key.
ESC
OK
Min­adjust at %
0,0
Max­adjust at % 100,0
0% at mA 4,000
100% at mA 20,000
Current at 100%
20,000
Light grey menu items are only displayed if necessary (de­pending on the adjustment in other menu items).
VEGAMET 513 45
Menu schematic "extended menu"
T AG ­No. 1
%
xx,x
Param.
TAG­No. 1
Adjust­ment
with medium

10.2 Menu schematic "extended menu"

MET display
prop. to
Per­cent
Unit
0,0%
Current output
4/20mA
Density in Kg/dm
1,000
prop. to
unde­fined
Add'l func­tions
PC/PLC outputs
PC/PLC
Unit
output1
0,0%
prop. to
Per­cent
Volt
Volt
output
at
0/10V
0%
0,000
Current
Current
at
at
100%
0%
20,000
4,000
DK value (Er)
3
81,00
Unit
– –
Meas. value limita­tion
nega­tive values yes
Signal condi­tioning
prop. to
Per­cent
Scaling Lin .
curve
linear
100%
0%
corre-
corre-
sponds
sponds
1000
0
without medium
Out­puts
Cur­rent out­puts
Cur­rent output 1
Confi­gura­tion
see following pages
Volt outputs
Volt output 1
prop. to
Per­cent
Unit
0,0%
Integr ation time s 0
Deci­mal point
888,8
PC/PLC output2
Unit
0,0%
Volt at 100%
10,000
Failure mode
0mA
Failure mode
Stan dard
PC/ PLC output 3
as PLC outp.1
Fail­ure mode
0V
Current limita­tion
on
Volt limita­tion
on
Min­adjust at % 0,0
Max­adjust at % 100,0
Adjust­ment
mA
Offset cor­rection
Sensor unpres­sur'd ? OK ?
Offset corr. now! OK ?
at
mA
4,000
100% at
mA
20,000
0%
46 VEGAMET 513
Menu schematic "extended menu"
Simu­lation
Special func­tions
DIS outputs
DIS out­put1
prop. to
Per­cent
DIS out­put2
as DIS outp.1
Unit
0,00%
DIS
out-
put3
Simu­lation now! OK?
Simu­lation %
XX,X
Reset
Level
Reset OK ?
Reset now!
OK ?
Manu­al corr.
Offset cor­rec­tion
Offset correc­tion OK?
Cor­rection now! OK ?
Real value corr.
Real value corr. OK?
Cor­rection % 0,0
Cor­rection now! OK ?
Sensor type
Hydro­static
Bold print/italic is the sensor or measured value information which cannot be modified in this position.
In white letters you can see the parameters which can be modi­fied with the [+] or [–] key and saved with the [OK] key.
Light grey menu items are only displayed if necessary (de­pending on the adjustment in other menu items).
ESC
OK
With these keys you move
Lan­guage
Eng­lish
Cur­rent at 100%
20,000
in the menu field
VEGAMET 513 47
T AG ­No. 1
%
xx,x
Param.
TAG­No. 1
Confi­gura­tion
Add'l func­tions
Menu schematic "extended menu"
see previous pages
Config
Config
inputs
meas. loop
TAG 1
Level
Appli­cation
Level
1) 1) 1)
1) The parameters in these menu items
Input No. 1
Config outputs
Config current output
Current1 to
TAG ­No. 1
Sensor type
Hydro­static
can only be modified when a "Reset to single measurement" has been carried out first.
see following pages
Config Volt output
Volt1 to
TAG ­No. 1
Mode
Stan­dard
Config relay output
Fail safe relay
Relay
Stan­dard
Option
no option
1)
Config PC/PLC output
PC/PLC meas. values
PLC 1 to
T AG ­No. 1
Sensor coordi­nation
Posi­tion A
In­put1
PC/PLC relay status
off
PLC 2 to
----
TAG­name
TAG ­No. 1
Config VEGA­DIS
DIS 1 to
TAG ­No. 1
PLC 3 to
----
DIS 2 to
----
DIS 3 to
----
Input from
local Met
Channel No.
S1
Input
undef­ined
Sensor charac­teristics
Min. meas. range
0,00
Max. meas. range
1,00
Min. sensor value
4,000
Max. sensor value
20,000
48 VEGAMET 513
Menu schematic extended menu"
Bold print/italic is the sensor or measured value information which cannot be modified in this position.
In white letters you can see the parameters which can be modi­fied with the [+] or [–] key and saved with the [OK] key.
Light grey menu items are only displayed if necessary (de­pending on the adjustment in other menu items).
ESC
OK
With these keys you move
Sensor type
Hydro­static
Lan­guage
Eng­lish
Current at 100%
20,000
in the menu field
VEGAMET 513 49
T AG ­No. 1
%
xx,x
Param.
TAG­No. 1
see previous pages
Confi­gura­tion
Add'l func­tions
Menu schematic "extended menu"
Pass­word
off
Edit lin. curve
Lin.­curve1
Info Lan-
xxxx
S1
Meas. loop info
TAG 1
TAG ­No. 1
Min­adjust at %
0,0
Instr. addr.
Input
In­put1
1
Input info
Input1
Sensor type
Hydro­static
Lin.­curve2
VEGA­MET info
Type MET513
Input from
local MET
Lin.­curve3
Pro­gram info
Pro­gram info
xxxxxx
Serial number
xxxx
Channel No.
Min­adjust
bar
0,000
Softw. vers.
V1.13 06
Sensor char­acter­istics
Min. meas. range
0,00
guage
Eng­lish
Max­adjust at %
100,0
Softw. date
47/97
act. sensor value
xx,xxx
Max. meas. range
1,00
Max­adjust
bar
1,000
Param. vers.
5
Min. sensor value
4,000
Param­eter
Level
Max. sensor value
20,000
as LIN-curve 1
Add lin.point
x % 0,0 y V% 0,0
Edit lin. curve 1
x
0 %
0,0
y 0 V% 0,0
x 1 %
x 2 %
100,0
y 1 V% 100,0
100,0
y 2 V% 100,0
Index marker number (0…32)
x32 %
100,0
y32 V% 100,0
Delete lin. point
x 0,0 y 0,0
delete
De­lete now?
x100,0 y100,0
delete
De­lete now?
50 VEGAMET 513
Menu schematic "extended menu"
Reset VEGA­MET
Reset confi­gura­tion
TAG 1 to de fault
Reset
OK?
Reset Now!
OK?
to single meas.
Reset TAG1
Delete TAG1?
Reset
OK? Reset
now! OK?
Reset sensor values
Reset input1
Reset
OK?
Reset now!
OK?
Reset lin.­curves
Reset lin.­curve1
Reset
OK?
Reset now!
OK?
Ser­vice
only accessible with password
Reset lin.­curve2
Reset
OK?
Reset now!
OK?
Menu mode
Ex­tended
Reset lin.­curve3
Reset
OK?
Reset now!
OK?
Reset all curves
Delete all curves?
Reset
OK? Reset
now! OK?
Sensor type
Hydro­static
Bold print/italic is the sensor or measured value information which cannot be modified in this position.
In white letters you can see the parameters which can be modi­fied with the [+] or [–] key and saved with the [OK] key.
Light grey menu items are only displayed if necessary (de­pending on the adjustment in other menu items).
ESC
OK
With these keys you move
Lan­guage
Eng­lish
Current at 100%
20,000
in the menu field
VEGAMET 513 51
VEGA Grieshaber KG Am Hohenstein 113 D-77761 Schiltach Phone (07836) 50-0 Fax (07836) 50-201 E-Mail info@de.vega.com
www.vega.com

Safety information

Please read this manual carefully, and also take note of country-specific installation standards (e.g. the VDE regulations in Germany) as well as all prevailing safety regulations and acci­dent prevention rules. For safety and warranty reasons, any internal work on the instruments, apart from that in­volved in normal installation and electrical con­nection, must be carried out only by qualified VEGA personnel.

Note Ex area

Please note the attached safety instructions containing important information on installation and operation in Ex areas. These safety instructions are part of the oper­ating instructions and come with the Ex ap­proved instruments.
ISO 9001
All statements concerning scope of delivery, application, practical use and operating conditions of the sensors and processing sys­tems correspond to the latest information at the time of printing.
Technical data to subject to alterations
2.21 844 / February 2001
Loading...