VEGA MET407Z User Manual

VEGAMET 407 Z
TIB • Technical Information • Operating Instructions
Signal conditioning instrument for continuous level measurement
Supply for
- one pressure sensor or
- one capacitive measuring electrode
Conditioning of analog transmitted measuring data
VEGA Grieshaber KG
Am Hohenstein 113 Postfach 11 42 D-77757 Schiltach Phone 0 78 36/50-0
MOD
+
-
STO
!
t
SIM
VEGAMET
407 Z
50.0
%
Contents
Contents of the instruction manual
The described module must only be inserted and operated as described in this TIB. Please note that other action can cause damage or destruction for which VEGA does not take responsibility.
The measuring systems certified as overfill protection acc. to WHG and as overfill protection acc. to the regulation for combustible liquids (VbF) are listed on page 6 and 7.
Security information
Introduction Contents of the instruction manual .....................................................2
Security information ............................................................................2
Product description .............................................................................3
Technical Information Configuration of a signal conditioning instrument ...............................3
Configuration of a measuring system .................................................3
Technical data ....................................................................................4
Galvanical separation .........................................................................5
Dimensional drawing ..........................................................................5
Approvals ............................................................................................6
Mounting instructions ..........................................................................8
Electrical connection ...........................................................................8
Operating surface Indication and operating elements ......................................................9
Operation...........................................................................................10
Set-up ...............................................................................................10
Parameter adjustment Empty / full adjustment ..................................................................11
Integration time .................................................................................12
Simulation .........................................................................................12
Password ..........................................................................................13
Alarm information Alarm signal ......................................................................................13
Fault diagnosis .................................................................................14
The
Technical Information / Operating instruc-
tions is called TIB. It contains all necessary infor-
mation for correct:
- installation
- connection
- set-up
- parameter adjustment of the signal conditioning instrument VEGAMET 407 Z.
If you feel that any points in this data sheet are not adequately covered our technical sales or service departments will be pleased to assist.
Additional copies of this data sheet are freely available and are automatically supplied with quotations and purchases product.
Introduction
Product description
The signal conditioning instrument VEGAMET 407 Z is used for manifold applications for continuous level measurement.
VEGAMET 407 Z is integrated in a series 400 plastic housing.
A sensor (pressure transmitter or capacitive mea­suring electrode) can be connected via a two-core line to the signal conditioning instrument. This line is responsible for the power supply from the signal conditioning instrument to the sensor. The measur­ing currents are transmitted analog from the sensor to the signal conditioning instrument and evaluated.
The signal conditioning instrument can be calibrated and adapted to the measurement by the user via parameter adjustment.
These adjustments are made without additional facilities and tools via a 5-button keyboard integrated on the front panel.
Configuration of a signal conditioning instrument
MOD
+
-
STO
!
t
SIM
VEGAMET
407 Z
or
4-digit LC-display current output 0/4 … 20 mA voltage output 0 … 5 V voltage output 0 … 10 V
Fail safe relay Alarm LED
capacitive measuring electrode
pressure transmitter
Input Signal conditioning instrument Outputs:
50.0
%
Capacitive measuring electrode with oscillator
or
Pressure transmitter with oscillator
Optional auxiliary instruments e.g.: - Overvoltage arresters
- Indicating meters VEGADIS 171 (connection 0 … 20 mA)
- Auxiliary level switch VEGASEL ……
- Safety barrier type 145
Configuration of a measuring system
Signal conditioning instrument
VEGAMET 407 Z mounted into plastic housing of series 400
Technical Information
Technical data
Power supply Operating voltage value tolerance frequency
Standard 230 V AC +10 % –15 % 50 / 60 Hz Options 110 V AC
130 V AC +15 % –10 % 50 / 60 Hz 240 V AC 24 V AC 42 V AC +15 % –10 % 50 / 60 Hz 48 V AC 16 … 60 V DC
Power consumption approx. 6 VA or 4 W
Measuring data Supply voltage for capacitive
measuring electrode or pressure transmitter 24 V (max. 26 V) short-circuit proof, galvanically isolated Data transmission analog Connection cable 2-core, unscreened (standard line) Resistance per conductor max. 200 Valid measured values 2 … 22 mA Fault signal at < 2 mA; > 22 mA
Min. measuring distance 300 µA Indication LC-display 4-digit Current output Range 0 … 20 mA or 4 … 20 mA
Load max. 750
Galvanical separation to power supply unit and input
Resolution 0,05 % of range
Linearity error 0,05 % of range
Temperature error 0,06 % / 10 K of sensor Voltage output 1 Range 0 … 10 V, max. 1 mA
Galvanical separation to power supply unit and to input
Resolution 0,05 % of range
Linearity error 0,1 % of range
Temperature error 0,06 % / 10 K of sensor Voltage output 2 Range 0 … 5 V, max. 1 mA
Galvanical separation to power supply unit and to input
Resolution 0,05 % of range
Linearity error 0,1 % of range
Temperature error 0,06 % / 10 K of sensor Fail safe relay Relay data:
1 spdt floating
Contact material Ag CdO and Au plated
min. turn-on voltage 10 mV
switching circuit 10 µA
AC DC
max. turn-on voltage U = 250 V U = 60 V
switching circuit I = 2 A I = 1 A
max. breaking capacity S = 125 VA P = 54 W Operating Permissible operating temperat. –20°C … +60°C
conditions Storage and transport temperat. –20°C … +70°C Electrical Protection IP 40
protective measures Protection class II Mechanical Series Panel mounting, housing plastic ABS light grey
data Dimensions W = 53 mm, H = 127 mm, D = 143 mm
Weight approx. 700 g
Technical Information
127
110
58
4,8
143
22,6
8,7
15,8
2
(dimensions in mm)
Dimensional drawing
Galvanical separation
Transparent cover Plug-in socket
Holes ø 4,5 or thread M4
Block diagram
Input Mains
Current output Voltage outputs Fail safe relay
Measuring data input Power supply
Microcomputer control and outputs
Technical Information
Approvals
(for following measuring systems)
Approval as overfill protection acc. to
WHG
Pressure transmitters, approved for the following measuring systems
Type .............................................................................D33, D34, D35, for type A, F, G, N, K
D36, Type G, N, F, S063 D37, Type G, N, S052 D38, Type G, N
Oscillator ................................................................... E27, E27 B
Signal conditioning instrument .................................. VEGAMET 407 Z
Auxiliary level switch .................................................. VEGASEL 444, 441 B, 441 C
defined in test certificate no. ..................................... PA-VI 810.76
Capacitive measuring electrodes, approved for the following measuring systems
Type .............................................................................12.02, 12.12, 12.42 Ex, 12.72 Ex
22.02, 22.12
23.02, 23.12, 23.42 Ex, 23.72 Ex
25.02, 25.03, 25.12, 25.13
25.02 Ex, 25.03 Ex, 25.12 Ex, 25.13 Ex
26.02, 26.03, 26.12, 26.13
27.01, 27.11, 27.41 Ex, 27.71 Ex
32.04, 32.05, 32.14, 32.15
32.44 Ex, 32.45 Ex, 32.74 Ex, 32.75 Ex
42.04, 42.05, 42.14, 42.15
52.04, 52.05, 52.14, 52.15
Oscillator ................................................................... 117 A, 117/4 A, 117/4 A Ex
Signal conditioning instrument ................................... VEGAMET 407 Z
Auxiliary level switch ................................................. VEGASEL 444, 441 B, 441 C
defined in test certificate no. ...................................... PA-VI 870.15
If measuring systems acc. to the below approval are installed, the legal documents have to be observed.
Measuring systems for the use in hazardous areas must only be operated in conjunction with pressure transmitters or capacitive measuring electrodes in Ex-version and safety barrier type 145.
see
- Conformity certificate PTB-no. Ex-85.B.2038
- diagram page 7.
Technical Information
Approvals
(continued)
Approval as overfill protection acc. to the regulation for combustible liquids
VbF
Capacitive measuring electrodes, approved for the following measuring systems
Type..............................................................................12.02, 12.03, 12.12, 12.13
23.02, 23.03, 23.12, 23.13
27.00, 27.01, 27.10, 27.11
32.04, 32.05, 32.06, 32.07
42.04, 42.05, 42.06, 42.07
32.14, 32.15, 32.16, 32.17
42.14, 42.15, 42.16, 42.17
12.42 Ex, 12.43 Ex, 12.72 Ex, 12.73 Ex
23.42 Ex, 23.43 Ex, 23.72 Ex, 23.73 Ex
27.40 Ex, 27.41 Ex, 27.70 Ex, 27.71 Ex
32.44 Ex, 32.45 Ex, 32.46 Ex, 32.47 Ex
32.74 Ex, 32.75 Ex, 32.76 Ex, 32.77 Ex
25.02 Ex, 25.03 Ex
25.12 Ex, 25.13 Ex
Oscillator ................................................................... 117/4 A Ex
Signal conditioning instrument .................................. VEGAMET 407 Z
Auxiliary level switch ................................................. VEGASEL 444, 441 B, 441 C
defined in test certificate no. ...................................... PTB-no. III B/S 2032 F
and type approval....................................................... 01/PTB-no. III B/S 2032 F
Transducer
(capacitive measuring electrode or pressure transmitter) If the sensor is installed in hazardous areas, the special conditions of the conformity certificate must be observed.
Signal conditoning instrument
The signal conditioning instrument VEGAMET 407 Z must be generally installed outside hazardous areas (or special protective measures must be taken.
Measuring systems for the use in hazardous areas must only be operated in conjunction with pressure transmitters or capacitive measuring electrodes in
Ex-version and safety barrier type 145. See conformity certificate PTB-no. Ex-85.B.2038.
MOD
+
-
STO
!
t
SIM
VEGAMET
407 Z
Ex-area not Ex-area
Zone 0 Zone 1
Safety barrier type 145
VEGAMET 407 Z
50.0 %
Technical Information
18 17 16
15 14 13
N
L1
9
2 1
+ –
+
– +
5
7
+
1
Sensor 1
1
2 3
4 … 20 mA
8
6
18 17 16
15
13
9
2
5
7
1
8
6
14
Sensor 1
1
2 3
0 … 20 mA
-
+
Electrical connection
Installation regulations:
- The wiring between VEGAMET 407 Z and sensor
(capacitive measuring electrode or pressure transmitter) can be made with standard cable.
- In case of strong electromagnetic interferences, screened cable must be used.
The screening must be earthed at one sensor
end.
Signal conditioning instrument back view (type plate)
Plug-in socket with terminals
VEGAMET 407 Z
Selection of the current output
Alarm signals Fault-monitoring relay
Supply voltage (see data plate)
Voltage otuput 0 … 10 V Voltage otuput 0 … 5 V
Current output 0/4 … 20 mA
capacitive measuring electrode
pressure transmitter
Mounting instructions
14 13
VEGAMET
VEGAMET
15
14 13
15
N
L1
The plug-in base is provided with
- field terminals
- interconnection pins
- spacers for installation in series
- key coded For installation in series the interconnection
pins are the power supply connections and the distance sleeves ensure that adjacent instruments have a minimum gap of 5 mm between each other.
Remove the interconnection pins on the first plug-in socket.
Warning: Beware of high voltage on
power supply terminals.
Plug-in base
Spacers
Key code
Interconnecting pins for supply voltage
In case of single mounting remove the interconnec­tion pins and spacers, connect the supply voltage directly.
The key coded base prevents other series 400 instruments being inserted. Use adapter no. 040 002 for mounting on standard rail.
Operating surface
0407
Indication and operating elements
Measurements
Mode range
0.0
%
100.0
% Level 0 … 100 %
-10 % … 110 %
0 … 200 sec.
Adjustment in % or in mA
Alarm signal
Empty adjustment
Full adjustment
Integration time
Simulation
Password
(Pass­word)
MOD
+
-
STO
!
VEGAMET
407 Z
t
SIM
E1
E9
0 - -
0
Fault-monitoring LED-indication
Selection of the mode Cursor position Value (increase) Value (decrease)
Storing programmed data
-8.8.8.8
PARAMETER FIELD
Measurements
MODEFIELD
%
Operating surface
Operation
Set-up
- mounting socket
- connect capacitive measuring electrode or pressure transmitter with the mounting socket terminal 1 and 2, see page 8
- adjust the current output, see page 8
- check the connection and type plate push VEGAMET 407 Z onto mounting socket and fasten
- switch on power supply LED (green) voltage supply lights LED (red) fault signal lights fault monitoring relay remains de-energized software stage is indicated
- after approx. 2 sec. fault-monitoring LED extinguishes fault-monitoring relay is energized a meaningless figure is displayed
- program empty and full adjustment, see page 11
- if necessary, program integration time, see page 12 password, see page 13
(procedure)
MOD
MOD
+
-
MOD
STO
SIM
0.0 %
000.0
001.6
z.B.
% %
The VEGAMET 407 Z has 3 modes which can be obtained by scrolling the MOD-button:
Mode: 1. Measurement
2. Mode range
3. Parameter adjustment
Note that if no pushbutton is operated, after a period of 60 minutes the display resets to level measurement.
1. Measurement
2. Mode range
3. Parameter adjustment
Measurement: Level: %
Enquiry of the mode numbers in the MODE­FIELD. The parameters of the enquired modes can be indicated or modified in mode 3.
Programming of the parameters in the PARAMETER FIELD. The parameter of the respectively selected mode can be modified and stored with the STO­button. If no change should be realized, push the MOD-button. In both cases reset to mode 1.
Cursor position
Cursor position Value (increase)
Value (decrease) Storage
Parameter adjustment
Empty, full adjustment in %
The measurement range for level 0 % and 100 % is defined via the adjustment procedure.
When the vessel is partly filled or emptied the pro­gramming is as described on the right, however with previously determined %-values. The min. measuring range must correspond to a current
of > 300 µA.
Example
Full
• fill vessel
adjustment • select mode in MODEFIELD
• program level 100 % in PARAMETER FIELD
• then store with STO
Empty • empty vessel adjustment • select mode in MODEFIELD
• program level 0 % in PARAMETER FIELD
• then store with STO
The empty and full adjustments may be performed in any order.
%
100
0 %
Vessel full
Vessel empty
50
Empty, full adjustment in mA
The measuring current values are coordinated to the levels 0 % and 100 % with the adjustment.
The measuring currents are experience values or can be taken from the attached test certificate.
The procedure is used:
- for adjustment without rate of product level change
- for correction of previous adjustments (alarm E3 or E4)
- for adjustment without connection of a capacitive electrode or a pressure transmitter (alarm E2)
Example
Full • select mode in MODEFIELD adjustment • push button + and button MOD
simultaneously (data input for mA)
• program 18,75 mA in PARAMETER FIELD
• then store with STO
Empty • select mode in MODEFIELD adjustment • push button + and button MOD
simultaneously (data input for mA)
• program 5,28 mA in PARAMETER FIELD
• then store with STO
The empty and full adjustments may be performed in any order.
%
100
0
mA 18,75
5,28
Level 100 % ^ measuring current 18,75 mA
Level 0 % ^ measuring current
5,28 mA
50
Effects within the measuring range outside the measuring range
-10 % … 0 %...............100 % … 110 % < -10 % or >110 %
0/4 mA...............20 mA 22 mA
0 V..................10 V 11 V
0 V....................5 V 5,5 V
Example to end simulation ...................................... • push MOD–button again
Effects - Cancel the simulated output values
- Transmits the true output values
Parameter adjustment
Integration time
Application
- Where the product surface is agitated the system outputs may be stabilized by adjusting the inte­gration time.
Important notes: The integration time depends on the filling and emptying period of the vessel, i.e. integration time filling / emptying time. Mis-adjustment of the integration time may degrade output sensitivity.
Definitions
- range = 0 … 199 sec.
- (0 … 199 secs. corresponds to the definition in sec.) At 200 sec. effects a time period, the actual value is approx. 45 minutes.
- settings > 200 sec. are automatically limited to the max. value 200 sec.
Example
- integration time of e.g. 15 sec.
• select mode t in MODEFIELD
• program 15 sec. in PARAMETER FIELD
• then store with STO
Example..............to activate the simulation ……… • select mode SIM in MODEFIELD
• activate the simulation with button MOD
• increase or reduce the output with button + or button –
t
Simulation mode
In the simulation mode it is possible to test the measuring system over the whole measuring range independent of the process.
Button + increases and button – reduces all output values.
The longer the simulation button + and – are pressed the greater the rate of change.
Integration time is ignored during the simulation sequence.
t
fault-monitoring-LED lights fault-monitoring relay de-energizes
Parameter adjustment
Password
All parameters can be interrogated as previously described and their data indicated on the display.
Data input can be inhibited by programming the password.
Alarm signals
Indication Reason Result
Measuring results < - 10 % Input below minimum limit (flashing) without fail safe
> 110 % Input above maximum limit (flashing)
Error code E1 Connection cables reversed on with fail safe
short-circuit E2 Line break E3 Incomplete or incorrect adjustm. proced.
E4 (together with flashing mode segments) E8.1 … Fault during Current output = 22 mA
E8.4 data transfer (acc. to STO) Voltage output
= 11 V or 5,5 V
E9 Fault in the EEPROM-memory
Activate password .................................................... • select mode - - - - in MODEFIELD
• program figure 1 in PARAMETER FIELD
• then store with button STO
Adjust password ....................................................... • select the mode required for parameter adjust-
ment in the MODEFIELD, in the example mode t
• select data input, the keyword 0 - - 0 is displayed in the PARAMETER FIELD
• program
0407 as password
• then store with button STO
• the parameter adjustment of e.g. mode
t can be
made
(fail safe)
Alarm information
E1 E2
1
2
+
-
VEGAMET 407 Z
V
mA
4 … 20
12 … 24
2
1
2 1
Sensors Measuring line
Capacitive Pressure measuring transmitter electrode
Fault diagnosis related to E1 or E2
Signal conditioning instrument
Short-circuit
current > 22 mA
Check all connections
and measuring lines
Yes
No
Yes
No
Yes
No
Yes
No
Yes
No
Yes
No
Short­circuit
removed
?
Short-
circuit
removed
?
Short-
circuit
removed
?
Sensor defect
Short-circuit in the
connection cable
Separate sensor from
connection cable
Separate signal conditionining
instrument from connection cable
Line break
current < 2 mA
Check supply voltage
and measuring line
Signal conditioning
instrument defect
approx.
24 V
?
Alarm
E1 dis-
played?
Alarm
E1 is
displayed
?
Auswertgerät defekt
Fault or break on the
sensor (capacitive
measuring electrode or
pressure transmitter)
Cable break
Short-circuit the signal conditioning
instrument terminals
Remove short-circuit of the terminals on the
signal conditioning instrument, then short-
circuit terminal 1 and 2 on the sensor
Signal conditioning
instrument defect
E1 extinguishes
Signal conditioning
instrument defect
Help for fault diagnosis The measuring current stored during empty and full
adjustment can be displayed in the mode range by pushing the plus-button.
Application with …………………… - inaccurate measurements or
- alarm E3 or E4
Example: Measuring current of the previous
adjustment related to 0 % • select mode in MODEFIELD
• push plus-button, the adjustment current related to 0 %, is displayed in PARAMETER FIELD
• reset by pushing the MOD-button twice
Measuring current of the previous adjustment related to 100 % • select mode in MODEFIELD
• push plus-button, the adjustment current related to 100 %, is displayed in PARAMETER FIELD
• reset by pushing the MOD-button twice
Alarm information
E3
E4
= Adjustment had been carried with no or with too
small level change.
= The modes or %-values had been exchanged
during adjustment
or
Fault diagnosis related to E3
Fault diagnosis related to E4
Alarm
removed
?
Repeat the adjustment
(e.g. empty adjustment)
Repeat the 2nd part of the
adjustment (e.g. full
adjustment)
or carry out
adjustment in mA
see page 11
E3 or E4 and mode segment extinguish
E3 or E4 and
mode segment extinguish
Note
- %-value and
- mode
Note: min. measuring distance; %­value and mode
VEGA Grieshaber KG
Am Hohenstein 113 Postfach 11 42 D-77757 Schiltach Phone 0 78 36/50-0
Technical data subject to alterations
2.12 245 / März '94
Alarm information
E8.1
Fault diagnosis related to E 8.1
The empty adjustment data has not been transferred
Repeat empty adjustment, see page 11
Alarm E 8.1 extinguishes
O.K.
?
Auswertgerät defekt
E8.2
The full adjustment data has not been transferred
Repeat full adjustment, see page 11
Alarm E 8.2 extinguishes
O.K.
?
Auswertgerät defekt
E8.3
The integration time data has not been transferred
Repeat programming of integration time, see page 12
Alarm E 8.3 extinguishes
O.K.
?
Auswertgerät defekt
E8.4
The password data has not been transferred
Repeat activation or adjustment of password, see page 13
Alarm E 8.4 extinguishes
O.K.
?
Auswertgerät defekt
E9
Try a new set-up, see page 10
Alarm E 9 extinguishes
O.K.
?
Auswertgerät defekt
Fault (data loss) in the EEPROM-memory
Yes
No
Yes
No
Yes
No
Yes
No
Yes
No
Signal conditioning
instrument defect
Signal conditioning
instrument defect
Signal conditioning
instrument defect
Signal conditioning
instrument defect
Signal conditioning
instrument defect
Loading...