VEGA LOG571 User Manual

Operating Instructions
VEGALOG 571 CPU and carrier
on on
on
PC
on
1 2 3 4 5 6 7 8 9
10
571 CPU
VEGALOGVEGALOG
571 EA
VEGALOGVEGALOG
571 EP
VEGALOGVEGALOG
571 AR
!
!
!
!
BA
inin
outout

Contents

1 About this document
1.1 Function .............................
4
1.2 Target group ..........................
4
1.3 Symbolism used .......................
4
2 For your safety
2.1 Authorised personnel....................
5
2.2 Appropriate use........................
5
2.3 Warning about misuse ...................
5
2.4 CE conformity .........................
5
2.5 Environmental instructions ................
6
3 Product description
3.1 Conguration..........................
7
3.2 Principle of operation ....................
7
3.3 Operation ............................
8
3.4 Storage and transport ...................
8
4 Mounting
4.1 General instructions.....................
10
4.2 Carrier ..............................
10
4.3 Mount female multipoint connectors .........
11
4.4 Coding ..............................
11
5 Connecting to power supply
5.1 General connection instructions ............
14
5.2 Additional instructions for Ex applications .....
15
5.3 Wiring plan ...........................
16
6 Set up
6.1 Indicating and adjustment elements .........
19
6.2 Module card types......................
19
6.3 Setup requirements .....................
22
6.4 Start PACTware™ .....................
23
6.5 Creating a project ......................
24
6.6 Example projects.......................
25
6.7 Parameter adjustment ...................
26
7 Maintenance and fault rectication
7.1 Maintenance ..........................
30
7.2 Fault rectication .......................
30
7.3 Instrument repair .......................
31
2 VEGALOG 571 - CPU and carrier
Contents
31947-EN-060606
8 Dismounting
8.1 Dismounting procedure ..................
32
8.2 Disposal .............................
32
9 Supplement
9.1 Technical data.........................
33
9.2 Dimensions ...........................
35
VEGALOG 571 - CPU and carrier 3
Contents
31947-EN-060606

1 About this document

1.1 Function

This operating instructions manual has all the information you need for quick setup and safe operation. Please read this manual before you start setup.

1.2 Target group

This operating instructions manual is directed to trained, qualied personnel. The contents of this manual should be made available to these personnel and put into practice by them.

1.3 Symbolism used

Information, tip, note
This symbol indicates helpful additional information.
Caution: If this warning is ignored, faults or malfunctions can result. Warning: If this warning is ignored, injury to persons and/or serious damage to the instrument can result. Danger: If this warning is ignored, serious injury to persons and/or destruction of the instrument can result.
Ex applications
This symbol indicates special instructions for Ex applications.
l List
The dot set in front indicates a list with no implied sequence.
à Action
This arrow indicates a single action.
1 Sequence
Numbers set in front indicate successive steps in a procedure.
4 VEGALOG 571 - CPU and carrier
About this document
31947-EN-060606

2 For your safety

2.1 Authorised personnel

All operations described in this operating instructions manual must be carried out only by trained specialist personnel authorised by the operator. For safety and warranty reasons, any internal work on the instruments must be carried out only by personnel authorised by the manufacturer.

2.2 Appropriate use

VEGALOG 571 is a modular processing system for a wide range of applications, e.g. for level, process pressure and dierential pressure measurement.

2.3 Warning about misuse

Inappropriate or incorrect use of the instrument can give rise to application-specic hazards, e.g. vessel overll or damage to system components through incorrect mounting or adjustment.

2.4 General safety instructions

VEGALOG 571 CPU is a high-tech instrument requiring the strict observance of standard regulations and guidelines. The user must take note of the safety instructions in this operating instructions manual, the country-specic installation standards (e.g. the VDE regulations in Germany) as well as all prevailing safety regulations and accident prevention rules.

2.5 CE conformity

The VEGALOG 571 CPU(Ex) module card is in CE conformity with EMVG (89/336/EWG) and LVD (73/23/EWG).
Conformity has been judged according to the following standards:
l EMC:
- Emission EN 50081-2
- Susceptibility EN 50082-1
l LVD: EN 61010
VEGALOG 571 - CPU and carrier 5
For your safety
31947-EN-060606

2.6 Environmental instructions

Protection of the environment is one of our most important duties. That is why we have introduced an environment management system with the goal of continuously improving company environmental protection. The environment man­agement system is certied according to DIN EN ISO 14001.
Please help us full this obligation by observing the environ­mental instructions in this manual:
l Chapter "Storage and transport" l Chapter "Disposal"
6 VEGALOG 571 - CPU and carrier
For your safety
31947-EN-060606

3 Product description

3.1 Conguration
The scope of delivery encompasses:
l 19" module card VEGALOG 571 CPU l 19" carrier with integrated bus board l Female multipoint connectors with card guide, screws and
coded pins (optional)
l Documentation
- this operating instructions manual
- Ex-specic "Safety instructions" (with Ex versions)
- if necessary, further certicates
A VEGALOG 571 processing system consists of a CPU, one or several peripheral cards as well as a power supply unit which are inserted into the 19" carrier BGT LOG 571. CPU and peripheral card are designed as module cards in European size (DIN 41494) with 5 TE width (25.4 mm). The supply voltage of the cards with 24 VDCis provided e.g. via a power supply unit VEGASTAB 593. The carrier with a width of 84 TE and a height of 3 HE corresponds to the 19" standard format, however, has an integrated LOGBUS board for communication among the cards.
The maximum conguration of a VEGALOG consists of two carriers mounted above one another with one CPU, 31 peripheral cards and one power supply unit. With this conguration, up to 255 measurement loops can be set up.

3.2 Principle of operation

VEGALOG 571 is a modular processing system for a wide range of applications, e.g. for level, process pressure and dierential pressure measurement.
To suit the application and the individual requirements, VEGALOG 571 is put together using several module cards. A CPU card and dierent input/output cards are available which
are inserted into a 19" carrier.
To suit these applications, VEGALOG 571 powers the connected sensors and processes their analogue/digital measuring signals or switching commands. The peripheral cards take over the power supply as well as the processing of the measuring signals. The processing is carried out in the CPU through a special software consisting of function
Scope of delivery
Area of application
Physical principle
VEGALOG 571 - CPU and carrier 7
Product description
31947-EN-060606
components (FB), input components (EB) and output compo­nents (AB). The input components receive the measuring signals, the output components make them available via the hardware outputs of the peripheral cards or the CPU. The communication among the individual cards is carried out via an own bus system (LOGBUS).
On the input side, 0/4 20 mA current outputs or Probus PA inputs are available. On the output side, there are relay or current outputs. In addition, digital output cards for Ethernet,
Probus, Modbus, Interbus and RS232/ASCII are available.
Voltage is supplied by a 19" power supply unit type VEGASTAB. Detailled information on the voltage supply is
available in the "Technical data" in the "Supplement".

3.3 Operation

The operation of VEGALOG 571 is carried out via a PC which can be connected via the RS232 interface of the CPU. Asan alternative, connection via Ethernet and VEGACOM 558 is possible.
The adjustment software PACTwarewith the corresponding DTMs is installed under Windowsand ensures easy
conguration of measuring systems as well as parameter adjustment of connected VEGA sensors. For this purpose, PACTwareprovides a clear adjustment interface with menu structure, window technology and graphic support. In addition, online help is available which describes the available functions and parameter adjustment options. For earlier VEGALOG systems with CPU software 1.xx, the previous software VVO (VEGA Visual Operating) must be used for operation.

3.4 Storage and transport

Your instrument was protected by packaging during transport. Its capacity to handle normal loads during transport is assured by a test according to DIN EN 24180.
The packaging of standard instruments consists of environ-
ment-friendly, recyclable cardboard. For special versions, PE foam or PE foil is also used. Dispose of the packaging material via specialised recycling companies.
l Storage and transport temperature see "Supplement -
Technical data - Ambient conditions"
Power supply
Packaging
Storage and transport tem-
perature
8 VEGALOG 571 - CPU and carrier
Product description
31947-EN-060606
l Relative humidity 20 85 %
VEGALOG 571 - CPU and carrier 9
Product description
31947-EN-060606

4 Mounting

4.1 General instructions

The module cards of VEGALOG 571 can only be mounted into the 19" carrier BGT LOG 571. It is provided with a special bus board for data transmission between CPU and the individual peripheral cards (LOGBUS). The carrier is designed for mounting into a switching cabinet or 19" housing.
The plug position for the individual cards is individually selectable, the system saves the card positions when switch­ing on.
Note:
The plug positions must not be changed after the parameter adjustment because measurement loops that have already been set up would otherwise have to be recongured.

4.2 Carrier

By means of the plug connectors on the bus board, a xed pattern is created for the use of the modules. This ensures that each module card is plugged into the multipoint connector and also into its LOGBUS socket.
l Number of subunits (TE)
- 84 TE, thereof one 4 TE blind cover on module 1
l Width of the module cards
- 5 TE for CPU and peripheral cards
- 10 TE for VEGASTAB 593
l Number of module cards in the BGT LOG 571
- max. 16 pcs.(e.g. 1x VEGASTAB 693, 1x CPU and
13x peripheral cards)
A VEGALOG 571 in the maximum conguration consists of two completely equipped carriers which are connected to each other via a pluggable bus cable (see "Chapter Electrical connection"). Because the bus cable may not be lengthened, the two carriers must be mounted directly above one another.
Note:
In the following cases, it is recommended to mount a 19" ventilator to avoid a temperature increase in VEGALOG.
l If more than one carrier is placed above the other l If air cannot circulate in the area of the carrier
10 VEGALOG 571 - CPU and carrier
Mounting
31947-EN-060606
l With increased ambient temperatures

4.3 Mount female multipoint connectors

The carrier BGT LOG 571 is supplied completely assembled. To mount the individual module cards, modules must be provided in the requested positions. A module consists of:
l a female multipoint connector according to DIN 41612,
series F, 48-pole
l two xing screws l two coded pins l two guide rails
The female multipoint connector is available with the following connections:
l Wire-Wrap standard connection 1.0x1.0 mm l Plug connection 2 .8x0.8 mm l Termi-Point standard connection 1.6x0.8 mm l Soldering connection l Screw terminals 0.5 mm²
If the VEGALOG 571 is supplied completely with carrier and peripheral cards, the modules are completely mounted and voltage supply for the individual cards is already looped. In case of part or supplementary orders, the female multipoint connectors must be mounted in the requested position by means of the attached screws. Also the card guides must be plugged in the corresponding positions. To complete the setup, connect the 24 V supply voltage, the terminal assign­ment is stated in chapter "Connecting to power supply".
Tip:
Determine the position of the individual cards now and plug in the coded pins as described in chapter "Coding".

4.4 Coding

A mechanical coding system avoids later interchanging of the various module cards in the carrier.
The coding system consists of:
l two coded pins in the female multipoint connector l two holes in the male multipoint connector of the respective
component
The coded pins are attached to the module.
VEGALOG 571 - CPU and carrier 11
Mounting
31947-EN-060606
Equip the female multipoint connector with the two coded pins
according to the "Coding chart" and "Position of the coded pins". The function coding points out that these are module
cards of VEGALOG. The instrument coding is used to dierentiate between the individual module cards.
The male multipoint connectors of the individual module cards point to the holes suiting the pin positions.
Instrument coding Function coding
CPU card a1 c3
EP card a3 c3 and c23 with Ex
AA card a5 c3
AR card a7 c3
AT card a9 c3
EA card a11 c3
VEGACOM 557 a27 c3, c11
VEGACOM 558 a29 c11
VEGASTAB 593 -- --
o 9 o
z b d
o 1 o
a c
a1 a3
a5 a7
o 3 o
o 5 o
o 7 o
o11o
o13o
o15o
c3
o17o
o19o
o21o
o23o
o25o
o27o
o29o
o31o
a9 a11
a13
c11
c23
a23 a25 a27
3
1
2
Fig. 1: Positioning of the coded pins on the male multipoint connector 1 Instrument coding 2 Function coding 3 Ex coding
12 VEGALOG 571 - CPU and carrier
Mounting
31947-EN-060606
1
Fig. 2: Detail coded pin mounting 1 Coded pin
VEGALOG 571 - CPU and carrier 13
Mounting
31947-EN-060606

5 Connecting to power supply

5.1 General connection instructions

Always observe the following safety instructions:
l Connect only in the complete absence of line voltage l If overvoltage surges are expected, overvoltage arresters
should be installed
In hazardous areas you should take note of the appropriate regulations, conformity and type approval certicates of the sensors and power supply units.
The VEGALOG cards must be powered with extra low voltage (24 VDC) to keep protection class II. Detailled infromation to voltage supply is available in the "Technical data" in the "Supplement". When using a VEGASTAB 593, a reliable separation from the mains circuits is ensured according to DIN
VDE 0106, part 101.
If voltage supply is not taken over by VEGASTAB, the supply cable must be looped via the supplied NF lter (type: Schaner FN660-10/06). The supply cable after the lter must be wired
with a considerable distance to the signal cables to avoid couplings.
Note:
Sum the power consumptions of the individual cards and sensor and select a power supply unit with sucient power reserve.
Power supply is connected with standard cable acc. to the national installation standards.
To connect 4 … 20 mA instruments, standard two-wire cable without screen can be used. If electromagnetic interference is expected which is above the test values of EN 61326 for industrial areas, screened cable should be used.
When connecting Probus PA sensors, screened cable according to Probus specication must be used.
Please make sure that your installation is carried out according to the Probus specication. In particular, make sure that the termination of the bus is done with appropriate terminating resistors.
Note safety instructions
Take note of safety
instructions for Ex applications
Select power supply
Selecting the connection ca-
ble
14 VEGALOG 571 - CPU and carrier
Connecting to power supply
31947-EN-060606
Connect the cable screen on both ends to ground potential. In
the sensor, the screen must be connected directly to the internal ground terminal. The ground terminal outside on the sensor housing must be connected to the potential equal­isation (low impedance).
If potential equalisation currents are expected, the screen connection on the side of VEGALOG 571 CPU must be made via a ceramic capacitor (e.g. 1 nF, 1500 V). The low frequency potential equalisation currents are thus suppressed, but the protective eect against high frequency interference signals remains.
Take note of the corresponding installation regulations for Ex applications. In particular, make sure that no potential equal­isation currents ow over the cable screen. In case of grounding on both sides this can be achieved by the use of a capacitor or a separate potential equalisation.
The total capacitance of the cable and of all capacitors must not exceed 10 nF in Ex applications.

5.2 Additional instructions for Ex applications

Applications in the area according to the CENELEC Ex protective reguations and ElexV (Germany) zone 0 require the use of approved sensors.
For these applications, not the respective legal documents (test certicates, test notes and conformity certicates). These belong to the scope of delivery of the respecitive instrument.
These sensors must only be powered via an intrinsically safe circuit. With the EA card, the sensors must be connected via a safety barrier. The EP card is available in Ex version, no separate separating facility necessary.
Also note the legal documents of these instruments.
To mount, note the following:
l VEGALOG 571 as well as the used separting facilities
must be only used outside the Ex area.
l A separating wall must be provided between the con-
nection parts of intrinsically safe and non-intrinsically safe circuits so that there is a min. distance of 50 mm
l Only one sensor must be connected to each safety barrier
Cable screening and ground­ing
Select connection cable for Ex applica­tions
Mounting instructions
VEGALOG 571 - CPU and carrier 15
Connecting to power supply
31947-EN-060606

5.3 Wiring plan

3
1
2
Fig. 3: Connection with NF lter 1 Supply cables 2 NF lter 3 Signal cables
2
1
L (+) N (-)
2
6
12
20
24
22
10
16
18
30
28
32
dbz
14
26
8
4
Fig. 4: Terminal assignment VEGALOG 571 CPU 1 Supply voltage 2 The contacts (d/b/z 4 to d/b/z 32) are free
BGT/NF lter
CPU card
16 VEGALOG 571 - CPU and carrier
Connecting to power supply
31947-EN-060606
Coupling of the carriers
If the number of the available modules of a carrier (BGT) is not sucient, the VEGALOG 571 can be also completed with a second BGT.
The carriers are place above another and connected via the supplied ribbon cable. On the rear of the bus board there is an appropriate plug connection.
For the conguration with two carriers you have to set the following two switch positions according to below description.
l Hook switch for the termination resistor l Slide switch
Hook switch - closed
Slide switch - position M
l BGT 1
- Hook switch - closed
- Slide switch - position M
l BGT 2
- Hook switch - open
- Slide switch - position S
Switch position, one BGT
Switch position, two BGT
VEGALOG 571 - CPU and carrier 17
Connecting to power supply
31947-EN-060606
M S
M S
5
4
3
2
1
Fig. 5: Coupling of two carriers 1 Hook switch 2 Slide switch 3 BGT 1 (modules 1 … 16) 4 Bus cable 5 BGT 2 (modules 17 … 32)
18 VEGALOG 571 - CPU and carrier
Connecting to power supply
31947-EN-060606

6 Set up

6.1 Indicating and adjustment elements

1
2
3
on
PC
VEGALOGVEGALOG
571 CPU
!
Fig. 6: Indicating and adjustment elements VEGALOG 571 CPU 1 RS232 interface 2 LED for fault signal 3 LED for operating voltage
l LED fault signal [1]
- ashes in case of communication problems on the
LOGBUS
- lights during initialisation and during the self-test
- lights permanently during a hardware error
l LED operating voltage [2]
- lights when voltage supply is on
The module cards of the VEGALOG system have no own adjustment elements. All adjustment measures are carried out through the PC via the adjustment software PACTware™.

6.2 Module card types

The modular system of VEGALOG 571 consists of dierent, special module card types:
l CPU card
Description of the status LEDs
VEGALOG 571 - CPU and carrier 19
Set up
31947-EN-060606
l Input cards l Output cards l Communication cards for standard bus systems l Power supply cards for supply of the individual module
cards
The processor card is the centre of VEGALOG. It has the following functions:
l Communication handling among the individual cards l Creating and administrating of individual measurement
loops
l Calculating tasks such as adjustment, scaling, linearisa-
tion, dierential generation etc.
l Coupling to the PC via RS232 interface
The CPU is further used for detection of levels or for monitoring the switching on and switching otimes.
The CPU read cyclically measured values from the peripheral cards (e.g. with 30 measurement loop in the 300 ms cycle). These are compared with the programmed data, standardised and processed. The programmed data (conguration data, adjustment parameters etc.) are available in the EEPROM where they remain even in case of voltage loss. In the memory of the CPU, a process picture is created which is outputted to the peripheral cards via LOGBUS.
For backup, the programmed data can be read out any time via the RS232 interface and can then be saved on the PC.
EA card
Up to ten 0/4 … 20 mA instruments can be connected to the EA card (Eingang Analog, i.e. input analogue), e.g.:
l Capacitive probes l Hydrostatic pressure transmitters l Vibrating level switches l Conductive probes l Process and dierential pressure transmitters l Switching contacts (level signaller)
The inputs can be connected actively (sensor is powered by the EA card) or passively (sensor delivers current).
Within an EA card, mixed connection of active/passive inputs is permitted.
CPU card
Input cards
20 VEGALOG 571 - CPU and carrier
Set up
31947-EN-060606
EP card
The EP card (Eingang Probus PA, i.e. input PROFIBUS PA) is used as input card for Probus PA sensors of VEGA or other manufacturers. Up to max. 15 Probus PA sensors (max. 10 with Ex version) can be connected.
The EP (Ex) card recognises VEGA sensors on their serial number and assigns automatically a bus address. For instru­ments of other manufacturers, the Probus address must be assigned separately for each instrument.
The power supply of the sensors, the transmission of the sensor measuring signals as well as the parameter adjustmetn commands are carried out via the same bus cable.
AA card
The AA card (Ausgang Analog, i.e. output analogue) provides the processing results via up to ten analogue currents in the range of 0 … 20 mA. The scaling as well as the denition as rising or falling characteristics is carried out via the PC with
PACTware™.
Indicating instruments, recorders, controllers or PLC systems
are connected to these outputs.
AR card
The AR card (Ausgang Relais, i.e. output relay) provides ten relay outputs with oating contacts. Connected are, for example:
l Acoustic or optical signalling systems l Magnet valves l Contactors for pump control, etc.
The AR card is used to output switching, single or sum fault messages. The switching status of each relay is indicated via a two-colour LED in the front plate. This LED lights depending on the parameter adjustmetn of the relay (limit contact yellow or fail safe relay red). Each fail safe relay can be individually assigned to one or several measurement loops. The denition of the relay function, the switching points as well as the LED colour is carried out via the PC with PACTware™.
AT card
The AT card (Ausgang Transistor, i.e. output transistor) provides ten oating outputs via NPN trransistors. Binary input cards of PLC systems are connected.
The application possibilities and the signalling of the switching condition correspond to those of the AR card.
Output cards
VEGALOG 571 - CPU and carrier 21
Set up
31947-EN-060606
VEGACOM 558
The communication card VEGACOM 558 is an interface converter for Ethernet connection via TCP/IP. Hence the parameter adjustment of VEGALOG as well as reading out of measured values from any network PC is possible. It can be used as webserver and provides the measured values as HTML pages to all network participants. E-mails can be sent also with the actual measured values or event messages.
VEGACOM 558 can be also used for connection to Visual VEGA. Here all measured values and trend curves can be enquired via Ethernet and displayed on any PC.
VEGACOM 557
The VEGACOM 557 communication card is an interface converter (Gateway) for conversion of VEGA-specic data formats into standard protocols. It is used for connection of the VEGALOG system to a PLC or a PLC system. The communication card is available for the following protocols:
l Siemens S5 (3964R procedure) l Modbus (RTU and ASCII) l Interbus S l Probus FMS l Probus DP l VEGA-ASCII
The communication card can also be used to provide data of VEGALOG via RS232 to the visualisation software Visual VEGA. For this case, the communication card is also available
without interface function.
Adapter print
With the adapter card VEGACOM 557 AP, data of standard protocols (Probus, Interbus etc.) which are normally only available on the rear of the carrier, are led to the front plate.
VEGASTAB 593
The 19" power supply unit powers all cards of VEGALOG with 24 VDC. The sensors are also powered via the active inputs of
the input cards. The versions VEGASTAB 593-60 (24 V, 45 W) and VEGASTAB 593 (24 V, 120 W) are available.

6.3 Setup requirements

The adjustment software PACTwarewith the corresponding DTMs is installed under Windowsinstalliert and enables
easy conguration of measuring systems as well as parameter adjustment of connected VEGA sensors. For this purpose,
Communication cards
Power supply card
22 VEGALOG 571 - CPU and carrier
Set up
31947-EN-060606
PACTwareoers a clear adjustment surface with menu
structure, window technology and graphic support as well as an online help. For older VEGALOG systeme with CPU software 1.xx the previous software VVO (VEGA Visual
Operating) must be used.
All currently available VEGA DTMs are provided in a DTM Collection with the current PACTwareversion on CD. This CD is available from an authorised VEGA agency for a token fee. The basic version of this DTM Collection incl. PACTwareis also available as a free-of-charge download
from the Internet. The professional version also includes saving and printing of project documentation. A DTM licence for the respective instrument family can be purchased via the responsible VEGA agency.
Tip:
You nd further information in the operating instructions manual "DTD-Collection/PACTware" as well as in the online help.
Connect the PC via an RS232 cable (interlink modem) to the PC interface of the CPU card in the front. If your VEGALOG
has also a VEGACOM 557/558 you can connect the PC also to its RS232 interface. As an alternative the connection via Ethernet and VEGACOM 558 is also possible. This has the advantage that the adjustment can be carried out on any PC within the network.

6.4 Start PACTware

Start PACTwarevia the Windows start menu. For the rst log in, select the user "Administrator" and enter the password "manager". Please enter uppercase/lowercase letters cor­rectly. This password can be modied under the PACTwar­emenu item "Extras - User management". Here, you can assign a password for the users with limited rights.
Information:
To ensure that all instrument functions are supported, you should always use the latest DTM Collection. Furthermore all not described functions are included in older rmware versions. For many instruments, the latest instrument software can be downloaded from our homepage. The transmission of the instrument software is carried out via PACTwareand an individual interface. A description of the update sequence is also available in the Internet.
VEGALOG 571 - CPU and carrier 23
Set up
31947-EN-060606

6.5 Creating a project

Starting point for the adjustment of all types of eld devices is the partial or complete mapping of the instrument network in a PACTwareproject. For this purpose, PACTwareprovides an area, the instrument catalogue, in which all installed DTMs are displayed. Typically the DTMs have the same name as the instruments that are adjusted by them. In addition, PACTwareprovides a second area, the project window, in which the instrument network is mapped.
The easiest and quickest way to generate an instrument network in the project window of PACTwareis via the VEGA projectassistantt. It is available as manufacturer-specic extension module in all VEGA DTM Installation package and extends hence automatically the functions of PACTware™3.0. The automatic generation of projects by means of the VEGA projectassistantt, however, is only possible for instrument networks in which only VEGA instruments are used.
You open the VEGA project assistant from the PACTware menu board under "Project - VEGA project assistant". The window "VEGA project assistant" opens and you just have to select the requested interface for automatic generation of the project. Further information on the VEGA project assistant is available in the corresponding online help. The online help can be opened directly in the window "VEGA projekt assistant".
Fig. 7: Project assistant
To create a project in the project window, paste in the DTMs from the instrument catalogue - one DTM for each actually used instrument. The entry HOST-PC is the starting point for pasting in the DTMs. The requested DTM can be brought over
Generate a project automati­cally
Generate a project manually
24 VEGALOG 571 - CPU and carrier
Set up
31947-EN-060606
from the instrument catalogue to the project window with a double click or Drag and Drop. If the project window or the instrument catalogue are not visible, they can be activated in the menu bar under " View ".

6.6 Example projects

Project creation VEGALOG and Probus PA sensor
The following example shows a typical VEGALOG project with EP card and Probus sensors. We recommend using the
"VEGA project assistant", this considerably facilitates the project creation and errors during the address assignment of the VEGALOG module cards and the sensors are avoided. All existing cards are found automatically and are added to the project. Also all connected Probus sensors are automatically taken over into the project.
In case the planning is nevertheless carried out manually, e.g. when creating an oine project, the following DTMs must be added to the project tree:
1 First of all a driver must be selected by which the
communication via the PC can be carried out. Select the "VEGA Ethernet" DTM from the instrument catalogue. With this driver, the connection to VEGACOM 558 in the
VEGALOG 571 processing system is established.
When the "VEGA Ethernet" DTM in the project tree is selected, you can later adjust the IP address for the VEGACOM 558 module card in the PACTwaremenu
under "Device data - Add'l functions - Change DTM addresses". The implementation of this setting is only
possible if a suitable DTM (e.g. VEGACOM 558) has already been added to the project tree.
2 Finally the DTM "VEGALOG 571" must be added. This
DTM represents the VEGALOG 571 processing system. In
this DTM, measurement loops are created and processed later on.
When the "VEGALOG 571" DTM in the project tree is selected, you can later adjust the card addresses for the VEGALOG module cards in the PACTwaremenu under
"Device data - Add'l functions - Change DTM addresses".
The implementation of this setting is only possible if a corresponding DTM (e.g. VEGACOM 558) has already been added to the project tree.
Connection via VE­GACOM 558/Ethernet
VEGALOG 571 - CPU and carrier 25
Set up
31947-EN-060606
3 Then the DTMs for the individual VEGALOG module cards
must be added to the project tree. These are in this example: VEGALOG CPU, VEGACOM 558, VEGALOG
571EP.
4 The two DTM types "VEGALOG 571 EP" and "VEGALOG
571 EV" are VEGALOG module cards for connection of digitally communicating VEGA sensors. This means, corresponding sensor DTM can be added to these cards. Select the suitable sensor DTM from the device catalogue and transfer it to the project window.
If the sensor is already connected, it is possible to search for it with PACTware™. In this case, the VEGALOG 571 DTM must be in online mode (right mouse key ­"Connect"). Then the automatic search function can be started via the right mouse key - "Add'l functions -
Instrument search".
Fig. 8: Project VEGALOG 571 with Probus PA sensors

6.7 Parameter adjustment

After the project was created, the parameter adjustment of the instrument can be started. This is done via double click to the requested DTM in the project window or via the right mouse key by selecting "Parameter".
In the following procedure, adifference is made between oine and online mode.
26 VEGALOG 571 - CPU and carrier
Set up
31947-EN-060606
Oine mode
The project can be prepared, created and stored in oine mode without instruments being connected. Later these data can be transferred in online mode to the instruments now being ready for operation. Keep in mind that saving of these data on the hard drive is only possible in the Professional version with costs.
Online mode
In online mode, the instruments on which the parameter adjustment is to be carried out must be connected and ready for operation. By selecting the appropriate DTM with the right mouse key and the command "Connect", the online mode is set up for operation. After double clicking, connection is initiated which simultaneously checks the communication, the sensor type and additional parameters. If necessary, all parameters will be transferred automatically. Via the DTM menu item "Device data - Read data from device", all parameters of the sensor can be loaded anytime. All settings which are carried out now must be transferred afterwards to the instrument. This can be done via the DTM menu item
"Device data - Write data to device".
Fig. 9: DTM connection to VEGALOG 571
The most important thing is to creare the requested measurement loops. For this purpose, a comfortable assistant is available which is asking for the necessary settings. Select the DTM menu item "Measurement loops" and push the button "Create new measurement loop". The following applications are available:
l Level measurement l Process pressure measurement
Create measurement loops
VEGALOG 571 - CPU and carrier 27
Set up
31947-EN-060606
l Connection 0/4 20 mA instrument l Arithmetik l Temperature measurement l Universal
Depending on the selected application, a suitable sensor or the measuring principle and probable options will be enquired. The designation of the measurement loop with an individual name is made at the end of the assistant setup.
Fig. 10: Creating/modifying measurement loop
After creating the measurement loop you can carry out the adjustment, select a linearization or assign and congure relay/ current outputs.
When using the EP card, the project includes also all connected PA sensors. Via the same cable connection you have also access to these sensors to show e.g. the echo curve or carry out a false echo memory. With analogue 4 … 20 mA instruments, however, this direct access is not possible. In this case, each sensor must be connected individually, e.g. via a
VEGACONNECT.
Sensor parameter adjustment
Set up
28 VEGALOG 571 - CPU and carrier
31947-EN-060606
Fig. 11: DTM view, VEGAPULS 61 PA
Information:
Detailed expalantions to the parameter adjustmetn and project creation are available in the onling help of PACTwareand the DTMs. Also consult the operating instructions manual of the corresponding instrument for setup and correct parameter adjustment.
Set up
VEGALOG 571 - CPU and carrier 29
31947-EN-060606
7 Maintenance and fault rectication

7.1 Maintenance

When used as directed in normal operation, the module card VEGALOG 571 CPU is completely maintenance-free.
7.2 Fault rectication
VEGALOG 571 CPU oers maximum reliability. Nevertheless faults can occur during operation. These may be caused by the following, e.g.:
l Measured value of the sensor not correct l Voltage supply l Interference on the cables
The rst measures to be taken are checking the input/outout signal as well as processing failure messages. The diagnostic information are updated cyclically in a 5 sec. pattern.
PACTwarewith the suitable DTM oers comprehensive diagnostics options. The integrated online help oers you additional information. In many cases, these causes can be thus determined and faults can be rectied.
If these measures are not successful, you can call the VEGA service hotline in urgent cases under the phone no.
+49 1805 858550.
The hotline is available to you 7 days a week round-the-clock. Since we oer this service world-wide, the support is only
available in the English language. The service is free of charge, only the standard telephone costs will be charged.
The operating condition of the CPU and peripheral cards is displayed via the status LEDs in the front plate.
l LED failure message (red)
- flashes in case of communication problems on the
LOGBUS
- lights during initialisation and during the self-test
- lights permanently during a hardware error
l LED operating voltage (green)
- lights when voltage supply is on
Causes of malfunction
Fault rectication
24 hour service hotline
Fault messages via LED sta­tus indication
Maintenance and fault rectication
30 VEGALOG 571 - CPU and carrier
31947-EN-060606

7.3 Instrument repair

If a repair is necessary, please proceed as follows:
You can download a return form (23 KB) from our homepage
www.vega.com under: "Downloads - Forms and Certicates - Repair form".
By doing this you help us carry out the repair quickly and without having to call back for needed information.
l Print and ll out one form per instrument l Clean the instrument and pack it damage-proof l Attach the completed form and possibly also a safety data
sheet to the instrument
l Please request the address for the return shipment from
the VEGA agency serving you.
Maintenance and fault rectication
VEGALOG 571 - CPU and carrier 31
31947-EN-060606

8 Dismounting

8.1 Dismounting procedure

Warning:
Before dismounting, be aware of dangerous process con­ditions such as e.g. pressure in the vessel, high temperatures, corrosive or toxic products etc.
Take note of chapters "Mounting" and "Connecting to power supply" and carry out the listed steps in reverse order.

8.2 Disposal

The instrument consists of materials which can be recycled by specialised recycling companies. We use recyclable materials and have designed the electronic modules to be easily separable.
WEEE directive 2002/96/EG
This instrument is not subject to the WEEE directive 2002/96/ EG and the respective national laws (in Germany, e.g. ElektroG). Pass the instrument directly on to a specialised
recycling company and do not use the municipal collecting points. These may be used only for privately used products according to the WEEE directive.
Correct disposal avoids negative eects to persons and environment and ensures recycling of useful raw materials.
Materials: see "Technical data"
If you cannot dispose of the instrument properly, please
contact us about disposal methods or return.
Dismounting
32 VEGALOG 571 - CPU and carrier
31947-EN-060606

9 Supplement

9.1 Technical data

General data carrier BGT
Series 19" carrier for mounting in switching cabinet or
housing
Dimensions W = 482.6 mm (19 in), H = 132.5 mm (5.22 in),
D = 254 mm (10 in)
Weight approx. 1650 g (3.53 lbs)
Material Alumininium anodized
General data
Series 19" module card for BGT LOG 571 Dimensions W = 25.4 mm (1 in), H = 128.4 mm (5.06 in), D
= 166 mm (6.54 in)
Weight approx. 400 g (0.882 lbs)
Voltage supply
Supply voltage U
nom
= 24 VDC(18 36 V)
Power consumption
- CPU card max. 6 W
- EA card max. 11 W
- EP card max. 8 W
- AA card max. 9 W
- AD card max. 10 W
- AR card max. 6 W
- AT card max. 6 W
- VEGACOM 557 max. 6 W
- VEGACOM 558 max. 4 W
Fuse protection Pigtail fuse 1 A slow-blow
Electrical connection
Module card Multipoint connector according to DIN 41612,
series F, 48-pole (d, b, z) with coding hole
Module in the carrier BGT LOG 571 Suitable female multipoint connector according
to DIN 41612 with connection via standard connection technologies
Supplement
VEGALOG 571 - CPU and carrier 33
31947-EN-060606
RS232 interface
Quantity 1x on front plate Data transmission 9600 baud, 8 data bits, 1 stop bit, no parity Plug connection 9-pole D-SUB plug
Displays
LED displays
- Status indication operating voltage 1x LED green
- Status indication fault signal 1x LED red
Ambient conditions
Ambient temperature -20 +60 °C (-4 +140 °F) Storage and transport temperature -20 +80 °C (-4 +176 °F)
Electrical protective measures
Protection mounted in BGT LOG 571
- front side completely equipped or covers
IP 40
- Upper and lower side IP 20
- Wiring side IP 00
Protection class I (in carrier BGT LOG 571)
Overvoltage category II
Electrical separating measures
Reliable separation according to VDE 0106 part 1 between voltage supply, LOGBUS connection and RS232 interface
- Reference voltage 250 V
- Insulation resistance 2.3 kV
Supplement
34 VEGALOG 571 - CPU and carrier
31947-EN-060606

9.2 Dimensions

185mm (7 9/32")
3mm (
1
/8")
132,5mm (5
7
/
32
")
10,5mm (13/32")
465mm (18
5
/16")
19" = 482,6mm
84 TE = 426,72mm (16
3
/4")
258mm (10
5
/32")
7,5mm (
19
/
64
")
57mm
(2
1
/
4
")
1
2
3
Fig. 12: Dimensions 19" carrier BGT LOG 571 1 Carrier 1 2 Carrier 2 319" ventilator (optional)
100mm (3
15
/16")
162mm (6 3/8")
5,5mm (
7
/32")
9mm (
23
/64")
128,4mm (5
1
/16")
25,4mm
(1")
5 TE
on
PC
VEGALOGVEGALOG
571 CPU
!
Fig. 13: Dimensions VEGALOG 571 CPU
Supplement
VEGALOG 571 - CPU and carrier 35
31947-EN-060606
VEGA Grieshaber KG Am Hohenstein 113 77761 Schiltach Germany Phone +49 7836 50-0 Fax +49 7836 50-201 E-mail: info@de.vega.com
www.vega.com
ISO 9001
All statements concerning scope of delivery, application,
practical use and operating conditions of the sensors and
processing systems correspond to the information avail-
able at the time of printing.
© VEGA Grieshaber KG, Schiltach/Germany 2006
Technical data subject to alterations 31947-EN-060606
Loading...