VEGA KLD2-PL2-1PA User Manual

- PROFIBUS-PA output per EN 50 170/2 and IEC 61158-2;
31.25 kbit/s
- Installation in Zone 2 (KLD2-PL2-1.PA only)
- Up to 32 PROFIBUS PA I/Os can be connected to the segment
- Supply voltage supplied by Power Rail
- Nominal supply voltage 24 V DC
- Removable terminals and power rail
PROFIBUS-PA Power Link Module
PROFIBUS-PA Segment
1132143
-
Shield/PA
15
+
KLD2-PL(2)-1.PA
The Power Link Module forms a segment coupler with the KLD2-GT(2)-DP(R).xPA bridge station and can only operate with this component. The KLD2-PL-1.PA is in­stalled within a safe area and the KLD2­PL2-1-PA can be mounted within Zone 2. The Power Link Module therefore provides an instrinsically safe interface per IEC 61158-2. The Power Link supplies PROFIBUS-PA I/Os powered by the bus.
The data transmission between Power Link Module and bridge station KLD2-GT(2)­DP(R).xPA Master 1 results by Power Rail. Is the Power Link Module connected to Master 2,3 or 4 of the bridge station a wire Link for the data transmission has to be made between Power Link Module termi­nals and bridge station terminals.
The communication is seamless. The Po­wer Link Module does not have to be programmed.
The PROFIBUS-PA segment has a baud rate of 31.25 kbit/s in accordance with IEC 61158-2.
Note:
No external voltage have to be supplied to the Profibus PA segment terminals. This could lead to the destruction of the device.
Information on Installation of PROFIBUS PA can be taken from PNO PROFIBUS User Organisation Guideline.
Bus
Termination
Physical
Conversion
U
red
green
-
Shield/FE
+
302829
To Bridge Station KLD2-GT(2)-DP(R).xPA Power Power Rail Master channels 1 ... 4 Supply
FE
+
464748
-
Frontansicht
removeable terminals green
U
123 4 56 78 9 101112
13 14 15 16 17 18 19 20 21 22 23 24
LED green: Power
COM/ ERR PWR
LED red: Hardware Error
25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48
1
P000357E 01/01 02
Subject to reasonable modifications due to technical advances. Copyright Pepperl+Fuchs, Printed in Germany
Pepperl+Fuchs Group · Tel.: Germany (6 21) 7 76-22 22 · USA (3 30) 4 25 35 55 · Singapore 779 90 91 · Internet http://www.pepperl-fuchs.com
Flashing: Communications
removeable terminals green
Error, no activity on PROFIBUS-PA Segment Line
1
PROFIBUS-PA Power Link Module
KLD2-PL(2)-1.PA
Technical Data Power
Nominal voltage DC 20 V ... 35 V Ripple Current consumption 790 ... 400 mA
PROFIBUS-PA PROFIBUS-PA Nominal voltage U Maximum current I Terminator impedance 100 Ohm, integrated
S
S
Master channel
Baud rate 31.25 kbit/s for connection to KLD2-GT... Cable length min. 852 m at maximum output current and cable type A, 0.8 mm2 (AWG 18)
Galvanic Isolation
PROFIBUS-PA - Master channel PROFIBUS-PA - power supply Master channel - power supply All circuits - FE (terminal 46) Function isolation per EN 50 178, design isolation voltage is 50 V All circuits - screen/FF (terminals 1, 13) Function isolation per EN 50 178, design isolation voltage is 50 V
Conformity to Standards
Environmental conditions DIN IEC 60 721-2-1 1992 EMC NAMUR NE 21 1998
Isolation coordinates EN 50 178 1998 Fieldbus Standards IEC 61158-2 1993
Environmental Conditions per DIN IEC 721 Class 3K3 Ambient temperature 253 K ... 333 K (-20 °C ... +60 °C / -4 °F ... 140 °F) Storage temperature 233 K ... 358 K (-40 °C ... +85 °C / -40 °F ... 185 °F) Protection method per DIN 40 050 IP 20 High relative humidity 75 % Ambient conditions max. grime accumulation level 2 per IEC 664
Mechanical
Design Makrolon modular housings, flammability class per UL 94: V - 0 Installation Can be snapped onto a 35 mm DIN rail per DIN EN 50 022 or wall mounted Connectivity Adjustable, removable device terminals with a max. diameter of 2.5 mm2 (14 AWG) Weight about 600 g
Accessories
Power Rail, PR 05 Insert for standard rail per DIN EN 50 022, normal length is 500 mm Power feed module, KFD2-EB2.B supplies Power Rail with a voltage of DC 24 V and a max. current of 4 A Fieldbus Terminator, KMD0-FT-Ex closes the PROFIBUS-PA branch in the field. The KMD0-FT-Ex is connected to the last
Bridge station,
KLD2-GT(2)-DP(R).xPA
I/O Number, The max. combined current consumption of the connected I/Os must be lower I/O Current Consumption: than the nominal current IS of the segment coupler. The modulation current used by anI/O
Models:
KLD2-PL-1.PA Power Link Module KLD2-PL2-1.PA Power Link Module for installation within Zone 2
£
10 %
24 ... 26 V 400 mA
Function isolation per EN 50 178, design isolation voltage is 50 V Function isolation per EN 50 178, design isolation voltage is 50 V Function isolation per EN 50 178, design isolation voltage is 50 V
DIN EN 50 081-2 1994 EN 61 326 1999
ISA S 50.02 Part 2 1992
PROFIBUS-PA I/O. Bridge for PROFIBUS-DP (up to 12 Mbit/s)
to send data, does not need to be observed.
eff. eff. eff. eff. eff.
Dimensions
2
Removable terminals green
80
Power Rail
115
92,5
107
Adjustable extensions
Protective cap,
Removable terminals green
Subject to reasonable modifications due to technical advances. Copyright Pepperl+Fuchs, Printed in Germany
remove when power is supplied by Power Rail
Pepperl+Fuchs Group · Tel.: Germany (6 21) 7 76-22 22 · USA (3 30) 4 25 35 55 · Singapore 7 79 90 91 · Internet http://www.pepperl-fuchs.com
P000357E 01/01 02