VEGA FLEX52P User Manual

Operating Instructions
PROF I
BUS
PROCESS FIELD BUS
VEGAFLEX 51P and 52P (Profibus PA)
Level and Pressure
Contents
Please read this manual carefully, and also take note of country-specific installation standards (e.g. the VDE regulations in Germany) as well as all prevailing safety regulations and acci­dent prevention rules.
For safety and warranty reasons, any internal work on the instruments, apart from that in­volved in normal installation and electrical con­nection, must be carried out only by qualified VEGA personnel.
2 VEGAFLEX 51P and 52P

Note Ex area

Please note the approval documents (yellow binder), and especially the included safety data sheet.
Contents
Contents
Safety information ........................................................................ 2
Note Ex area ................................................................................ 2
1 Product description
1.1 Function ................................................................................. 4
1.2 Application features ............................................................. 5
1.3 Adjustment media ................................................................ 5
1.4 Profibus output signal .......................................................... 6
1.5 Type code ........................................................................... 10
1.6 Bus configuration ............................................................... 11
1.7 Technical data ..................................................................... 14
1.8 Approvals ........................................................................... 17
1.9 Data format of the output signal ........................................ 17
1.10 Dimensions ......................................................................... 18
2 Mounting
2.1 Installation instructions ...................................................... 20
3 Electrical connection
3.1 Connection – Connection cable – Screening ................... 23
3.2 Sensor address ................................................................. 27
3.3 Connection of the sensor .................................................. 29
3.4 Connection of the external indicating instrument ............ 30
4 Setup
4.1 Adjustment media .............................................................. 31
4.2 Adjustment with the adjustment module MINICOM ........ 32
4.3 Adjustment with the PC ...................................................... 38
5 Diagnostics
5.1 Simulation ............................................................................ 43
5.2 Function diagram ............................................................... 43
5.3 Error rectification ................................................................ 48
5.4 PA parameters .................................................................... 49
VEGAFLEX 51P and 52P 3

1 Product description

Product description

1.1 Function

High frequency microwave impulses are guided along a steel rope. When reaching the product surface, the microwave impulses are reflected. The running time of the im­pulses is processed by the integrated elec­tronics and outputted as level.
The sensors measure the levels of all kinds of solids. Density, conductivity, dust generation and dielectric constant of the product do not influence the measurement. Also, the chang­ing features of a solid do not influence the measured value.
Lime, cement, cereals, plastic granules, flour, gravel - VEGAFLEX microwave sensors solve difficult application problems in solids. The level is also detected reliably in products with varying moisture content or fluctuating dielectric constant. High, narrow vessels or steep material cones in which non-contact measuring principles did not deliver optimum measuring results, can be measured without problem with VEGAFLEX.
VEGAFLEX 51 and 52 differ mainly in the thickness of the measuring cable.
VEGAFLEX 51 has a cable with 4 mm diam­eter and is available up to a length of 10 m.
• Measuring range up to 20 m with low min. distance.
• Up to 32 sensors (Ex area: 8 sensors) can be connected via one two-wire cable.
• Two-wire sensor, supply and digital meas­uring signal via one two-wire cable.
• Unaffected by application conditions such as:
- dust and noise generation
- humidity changes
- varying products
- buildup
• Adjustment without vessel filling or empty­ing.
• Unaffected by vessel material, e.g. metal, concrete, plastic etc.
• Measuring cable or gravity weight must not be insulated from the vessel.
The cable of VEGAFLEX 52 has a diameter of 8 mm and can have a length of up to 20 m. Due to the stronger cable it is suitable for solids subjected to higher extracting forces.
4 VEGAFLEX 51P and 52P
Product description
1.2 Application features
Applications
Level measurement in solids.
Measurement also in vacuum.
All slightly conductive substances and all
products with a dielectric constant er > 1.7 can be measured.
Measuring ranges VEGAFLEX 51 0 … 10 m VEGAFLEX 52 0 ... 20 m
Rugged
High-resistance materials: PA, 1.4401.
Precise and reliable
Resolution 1 mm.
Unaffected by noise, steam, dust, gas
compositions and inert gas stratifications.
Unaffected by varying density.
Measurements under pressure up to
16 bar and at product temperatures up to 120°C.
Communicative
Integrated measured value display.
Optional display and adjustment module
separate from the sensor.
Adjustment from the PLC level.
Approvals
StEx Zone 10
Ex Zone 0
1.3 Adjustment media
Adjustment with the adjustment module MINICOM
With the 6-key adjustment module MINICOM (3.2 cm x 6.7 cm) the adjustment can be carried out in clear text dialogue. The adjust­ment module can be plugged into the VE­GAFLEX or into the external indicating instrument VEGADIS 50. It also possible to adjust VEGAFLEX from the external indicat­ing instrument VEGADIS 50.
Tank 1 m (d)
12.345
Pluggable adjustment module MINICOM
Adjustment with PC
The setup and adjustment of the VEGAFLEX sensors can be done on the PC with the adjustment program VVO (VEGA Visual Ope­rating) under Windows®. The software leads quickly through adjust­ment and parameter setting by means of pictures, graphics and process visualisations.
ESC
+
-
OK
The adjustment program VVO from VEGA makes the full range of functions of VEGA sensors accessible and, if necessary, can update the entire sensor software. For this reason, the adjustment program must be installed on a PC which is equipped with a Profibus Master Class 2 interface card (Softing) (see figure under "1.4 Profibus output signal").
VEGAFLEX 51P and 52P 5
Product description
The PC with the Profibus interface card can be connected directly at any location to the DP bus by means of the standard RS 485­Profibus cable.
The adjustment and parameter data can be saved with the adjustment software on the PC. On request, the adjustment can be also transferred to other sensors.
2
......
VEGALOG
VEGALOG
571 CPU
571 EA
1 ... 15
1 32
Adjustment with the PC and the standard cable RS 232 on the VEGALOG processing system
1.4 Profibus output signal
As a process automation bus, Profibus PA enables power supply over the bus. Up to 32 sensors can be operated on a shielded two­wire cable that carries both power supply and measuring signal. In Ex areas, up to ten sensors can be connected from the PA level to one two-wire cable (EEx ia).
Bus structure
The DP and PA bus consists of up to 126 master and slave participants. Data are al­ways exchanged from point to point, with the data traffic being exclusively controlled and checked by master devices. Communication is carried out according to the Token-Passing procedure. This means that the master hold­ing the token can contact the slaves, give instructions, enquire data and cause the slaves to receive and transmit data. After the work is done or after a predetermined time interval, the token is passed on by the mas­ter to the next master.
Master-Class 1
is the actual automation system, i.e. the proc­ess control computer or the PLC that en­quires and processes all measured values.
Master-Class 2
One or several Master-Class 2 can operate in a Profibus network. As a rule, Master-Class 2 devices are engineering, adjustment or visu­alisation stations. The VEGA adjustment soft­ware VVO (VEGA Visual Operating) operates as Master-Class 2 participant on the DP bus and can work on an engineering PC, on an adjustment PC or on the process control computer and can access any VEGA sensor on the PA level.
6 VEGAFLEX 51P and 52P
Product description
Profibus adjustment structure
In the Profibus environment, there are differ­ent adjustment concepts and adjustment tools which often differ considerably from manufacturer to manufacturer. From the us­ers point of view, a manufacturer-independ­ent adjustment program which could be operated directly on the Profibus DP, but also at a central point (e.g. the engineering station or the process control), would be ideal.
In the past, only the program "SIMATIC PDM", based on the HART® adjustment structure, could fulfil this wish. However, this program also has the limitations common to HART®. As with HART®, the availability of an instrument­specific database for a comprehensive ad­justment with PDM (Process Device Manag­ing) is a requirement. Otherwise, only the basic instrument functions such as adjust­ment will be available. In the PDM environ­ment, this instrument-specific database is called EDD (Electronic Device Description), in complete analogy to the HART® environ­ment which, except for the VEGA-HART instruments, also requires a DD (Device Description) for each sensor.
®
VEGAFLEX 51P and 52P 7
Product description
Adr. 21
SPS
Adr. 22
VVO
3
PA-
Adr. 23
Master-Class 1
Adr. 1
DP-Bus
Adr. 24
DP interface card as Master­Class 2 (e.g. Softing)
Adr. 10
3
Adr. 57
Segment coupler
Adr. 25 … 56
2
(max. 32 participants)
Adr. 58
Adr. 60
Adr. 59
Adjustment of the VEGAFLEX sensors from the process control via a Profibus interface card in the process control computer or in an additional PC. The adjustment software VEGA Visual Operating (VVO) accesses via the interface (interface card) the sensors bidirectionally.
8 VEGAFLEX 51P and 52P
Product description
Adjustment with adjustment module MINICOM
With the small (3.2 cm x 6.7 cm) 6-key ad­justment module with display in the sensor, the sensor-relevant adjustments can be car­ried out directly on the sensor.
Tank 1 m (d)
12.345
Detachable adjustment module MINICOM
The adjustment module can be plugged into the sensor or into the optional, external indi­cating instrument.
ESC
+
-
Tank 1 m (d)
12.345
OK
2
PA-Bus
ESC
+
-
OK
Adjustment with the SIMA TIC PDM ad­justment program
For adjustment of all essential functions of the VEGA sensor with the adjustment station SIMATIC PDM from Siemens, a so-called EDD is required. Without this EDD, only the basic functions such as min./max. adjustment or the integration time can be adjusted with the PDM adjustment program. Further impor­tant adjustment functions, such as input of measuring environment data or false echo storage, are not available without EDD. After integration of the EDD files in the Simatic PDM adjustment software, all important adjustment functions are accessible. If it is not at hand, the obligatory GSD (instrument master file) as well as the EDD (Electronic Device De­scription) necessary for PDM can be downloaded from the VEGA-Homepage (http://www.vega.com).
ESC
+
-
Tank 1 m (d)
12.345
OK
4
max. 25 m
Adjustment with detachable adjustment module. The adjustment module can be plugged into the sensor or the external indicating instrument VEGADIS 50.
The sensor can be adjusted with the adjust­ment module MINICOM and basic functions can be set. Beside the measuring conditions and the simulation mode, the Profibus ad­dress can also be adjusted and a false echo storage can be carried out, see "4.2 Adjust­ment with MINICOM".
VEGAFLEX 51P and 52P 9

1.5 Type code

The second figure of the type name, e.g. VEGAFLEX 5[1] distinguishes the instru­ments acc. to the stability of the cable.
The letter, e.g. VEGAFLEX 51[P] indicates the output signal: K stands for an analogue 4 20 mA output signal (compact instrument) V stands for a digital output signal (VBUS). P stands for a digital output signal with Profi­bus PA
VEGAFLEX XX P EXS.X G
G - Connection to segment coupler Profibus PA
Dust Ex approved
P - Digital output signal for connection to
Profibus PA
Type 51: Instrument series with 4 mm cable Type 52: Instrument series with 8 mm cable
Measuring technology (FLEX for guided microwave)
Product description
10 VEGAFLEX 51P and 52P
Product description

1.6 Bus configuration

The type of sensor you use depends on the process requirements and mounting condi­tions, as well as on the requirements of your control, regulative, or process control sys­tem.
VEGAFLEX 51P and 52P Profibus sensors are sensors for use in Profibus PA environ­ment. Profile 3 has been implemented in the sensors. A measuring system consists of one or several sensors, one or several seg­ment couplers and one DP master computer, such as e.g. a S7 PLC with Profibus interface or a process control system with Profibus DP-Master-Slot. The processing unit, e.g. the PLC, evaluates the level-proportional, digital measuring signals in a number of evaluation routines and puts them to use process-spe­cifically.
On the following two pages you will find a schematic of the bus configuration.
The automation system as Master-Class 1 takes over the complete bus control. It reads out all signals cyclically and, if necessary, gives instructions to the participants (e.g. sensors). In addition, further master systems (e.g. visualisation systems or adjustment tools) can be connected to the DP bus. These systems operate as so-called Master­Class 2 participants. Like the Master-Class 1 system, they can read out signals, give in­structions and operate in acyclical mode.
A DP bus does not allow power supply via signal cable, whereas the PA bus does. Both, DP and PA, require at least one screened two-wire cable. The DP bus can additionally have up to 8 cores (screened), some of which can be supply cables.
Each participant on the bus must have an address. The addressing covers both bus levels. A Profibus DP system can have max. 126 participants, including all participants on the PA level. In practice, each Master-Class 1 computer gets address 1 and the Master­Class 2 computers address 10 … 20. As a rule, the slaves or participants get the ad­dresses 21 … 126. On the Profibus PA level, max. 32 sensors are possible on one PA segment coupler.
Ex environment
In Ex environment, intrinsically safe (EEx ia) PA sensors are used with Ex segment cou­plers. Generally, the number of PA sensors on a segment coupler (Ex or non Ex) de­pends on the current requirement of the sensors and on the current supplied by the segment coupler. Segment couplers for EEx ia environment provide 90 … 110 mA. The number of sensors results from the sum of:
- the basic current intake of all sensors
- plus 9 mA communication signal
- plus the leakage currents of all sensors
- plus a recommended current reserve (approx. 10 mA)
The min. basic current has been set at 10 mA according to the Profibus specification. VEGA Profibus sensors constantly consume a basic current of 10 mA and operate without leakage current requirement, so that in Ex environment, up to ten VEGA sensors can be operated on one segment coupler.
VEGAFLEX 51P and 52P 11
Address 1
Product description
28
Segment coupler
PLC/DCS
Address
21...52
3
2
Profibus PA
21 22 52
1 32 sensors (Ex: 1 10)
Master-Class 2 interface card
12 VEGAFLEX 51P and 52P
Address 10
Product description
Profibus DP
Segment coupler
Address
53...84
M
Address
85
3~M
Address
86
2
Profibus PA
53 54 84
Address
87
1 32 sensors
VEGAFLEX 51P and 52P 13
Technical data

1.7 Technical data

Power supply
Supply voltage 9 … 32 V DC) (output voltage UO of the segment dependent on the segment coupler used coupler) see PA specification, e.g.
- non Ex e.g. 22 V DC (nominal voltage of the segment
- Ex 13.5 V DC nominal voltage of the segment
Current consumption constant 10 mA (no leakage current output) Cable load dependent on the segment coupler, see
Measuring range
VEGAFLEX 51 0.3 10 m VEGAFLEX 52 0.3 20 m
Output signal
digital (Profibus) two-wire technology:
Integration time 0 999 seconds (adjustable)
coupler) max. 32 sensors on one two-wire cable
coupler max. 10 sensors on one two-wire cable (typical 8 sensors)
technical data of the segment couplers and Profibus specification
the digital output signal (meas. signal is modulated onto the power supply and is further processed in the PLC or in the process control
Adjustment
- adjustment software VEGA Visual Operating on Master-Class 2 PC
- adjustment module MINICOM in the sensor or in the external indicating instrument (optional)
- process adjustment interface PACTwareTM (VVO as subprogram)
- SIMATIC PDM in conjunction with Electronic Device Description (EDD)
Accuracy
1)
(under reference conditions acc. to IEC 770 - relating to the max. measuring range)
Linearity error < 0.1 % Temperature drift 0.015 %/10 K Characteristics linear Deviation in characteristics including
linearity, reproducibility and hysteresis (determined acc. to the limit point method) better than 0.05 %
Average temperature coefficient of the zero signal 0.06 %/10 K Resolution general max. 1 mm Resolution of the output signal 0.005 % or 1 mm
1)
Similar to DIN 16 086, reference conditions according to IEC 770, e.g. temperature 15°C 35°C; moisture 45 % 75 %; pressure 860 mbar 1060 mbar
3)
The adjustment time (also actuating time, response time or adjustment period) is the time the sensor requires to output the correct level (with max. 10% deviation) after a quick level change.
14 VEGAFLEX 51P and 52P
Technical data
Characteristics
Min. span between full and empty adjustment
- digital output signal 10 mm
Adjustment time
2)
> 1 s (depending on the parameter setting) Measuring range begin 300 mm below the seal surface Measuring range end upper edge of the gravity weight or
the cable loop
Ambient conditions
Vessel pressure -1 … 16 bar Ambient temperature on the housing -40°C … +60°C Process temperature -40°C … +120°C Storage and transport temperature -60°C … +80°C Protection IP 66/IP 67 (meets both protections) Protection class
- two-wire sensor II Overvoltage category III Max. tensile load
- cable ø 4 mm 5 KN
- cable ø 8 mm 20 KN
Ex technical data
StEx Zone 10 Ex Zone 0 The permissible operating data of VEGAFLEX sensors for StEx areas are stated in the certificate.
Process connections
VEGAFLEX 51 and 52 G 11/2 A, 11/2" NPT
chromized steel or 1.4301 (stainless steel)
Connection cables
Two-wire sensors power supply and signal via one
Wire cross-section generally 2.5 mm
two-wire cable
Ground connection max. 4 mm
2
2
Cable entry 2 x M20 x 1.5 (cable entry 5 9 mm)
Materials
Housing PBT (Valox) or Aluminium (powder-coated) Cable 1.4401 (stainless steel, 316) or
galvanized steel/PA coated
VEGAFLEX 51P and 52P 15
Product description
CE conformity
VEGAFLEX sensors meet the protective regulations of EMC (89/336/EWG) and NSR (73/ 23/EWG). Conformity has been judged acc. to the following standards: EMC Emission EN 50 081 - 1: 1992
Susceptibility EN 50 082 - 2: 1995
NSR EN 61 010 - 1: 1993
Display indication
Display scalable analogue and digital
display of measured values (option) An external measured value display powered by the sensor can be mounted at a distance of up to 25 m from the sensors.
Signal output
Signal output digital output signal in two-wire technology
(Profibus)
Two-wire technology: The digital Profibus output signal (measuring signal) is superimposed on the power supply and further processed in the signal conditioning instrument or in the processing system.
16 VEGAFLEX 51P and 52P
Product description

1.8 Approvals

VEGAFLEX sensors are approved for StEx Zone 10.
Please note the attached approval documents if you want to use a sensor in Ex environment.

1.9 Data format of the output signal

Byte4 Byte3 Byte2 Byte1 Byte0
Status Meas. value (IEEE-754 format, see below)
Status byte:
The status byte corresponds to the profile 3.0 "Profibus PA Profile for Process Control De­vices" coded. The status "Meas. value OK" is coded as 80 (hex) (Bit7 = 1, Bit 6 0 = 0).
Measured value:
The meas. value is transferred as 32 Bit floating point number in the IEEE-754 format.
Byte n Byte n+1
Bit Bit Bit Bit Bit Bit Bit Bit Bit Bit Bit Bit Bit Bit Bit Bit
7654321076543210 VZ 27262524232221202-12-22-32-42-52-62
Sign
Exponent Mantissa
-7
Byte n+2 Byte n+3
Bit Bit Bit Bit Bit Bit Bit Bit Bit Bit Bit Bit Bit Bit Bit Bit
7654321076543210
2-82-92
-102-112-122-132-142-152-162-172-182-192-202-212-222-23
Mantissa Mantissa
Formula: Meas. value = (-1)VZ 2
Examples: 41 70 00 00 (hex) = 0100 0001 0111 0000 0000 0000 0000 0000 (bin)
Meas. value = (-1)0 2
(Exponent - 127)
(130 - 127)
(1 + 2-1 + 2-2 + 2-3)
(1 + Mantissa)
= 1 • 23 (1 + 0.5 + 0.25 + 0.125) = 1 8 1.875 = 15.0
VEGAFLEX 51P and 52P 17
1.10 Dimensions
VEGAFLEX 51
Plastic housing Aluminium housing
201
10˚
101
215
185
Product description
25 116
322
182
165
Cable ø 4 mm uncoated 125 mm Cable ø 4 mm coated 250 mm
SW 55
G 1½ A
244
90
25
70
ø 4
L
155
ø 8
8
ø 20
370
205
EXD connec­tion housing
268
SW 55
G 1½ A
L
ø 8
Adjustment module MINICOM Cable loops
Tank 1 m (d)
12.345
-
ESC
+
OK
32,5
25
70
ø 4
155
8
ø 20
67,5
74
Adjustment module to be plugged into the series 50 sensors or into the external indicat­ing instrument VEGADIS 50
Cable - steel
18 VEGAFLEX 51P and 52P
Cable - plastic coated
Product description
VEGAFLEX 52
Plastic housing Aluminium housing
201
215
185
10˚
322
182
165
345
L
SW 64
G 1½ A
101
370
90
25
80
ø 8
205
EXD connection housing
25 116
368
SW 64
G 1½ A
L
25
80
ø 8
250
Cable ø 8 mm uncoated 200 mm Cable ø 8 mm coated 400 mm
ø 12
ø 40
15
ø 12
15
ø 40
VEGAFLEX 51P and 52P 19
250

2 Mounting

Mounting

2.1 Installation instructions

Lateral load
Make sure that the measuring cable is not subjected to strong lateral forces. Mount VEGAFLEX to a position in the vessel where no interfering influences from e.g. stirrers, filling openings etc., can occur.
Lateral load
Extraction forces
In case of strong extraction forces, e.g. dur­ing quick emptying or settling of solids, high tensile loads can occur.
When such an installation position is neces­sary, the cable should not be anchored but only equipped with a gravity weight, so that the cable can more easily follow the product movements.
Shortening the measuring cable
The cable can be shortened later as re­quired. Loosen the three set screws on the gravity weight (hexagon) and remove them. Pull the cable out of the gravity weight.
To avoid fraying the steel cable during cut­ting, you have to tin the cable around the cutting position with a soldering iron or torch, or wrap the cable tightly with wire or insulat­ing tape. Shorten the cable with a metal cut­ting saw or a cutting wheel to the desired length.
In case of insulated cables with gravity weight, a certain length of insulation should be removed (VEGAFLEX 51: 45 mm; VE­GAFLEX 52: 60 mm). In cable loops, the insulation must remain on the cable.
After shortening, reinsert the cable (see "4.2 Adjustment with adjustment module MINI­COM").
L
Make sure that the vessel top can support the max. tensile load.
Pressure
In case of gauge or low pressure in the ves­sel, the mounting boss should be sealed on the thread. Use the attached seal ring. Check if the seal ring is resistant against the con­tained medium.
20 VEGAFLEX 51P and 52P
Shortening the measuring cable
Mounting
Cable entries
When mounting outdoors, on cooled vessels or in humid areas where cleaning is done e.g. with steam or high pressure, the seal of the cable entry is very important.
Use cable with a round conducting cross­section and tighten the cable entry. The cable entry is suitable for cable diameters of 5 mm to 9 mm.
Moisture from outside
To avoid moisture ingress, the electrical con­nection cable should be looped downward behind the cable entry so that rain and con­densation water can drain off.
This is mainly valid for mounting outdoors, in areas where humidity is expected (e.g. by cleaning processes) or on cooled or heated vessels.
If this happens, anchor the cable. When straining the cable, avoid high cable tension. In our price list, you will find a spring (as accessory) which prevents overloading of the cable.
Please note that in solids, strained cables must be able to resist strong forces. In case of strong extracting forces, the cable should not be anchored. Please note the paragraph "Extracting forces".
Cable electrode in solids
Buildup
Generally, buildup on the cable will cause only slight changes of the measured value. If strong buildup on the cable is expected, the use of insulated cable is recommended. The higher surface quality prevents buildup.
Abrasion
In very abrasive products, e.g. in loose
Moisture
Anchoring
In general, the measuring result will be no­ticeably influenced if the gravity weight comes into contact with the vessel wall. De­pending on the kind of solid, the installation or the kind of filling, the cable can "float" in spite of the gravity weight. The solid can push the
chippings, use a measuring cable without insulation.
Socket
Sockets cause strong interfering reflections. Therefore avoid socket mounting. If this is not possible, choose the flattest socket possible and use a socket with a diameter of at least 600 mm.
cable to the vessel wall or to the top, causing incorrect measured values.
VEGAFLEX 51P and 52P 21
Mounting
Material cone
When selecting a mounting location for VEGAFLEX in the vessel, please remember that material cones can form in solids, caus­ing inaccurate measuring results. We recom­mend selecting a mounting location where the cable detects an average value of the mate­rial cone.
d 6
d
d 6
VEGAFLEX should be installed at a spot that takes the filling and emptying apertures of the vessel into consideration. To compensate measuring errors caused by the material cone, you should install the cable at a dis­tance of d/6 from the vessel wall or vessel installation. In any case keep, a min. distance of 300 mm.
d
3
10
d
d
1 Emptying 2 Filling opening 3 VEGAFLEX
22 VEGAFLEX 51P and 52P
1
2
Electrical connection

3 Electrical connection

3.1 Connection – Connection cable
– Screening
Safety information – Qualified person­nel
Instruments which are not operated with protective low voltage or DC voltage must be connected only by qualified personnel. This also applies to the configuration of measuring systems planned for Ex environment.
As a rule, do all connecting work in the com­plete absence of line voltage. Always switch off the power supply before you carry out connecting work on the sensors. Protect yourself and the instruments.
Connection cables and bus configura­tion
Very often "Electromagnetic pollution" by electronic actuators, energy lines and emit­ting systems is so considerable that the two­wire cable should be screened.
We recommend the use of screened cable. This screening also guards against future sources of interference. The screening should be applied only to one sensor end (fig. 3.1 a). It is better if the screens are earthed on both ends. However, it must be certain that no earth compensation currents flow via the sensor cable screens (fig. 3.1 b). Earth com­pensation currents can be avoided by con­necting the cable screen (in case of earthing on both sides) on one earthed side (e.g. in the switching cabinet) via a capacitor (e.g.
0.1 µF; 250 V AC) to earth potential. Use a very low impedance earth connection (foun­dation, plate or mains earth). In dust-Ex ap­plications the screen should be on one end. Potential losses can be caused by earthing on both ends.
Note the Profibus specification. The connec­tion cables must be specified for the ex­pected operating temperatures in the plant and must have an outer diameter of 6 12 mm, to ensure the seal effect of the cable entry on the sensor.
For power supply and bus communication, a two-wire cable acc. to the Profibus specifica­tion (up to max. 2.5 mm2 cross-section area of conductor) is used. The electrical connec­tion on the sensor is made by spring-loaded terminals.
In a laboratory setup, a Profibus system will also work with standard, unshielded two-wire cable. In practice however, an automation network and bus system can only be pro­tected reliably against electromagnetic inter­ference with screened cable. Acc. to the Profibus specification (IEC 1158-2), screened and twisted cables are prescribed.
All participants are connected in one line (serially). At the beginning and end of the bus segment, the bus is terminated by an active bus termination. On the DP bus level, most participants already have a bus termi­nation implemented. With more than 32 par­ticipants on the DP level, a so-called repeater must be used to open and combine another DP level with a max. of 32 additional partici­pants. On the PA bus branch of the segment coupler, the PA radar sensors work also with max. 32 participants (Ex max. 10 partici­pants).
A PA sensor can work only in conjunction with a Profibus DP system, to which a Profibus PA subsystem is connected. A PA Profibus par­ticipant must consume min. 10 mA supply current.
VEGAFLEX 51P and 52P 23
Electrical connection
Earthing on one sensor end
Processing
Earthing on both ends (on the processing unit via potential separating capacitor)
Fig. 3.1 a
³ 0.1 µF 250 V AC
Processing
In dust-Ex applications the screening should only be made on one side. Due to potential difference earthing on both sides is not al-
Fig. 3.1 b
lowed.
24 VEGAFLEX 51P and 52P
Electrical connection
Connection cable and cable length
Connection cables must correspond to the Profibus specification and the FISCO model. The sensor cable must be in conformity with the values of the reference cable acc. to IEC 1158-2:
0.8 mm2; R Z
= 80 120 W; damping = 3 dB/km;
31.25kHz
C
asymmetric
The max. cable length first of all depends on the transmission speed:
up to 32 kbit/s: 1900 m Profibus PA up to
94 kbit/s: 1200 m Profibus DP
up to
188 kbit/s: 1000 m Profibus DP
up to
500 kbit/s: 500 m Profibus DP
up to
1500 kbit/s: 200 m Profibus DP
up to
12000 kbit/s: 100 m Profibus DP
The distributed resistance of the cable, in conjunction with the output voltage of the segment coupler and the current requirement (VEGAFLEX 10 mA) or the voltage require­ment (VEGAFLEX 9 V) of the sensors, deter­mines the max. length of the cable.
In a practical application of a PA bus branch, the max. length of the cable is also deter­mined (beside the required supply voltage and max. current consumption of all partici­pants on the PA bus branch) by the bus structure and the type of segment coupler used.
= 44 W/km;
DCmax.
= 2 nF/km.
Ground terminal
The electronics housings of the sensors have a protective insulation. The ground terminal in the electronics is galvanically connected with the metallic process connection. For sensors with a plastic thread as process fitting, the sensor grounding must be made by a ground connection to the outer ground termi­nal.
Screening
According to the Profibus specification screening should be applied to both ends. To avoid potential equalisation currents, a po­tential equalisation system must be available in addition to the screening.
According to specification, we recommend the use of twisted and screened two-wire cable, e.g.: SINEC 6XV1 830-5AH10 (Sie­mens), SINEC L26XV1 830-35H10 (Siemens), 3079A (Belden).
Alternatively, when grounding at both ends in non-Ex areas, the cable shielding can be connected on one ground side (in the switch­ing cabinet) via a capacitor (e.g. 0.1 µF; 250 V) to the ground potential. Make sure that the ground connection has the lowest possible resistance (foundation, plate or mains earth).
The cable length results from the sum of all cable sections and the length of all stubs.
Profibus P A in Ex environment
The length of the individual stubs must not exceed the following lengths: 1 12 stubs 120 m (Ex: 30 m) 13 18 stubs 60 m (Ex: 30 m) 19 24 stubs 30 m (Ex: 30 m)
When used in Ex area, a PA bus with all con­nected instruments must be carried out in intrinsically safe protection class "i". Four-wire instruments requiring separate supply must at least have an intrinsically safe PA connec-
More than 24 stubs are not permitted, whereby each branch longer than 1.2 m is
tion. VEGA sensors for PA-Ex environment are generally "ia two-wire instruments.
counted as a stub. The total length of the cable must not exceed 1900 m (in Ex version 1000 m).
VEGAFLEX 51P and 52P 25
Electrical connection
In the so-called Fieldbus Intrinsically Safe Concept (FISCO), the general conditions for an Ex safe bus configuration have been laid down. Therein the participants and the bus cables with their electrical data have been determined, so that the linking of these com­ponents always meets the Ex requirements. A more time-consuming Ex calculation is therefore not necessary. You can build your Ex bus according to the IEC standard 1158-
2.
The Ex segment coupler delivers a controlled power supply to the PA bus. All other compo­nents (field instruments and bus terminators) are only consumers. A field instrument must consume at least 10 mA. Ideally, an individual sensor should not consume more than 10 mA, so that the number of instruments can be as large as possible.
VEGA PA sensors, whether Ex or non Ex, consume a constant current of 10 mA. Ac­cording to the Profibus specification, this is the minimum participant current. With VEGA sensors it is therefore possible to connect 10 sensors (also in Ex environment) even with a limited energy supply from the Ex segment couplers.
Watch out for potential losses
Due to potential losses, earthing on both sides without a potential equalisation system is not allowed in Ex applications. If an instru­ment is used in hazardous areas, the re­quired regulations, conformity and type approval certificates for systems in Ex areas must be noted (e.g. DIN 0165). Please also note the approval documents with the safety data sheet attached to the Ex sensors.
Ex protection
If an instrument is used in hazardous areas, the required regulations as well as the dust­Ex certificates of VEGAFLEX for systems in dust-Ex areas must be noted.
Electrical data of the cables
R
DC
No. of A in Z cores mm
2
31.25kHz
C in Damping Screen nF/km
SINEC 6XV1 44 W/km 2 0.75 100 W < 90 < 3 dB/km Cu braiding 830-5AH10 +/- 20 W 39 kHz (Siemens)
SINEC L26XV1 44 W/km 2 0.75 100 W < 90 < 3 dB/km Cu braiding 830-35H10 +/- 20 W 39 kHz (Siemens)
3079A 105 W/km 2 0.32 150 W 29.5 < 3 dB/km Foil (Belden) 39 kHz
26 VEGAFLEX 51P and 52P
Electrical connection
1
2
4
8
16
32
64
128
8765 4
3
2
1

3.2 Sensor address

In a Profibus system composed of Profibus DP and Profibus PA subsystem, each partici­pant must have a unique address. Each participant, whether master or slave, is accessed by means of its own address in the bus system. The address of a partici­pant, whether on DP or PA level, should be assigned before connecting to the bus, be­cause an address can be used only once. If an address is used twice, interference in the bus will be caused.
The address of a VEGAFLEX sensor can be set in three ways:
- with the adjustment software VVO (soft-
ware addressing),
- with the DIP switch block in the sensor
(hardware addressing) or
- with the adjustment module MINICOM.
VEGA Profibus sensors are dispatched with the address set at 126 (all DIP switches to "ON"). Remember, in a Profibus system there are max. 126 participants possible. When the DIP switch is set to address 126 (or higher), the address can be adjusted with the adjust­ment software VVO, the adjustment module MINICOM or another configuration tool (e.g. PDM). However, there can be only one sen­sor on the bus with address 126 (delivery status) during address assignment via soft­ware. For that reason, hardware addressing (DIP switch) before connection to the bus is recommended.
Hardware addressing
The DIP switches generate an address number in the binary system. This means that, from right to left (ascending), any switch represents a number twice as high as the previous switch on the right. The corre­sponding number in the decimal system results from the sum of all switches set to "ON". In the illustration, you see the decimal number that corresponds to each individual DIP switch.
DIP switch 8 corresponds to the number 128, switch 1 corresponds to the number 1 and switch 3 corresponds to the decimal number
4.
Example 1
The switches 3, 5 and 7 are set to "ON". The address is then: DIP switch 3 to "ON" means 4 DIP switch 5 to "ON" means 16 DIP switch 7 to "ON" means 64
4 + 16 + 64 = Address 84
ON
1
2
8765 4
3
64
VEGAFLEX 51P and 52P 27
16
64 + 16 + 4 = 84
4
Electrical connection
Example 2
You want to set address 27. 16 + 8 + 2 + 1 = 27
You must set the DIP switches 5 = 16 4 = 8 2 = 2 1 = 1 to "ON".
Example 3
You want to set address 99 64 + 32 + 2 + 1 = 99
You must set the DIP switches 7 = 64 6 = 32 2 = 2 1 = 1 to "ON".
Software addressing
The DIP switches must be set to an address of 126 255, i.e.
- either all DIP switches are set to "ON", corresponding to address 255 (delivery status)
OFF
1
2
64
3
ON
8765 4
32
16
1
2
3
1
2
4
8
8765 4 Addr.
- or only DIP switch 8 is set to "ON", corre­sponding to address 128.
128
Of course, software addressing is also pos­sible if the switches 7 2 are set to "ON" (address 126).
The adjustment of the address with software VVO is described in the operating instruc­tions of the adjustment software VVO.
It is also possible to set the address with the adjustment module MINICOM. Please check the menu schematic of MINICOM.
28 VEGAFLEX 51P and 52P
Electrical connection
3.3 Connection of the sensor
Loosen the closing screw on the upper side of the sensor.
Open the sensor cover.
Remove the compression nut from the
cable entry and slide the nut a small dis­tance over the connection cable.
Remove the rubber seal from the cable entry and slide it over the connection ca­ble.
Strip off the insulation of the connection cable over a length of approx. 10 cm.
Version with Aluminium housing
Power supply and Profi­bus signal
+
To the indicating instrument in the sensor lid or to the external indicating instrument VEGADIS 50
M20x1.5 (diam­eter of the connection cable 69 mm)
Insert the cable through the cable entry into the sensor.
Connect the cables. Push back the white tabs of the spring terminals with a small screwdriver and insert the copper core of the connection line into the terminal opening. Check the hold of the cables in the terminal by slightly pulling on them.
Screw the compression nut back on to the cable entry and fasten it tightly.
Version with plastic housing
Power supply and Profibus signal
M20x1.5 (diam­eter of the connection cable 69 mm)
+
To the indicating instru­ment in the sensor lid or to the external indicating
instrument
Spring-loaded terminals (max. 2.5 mm2 wire cross-section)
1
2
3
87654
1
2
3
8 765 4
+1 2- 5678
Addr.
Bus
Display
ON
ESC
-
+
OK
Opening tabs
Pluggable adjustment module MINICOM
+1 2- 5678
Addr.
Bus
Tank 1 m (d)
12.345
Display
ON
ESC
+
-
OK
VEGAFLEX 51P and 52P 29
3.4 Connection of the external indicating instrument
Loosen the four screws of the housing lid on VEGADIS 50. The connection procedure can be facilitated by fixing the housing cover during connec­tion work with one or two screws on the right of the housing.
Adjustment module
OUTPUT (to the sensor)
3
2
1
4
5
8
6
7
VEGADIS 50
+
-
Tank 1 m (d)
12.345
Electrical connection
ESC
OK
Voltage supply and digital meas. signal
-
+
8 7654
+1 2- 5678
Addr.
Bus
Tank 1 m (d)
12.345
DISPLAY (in the lid of the indicating instrument)
1
2
3
Display
ON
ESC
+
-
OK
Screws
30 VEGAFLEX 51P and 52P
Setup

4 Setup

4.1 Adjustment media

All VEGA Profibus sensors operate in profile 3 and can be adjusted with:
- the adjustment program VVO on a PC with Profibus card
- the adjustment program PACTwareTM, under which VVO runs as a subprogram
- the Siemens software PDM in conjunction with an EDD (Electronic-Device-Descrip­tion)
- the adjustment module MINICOM in the sensor.
Adjustment with VVO on the PC
The adjustment program VVO enables user­friendly adjustment of VEGA Profibus PA sensors. All functions and options of sensor adjustment are accessible. The program runs under Windows® on a PC with a Profi­bus-Master-Class 2 interface card on Profi­bus DP level as Master-Class 2 tool. The VVO program accesses the VEGA PA sen­sors via the DP bus, the segment coupler and the PA bus.
The adjustment program VVO from VEGA makes full range of functions of VEGA sen­sors available and can update the entire sensor software if necessary. For this reason, the adjustment program must be installed on a PC which is equipped with a Profibus­Master-Class 2 interface card (Softing) (see figure on the next page).
The adjustment and parameter data can be saved with the adjustment software on the PC and protected by passwords. On re­quest, the adjustment can be also trans­ferred to other sensors.
In practice, the adjustment program VVO is often installed as a tool on an engineering station or an adjustment station. VVO then accesses over the bus each VEGA sensor via the Profibus interface card (e.g. from Softing) as Master-Class 2, from the DP level, through the segment coupler on the PA level right down to the individual sensor
Device description (DD)
Beside the instrument master file (GSD), by which a sensor is logged on the Profibus system, the majority of all Profibus sensors requires for adjustment, beside the specific adjustment software, also a so-called EDD (Electronic Device Description) for each sensor, to access and adjust the sensor from the bus levels. This is not the case with VVO. The adjustment software VVO can communi­cate at any time with all VEGA sensors with­out requiring a special database. Of course, all other VEGA sensors can be adjusted with the adjustment software as well (4 … 20 mA sensors or VBUS sensors). With VEGA sen­sors, it is not necessary to go looking for the latest EDD. This is the essential requirement of a manufacturer-independent adjustment program anticipated by many users.
The PC with the Profibus interface card can be connected directly at any location on the DP bus by means of the standard RS 485­Profibus cable.
VEGAFLEX 51P and 52P 31
Setup
Adjustment with P ACT ware
TM 1)
The adjustment with PACTwareTM corre­sponds to VVO adjustment, in this case, VVO runs as a subprogram of PACTwareTM. The adjustment instructions can be found in the documentation of PACTwareTM.
Adjustment with PDM
The sensors can be adjusted completely with PDM. However, some user-friendly functions and many special features, like e.g. display of an echo curve, are not available. In addi­tion to the PDM software, an EDD (upon request available from VEGA) is required for each sensor type. The adjustment instruc­tions for PDM are described in the PDM documentation.
Adjustment with the adjustment module MINICOM
With the adjustment module MINICOM, you adjust the individual sensor directly on the sensor or in the external indicating instrument VEGADIS 50. The adjustment module MINI­COM enables (with the 6 key adjustment field with text display) all essential functions of parameter setting and adjustment.
4.2 Adjustment with the adjustment module MINICOM
As with the PC, the sensor can also be ad­justed with the small detachable adjustment module MINICOM. The adjustment module is inserted into the sensor or into the external indicating instrument (optional).
ESC
+
Tank 1
-
m (d)
12.345
OK
2
4 ... 20 mA
ESC
+
Tank 1
-
m (d)
12.345
OK
4
The adjustment module also provides all the adjustment options available on the PC with adjustment program VVO. All adjustment steps can be carried out with 6 keys of the adjustment module. A small display gives you, beside the measured value, a short information on the menu item or the value of a menu adjustment.
Not possible, however, are parts of the ad­justment relating to the configuration and signal processing (e.g. linearisation curve). This is only possible with the PC.
32 VEGAFLEX 51P and 52P
Setup
Adjustment elements
The adjustment module MINICOM is menu orientated. The clear text indications on the display lead through the menu. The functions of the keys are described in the following.
2
1
Tank 1
-
m (d)
12.345
5
OK key (4)
With the OK key adjustments can be con­firmed.
When the symbol or is displayed, you can move with the OK key to the next lower menu level.
With the symbol there is no branch below
▼ ▼
the menu item but only another menu item of respective function.
ESC key (3)
With the Escape key (ESC) you can, de­pending on the menu item, interrupt an ad­justment or a function or change to the next higher menu level.
3
ESC
+
OK
4
▼ ▼
Arrow keys (5)
With the keys > and < you can move within the menu level from one menu item to the other.
Digital indication (1)
On the digital indication the actual measured value is displayed during operation. When you adjust the instrument, the clear text indi­cation displays the appropriate function.
Branching point from which you can change to a lower menu.
This symbol informs you about an ensu-
ing safety enquiry.
E.g. to reach the top menu level, push the ESC key several times.
+ and - key (2)
With the keys + and - you can modify the values of the parameters or choose from several possibilities.
After pushing the first time, the value to be adjusted flashes. The value will be modified by further pushing the key.
VEGAFLEX 51P and 52P 33
Setup
Address
First choose a free bus address (see chap­ter 3.2 Sensor address").
Adjustment steps
On the following pages you see the menu schematic of the adjustment module MINI­COM.
Set up the sensor in the following sequence. The numbers are stated near the appropriate menu items in the menu schematic on the following pages.
1. Adjustment
2. Conditioning
3. Outputs
4. Operating range
5. Meas. conditions
6. Indication of the useful and noise level
1. Adjustment
Under the menu item " the sensor with which span it should work.
Max.
Min.
Adjustment
100 % (distance to the medium
0.300 m) corresponds to 1200 l
0 % (distance to the medium
5.850 m) corresponds to 456 l
" you inform
Span
Adjustment without medium
Enter with the "+" and "–" key the distance
to the medium your sensor has at 0 % filling (example: 5.850 m) If you do not know the distance, you have to do a sounding.
Enter the distance to the medium which
your sensor has at 100 % filling.
Key Display
Sensor
m(d)
4.700
Para-
OK
OK
OK
OK
meter adjust­ment
Ad­just­ment
without medium
Ad­just­ment in
(min. adjustment)
m(d)
0.0 %
at
m (d)
XX.XXX
1)
Adjustment with medium
Fill the vessel e.g. to 10 %, enter in the menu "
Min. adjustment
" with the "+" and "–" keys 10 % and confirm with the "OK" key. Then fill the vessel e.g. 80 % or 100 %, enter in the menu "
Max. adjustment
" with the "+" and "–" keys 80
% or 100 % and confirm with the "OK" key.
with medium
You can carry out the adjustment without medium. Generally, you will carry out the adjustment without medium, since you can adjust without filling the vessel.
1)
In case of two values which can be modified, you can move with the "OK" key to the second value.
34 VEGAFLEX 51P and 52P
Min. adjust at %
XXX.X
Max. adjust at %
XXX.X
Setup
2. Conditioning
Under the menu item " choose the distance at 0 % and at 100 % filling. Then you enter the parameter and the appropriate unit as well as the decimal point.
Enter in the menu window "
sponds
" the value of the 0 % filling. This will
be e.g. "80" for 80 l.
Confirm with "OK".
With the arrow key you change to the
100 % menu. Enter here the value of your parameter corresponding to a 100 % filling. E.g. "1200" for 1200 l.
Confirm with "OK".
If necessary, choose a decimal point. Note
that max. 4 digits can be shown.
In the menu " rameter (mass, volume, distance…)
In the menu " unit (kg, l, ft3, gal, m3 ).
With the ESC key you change to the next higher menu level. With the arrow key you choose the next menu item.
In the menu between three standard linearisation curves. Preadjusted is a linear dependence be­tween percentage value of the product distance and the percentage value of the filling volume. You can choose between linear, spherical tank and cylindrical tank. The adjustment of a user-programmable curve is only possi­ble with the PC and the adjustment pro­gram VVO.
In the menu item adjust a delay for the signal output.
Conditioning
0 % corre-
prop. to
" you choose the pa-
Unit
" you choose the physical
"Lin. curve"
you can choose
"Integration time"
" you
you can
3. Outputs
4. Operating range
Without special adjustment, the operating range corresponds to the measuring range. The measuring range was already adjusted with the min./max. adjustment. It is usually better to choose a slightly bigger operating range (approx. 5 %) than the measuring range (span).
Example: Set min./max. adjustment: 0.300 5.850 m; operating range to approx. 0.250 real cable length. If you shorten the cable, you have to redefine the cable length.
5. Meas. conditions
With these functions you can enter the ambi­ent conditions in the vessel. (see menu schematic)
6. Useful level and noise level
In the menu tion on the signal quality of the product echo. The higher the " the measurement.
Ampl.: means amplitude of the product echo
S-N: means Signal-Noise (useful level
The higher the S-N value (useful level minus noise level), the higher the reliability: > 50 dB Measurement very good 40 50 dB Measurement good 20 40 dB Measurement satisfactory 15 20 dB Measurement sufficient < 15 dB Measurement bad
"Info"
you get important informa-
S-N
" value, the more reliable
in dB (useful echo)
minus noise level)
Under the menu " display and determine which parameter the sensor display should show.
VEGAFLEX 51P and 52P 35
Outputs
" you can scale the
Menu schematic of the adjustment module MINICOM
Setup
Sensor
m(d)
4.700
Para­meter
Sensor opti­mise
Sensor Tag
Sensor
Meas. enviro nment
Opera­ting range
Begin
m (d)
FLEX51 P
0.50
0.50
When switching on, the sensor type and the software version are displayed for a few seconds.
Confi­gura­tion
4.
Cable length
m (d)
6.00
Meas. condit ions
Condit ion
solid
Sensor Tag
Sensor
5.
Foam­ing prod.
No
Sensor addr.
(••••/ • •••)
Low DK pro­duct
No
126
Meas. unit
m (d)
False echo memory
Update
Meas. dist.
m (d)
X.XX
Echo learn Now !
OK ?
Lear­ning!
Update
Meas. dist.
m (d)
X.XX
Update Now !
OK ?
Lear­ning!
Delete
Delate Now !
OK ?
Delat­ing!
Adjust­ment
w.out medium
Adjust­ment in
m(d)
1.
0.0 %
at
m (d)
XX.XXX
100.0%
at
m (d)
XX.XXX
with medium
Min­adjust at %
XXX.X
Max­adjust at %
XXX.X
Note:
Set up the sensor in the sequence of the numbers.
Signal condi­tioning
Sca­ling
0 % corres­pond
XXXX
2.
Lin. curve
Linear
100 % corres­pond
XXXX
Integr ation time
Deci­mal­point
888.8
0 s
Prop.
Unit
to
Masse
kg
36 VEGAFLEX 51P and 52P
Setup
With these keys you move in the menu field to the left, the right, top and bottom.
ESC
False echo memory
Reset Now !
OK ?
Reset ing!
Dis­tance
m (d)
4.700
Ampl.:
XXdB
S-N:
XX
wei­tere Funkt.
Info
False echo
dB
memory
Reset Now !
OK ?
Reset ing!
Lang­uage
Eng­lish
OK
6.
Ampl.:
Sensor Tag
Sensor
Sensor type
FLEX51 P
Serial number
1094 0213
Softw. vers.
1.00
Softw. date
15.09. 1997
Sensor addr.
(••••/ • •••)
126
Dis­tance
m (d)
4.700
S-N:
XXdB
XX
dB
3.
Out­puts
PA­out­put
Prop. to
Di­stance
Error mode
last value
Sensor displ.
Prop. to
Di­stance
VEGAFLEX 51P and 52P 37
Simu­lation
Simu­lation Now!
Simu­lation
XXX.X
OK?
act. dist.
%
m
X,XX
Fast change
Yes
Bolt print figures are sensor or measured value information and cannot be modified in this posi­tion.
The menu items in white letters stand for figures which can be modified with the "+" or "–" key and saved with the "OK" key.
Setup

4.3 Adjustment with the PC

Before you can adjust the sensors with the adjustment program VVO (VEGA Visual Operating), they must be integrated into the Profibus system. First of all address the sensors and connect them to your PA seg­ment. With the attached GSD file you inte­grate the sensors into your system.
To adjust VEGA sensors with the adjustment software VVO, the PC or the adjustment station on which VVO is installed must be equipped with a Profibus DP interface card (e.g. of Messrs. Softing). The PC or the ad­justment station communicates then as Mas­ter-Class 2 participant on the DP bus with the VEGA sensors on the PA bus segment.
To connect the PC to the DP bus, a standard RS 485-DTE interface cable (Data Terminal Equipment) is required. With the cable you connect the DP interface card on the bus or to the segment coupler.
PC BUS
Screen 1 1 Screen – – 2 2 M24
RxD/TxD-P 3 3 RxD/TxD-P
– – 4 4 CNTR-P
GND 5 5 GND
– – 66VP – – 7 7 P24
RxD/TxD-N 8 8 RxD/TxD-N
– – 9 9 CNTR-P
Profibus-DP DP bus (in brackets the interface card PIN number of the P+F
segment couplers)
(40)
(55)
(41)
Segment coupler
Profibus PA cable
VVO
DP cable
Profibus DP interface card (Messrs. Softing)
Sensor Sensor Sensor Sensor
If the computer is connected to the Profibus DP cable, you can start VVO.
Switch on the power supply of the con­nected sensor.
Start the adjustment software VVO (VEGA Visual Operating) on your PC.
In the entrance window you choose with the arrow keys or the mouse the item
ning
and click to OK.
You should only choose
Planning
Plan-
if you are authorised to modify instrument param­eters. Otherwise choose
tenance
In the window
.
User identification
Operator
or
Main-
you are
asked for the name and the password.
For setup (
planning
) enter under name: VEGA and under password also: VEGA. It does not matter if you use capital or small letters.
VVO determines automatically the type of the connected sensor and shows shortly with which sensor a connection exists.
Further information on the adjustment with PC and the adjustment software VVO is stated in the operating instructions of the adjustment software VEGA Visual Operating (VVO).
38 VEGAFLEX 51P and 52P
Setup
Configuration
The term "Configuration" means the basic adjustments of the meas. system. You inform the meas. system about the application (level measurement, gauge, distance ), the measurement loop name and the DCS output address of the sensors. The configuration corresponds to an electronic wiring and labelling of your sensor or, in other words, telling the system which sensor for what application and where.
Parameter adjustment
After the configuration, you carry out the parameter adjustment for each individual sensor. This means adjusting the sensors to the respective operating range and adjusting to the actual application. You inform the sen­sor which product distance (which level) is "empty" and which "full". This is called adjust­ment. Here you choose in which physical unit (volume, mass) and unit of measurement (m3, gal, liters ) the adjusted measured value should be outputted. In the submenu "Sensor optimisation" you inform the sensor electron­ics about the actual environment, such as e.g. quick changes of the measured value, foam generation, gas stratification, solid or liquid.
To do this click to " "
Program
" and click to "
Configuration
Communication
", point to
".
First click to "
Profibus DP (for PA sensors
Then choose the Profibus card which is installed in your PC.
The window for the bus communication ad­justments opens. Ten is preadjusted as ad­dress for the Master-Class 2 interface card. If participant number ten is free on your bus, you can accept the setting. Typical values for bus parameters have been preset. At this point, you should adjust the communication parameters that apply to your system.
).
Now click to "OK".
The message "
dows® must be restarted
VEGAFLEX 51P and 52P 39
VVO will shut down and Win-
" appears.
Note: As a rule, a Windows® restart is not necessary.
Now start VVO (restart).
Special functions
As soon as a VEGAFLEX sensor has been identified, you can choose with the adjust­ment software VVO some special functions of VEGAFLEX.
Under the menu item Instrument data/Param­eter adjustment you can choose the sensor optimisation. Here you find all special functions of VE­GAFLEX:
- meas. environment
- echo curve
Measuring environment
Setup
Operating range
With this command you can limit the operat­ing range of the sensor or enter the cable length again after shortening the cable. Carry out the adjustment before modifying the oper­ating range, since a later adjustment can overwrite the values of the operating range.
The right side of the graphics shows the operating range, the left side the adjustment.
If you, for example, do not want to fill your vessel completely, you can limit the operating range.
Echo curve
The echo curve shows all reflections of the guided microwave signal. This means not only the product signal is shown but also false signals caused, e.g. by vessel installa­tions.
Measuring conditions
Choose in this menu if you want to measure in solids or liquids.
If you want to measure a product the DK value of which is below 2, you can increase the sensitivity of the sensor.
40 VEGAFLEX 51P and 52P
Generally, the sensor identifies the biggest amplitude as the useful echo. You see a black arrow above the highest amplitude. When you click to "Display info", a small win­dow is displayed, listing the detailed values of the selected echo.
Setup
Empty vessel profile (blue)
This curve shows in normal condition the actual empty vessel profile.
To gate out of false echoes, you can modify the blue curve of the vessel profile with the function "Empty vessel profile".
Reference line (green)
All amplitudes of the red curve which are below the green reference line are sup­pressed (ringing, noise, false echoes etc.).
Zoom/Unzoom
After activation of these two functions, you can either zoom or unzoom the curve with the left mouse key.
When you activate "Zoom", you can choose the requested part of the figure by pushing the left mouse key and drawing a frame.
The following curves can be displayed:
Raw value curve (red)
The red curve means the absolute signal which the receiver of VEGAFLEX detects. Beside the useful echo, this curve also con­tains false signals.
The highest amplitude is detected as useful echo. Check by sounding to determine if the value of the useful echo corresponds to the actual distance to the level.
If the two values do not correspond, you have to gate out the dominant false echoes with the function "Empty vessel profile".
All amplitudes above this line are possible echoes which are processed by the soft­ware.
Logarithmic raw value curve (black)
The curve shows the difference between raw value curve (red) and reference line (green). The scale on the right side (dB) applies to this curve.
Documentation
If you click on the button "Documentation", the actual echo curve will be saved.
Echo data
If you click on the button "Echo data", a win­dow is displayed in which all echoes de­tected by the sensor are listed with dB information and a probability evaluation.
VEGAFLEX 51P and 52P 41
Start
If you click to "Start", the echo curve will be updated continuously. With "Stop" you can terminate the update.
Empty vessel profile
With the functions in this window you can gate out false echoes. The blue empty vessel profile curve in the echo curve window shows the actual empty vessel profile.
Determine the level by sounding. If the sen­sor has identified a false echo as most prob­able echo instead of the actual filling level, you can gate the echo out.
Choose the function "Create new". Enter the measured distance to the medium. All false echoes in the range up to the adjusted dis­tance are automatically gated out.
With "Update" you can extend the empty vessel profile if new false echoes occur as the level falls. If you want to delete the exist­ing empty vessel profile, click to "Cancel".
Setup
42 VEGAFLEX 51P and 52P
Diagnostics

5 Diagnostics

5.1 Simulation

To simulate a certain filling, you can call up the function "Simulation" on the adjustment module MINICOM or in the software VVO program.
You simulate a certain measured value and thereby a certain sensor current. Please note that connected instruments, such as e.g. a PLC, react according to their adjustments and will probably activate alarms or system functions.
Simulation with VVO
If you start the simulation mode with the ad­justment program VVO on the PC, the simu­lated level is outputted until you quit the simulation mode.
Simulation with MINICOM
If you start the simulation mode on the adjust­ment module MINICOM, the sensor returns to standard operating mode after one hour.

5.2 Function diagram

The following function diagram is used for setup with the automation system, if there is no adjustment software available. Make sure that all VEGA sensors are profile 3 sensors. In general, the setup of the sensors can be carried out very conveniently with the VEGA adjustment software VVO or with the adjust­ment module MINICOM in the sensor.
The function diagram is generally not neces­sary for setup and is used only to deepen the knowledge of the interested user who is able to read in the sensor measured values into the processing system (also without adjustment tool).
VEGAFLEX 51P and 52P 43
Raw-Distance (value, status) [in m]
Sensor value (Float) [sensor unit (m,ft ...)]
Sensor offset (Float) [sensor unit (m,ft ...)]
Zero adjust
Zero offset
Function diagram and PA parameters
F Time (Float) (sec) (not available over PA Parameter)
Filter
Cal point hi, cal point lo (Float) [sensor unit (m,ft ...)]
Level hi, level lo (Float) [level unit (%,m,ft ...)] (*1)
Cal type (Unsigned8) Live adjustment (min-max) and dry adjustment possible
Cal
Level hi
Level lo
Cal point hi Cal point lo
Simulate procent value (DS_50) [level unit (%,m,ft...)] (*1) (manuf. spec. parameter)
Simulation
off
on
Simulate value
Level (Float) [level unit (%,m,ft...)] (*1)
Level offset (Float) [level unit (%,m,ft...)] (*1)
Offset
Offset
44 VEGAFLEX 51P and 52P
Function diagram and PA parameters
Simulation distance value (DS_50) [sensor unit (m,ft ...)] (manuf. spec. parameter)
Simulation
off
on
Simulate value
Secondary value 2 (DS_33) [secondary value 2 unit, (m,ft ...)]
distance
Max min memory
max min
Secondary value 1 (DS_33) [secondary value 1 unit (%,m,ft...)] (*1)
Max sensor value, min sensor value (Float) [sensor unit (m,ft ...)]
Lin type (Unsigned8), Tab index (Unsigned8), Tab X Y value (2 x Float) [level unit (%,m,ft ...). (*1) primary value unit (%,m,ft ...)]. (*1) Tab min number (Unsigned8), Tab max number (Unsigned8), Tab op code (Unsigned8), Tab status (Unsigned8), Tab actual number (Unsigned8)
Linearization
level %
Transducer
Block
Primary value (DS_33) [primary value unit (%,m,ft...)] (*1)
lin %
A
B
distance
C
VEGAFLEX 51P and 52P 45
lin % level % distance
Display source select (Unsigned8)
Source selector
scale
PV FTime (Float) [sec]
Function diagram and PA parameters
Sensordisplay
VEGA
Hi hi limit, hi limit, lo limit, lo lo limit, alarm hys (Float) [out scale unit]
Alarm checkFilter
Hi hi limit Hi limit
Lo limit Lo lo limit
Alarm hyst
Hi hi alarm, hi alarm, lo alarm, lo lo alarm (DS_39) Alarm sum (DS_42)
lin %
A
B
C
level %
Channel (Unsigned16)
Channel
distance
Simulate Linearization value (DS_50) [primary value unit (%,m,ft ...).(*1) secondary value 1 unit, (%,m,ft ...).(*1) secondary value 2 unit, (m,ft ...) (dep. on channel)]
Simulation
off
on
Simulate value
46 VEGAFLEX 51P and 52P
Function diagram and PA parameters
Fail safe value (Float) [out scale unit]
Fail safe type (Unsigned8)
Target mode (Unsigned8)
Out (DS_33) [out scale unit]
Fail safe
Fail safe value
Divice status
PV scale (2 x Float) [primary value unit (%,m,ft ...).(*1) secondary value 1 unit, (%,m,ft ...).(*1) secondary value 2 unit, (m,ft ...) (dep. on channel)]
PV Scale
1
0
EU 0% EU 100%
Mode
Auto
Man
Mode & Status calc.
Out scale (DS_36) [out scale unit (included)]
Out Scale
EU 100%
EU 0%
Data value (DS_33) [out scale unit]
Actual mode (DS_37)
Function
Block
10
VEGAFLEX 51P and 52P 47

5.3 Error rectification

Error Error rectification
Diagnostics
E 013 Sensor cannot find - Message is displayed during the warm-up
E 017 Adjustment span too small Carry out a new adjustment.
E 036 Software update incorrect Return the instrument for repair.
E 040 Hardware failure / Check all connection cables.
level echo phase.
- If the message remains, the DK-value of the medium could be too low.
Check the useful level and noise level. See 4.2 Adjustment with adjustment module MINICOM / Useful and noise level (6). If the message still remains, carry out a new adjustment.
Make sure that the difference between min. and max. adjustment is at least 10 mm.
- Sensor requires programming (service).
- Failure message remains also during a current programming.
electronics defect Contact our service department.
48 VEGAFLEX 51P and 52P
Parameters

5.4 PA parameters

The following parameter listing and the func­tion diagram are used for setup with the automation system, if no adjustment software is available. The listing represents the pa­rameters of the function block and trans­ducer block and is only meant for very experienced Profibus users. Make sure that all VEGA sensors are profile 3 sensors. Nor­mally, you will carry out the setup of the sen­sors with greater ease using the VEGA adjustment software VVO or the adjustment module MINICOM in the sensor.
The PA parameters and the function diagram are generally not necessary for setup.
VEGAFLEX 51P and 52P 49
Index P arameter Object Read Write T ype Size Store Unit
0 Directory object header DM Ja Nein Array of
1 Composite list directory
entries
16 Block object FB_Primary_Value Ja Nein DS-32 20 C m
17 St rev FB_Primary_Valu e Ja Nein Unsigned16 2 N m
18 Tag desc FB_Primary _Value Ja Ja OctetString 32 S m
19 Strategy FB_P rimary_Value Ja Ja Unsigned16 2 S m
20 Alert key FB_Primary_Valu e Ja Ja Unsigned8 1 S m
21 Target mode FB _Primary_Value Ja Ja Unsigned8 1 S m
22 M ode blk FB_Primary_Valu e Ja Nein DS-37 3 D m
23 Alarm sum FB_Primary_Value Ja Nein DS-42 8 D m
24 Batch FB_Primary_Value Ja J a DS-67 10 S m
26 Out FB_Primary_Value Ja Ja (*1) DS-33 5 D [out scale unit] m
27 PV scale FB_Prima r y_V a l ue Ja Ja 2 * Fl oa t 8 S [pri m, sec1, sec2 v a l ue
28 Out scale FB_Primary_Va lue Ja Ja DS-36 1 1S includes out scale unit m
29 Lin type FB_Primary_Value Ja Ja (*1) Unsigned8 1 S m
30 C hannel FB_Primary_Value Ja Ja Unsigned16 2 S m
32 PV FTime FB_Primary_Value Ja Ja Float 4 N sec m
33 Fsafe type FB _Primary_V alue Ja Ja Unsigned8 1 S o
34 Fsafe value FB_Primary_Value Ja Ja Float 4 S [out scale unit] o
35 Alarm hys FB_Primary_Value Ja Ja Float 4 S [out scale unit] m
37 HI HI Lim FB_Primary_Value Ja Ja Float 4 S [out scale unit] m
39 HI Li m FB_Primary_Value Ja Ja Float 4 S [out scale unit] m
41 LO Lim FB _Primary_Value Ja Ja Float 4 S [out scale unit] m
43 LO LO Lim FB_Primary_Value Ja Ja Float 4 S [o ut scale unit] m
46 HI HI Alm FB_Primary_Value Ja Nein DS-39 1 6 D o
47 HI Alm FB_Primary _Value Ja Nein DS-39 16 D o
48 LO Alm FB _Primary_Va lue Ja Nein DS-39 16 D o
49 LO LO Alm FB_Primary_Value Ja Nein DS-39 16 D o
50 Simulate FB_Prima r y_V a l ue Ja Ja DS-5 0 6 N [pr im, sec1, se c2 valu e
61 View object
FB_Primary_Value
DM Ja Nein Array of
FB_Primary_Value Ja Nein OctetString 18 D m
Unsigned16
Unsigned16
12 C m
24 C m
unit (dep. on channel)
unit (dep. on channel)
PA parameters
Optio nal
manda t ory
m
m
50 VEGAFLEX 51P and 52P
PA parameters
Index P arameter Object Read Write T ype Size Store Unit
66 Block obj e ct PB Ja Nei n DS- 3 2 20 C m
67 St rev PB Ja Nein Unsigned16 2 N m
68 Tag desc PB Ja Ja OctetString 32 S m
69 St rategy PB Ja Ja Unsigned16 2 S m
70 Alert key PB Ja Ja Unsigned8 1 S m
71 Target mode PB Ja Ja (* 1) Unsigned8 1 S m
72 M ode blk PB Ja Nein DS-37 3 (D) m
73 Alarm sum PB Ja Nein DS-42 8 D m
74 Softw a r e revis i on PB Ja Nein Octe tS tr i ng 16 C m
75 Hardwar e revisi on PB Ja Ne i n Oc te tStrin g 16 C m
76 Device man ID PB Ja Nein Unsigned16 2 C m
77 Devi ce ID PB Ja Nein OctetS tr i n g 16 C m
78 Device ser num PB Ja Nein OctetString 16 C m
79 Diagno sis PB Ja Nein OctetString 4 D m
81 Diagnosis mask P B Ja Nein OctetString 4 C m
83 Device certification PB Ja Nein OctetString 32 C o
84 Write locking PB Ja Ja Unsigned16 2 N o
85Factory reset PB JaJaUnsigned162S o
86 D ecriptor PB Ja Ja Octet String 32 S o
87 Device me ssa g e PB Ja Ja Octe tS tr i n g 32 S o
88 Devi ce i n sta l l d a te PB Ja Ja OctetS tr i n g 1 6 S o
90 Ident number select PB Ja Ja Unsigned8 1 S m
91 HW write protection PB Ja Nein Unsigned8 1 D o
99 VVO PB Ja Ja OctetString 32 o
100 View object PB PB Ja Nein Octe tS tr i n g 1 7 D m
180 Display source select TB Ja Ja Unsigned8 1 N o
120 Block object TB_Level Ja Nein DS-32 20 C m
Optio nal
manda t ory
VEGAFLEX 51P and 52P 51
PA-Parameter
Index P arameter Object Read Write T ype Size Store Unit
121 St rev TB_Level Ja Nein Unsigned16 2 N m
122 Tag desc TB_Level Ja Ja OctetString 32 S m
123 St rategy TB_Level Ja Ja Unsigned16 2 S m
124Alert key TB_Level JaJaUnsigned8 1S m
125 Target mode TB _Level Ja Ja (*1) Unsigned8 1 S m
126 M ode blk TB_Level Ja Nein DS-37 3 (D) m
127 Alarm su m T B_L e ve l Ja Nein DS - 42 8 D m
128 Primary value TB_Level Ja Nein DS-33 5 D [primary value unit] m
129 Primary value unit TB _Level Ja Ja Unsigned16 2 S m
130 Level TB_Level Ja Nein Flo at 4 D [level unit] m
131 Level unit TB_Level Ja Ja Unsigned16 2 S m
132 Senso r value TB_Level Ja Nein Float 4 D [sensor unit] m
133 Senso r unit TB_Level Ja Ja Unsigned16 2 S m
134 Seco ndary value 1 TB_Level Ja Nein DS-33 5 D [secondary value 1
135 Seco ndary value 1 unit TB_Level Ja Ja Unsigned16 2 S o
136 Seco ndary value 2 TB_Level Ja Nein DS-33 5 D [secondary value 2
137 Seco ndary value 2 unit TB_Level Ja Ja Unsigned1 6 2 S o
138 Senso r offset TB_Level Ja Ja Float 4 S [sensor unit] m
139 Cal type TB_Level Ja Ja Unsigned8 1 S m
140 Cal po int lo TB_Level Ja Ja Float 4 S [sensor unit] m
141 Cal point hi TB_Level Ja Ja Float 4 S [sensor unit] m
142 Level lo TB _Level Ja Ja Float 4 S [level unit] m
143 Level hi TB _Level Ja Ja Float 4 S [level unit] m
144 Level offset TB _Level Ja Ja Float 4 S [level unit] m
145 Lin type TB _Level Ja Ja Unsigned8 1 S m
148 Senso r high limit TB_Level Ja Nein Flo at 4 C [sensor unit] o
149 Senso r low limit TB_Level Ja Nein Float 4 C [sensor unit] o
150 Max sensor value TB_Level Ja Ja Float 4 N [sensor unit] o
15 1Mi n sensor va l u e TB_Level Ja Ja Float 4 N [se n sor unit] o
156 Tab index TB _Level Ja Ja Unsigned8 1 D o
unit]
unit]
Optio nal
manda t ory
o
o
52 VEGAFLEX 51P and 52P
PA-Parameter
Index P arameter Object Read Write T ype Size Store Unit
157 Tab X Y value TB_Level Ja Ja 2 * Float 8 N [secondary value 1 unit,
158 Tab min number TB_Level Ja Nein Unsigned8 1 C o
159 Tab max number TB_Level Ja Nein Unsigned8 1 C o
160 Tab op code TB_Level Ja Ja Unsigned8 1 D o
161 Tab status TB_Level Ja Nein Unsigned8 1 D o
162 Tab actual number TB_Level Ja Nein Unsigned8 1 D o
190 Simulate sensor value TB_Level Ja Ja DS-50 6 N [sensor unit] o
191 Simulate level TB_Level Ja Ja DS-50 6 N [level unit] o
19 2 F üllguttyp TB_Level Ja J a Unsigned8 1 N o
193 Echo quality TB_Level Ja Nein Unsigned8 1 D dB o
194 First echo factor TB _Level Ja Ja Unsigned8 1 N o
196 Lerndistanz TB _Level Ja Ja Float 4 D [sensor unit] o
19 7 S t ö rech o speicher-
Aktion
198 Arbeitsbereich
Ende
199 Arbeitsbereich
Anfang
200 schnelle
Meßwertänderung
201 unruhige
Füllgutoberfläche
202 Schaum bildung TB_Level J a J a Unsigned8 1 N o
203 st ark e
Staubentwicklung
204 Bodenreflexion / großer
Schüttwinkel
205 kleiner DK-Wert TB_Level Ja Ja Unsigned8 1 N o
210 Korrektur-
faktor Au sbr-.geschw.
211 Berechn. Korr.fak.
Ausbr.
212 Rohrdurchmesser TB_Level Ja Ja Float 4 N [sensor unit] o
250 View object TB_Level TB _Level Ja Nein OctetString 22 D m
TB_Level Ja J a Unsigned8 1 D o
TB_Level Ja Ja Float 4 N [sensor unit] o
TB_Level Ja Ja Float 4 N [sensor unit] o
TB_Level Ja J a Unsigned8 1 N o
TB_Level Ja J a Unsigned8 1 N o
TB_Level Ja J a Unsigned8 1 N o
TB_Level Ja J a Unsigned8 1 N o
TB_Level Ja J a Float 4 N % o
TB_Level Nein Ja Float 4 N [sensor unit] o
primary value unit]
Optional
manda to ry
o
VEGAFLEX 51P and 52P 53
Notes
54 VEGAFLEX 51P and 52P
Notes
VEGAFLEX 51P and 52P 55
VEGA Grieshaber KG Am Hohenstein 113 D-77761 Schiltach Phone (0 78 36) 50 - 0 Fax (0 78 36) 50 - 201 E-Mail info@de.vega.com www.vega.com
ISO 9001
All statements concerning scope of delivery, application, practical use and operating conditions of the sensors and processing sys­tems correspond to the latest information at the time of printing.
Technical data subject to alterations
2.25 321 / October 2000
Loading...