Vaisala WAC155 User Manual

Page 1
USER'S GUIDE
Vaisala Serial Wind Transmitter
WAC155
M210822EN-A
Page 2
PUBLISHED BY
Vaisala Oyj Phone (int.): +358 9 8949 1 P.O. Box 26 Fax: +358 9 8949 2227 FIN-00421 Helsinki Finland
Visit our Internet pages at http://www.vaisala.com/ © Vaisala 2007 No part of this manual may be reproduced in any form or by any means,
The contents are subject to change without prior notice. Please observe that this manual does not create any legally binding
obligations for Vaisala towards the customer or end user. All legally binding commitments and agreements are included exclusively in the applicable supply contract or Conditions of Sale.
Page 3
________________________________________________________________________________

Table of Contents

CHAPTER 1
GENERAL INFORMATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7
About This Manual . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7
Contents of This Manual . . . . . . . . . . . . . . . . . . . . . . . . . . .7
General Safety Considerations . . . . . . . . . . . . . . . . . . . . . .8
Feedback . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .8
Product Related Safety Precautions . . . . . . . . . . . . . . . . . . .8
ESD Protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .9
Recycling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .9
Warranty . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .10
CHAPTER 2
PRODUCT OVERVIEW . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .11
Introduction to Vaisala Serial Wind Transmitter WAC155 11
CHAPTER 3
INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .13
Selecting Location . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .13
Installation Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . .15
Jumper Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .16
Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .17
Sensor Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .19
Signal Output . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .20
Powering . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .21
Optional Heating Power . . . . . . . . . . . . . . . . . . . . . . . . . . .22
Wiring Examples . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .24
Mounting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .28
Mounting WAC155 to the Top of a Pole Mast . . . . . . . . . .28
Mounting Wind Sensors to WAC155 . . . . . . . . . . . . . . . . .29
Alignment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .29
Verification . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .30
CHAPTER 4
OPERATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .31
User Interface . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .31
Communication Interfaces . . . . . . . . . . . . . . . . . . . . . . . . . .31
NMEA Message Format . . . . . . . . . . . . . . . . . . . . . . . . . . .32
Polling Data using a Query . . . . . . . . . . . . . . . . . . . . . . . .33
Service Connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .34
List of Serial Commands . . . . . . . . . . . . . . . . . . . . . . . . . . .35
VAISALA________________________________________________________________________ 1
Page 4
________________________________________________________________________________
OPEN . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .36
CLOSE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .37
SETDEV . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .38
SETSPD . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .38
SETDIR . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .38
SETMES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .39
SETMEA . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .40
SETCOM . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .41
SETHEA . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .42
GETHEA . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .42
SETALR . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .43
SERVICE TIMEOUT . . . . . . . . . . . . . . . . . . . . . . . . . . . . .44
GETSET . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .45
HELP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .45
INIE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .45
RESET . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .46
ERRS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .46
CHAPTER 5
MAINTENANCE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .49
Periodic Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .49
Visual Checking . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .49
Replacing Consumables . . . . . . . . . . . . . . . . . . . . . . . . . . . .49
Parts List for Consumables . . . . . . . . . . . . . . . . . . . . . . . .49
CHAPTER 6
TROUBLESHOOTING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .51
Problem Situations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .51
Error Messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .52
Technical Support . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .53
Return Instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .53
Vaisala Service Centers . . . . . . . . . . . . . . . . . . . . . . . . . . . .54
CHAPTER 7
TECHNICAL DATA . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .55
Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .55
Dimensions in mm (inches) . . . . . . . . . . . . . . . . . . . . . . . . .57
2 _______________________________________________________________________________
Page 5
________________________________________________________________________________
List of Figures
Figure 1 Vaisala Serial Wind Transmitter WAC155 . . . . . . . . . . . . . . . .12
Figure 2 Recommended Mast Location in Open Area. . . . . . . . . . . . . .14
Figure 3 Recommended Mast Length on Top of a Building. . . . . . . . . .15
Figure 4 RS-485 Termination. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .16
Figure 5 WAC155 Component Board. . . . . . . . . . . . . . . . . . . . . . . . . . .17
Figure 6 Cable Shield Bent over the Plastic Sleeve and O-ring. . . . . . .17
Figure 7 I/O Connectors. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .18
Figure 8 Wiring of the Sensors. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .20
Figure 9 Typical System with 12 VDC Power Supply. . . . . . . . . . . . . . .21
Figure 10 Heating Power Connection with 40 V Power Supply . . . . . . . .22
Figure 11 Heating Power Connection with 20 V Power Supply . . . . . . . .23
Figure 12 Heating Power Connection for Anemometer Only. . . . . . . . . .23
Figure 13 Heating Power Connection for Wind Vane Only . . . . . . . . . . .24
Figure 14 Basic Wiring with WAA151 and WAV151 Sensors . . . . . . . . .25
Figure 15 Wiring with WHP151 Mains Power Supply . . . . . . . . . . . . . . .26
Figure 16 Wiring with WHP25 Mains Power Supply and the WA252
Series Wind Sensors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .27
Figure 17 Mounting WAC155 to the Top of a Pole Mast . . . . . . . . . . . . .28
Figure 18 Installation of the Wind Sensors WAA151 and WAV151
to WAC155. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .29
Figure 19 WAC155 Dimensions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .57
VAISALA________________________________________________________________________ 3
Page 6
________________________________________________________________________________
4 _______________________________________________________________________________
Page 7
________________________________________________________________________________
List of Tables
Table 1 Anemometer Connector (X1) Pinout . . . . . . . . . . . . . . . . . . . . . .18
Table 2 Power/Control Connector (X2) Pinout . . . . . . . . . . . . . . . . . . . . .19
Table 3 Wind Direction Sensor Connector (X3) Pinout. . . . . . . . . . . . . . .19
Table 4 WAC155 Default Serial Communication Settings . . . . . . . . . . . .32
Table 5 Checksum table . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .34
Table 6 List of Serial Commands . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .35
Table 7 Meaning of the Command Line Elements . . . . . . . . . . . . . . . . . .36
Table 8 Available Spare Parts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .49
Table 9 Problem Situations and Corrective Actions . . . . . . . . . . . . . . . . .51
Table 10 Self-diagnostics Error Codes . . . . . . . . . . . . . . . . . . . . . . . . . . . .52
Table 11 Performance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .55
Table 12 Inputs and Outputs. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .56
Table 13 Operating Conditions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .56
Table 14 Dimensions and Mechanics. . . . . . . . . . . . . . . . . . . . . . . . . . . . .56
VAISALA________________________________________________________________________ 5
Page 8
________________________________________________________________________________
6 _______________________________________________________________________________
Page 9
Chapter 1 ________________________________________________________ General Information
CHAPTER 1
GENERAL INFORMATION
This chapter provides general notes for the manual and the product.

About This Manual

This manual provides information for installing and maintaining the
Vaisala Serial Wind Transmitter WAC155.

Contents of This Manual

This manual consists of the following chapters:
- Chapter 1, General Information: This chapter provides general notes for the manual and the product.
- Chapter 2, Product Overview: This chapter introduces the features of the Vaisala Serial Wind Transmitter WAC155.
- Chapter 3, Installation: This chapter provides you with information that is intended to help you install this product.
- Chapter 4, Operation: This chapter contains information that is needed to operate the Vaisala Serial Wind Transmitter WAC155.
- Chapter 5, Maintenance: This chapter provides information that is needed in basic maintenance of the Vaisala Serial Wind Transmitter WAC155.
VAISALA________________________________________________________________________ 7
Page 10
User's Guide ______________________________________________________________________
- Chapter 6, Troubleshooting: This chapter describes common problems, their probable causes and remedies, and contact information.
- Chapter 7, Technical Data: This chapter provides technical data of the Vaisala Serial Wind Transmitter WAC155.

General Safety Considerations

Throughout the manual, important safety considerations are highlighted as follows:
WARNING
CAUTION
NOTE
Warning alerts you to a serious hazard. If you do not read and follow instructions very carefully at this point, there is a risk of injury or even death.
Caution warns you of a potential hazard. If you do not read and follow instructions carefully at this point, the product could be damaged or important data could be lost.
Note highlights important information on using the product.

Feedback

Vaisala Customer Documentation Team welcomes your comments and suggestions on the quality and usefulness of this publication. If you find errors or have other suggestions for improvement, please indicate the chapter, section, and page number. You can send comments to us by e­mail: manuals@vaisala.com
.

Product Related Safety Precautions

The Vaisala Serial Wind Transmitter WAC155 delivered to you has been tested for safety and approved as shipped from the factory. Note the following precautions:
8 ____________________________________________________________________M210822EN-A
Page 11
Chapter 1 ________________________________________________________ General Information
WARNING
CAUTION
Ground the product, and verify outdoor installation grounding periodically to minimize shock hazard.
Do not modify the unit. Improper modification can damage the product or lead to malfunction.

ESD Protection

Electrostatic Discharge (ESD) can cause immediate or latent damage to electronic circuits. Vaisala products are adequately protected against ESD for their intended use. However, it is possible to damage the product by delivering electrostatic discharges when touching, removing, or inserting any objects inside the equipment housing.
To make sure you are not delivering high static voltages yourself:
- Handle ESD sensitive components on a properly grounded and protected ESD workbench. When this is not possible, ground yourself with a wrist strap and a resistive connection cord to the equipment chassis before touching the boards. When neither of the above is possible, at least touch a conductive part of the equipment chassis with your other hand before touching the boards.

Recycling

- Always hold the boards by the edges and avoid touching the component contacts.
Recycle all applicable material.
Dispose of batteries and the unit according to statutory regulations. Do not dispose of with regular household refuse.
VAISALA________________________________________________________________________ 9
Page 12
User's Guide ______________________________________________________________________

Warranty

Vaisala hereby represents and wa rrants all Prod ucts manufactured by Vaisala and sold hereunder to be free from defects in workmanship or material during a period of twelve (12) months from the date of delivery save for products for which a special warranty is given. If any Product proves however to be defective in workmanship or material within the period herein provided Vaisala undertakes to the exclusion of any other remedy to repair or at its own option replace the defective Product or part thereof free of charge and otherwise on the same conditions as for the original Product or part without extension to original warranty time. Defective parts replaced in accordance with this clause shall be placed at the disposal of Vaisala.
Vaisala also warrants the quality of all repair and service works performed by its employees to products sold by it. In case the repair or service works should appear inadequate or faulty and should this cause malfunction or nonfunction of the product to which the service was performed Vaisala shall at its free option either repair or have repaired or replace the product in question. The working hours used by employees of Vaisala for such repair or replacement shall be free of charge to the client. This service warranty shall be valid for a period of six (6) months from the date the service measures were completed.
This warranty does not however apply when the defect has been caused through
a) normal wear and tear or accident;
b) misuse or other unsuitable or unauthorized use of the Product or negligence or error in storing, maintaining or in handling the Product or any equipment thereof;
c) wrong installation or assembly or failure to service the Product or otherwise follow Vaisala's service instructions including any repairs or installation or assembly or service made by unauthorized personnel not approved by Vaisala or replacements with parts not manufactured or supplied by Vaisala;
d) modifications or changes of the Product as well as any adding to it without Vaisala's prior authorization;
e) other factors depending on the Customer or a third party.
Notwithstanding the aforesaid Vaisala's liabi lit y under this clause shall not apply to any defects arising out of materials, designs or instructions provided by the Customer.
This warranty is however subject to following conditions:
a) A substantiated written claim as to any alleged defects shall have been received by Vaisala within thirty (30) days after the defect or fault became known or occurred, and
b) The allegedly defective Product or part shall, should Vaisala so require, be sent to the works of Vaisala or to such other place as Vaisala may indicate in writing, freight and insurance prepaid and properly packed and labelled, unless Vaisala agrees to inspect and repair the Product or replace it on site.
This warranty is expressly in lieu of and excludes all other conditions, warranties and liabilities, express or implied, whether under law, statute or otherwise, including without limitation any implied warranties of merchantability or fitness for a particular purpose and all other obligations and liabilities of Vaisala or its representatives with respect to any defect or deficiency applicable to or resulting directly or indirectly from the Products supplied hereunder, which obligations and liabilities are hereby expressly cancelled and waived. Vaisala's liability shall under no circumstances exceed the invoice price of any Product for which a warranty claim is made, nor shall Vaisala in any circumstances be liable for lost profits or other consequential loss whether direct or indirect or for special damages.
10 ___________________________________________________________________M210822EN-A
Page 13
Chapter 2 __________________________________________________________ Product Overview
CHAPTER 2
PRODUCT OVERVIEW
This chapter introduces the features of the Vaisala Serial Wind Transmitter WAC155.

Introduction to Vaisala Serial Wind Transmitter WAC155

The Vaisala Serial Wind Transmitter WAC155 converts the digital data supplied by the Vaisala 151 and 252 Series wind sensors for use in the RS-485 bus. The WAC155 transmitter consists of a component board in a junction box and a cross arm for mounting the wind sensors; see
Figure 1 on page 12.
The WAC155 unit is installed underneath the cross arm, and it communicates with the controlling system via a twisted pair RS-485 cable. The electrical connections to the sensors are 6-bit parallel gray­code for the direction measurement and up to 750Hz digital pulse for the wind speed measurement (anemometer).
The power to the sensors is supplied through the WAC155 transmitter. The transmitter accepts 9 ... 15.5 VDC as input power. The WAC155 transmitter also provides the sensors with a throughput for optional heating power. The unit automatically connects the heating power in temperatures below +3 °C (default setting).
VAISALA_______________________________________________________________________ 11
Page 14
User's Guide ______________________________________________________________________
The main features of the WAC155 are as follows:
- Communication with NMEA 0183 compliant protocol over RS-485 electrical interface (half-duplex)
- Capable of measuring the wind parameters at a configurable interval using the instant method according to the WMO standard
- Fail-safe RS-485 operation with configurable baud rate and turnaround delay
- Configurable RS-485 bus termination and ID setting
- Service connection via the RS-485 interface for configuration and maintenance
- Adjustable heating control of the sensors
- Automatic detection of sensor failure conditions
0710-010
Figure 1 Vaisala Serial Wind Transmitter WAC155
The following numbers refer to Figure 1 on page 12. 1 = Flange for mounting a Vaisala anemometer 2 = Junction box, containing the component board 3 = Flange for mounting a Vaisala wind vane
12 ___________________________________________________________________M210822EN-A
Page 15
Chapter 3 _______________________________________________________________ Installation
CHAPTER 3
INSTALLATION
This chapter provides you with information that is intended to help you install this product.

Selecting Location

Finding a suitable site for the product is important for getting representative ambient measurements. The site should represent the general area of interest.
Allow sufficient clearance for the wind sensors. Wind sensors should not be located next to a building or any other object that might affect the flow of air.
CAUTION
Installations on top of high buildings or masts and in sites on open grounds are vulnerable to lightning strikes. A nearby lightning strike may induce a high-voltage surge not tolerable by the internal surge suppressors of the instrument.
Additional protection is needed in regions with frequent, severe thunderstorms, especially when long line cables (> 30m) are used. Vaisala recommends using a surge protector such as the WSP150 in all sites where there is an elevated risk of lightning strike.
VAISALA_______________________________________________________________________ 13
Page 16
User's Guide ______________________________________________________________________
0204-040
Figure 2 Recommended Mast Location in Open Area
In general, any object of height (h) will not remarkably disturb wind measurement at a minimum distance of 10 h. There should be at least 150 m open area in all directions from the mast. Refer to Figure 2 on
page 14.
14 ___________________________________________________________________M210822EN-A
Page 17
Chapter 3 _______________________________________________________________ Installation
0204-041
Figure 3 Recommended Mast Length on Top of a Building
The recommended minimum length (marked with the letter h in Figure
3 on page 15) for the mast that is installed on top of a building is
1.5 times the height of the building (H). When the diagonal (W) is less than the height (H), the minimum length of the mast is 1.5 W.

Installation Procedure

For installation, follow the procedure below and refer to corresponding sections for details.
1. Remove the four screws holding the cover of the WAC155 transmitter. Remove the cover.
2. Select the RS-485 termination according to the instructions in section Jumper Settings on page 16.
3. Enter the power and signal cables through the cable glands(s). For better protection against RF interference, ground the cable shield as shown in Figure 6 on page 17.
4. Connect the wires to the X2 removable screw terminal block according to Figure 8 on page 20 and Figure 9 on page 21. Tighten the output cable gland(s).
5. Carefully reattach the enclosure cover with the four screws.
VAISALA_______________________________________________________________________ 15
Page 18
User's Guide ______________________________________________________________________
6. Attach the unit on the top of a pole mast with the mounting clamp as shown in Figure 17 on page 28.
7. Mount the sensors onto the cross arm. Refer to Figure 18 on page
29 and the sensors' manuals.
8. Align the cross arm as instructed in section Alignment on page 29 before erecting the mast.

Jumper Settings

RS-485 serial bus termination can be selected with the on-board jumper. Termination is on when pins 1 and 2 are shorted, and termination is off when pins 2 and 3 are shorted or when the jumper plug is fully disconnected. Termination is implemented by a 120 resistor on the component board.
In a simple point-to-point configuration where only one WAC155 transmitter is used the jumper is always in ON position. In a multidrop configuration where several WAC155 transmitters share the single RS-485 communication line, the termination jumper is in ON position only at the physically farthest transmitter (i.e. at the end of the communication line), and in OFF position at the other transmitters.
0701-017
Figure 4 RS-485 Termination
16 ___________________________________________________________________M210822EN-A
Page 19
Chapter 3 _______________________________________________________________ Installation
0702-001
Figure 5 WAC155 Component Board

Connections

The following numbers refer to Figure 5 on page 17. 1 = RS-485 termination jumper 2 = Status indicator LED
The WAC155 transmitter provides the line cable entry through a gland for a cable with a diameter from 7 to 10 mm. For better protection against RF interference, bend the cable shield as illustrated in Figure 6
on page 17.
0206-046
Figure 6 Cable Shield Bent over the Plastic Sleeve and O-ring
The WAC155 transmitter has three I/O connectors as shown in
Figure 7 on page 18. For the location of the connectors and the routing
of the cables through the cable glands, refer to Figure 8 on page 20.
VAISALA_______________________________________________________________________ 17
Page 20
User's Guide ______________________________________________________________________
0702-008
Figure 7 I/O Connectors
The following numbers refer to Figure 7 on page 18. X1 = Plug-in connector with screw terminals (5 pcs) for the
anemometer cable. Maximum wire cross section area is 1.5 mm2.
X2 = Plug-in connector with screw terminals (8 pcs) for the power
and signal cable. Maximum wire cross section area is 1.5 mm2.
X3 = Plug-in connector with screw terminals (11 pcs) for the wind
vane cable. Maximum wire cross section area is 1.5 mm2.
I/O connector X1-X3 pinouts are shown in following tables.
Table 1 Anemometer Connector (X1) Pinout
Pin # Signal Description
1 F Pulse input from sensor 2 F+ Supply voltage output to sensor 3 GND Sensor ground 4 HT1 Heating supply-1 from connector X2 5 HTC Heating common for heater serial connection
18 ___________________________________________________________________M210822EN-A
Page 21
Chapter 3 _______________________________________________________________ Installation
Table 2 Power/Control Connector (X2) Pinout
Pin # Signal Description
1 HT1+ Heating supply-1 input 2 HT2- Heating supply-2 input 3 Vin+ Supply voltage input 4 Vin+ Supply voltage input 5Vin-Ground 6Vin-Ground 7 RS-485 A(-) RS-485 inverting I/O 8 RS-485 B(+) RS-485 noninverting I/O
Table 3 Wind Direction Sensor Connector (X3) Pinout
Pin # Signal Description
1 HTC Heating common for heater serial connection 2 HT2 Heating supply-2 from connector X2 3 GND Sensor ground 4 D+ Supply voltage output to sensor 5 G5 Gray code input from sensor, bit-5 6 G4 Gray code input from sensor, bit-4 7 G3 Gray code input from sensor, bit-3 8 G2 Gray code input from sensor, bit-2 9 G1 Gray code input from sensor, bit-1 10 G0 Gray code input from sensor, bit-0 11 n.c. Not connected

Sensor Wiring

The transmitter connects to the wind sensors with the cross-arm's standard cables through two cable glands. Through these cables the WAC155 transmitter both feeds the sensor power and receives the wind data. Plug-in type screw terminal connectors are provided both for the sensor cables and the output line cable.
VAISALA_______________________________________________________________________ 19
Page 22
User's Guide ______________________________________________________________________
0702-007
Figure 8 Wiring of the Sensors
The following numbers refer to Figure 8 on page 20. 1 = Anemometer cable 2 = Glands for power and signal cables 3 = Wind vane cable

Signal Output

The WAC155 transmitter provides a half-duplex RS-485 serial bus connection. Wind data is provided in standard NMEA messages. In addition, a service connection is available for configuration and status information. The service connection is available through the same RS-485 interface. When the service connection is in use, data transmission and query are disabled.
Several transmitters can be connected to the same RS-485 bus. If only a single transmitter is connected, the transmitter can be configured in auto-transmit mode, i.e. the device transmits data messages at configured intervals. If there are several transmitters in the same bus, auto-transmission may not be enabled, and data must be polled using a query.
20 ___________________________________________________________________M210822EN-A
Page 23
Chapter 3 _______________________________________________________________ Installation
Each device in the same bus has a unique configurable ID, containing
1..5 characters. Alphabetical characters a-z and A-Z (case-sensitive) are accepted, as well as numbers 0-9.
Typically, only a 4-wire shielded cable is required for the line between the WAC155 transmitter and the receiving end. Two of the four wires provide the operating power for the system. A twisted pair can be used for the power wires to reduce interference. The other two wires are for the RS-485 serial bus connection from the WAC155 transmitter.
The maximum length of an unisolated RS-485 line is 1200m (4000ft). The cable used should be at least a twisted pair AWG 24 cable. The achievable line length is affected by electrical noise and the number of transmitters on the bus.
0702-002
Figure 9 Typical System with 12 VDC Power Supply

Powering

The WAC155 transmitter accepts 9 ... 15.5 VDC as input power. The power line is protected against incorrect polarity. Transient
protection is accomplished with VDRs, series inductors and resistors, and transient zener diodes on both the power line and each I/O line.
VAISALA_______________________________________________________________________ 21
Page 24
User's Guide ______________________________________________________________________

Optional Heating Power

The WAC155 transmitter also provides the sensors with a throughput for heating power, which can be connected if sensor heating is required. The heating power is galvanically isolated from the operating power.
The heating power connection requires an extra pair of wires. Since the heating elements in the shafts of the WAA151 and WAV151 sensors typically consume some 500 mA each, the heating power is most conveniently supplied from a local power source. Unit can automatically connect heating power in temperatures below +3 °C (default setting).
There are two ways to connect the heating power, depending on the heating power supply available. The default way is to connect a 40 VAC or VDC power supply in series; see Figure 10 on page 22. When a 40 V power supply is used, 500 mA is required. The 40 V power supply can only be used when both sensors are connected.
NOTE
If you connect DC heating power, observe the correct polarity of the X2 connector pins 1 and 2 (HT1+ and HT2-).
0702-014
Figure 10 Heating Power Connection with 40 V Power Supply
If a 20 VAC or VDC power supply is used, the heating power should be connected in parallel. The power supply must provide 500 mA for each connected WAV151 and WAA151 sensor; 1 A is required when both
22 ___________________________________________________________________M210822EN-A
Page 25
Chapter 3 _______________________________________________________________ Installation
sensors are connected. The parallel connection is illustrated in Figure 11
on page 23.
0702-019
Figure 11 Heating Power Connection with 20 V Power Supply
When a 20 V power supply is used, the heating power can also be connected to a single sensor. Refer to Figure 12 on page 23 and Figure
13 on page 24.
0702-020
Figure 12 Heating Power Connection for Anemometer Only
VAISALA_______________________________________________________________________ 23
Page 26
User's Guide ______________________________________________________________________
0702-021
Figure 13 Heating Power Connection for Wind Vane Only
NOTE

Wiring Examples

Figure 14 on page 25 illustrates the basic wiring when the WAA151 and
WAV151 wind sensors are connected to the WAC155 transmitter. Heating power is not connected in the figure.
Figure 15 on page 26 illustrates wiring with the WHP151 Mains Power
Supply, with heating power connected. Note that the WHP151 has jumpers for configuring the power output. Connect pins 2-3 of the X5 jumper to set the correct voltage, and remove the X4 jumper to provide continuous heating power. If you connect the heating in series to both sensors as shown in the figure, set the heating power to 38 Vrms 0.5 A by connecting pins 2-3 of the X8 jumper.
Figure 16 on page 27 illustrates the wiring with the WHP25 Mains
Power Supply and the WA252 series wind sensors. The WAC155 operating power is supplied from the WAA252 (+12Vout, F -> X2/3). Thus no external operating voltage shall be applied to the connector X2.
The expansion connector required for the high current wiring in Figure
16 on page 27 is included in the WAA252 accessories
24 ___________________________________________________________________M210822EN-A
Page 27
Chapter 3 _______________________________________________________________ Installation
0702-005
Figure 14 Basic Wiring with WAA151 and WAV151 Sensors
VAISALA_______________________________________________________________________ 25
Page 28
User's Guide ______________________________________________________________________
0702-022
Figure 15 Wiring with WHP151 Mains Power Supply
26 ___________________________________________________________________M210822EN-A
Page 29
Chapter 3 _______________________________________________________________ Installation
0702-006
Figure 16 Wiring with WHP25 Mains Power Supply and the
WA252 Series Wind Sensors
VAISALA_______________________________________________________________________ 27
Page 30
User's Guide ______________________________________________________________________

Mounting

Mounting WAC155 to the Top of a Pole Mast

Figure 17 on page 28 illustrates mounting of the WAC155 transmitter
to the top of a Ø 60 mm pole mast using the standard mounting clamp. The arrow on the cover of the junction box must point to north.
NOTE
0206-059
Figure 17 Mounting WAC155 to the Top of a Pole Mast
A long cable between different units (sensors, transmitters, power supplies, and displays) can cause a lethal surge voltage if a lightning strikes in the vicinity. Always ground the mast equipment case close to the mast with a short low-resistance cable.
28 ___________________________________________________________________M210822EN-A
Page 31
Chapter 3 _______________________________________________________________ Installation

Mounting Wind Sensors to WAC155

0110-005
Figure 18 Installation of the Wind Sensors WAA151 and
WAV151 to WAC155
The following numbers refer to Figure 18 on page 29. 1 = WAA151 Cup assembly 2 = WAV151 Tail assembly 3 = Cross arm 4 = WAC155 5 = Connector 6 = Mounting flange 7 = South 8=North

Alignment

After mounting the WAC155 transmitter to the mast, check that the WAV151 end of the cross arm is pointing to north with the required accuracy, see Figure 17 on page 28. To ensure a correct assembly after aligning the WAC155, you can mount the sensors on it only in one way.
VAISALA_______________________________________________________________________ 29
Page 32
User's Guide ______________________________________________________________________

Verification

Monitor the status indicator LED when powering up the WAC155 transmitter. The LED will flash green if the self-diagnostics are completed without errors, and red if there is an error condition.
An error condition may be caused by an erroneous installation, configuration, or a combination of both. For example, enabling sensor heating without connecting the heating power will cause an error state. You may be able to diagnose the problem using the service connection. Howerver, if the problem is with the operating power, the service connection may not be available even if the LED is flashing.
If the signal cable from the WAC155 transmitter is connected to a data collection system and the system is powered up, check that the wind readings react correctly. For testing the anemometer, rotate the cups manually. For testing the wind vane, hold the vane in a few fixed angles and verify the data.
30 ___________________________________________________________________M210822EN-A
Page 33
Chapter 4 ________________________________________________________________ Operation
CHAPTER 4
OPERATION
This chapter contains information that is needed to operate the Vaisala Serial Wind Transmitter WAC155.

User Interface

The WAC155 does not provide a direct user interface, except for a status indicator LED on the component board. The LED will flash green when the operational status is OK, and red when there is an error condition. The LED is activated for five minutes after the transmitter is powered up. The LED is also activated when the service connection is open.
The red LED does not indicate the type of the error. Service personnel must connect to the service connection to resolve the problem.
Data and service connections are provided over the RS-485 interface. These connections are described in the next section.

Communication Interfaces

The WAC155 transmitter communicates over a half-duplex RS-485 interface. The WAC155 can be configured to send wind data messages at regular intervals (auto-transmit mode), and it can provide the data as a response to an MWV query. The data is provided in standard NMEA wind speed and angle messages. In addition, a service interface is available for configuration and status information.
VAISALA_______________________________________________________________________ 31
Page 34
User's Guide ______________________________________________________________________
More than one transmitter can be connected to a single RS-485 bus. In the case of single transmitter, the auto-transmit mode can be used (the device transmits data messages with configured interval). If there are several transmitters in the same bus, auto-transmission may not be enabled, and data can be only polled by query.
Each device in the same bus has a unique configurable ID, containing
1..5 characters. Alphabetical characters a-z and A-Z (case-sensitive) are
accepted, as well as numbers 0-9.
Table 4 WAC155 Default Serial Communication Settings
Property Description / Value
Baud rate 9600 Data bits 8 Parity none Stop bit s 1

NMEA Message Format

The NMEA specification defines wind speed and angle message MWV as follows:
$WIMWV,<a.a>,<R>,<s.s>,<U>,<S>*<CS><cr><lf>
where $WIMWV = Fixed text at the start of the message <a.a> = Wind angle, 0..359 degrees <R> = Reference: R=relative, T=theoretical <s.s> = Wind speed <U> = Units: K=km/h, M = m/s, N=knots <S> = Status: A=valid, V=invalid * = Asterisk, indicating that the next field is the checksum <CS> = Two character checksum for the message
The comma "," is used as a separator between the fields. Here are some examples of MWV messages output by the WAC155:
32 ___________________________________________________________________M210822EN-A
Page 35
Chapter 4 ________________________________________________________________ Operation
$WIMWV,39,R,1.3,M,A*06 $WIMWV,39,R,0.5,M,A*01 $WIMWV,61,R,1.0,M,A*08 $WIMWV,59,R,1.2,M,A*01 $WIMWV,53,R,1.5,M,A*0c $WIMWV,46,R,1.2,M,A*0f $WIMWV,70,R,1.1,M,A*09

Polling Data using a Query

Polling for the MWV messages can be done using the following command:
$WIP<ID>Q,*<CS><cr><lf>
where $WIP= Fixed text at the start of the query <ID>= Transmitter device ID Q = Marks the message as a query * = Asterisk, indicating that the next field is the checksum <CS>= Two character checksum for the device ID
The data in the response follows the MWV message format, but the header is slightly different:
$P<ID>MWV,<a.a>,<R>,<s.s>,<U>,<S>*<CS><cr><lf>
where $P = Fixed text at the start of the response <ID> = Transmitter device ID MWV = Marks the message as a wind speed and angle message
After receiving a query that uses its device ID, the transmitter will reply with an MWV message containing the wind data. However, if you have not defined any messages of the type mwvmessage using the SETMES command, the transmitter will not respond.
Example polling command for transmitter with device ID "A":
$WIPAQ,*72
VAISALA_______________________________________________________________________ 33
Page 36
User's Guide ______________________________________________________________________
Example response:
$PAMWV,50,R,0.0,M,A*04
Table 5 on page 34 provides checksums and polling strings for some
typical device IDs.
Table 5 Checksum table
ID Character <id> Checksum <CS> Polling String
A 72 $WIPAQ,*72<cr><lf> B 71 $WIPBQ,*71<cr><lf> C70$WIPCQ,*70<cr><lf> D77$WIPDQ,*77<cr><lf> E 76 $WIPEQ,*76<cr><lf> F 75 $WIPFQ,*75<cr><lf> G 74 $WIPGQ,*74<cr><lf> H 7B $WIPHQ,*7B<cr><lf> I 7A $WIPIQ,*7A<cr><lf> J79$WIPJQ,*79<cr><lf> K 78 $WIPKQ,*78<cr><lf> L 7F $WIPLQ,*7F<cr><lf> M 7E $WIPMQ,*7E<cr><lf> N 7D $WIPNQ,*7D<cr><lf> O 7C $WIPOQ,*7C<cr><lf>

Service Connection

The service connection allows you to configure the device and gather status information. The same physical RS-485 interface connection is used for both the data transmission and the service connection. When the service connection is opened (using the OPEN command), the data transmission and query are disabled as long as the service connection remains open.
When you change any parameters using the service connection, remember that a reset (or a power-up) is required to take the new parameters into use.
The commands are not case-sensitive; formats 'COMMAND', 'command', 'Command' and all other combinations of upper and lower case letters are accepted. However, the device ID is case-sensitive. Commands are entered on a single line, terminated by a line feed <lf> or carriage-return <cr> characters. If the terminal provides both characters as the line end marker, the second EOL character is silently
34 ___________________________________________________________________M210822EN-A
Page 37
Chapter 4 ________________________________________________________________ Operation
discarded. Commands may include parameters and values which are separated by a space ' '. Only one parameter can be set with a single command; multiple parameters require multiple commands.
You can repeat the previous command by typing CTRL+P. The previous command will be brought to the console, but it will not be automatically executed. You can delete characters with the backspace key [<=]. Arrow keys are not available for data editing, and tabulator completion is not supported.
A list of the supported commands is provided in section List of Serial
Commands on page 35.

List of Serial Commands

The following table provides a list of the serial commands that are available in the service connection.
Table 6 List of Serial Commands
Command Description
OPEN Open the service connection CLOSE Close the service connection HELP Display the command list SETDEV Set the ID of the transmitter SETMEA Configure measurement parameters SETSPD Configure wind speed computation time period SETDIR Configure wind direction computation time period SETMES Specify data transmission mode SETCOM Configure communication ports SETALR Configure sensor stuck supervision functionality SETHEA Configure wind sensor heating control GETHEA Display the current heating status SERVICE TIMEOUT Configure timeout for service connection GETSET Display the current settings of the device ERRS Display the current error status INIE Reset the transmitter to factory default settings RESET R eset the transmitter to new settings
VAISALA_______________________________________________________________________ 35
Page 38
User's Guide ______________________________________________________________________
The sections below contain a description of each command. The meaning of the command line elements is presented in the table below.
Table 7 Meaning of the Command Line Elements
Element Meaning Text Style Used SAMPLE Specifies the name of
the command or utility.
{variable} Indicates a set of
choices from which the user must choose one, several or all.
[option] Indicates optional items. lower case enclosed in
<value> Specifies the value for
the option
. , : ; Punctuation marks are
considered as part of the command and should be included as they are.
<cr> Stands for pressing
ENTER (on your computer keyboard)
UPPER CASE BOLD
lower case enclosed in {braces}
[brackets] lower case enclosed in
<angle brackets> lower case
lower case

OPEN

The OPEN command establishes service communication with the transmitter. Transmitter configuration commands are effective only when the service connection is open.
OPEN [id]<cr>
where id = Case-sensitive device ID that specifies the transmitter
where the service connection is opened. Must be specified if a device ID has been set for the transmitter, or if there are multiple transmitters on the same RS-485 bus.
If there is only one transmitter on the RS-485 bus, and no device ID has been set for the transmitter using the SETDEV command, you can open the service connection without specifying the ID. The device ID can be
1..5 characters (a-z, A-Z, 0-9).
36 ___________________________________________________________________M210822EN-A
Page 39
Chapter 4 ________________________________________________________________ Operation
If there are multiple transmitters on the same bus, you should always open the service connection so that you specify the device ID. Do not install multiple transmitters on the same bus without assinging a different device ID for each transmitter.
NOTE
If you do not know the device ID of a transmitter, you can open the service connection by using the dollar sign "$" as the device ID:
OPEN $ Only use this command when you have a single transmitter on the bus.
The service connection will remain open until it is closed by the CLOSE command, or until the defined service timeout expires (i.e., no commands have been given within the defined timeout period). The timeout period is configured using the SERVICETIMEOUT command. Once the service connection is closed, the transmitter will return into the operation state it had prior to opening the connection, either auto-transmitting or polling mode.
Example:
>open
Vaisala Serial Wind Transmitter WAC155 SW version 2.0.7
Service connection opened >

CLOSE

The CLOSE command closes all current service connections. It is not necessary to define the device ID. Note that new parameters are not automatically taken into use when the service connection is closed; you must reset or power cycle the transmitter to do that.
CLOSE<cr> Example:
>close Service connection closed >
VAISALA_______________________________________________________________________ 37
Page 40
User's Guide ______________________________________________________________________

SETDEV

The SETDEV command sets the device ID of the transmitter. In a multi-transmitter network, the device ID of each transmitter must be unique.
SETDEV id <value><cr>
where value = Specifies the new device ID for the transmitter. The
ID may contain up to 5 characters, including A-Z, a­z, and 0-9. The ID is case-sensitive.
Example:
>setdev id A1 ID=A1 >

SETSPD

The SETSPD command configures the wind speed computation time period.
SETSPD average <value><cr>
where value = Wind speed computation time period in seconds. Range
0.25 ... 5.00 in 0.25 second increments (default 3.00)
Example:
>setspd average 3.00 AVERAGE=3.00 >

SETDIR

The SETDIR command configures the wind direction computation time period.
38 ___________________________________________________________________M210822EN-A
Page 41
Chapter 4 ________________________________________________________________ Operation
SETDIR average <value>
where value = W ind direction computation time period in seconds. Range
0.25 ... 5.00 in 0.25 second increments (default 3.00)
Example:
>setdir average 3.00 AVERAGE=3.00 >

SETMES

The SETMES command specifies the data transmission mode. The transmitter can support four (4) different messages at a time. Each message has its own settings for the message type and transmit inter val.
Three message types are supported:
- NONE (no message)
- MWV (standard wind speed and direction message)
- MWVQUERY (Vaisala extension to MWV message) SETMES {messagenumber} [type] [interval] <value><cr>
where messagenumber = The number of the message to configure. Range 0
... 3
type = Configures the message type. Possible values:
NONE MWV MWVQUER Y
interval = Configures the transmit interval. Zero value
disables data auto-transmission. Possible values: 0 ... 600.00 in 0.25 second increments
value = The value for the option.
VAISALA_______________________________________________________________________ 39
Page 42
User's Guide ______________________________________________________________________
Example:
>setmes 1 type mwvquery 0 TYPE=NONE INTERVAL=0.00 1 TYPE=MWVQUERY INTERVAL=1.00 2 TYPE=NONE INTERVAL=0.00 3 TYPE=NONE INTERVAL=0.00 >

SETMEA

The SETMEA command configures measurement parameters. The configurable parameters include anemometer transfer function parameters gain and offset.
SETMEA [allowedspdchange] [maxinvalidspdcount] [gaincorr] [offset] [powersave] <value><cr>
where allowedspdchange = Maximum allowed difference between two
adjacent samples in the sensor data, range
0.1 ... 25.0 (default 10.0)
maxinvalidspdcount= Maximum number of adjacent discarded
samples in the sensor data. Sensor data sanity check functionality is enabled if this value is not zero. Range 0 ... 15 (default 2)
gaincorr = Anemometer transfer function gain parameter.
Range 0.0 … 10.0 (default 0.09853)
offset = Anemometer transfer function offset
parameter. Range -10.0 … 10.0 (default
0.4054)
powersave = Defines whether sensor power is pulsed or
provided continuously. Pulsing saves power, since the sensors are only powered when they are being read. 0 = continuous power 1 = pulsed power (default)
value = Defines the value for the option.
40 ___________________________________________________________________M210822EN-A
Page 43
Chapter 4 ________________________________________________________________ Operation
Example:
>setmea offset 0.318 GAIN = 0.09853 OFFSET = 0.31800 POWERSAVE = 1 ALLOWEDSPDCHANGE = 10.0 MAXINVALIDSPDCOUNT = 2 >

SETCOM

The SETCOM command configures the co mmunication ports. Default communication port settings are 9600-n-8-1.
SETCOM [portnumber] [baudrate] [databits] [stopbits] [parity] [txddelay] <value><cr>
where portnumber= The number of the COM port to configure, 0 or 1. If
omitted, the configuration will apply to the current port in use.
baudrate = The baud rate of the port. Possible values: 300 600 1200
2400 4800 9600 19200 databits = The number of data bits, 7 or 8 stopbits = The number of stop bits, 1 or 2 parity = The parity to be used. Possible values: ODD EVEN
NONE txddelay = The RS-485 half-duplex transmission turn-around delay
in milliseconds, range 0 .. 200 value = The value for the option.
Example:
>setcom baudrate 9600 BAUDRATE = 9600 DATABITS = 8 PARITY = NONE STOPBITS = 1 TXDDELAY = 30 >
VAISALA_______________________________________________________________________ 41
Page 44
User's Guide ______________________________________________________________________

SETHEA

The SETHEA command configures the wind sensor heating control. Sensor heating is provided to prevent frost in sensor bearings. Heaters are powered by an external power supply, which is not the same as the sensor system power supply. Heating is not enabled by default. If necessary, heating can also be forced.
SETHEA [active] [tos] [thys] <value><cr>
where active = Enables the wind sensor heating functionality. Possible
values: 0 = disabled (default) 1 = enabled 2 = forced
tos = Control limit for heating in degrees Celcius, range -
55…+125 (default 4)
thys = Thermal hysteresis in degrees Celcius, range -55…+125
(default 1)
value = The value for the option
If heating is enabled, it is turned on when temperature drops below TOS-THYS. Heating is turned off when temperature rises above TOS+THYS. With the default values of TOS=4 and THYS=1, heating is enabled at +3 °C, and disabled at +5 °C.
Typical commands:
SETHEA ACTIVE 1 (enable sensor heating) SETHEA TOS 3 (set heating control limit to 3 degrees Celcius)
Example:
>sethea active 1 ACTIVE = 1 TOS = 4.00 THYS = 1.00 >

GETHEA

The GETHEA command displays the current heating status and temperature.
42 ___________________________________________________________________M210822EN-A
Page 45
Chapter 4 ________________________________________________________________ Operation
GETHEA<cr> Example:
>gethea Heating OFF Temperature 14.25 >

SETALR

The WAC155 can monitor the wind sensor movement to detect if the sensors appear to be stuck in place. The SETALR command is used to configure this functionality.
If the functionality is enabled and timeouts are not zero, sensors are cross-checked for changes, i.e. if the reading of the other sensor changes, but the other one does not for certain period of time, the sensor is considered stuck.
SETALR [active] [dir] [spd] [calm] [dirlimit] [spdlimit] <value><cr>
where active = Enables the wind sensor stuck supervision functionality. 0
or 1 (default 0)
dir = Timeout for wind direction change, range 0 ... 256 (default
60) spd = Timeout for wind speed change, range 0 ... 256 (default 60) calm = The calm timeout. Defines how long both sensors may be
unchanged until both sensors are considered being stuck. Range 0 ... 65535 (default 1440)
dirlimit = Threshold limit for wind direction change. If the wind
direction change is below the threshold, it is considered unchanged from the wind sensor stuck functionality point of view. Range 0 ... 180 (default 3)
spdlimit = Threshold limit for wind speed change. If the wind speed
change is below the threshold, it is considered unchanged from the wind sensor stuck functionality point of view. Range 0.0 ... 10.0 (default 0.0)
value = The value for the option
VAISALA_______________________________________________________________________ 43
Page 46
User's Guide ______________________________________________________________________
Typical commands:
SETALR ACTIVE 1 (activate the alarm functionality) SETALR DIR 60 (alarm if wind vane stuck for 60 seconds) SETALR SPD 60 (alarm if anemometer stuck for 60 seconds) SETALR CALM 1440 (alarm if both sensors stuck for 1440 minutes)
Example:
>setalr active 1 ACTIVE= 1 DIR= 60 SPD= 60 CALM= 1440 DIRLIMIT= 3 SPDLIMIT= 0.0 >

SERVICE TIMEOUT

The SERVICE TIMEOUT command configures the timeout period of the auto-close function of the service connection. If no data is input within the configured time interval, the connection will close itself and the device returns it normal operational state.
Zero value disables the auto-close function, which means that the service connection will never close unless explicitly closed using the
CLOSE command. SERVICE TIMEOUT <value><cr>
where value = The value of the service timeout, range 0 ... 30 min (default
5 min).
Example:
>service timeout 5 TIMEOUT=5 >
44 ___________________________________________________________________M210822EN-A
Page 47
Chapter 4 ________________________________________________________________ Operation

GETSET

The GETSET command will return the current configuration of the current unit.
GETSET <cr> Example:
>getset SETDEV ID=A1 SETSPD AVERAGE=3.00 SETDIR AVERAGE=3.00 …

HELP

The HELP command displays a list of the supported commands.
HELP<cr> Example:
>help CLOSE Close service connection SETDEV Set device ID SETSPD Speed computation average length SETDIR Direction computation average length ...

INIE

The INIE command resets the transmitter to factory defaults. Note that the current configuration settings will be lost. Before using the INIE command, it may be a good idea to view the current settings using the GETSET command , and record the output.
After using this command, you have to use the RESET command to take the factory defaults into use, and re-open the service connection with the OPEN command.
INIE <cr>
VAISALA_______________________________________________________________________ 45
Page 48
User's Guide ______________________________________________________________________
Example:
>inie FACTORY DEFAULTS >

RESET

The RESET command resets the transmitter, and takes any new configuration settings into use. After using this command, you have to re-open the service connection with the OPEN command.
RESET <cr> Example:
>RESET Wait 5 seconds delay...

ERRS

When issued alone without the [mask] option, the ERRS command returns the current error status of the transmitter. Possible errors, their codes, and the corresponding hexadecimal values are described inTable
10 on page 52.
You can use the [mask] option to define the set of errors that causes NMEA messages to be marked as invalid. The error mask is a hexadecimal number formed by combining the hexadecimal values of the desired errors. By default the mask is 0010 which means that only if both wind sensors are missing or broken, the NMEA data is invalid.
0400 + 0800 = 0C00
46 ___________________________________________________________________M210822EN-A
Page 49
Chapter 4 ________________________________________________________________ Operation
ERRS [mask] <value><cr>
where mask = Implements an error mask. value = The value for the error mask in hexadecimal format
(default 0010).
Example:
>errs Active errors:
ERROR 5: Heating control broken or heating power missing
ERRS = 0020 MASK = 0010 >
VAISALA_______________________________________________________________________ 47
Page 50
User's Guide ______________________________________________________________________
48 ___________________________________________________________________M210822EN-A
Page 51
Chapter 5 ______________________________________________________________ Maintenance
CHAPTER 5
MAINTENANCE
This chapter provides information that is needed in basic maintenance of the Vaisala Serial Wind Transmitter WAC155.

Periodic Maintenance

Visual Checking

Check every 1 to 2 years that the component board is not corroded.

Replacing Consumables

When replacing the component board, read carefully the section
ESD Protection on page 9.

Parts List for Consumables

Table 8 Available Spare Parts
Spare Part Order Code
Component Board for WAC155 WAC155CB Sensor Cable for Anemometer (0.8m) ZZ45036 Sensor Cable for Wind Vane (0.8m) ZZ45037
VAISALA_______________________________________________________________________ 49
Page 52
User's Guide ______________________________________________________________________
50 ___________________________________________________________________M210822EN-A
Page 53
Chapter 6 ___________________________________________________________ Troubleshooting
CHAPTER 6
TROUBLESHOOTING
This chapter describes common problems, their probable causes and remedies, and contact information.

Problem Situations

Table 9 Problem Situations and Corrective Actions
Problem Possible cause Action
Data is not received by the data collecting system
Shaft heating of the sensors is not working.
Improper or loose connections. Check wiring and tighten the
screw terminals.
Incorrect messaging settings. Check and correct using the
service connection.
Power failure. Check that the power supply is
online.
Heating power is not connected properly.
Heating is not enabled in the transmitter settings.
Power failure of the heating power supply.
Check wiring and tighten the screw terminals.
Check and correct using the service connection.
Check that the power supply is online.
VAISALA_______________________________________________________________________ 51
Page 54
User's Guide ______________________________________________________________________

Error Messages

The table below describes the error codes defined in the WAC155. If you use the ERRS command to specify an error mask, use the hexadecimal values that are provided in the table. For help in using the service connection to read the errors and configure the WAC155, refer to section List of Serial Commands on page 35.
Table 10 Self-diagnostics Error Codes
Error # H ex
equivalent
0 0001 Input voltage too low Input voltage below accepted limit,
1 0002 Input voltage too high Over-voltage condition 2 0004 Wind speed sensor missing or
3 0008 Wind direction sensor missing or
4 0010 Both sensors missing or broken Wind speed and direction sensors
5 0020 Heating control malfunction or
6 0040 Erroneous reading from temperature
7 0080 Internal error in non-volatile memory
8 0100 Internal error This error code is reserved for future
9 0200 Temperature sensor not calibrated.
10 0400 Wind direction sensor stuck The wind vane has not turned for a
11 0800 Wind speed sensor stuck Anemometer has not turned for the
12 1000 Both wind sensors stuck Both wind sensors have not turned
Message Description
sensor behaviour not defined
Self-diagnostics does not detect the
broken
broken
heating power missing
sensor
access
Heating control malfunctioning.
proper voltage drop caused by an operational sensor
Self-diagnostics does not detect the proper voltage drop caused by operational sensor
are both missing or broken Heating power control mechanism
malfunctioning or heating power is not connected
Internal temperature sensor gives erroneous readings
Storing or reading parameters from the internal non-volatile memory failed
use Production time calibration not
performed, temperature readings are erroneous
certain period, but the anemometer has
configured period of time, but the wind vane has
for a long time
52 ___________________________________________________________________M210822EN-A
Page 55
Chapter 6 ___________________________________________________________ Troubleshooting

Technical Support

For technical questions, contact the Vaisala technical support: E-mail helpdesk@vaisala.com Fax +358 9 8949 2790

Return Instructions

If the product needs repair, please follow the instructions below to speed up the process and to avoid extra costs to you.
1. Read the section Warranty on page 10.
2. Contact a Vaisala Service Center or a local Vaisala representative.
The latest contact information and instructions are available from www.vaisala.com. Addresses of the Service Centers are provided in section Vaisala Service Centers on page 54.
Please have the following information on hand:
- serial number of the unit
- date and place of purchase or last calibration
- description of the fault
- circumstances in which the fault occurs/occurred
- name and contact information of a technically competent person who can provide further information on the problem
3. Pack the faulty product in a strong box of adequate size, with proper cushioning material to avoid damage.
4. Include the information specified in step 2 in the box with the faulty product. Also include a detailed return address.
5. Ship the box to the address specified by your Vaisala contact.
VAISALA_______________________________________________________________________ 53
Page 56
User's Guide ______________________________________________________________________

Vaisala Service Centers

Vaisala Service Centers perform calibrations and adjustments as well as repair and spare part services. See contact information below.
Vaisala Service Centers also offer accredited calibrations, maintenance contracts, and a calibration reminder program. Do not hesitate to contact them to get further information.
./24(!-%2)#!.3%26)#%#%.4%2
6AISALA)NC$'ILL3TREET7OBURN-!53!
0HONE&AX %MAILUSCUSTOMERSUPPORT VAISALACOM
%52/0%!.3%26)#%#%.4%2
6AISALA)NSTRUMENTS3ERVICE6ANHA.URMIJÊRVENTIE&).6ANTAA&).,!.$
0HONE&AX
%MAILINSTRUMENTSSERVICE VAISALACOM
4/+9/3%26)#%#%.4%2
6AISALA+++AGURAZAKA#HOME3HINJUKU+U4OKYO*!0!.
0HONE&AX %MAILAFTERSALESASIA VAISALACOM
"%)*).'3%26)#%#%.4%2
6AISALA#HINA,TD&LOOR%!3"UILDING.O8IAO9UN2OAD$ONGSANHUAN"EILU
#HAOYANG$ISTRICT"EIJING02#().! 0HONE&AX %MAILCHINASERVICE VAISALACOM
ZZZYDLVDODFRP
54 ___________________________________________________________________M210822EN-A
Page 57
Chapter 7 ____________________________________________________________ Technical Data
CHAPTER 7
TECHNICAL DATA
This chapter provides technical data of the Vaisala Serial Wind Transmitter WAC155.

Specifications

Table 11 Performance
Property Description/Va lue
Equipment type Digital-to-RS-485 serial bus converter for
Full scale: for direction for speed
Resolution: for direction for speed
Updating interval: for direction for speed
Pulse-mode power feed: to the vane to the anemometer
Vaisala wind sensors
0 ... 360° 0 ... 75 m/s
5.625° (1.4° achieved by calculation)
0.1 m/s
3 s (default) 3 s (default)
500 µs / 4 Hz Nominal 50 µs / 2400 Hz Nominal
VAISALA_______________________________________________________________________ 55
Page 58
User's Guide ______________________________________________________________________
Table 12 Inputs and Outputs
Property Description/Value
Signal input: wind direction wind speed
Input operating power 9 ... 15.5 VDC, 8 mA typical incl. sensors
Maximum operating power 50 mA (when power-save mode is disabled) Input heating power 16 ... 24 VAC or VDC
Typical heating power 500 mA per sensor Output signals RS-485 serial bus Signal cable 4 wires minimum: VIN+, VIN-, RS-485 A(-),
6-bit parallel GRAY code Pulse frequency 0 ... 750 Hz
(when power-save mode is enabled)
32 ... 48 VAC or VDC can be used when heating power is connected in series to both sensors
RS-485 B(+)
Table 13 Operating Conditions
Property Description/Value
Temperature range: operating storage
Humidity 0 ... 100 %RH
-55 ... +55 °C
-60 ... +70 °C
Table 14 Dimensions and Mechanics
Property Description/Value
Dimensions: printed circuit board jucntion box
Cross arm length 800 mm Ingress protection IP65 Mounting To a Ø 60 mm pole mast Weight 1.5 kg Material:
cross arm junction box
115 × 58 mm 125 (w) × 80 (h) × 57 (d) mm
AI anodized AI painted gray
2
56 ___________________________________________________________________M210822EN-A
Page 59
Chapter 7 ____________________________________________________________ Technical Data

Dimensions in mm (inches)

0702-009
Figure 19 WAC155 Dimensions
VAISALA_______________________________________________________________________ 57
Page 60
www.vaisala.com
*M210822EN*
Loading...