Vaisala HMT100 Technical data

www.vaisala.com
HMT100 Series Humidity and Temperature Transmitter for Demanding HVAC Applications
HMT100 remote probe and wall mount models.
Features/Benefits
Full 0 ... 100 %RH measurement
Two-wire loop-powered or
three-wire voltage output configurations
Fixed and remote probe
models
Display available
Relative humidity, dewpoint,
temperature outputs
Vaisala HUMICAP® sensor
Interchangeable probe module
for minimal maintenance downtime
Dierent output scalings
Compatible with hand-helds
HM70 and HMI41 for calibration
IP65 (NEMA 4) housing
NIST traceable (certificate
included)
The Vaisala HUMICAP® Humidity and Temperature Transmitter Series HMT100 are designed for humidity and temperature monitoring in demanding environments.
Typical applications include stability rooms, HVAC, livestock farms, greenhouses, indoor swimming pools, and outdoor applications.
Performance
HMT100 incorporates Vaisala HUMICAP relative humidity accurately and reliably. Vaisala HUMICAP resistant to dust and most chemicals.
Available options
The HMT100 is available as a wall mount or remote probe model with an optional display. For high temperature applications or where space is limited, the remote probe is ideal.
®
technology that measures
®
is also
HMT100 can show relative humidity only, dewpoint only, or relative humidity and temperature, or dewpoint and temperature readings.
The probes are interchangeable without having to calibrate or adjust the transmitter.
HMT100 can also be installed outdoors using an installation kit, or directly into an air conditioning channel using a duct installation kit.
Annual calibration
Calibration is recommended typically at an interval of one year using either the Vaisala HUMICAP Humidity and Temperature Meter HM70 or the Vaisala HUMICAP Humidity Indicator HMI41.
The accuracy of the instrument can also be checked using the Vaisala Humidity Calibrator HMK15, which is based on saturated salt solutions.
®
Hand-held
®
Technical data
Performance
RELATIVE HUMIDITY
Measurement range 0 ... 100 %RH Accuracy against factory standards including non-linearity, hysteresis, and repeatability
at +15 ... +25 °C (+59 ... +77 °F) ±1.7 %RH (0 ... 90 %RH)
±2.5 %RH (90 ... 100 %RH) at ±0 °C ... +40 °C (+32 ... +104 °F) ±(1.7 +0.015 x reading) %RH at -40 ... ±0 °C, +40 ... +80 °C ±(2.0+0.025 x reading) %RH (-40 ... +32 °F, +104 ... +176 °F)
Factory calibration uncertainty at +20 °C (+68 °F) Response time (90 %) at 20 °C in still air
Humidity sensor Vaisala HUMICAP
TEMPERATURE
Measurement range -40 ... +80 °C (-40 ... 176 °F) Accuracy at +20 °C (+68 °F) ±0.2 °C (±0.36 °F)
ACCURACY OVER TEMPERATURE RANGE
±1.0 %RH (0 ... 15 %RH)
±1.5 %RH (>15 ... 78 %RH)
8 s with plastic grid
20 s with membrane filter
40 s with sintered filter
®
180
Inputs and outputs
Two-wire output signal 4 ... 20 mA
External loop load 10 ... 35 VDC (R
20 ... 35 VDC (R
= 0 ohms)
L
= 500 ohms)
L
Voltage output signals 0 ... 1 V, 0 ... 5 V, 0 ... 10 V
(0 ... X V see order form) Supply voltage 10 ... 35 VDC/24 VAC Current consumption, 35 VDC/24 VAC max. 12 mA External load R
min. 10 kΩ
L
Mechanics
Material
Housing ABS/PC plastic Probe chrome coated aluminum Mounting plate GM45160 ABS plastic
Housing classification IP65 (NEMA 4) Sensor protection
Plastic grid DRW010522 Plastic grid with membrane filter DRW010525 Sintered stainless steel filter HM46670SP
Connections screw terminals 0.5 ... 1.5 mm Probe cable lengths 3 m, 5 m, 10 m Calibration with HM70, HMI41,
or with internal 11 %RH & 75 %RH buttons
Display option
One line fixed variable or changing variables when two variables are ordered
2
Temperature sensor Pt1000 IEC 751 1/3 class B
DEWPOINT TEMPERATURE (CALCULATED)
Measuring range -20 ... +80 °C (-4 ... +176 °F)
Operating Environment
Operating temperature range
transmitter body, no display -40 ... +60 °C (-40 ... +140 °F) transmitter body, with display -30 ... +60 °C (-22 ... +140 °F)
probe (remote probe only) -40 ... +80 °C (-40 ... +176 °F) Storage temperature range -40 ... +60 °C (-40 ... +140 °F) Electromagnetic compatibility
Industrial Environment
For more information, visit www.vaisala.com or contact us at sales@vaisala.com
EN61326-1,
Options and accessories
Spare probe HMP100 Spare extension cable (10 m) DRW220095 Radiation shield DTR502B Rain shield with installation kit 215109 Installation plate DRW010699 Duct installation kit 215619 Connection cable for HMI41 2591722 Connection cable for HM70 211339
Ref. 210472EN-B ©Vaisala 2009
This material is subject to copyright protection, with all copyrights retained by Vaisala and its individual partners. All rights reserved. Any logos and/or product names are trademarks of Vaisala or its individual partners. The reproduction, transfer, distribution or storage of information contained in this brochure in any form without the prior written consent of Vaisala is strictly prohibited. All specifications — technical included — are subject to change without notice.
Loading...