Vaisala GMW45 Technical data

P.O. Box 26, FIN-00421 Helsinki, FINLAND
Tel: +358 9 894 91
Fax: +358 9 8949 2485
Email: industrialsales@vaisala.com
www.vaisala.com
Features/Benefits
Compact wall mount transmitter
for demand controlled ventilation
Incorporates Vaisala CARBOCAP®
Sensor - the silicon-based NDIR sensor
Excellent long-term stability
Five year recommended calibration
interval
Easy-to-install
Vaisala CARBOCAP® Carbon Dioxide Transmitter GMW45 is a basic wall mount transmitter for demand controlled ventilation.
The wall mount Vaisala CARBOCAP® Carbon Dioxide Transmitter GMW45 is ideal for monitoring the air quality in public, commercial and residential buildings. By monitoring CO2 in air with GMW45 and ventilating only on demand, indoor air can be kept fresh with no wasted energy.
Vaisala CARBOCAP
®
technology
The GMW45 transmitter features a silicon-based Vaisala CARBOCAP® Sensor. Due to its built-in reference measurement capabilities and simple structure, the sensor is extremely stable and reliable.
The temperature dependence of CARBOCAP® is negligible. In addition, the measurement accuracy of the sensor is not affected by dust, water vapor or most chemicals.
Easy maintenance
The recommended calibration interval for the GMW45 transmitter is five years. The use of the GMW45 results in considerable savings in energy consumption, maintenance and recalibration costs, and it ensures the best possible control of air quality.
Basic DCV transmitter
The GMW45 is a basic cost-effective CO2transmitter intended to be used in building energy management systems. It is easy to install. If CO2transmitters with additional measurements are required, Vaisala offers a wide variety of wall and duct mount CO2, CO2+T, RH and RH+T transmitters for demand controlled ventilation.
94 Vaisala Instruments Catalog 2005
94
Ref. B210435en rev. A
GMW45
24V OUTGND
0-10V 0-20mA 4-20mA
0-10V
0-20mA
4-20mA
SELECTED
SELECTED
SELECTED
POWER SUPPLY
ANALOGUE OUTPUT
OUTPUT SELECTION JUMPERS
OUT24V GND
Technical Data
CARBON DIOXIDE
Carbon dioxide
Measuring range 0...2000 ppm CO Accuracy at +25 °C (+77 °F) against certified factory references
<±[40 ppm CO
(includes repeatability and
+ 3% of reading]
2
calibration uncertainty) Non-linearity <±1.0 %FS Temperature dependence 0.15 %FS /°C of output (typically) Long-term stability <5.0 %FS /5 years Recommended calibration interval 5 years Response time (0...63%) 1 minute
Operating conditions
Operating temperature range -5…+45 °C (23 …113 °F) Humidity range 0...85 %RH
non-condensing
General
Output signals for CO
2
Resolution of analog outputs 10 ppm CO Recommended external load:
current output max. 500 Ohm
voltage output min. 1 kohm Power supply nominal 24 VAC/VDC Power consumption <2.5 W Warm-up time 1 minute
30 minutes full specification Housing material ABS plastic Weight 75 g Complies with EMC standard EN61326-1:1997 + Am1:1998 + Am2:2001; Generic Environment.
Selectable
0...20 mA or
4...20 mA or
0...10 V
Dimensions
2
Dimensions in mm
Wiring
2
CARBOCAP® is a registered trademark of Vaisala. Specifications subject to change without prior notice. ©Vaisala Oyj
Accessories
GM35001 Calibration pipe 19222GM Calibration software kit
GM70 hand-held carbon dioxide meter GM70 w/pump option hand-held CO2 meter for field verification
Ref. B210435en rev. A
(includes disk and serial COM adapter)
95Vaisala Instruments Catalog 2005