Vaisala GMW116 Technical data

www.vaisala.com
GMW116 Carbon Dioxide and Temperature Transmitter for Ventilation Control
The Vaisala CARBOCAP® Carbon Dioxide and Temperature Transmitter GMW116.
Features/Benefits
Compact dual-parameter
transmitter: measures both CO
and T
2
Incorporates Vaisala
CARBOCAP®, the silicon based NDIR sensor with unique internal referencing
Advanced, single-beam, dual
wavelength measurement with no moving parts
Excellent long-term stability
Ideal for ventilation control in
all types of occupied spaces including those with around­the-clock occupancy
No need for temperature
compensation
The Vaisala CARBOCAP® Carbon Dioxide and Temperature Transmitter GMW116 is the compact-size transmitter that measures both carbon dioxide and temperature. The sensor is accurate and durable and it has an excellent long-term stability, which decreases maintenance.
The excellent performance of the Vaisala CARBOCAP largely from the stable reference provided by the electrically tunable Fabry-Perot Interferometer (FPI).
In buildings with around-the­clock occupancy (e.g. hospitals, work-places, residential buildings, retirement homes), the assumed background CO is simply not applicable. The true internal reference measurement of
®
sensors results
level reference
2
®
Vaisala CARBOCAP provides years of stable CO measurements.
The GMW116 Transmitter is designed especially for demand controlled ventilation applications with CO measurement range of 0 … 2000 ppm and temperature range of 0 ... +50 °C.
With GMW116 there is no need for temperature compensation. The ideal gas temperature behaviour is taken into account automatically.
CO2 transmitters
2
2
Technical data
Performance
CO2-measurement range 0 ... 2000 ppm Temperature measurement range 0 ... +50 °C Accuracy (including repeatability, non­linearity and calibration uncertainty)
± (2 % of range + 2 % of
reading Long-term stability ± 5 % of range/5 years Response time T90 1 min Temperature dependence compensated Pressure dependence, typical +0.15 % of reading/hPa Temperature measurement accuracy ± 0.7 °C at 25 ° Warm-up time 1 min, 10 min for full.
specification
Product lifetime > 10 years
Operating environment
Temperature 0 ... +50 °C Humidity 0 ... 85 % RH Pressure 700 ... 1200 hPa Electromagnectic compatibility
Complies with EMS standard EN61326-1, Generic Environment
Inputs and outputs
Operating voltage 24 V (±20 %) AC/DC Power consumption <2 W Outputs 0 … 10 V
Dimensions
Housing
Material ABS/PC blend plastics Weight 120 g Cover and base colour white RAL 9003 Fire resistance UL94 V0 Ingress protection IP30
For more information, visit www.vaisala.com or contact us at sales@vaisala.com
Ref. B210872EN-A ©Vaisala 2010
This material is subject to copyright protection, with all copyrights retained by Vaisala and its individual partners. All rights reserved. Any logos and/or product names are trademarks of Vaisala or its individual partners. The reproduction, transfer, distribution or storage of information contained in this brochure in any form without the prior written consent of Vaisala is strictly prohibited. All specifications — technical included — are subject to change without notice.