www.vaisala.com
GMW116 Carbon Dioxide and Temperature
Transmitter for Ventilation Control
The Vaisala CARBOCAP® Carbon Dioxide and Temperature Transmitter GMW116.
Features/Benefits
Compact dual-parameter
▪
transmitter: measures both
CO
and T
2
Incorporates Vaisala
▪
CARBOCAP®, the silicon based
NDIR sensor with unique
internal referencing
Advanced, single-beam, dual
▪
wavelength measurement with
no moving parts
Excellent long-term stability
▪
Ideal for ventilation control in
▪
all types of occupied spaces
including those with aroundthe-clock occupancy
No need for temperature
▪
compensation
The Vaisala CARBOCAP® Carbon
Dioxide and Temperature Transmitter
GMW116 is the compact-size
transmitter that measures both
carbon dioxide and temperature. The
sensor is accurate and durable and it
has an excellent long-term stability,
which decreases maintenance.
The excellent performance of the
Vaisala CARBOCAP
largely from the stable reference
provided by the electrically tunable
Fabry-Perot Interferometer (FPI).
In buildings with around-theclock occupancy (e.g. hospitals,
work-places, residential buildings,
retirement homes), the assumed
background CO
is simply not applicable. The true
internal reference measurement of
®
sensors results
level reference
2
®
Vaisala CARBOCAP
provides years of stable CO
measurements.
The GMW116 Transmitter is designed
especially for demand controlled
ventilation applications with CO
measurement range of
0 … 2000 ppm and temperature range
of 0 ... +50 °C.
With GMW116 there is no need for
temperature compensation. The ideal
gas temperature behaviour is taken
into account automatically.
CO2 transmitters
2
2
Technical data
Performance
CO2-measurement range 0 ... 2000 ppm
Temperature measurement range 0 ... +50 °C
Accuracy (including repeatability, nonlinearity and calibration uncertainty)
± (2 % of range + 2 % of
reading
Long-term stability ± 5 % of range/5 years
Response time T90 1 min
Temperature dependence compensated
Pressure dependence, typical +0.15 % of reading/hPa
Temperature measurement accuracy ± 0.7 °C at 25 °
Warm-up time 1 min, 10 min for full.
specification
Product lifetime > 10 years
Operating environment
Temperature 0 ... +50 °C
Humidity 0 ... 85 % RH
Pressure 700 ... 1200 hPa
Electromagnectic compatibility
Complies with EMS standard EN61326-1, Generic Environment
Inputs and outputs
Operating voltage 24 V (±20 %) AC/DC
Power consumption <2 W
Outputs 0 … 10 V
Dimensions
Housing
Material ABS/PC blend plastics
Weight 120 g
Cover and base colour white RAL 9003
Fire resistance UL94 V0
Ingress protection IP30
For more information, visit
www.vaisala.com or contact
us at sales@vaisala.com
Ref. B210872EN-A ©Vaisala 2010
This material is subject to copyright protection, with all
copyrights retained by Vaisala and its individual partners. All
rights reserved. Any logos and/or product names are trademarks
of Vaisala or its individual partners. The reproduction, transfer,
distribution or storage of information contained in this brochure
in any form without the prior written consent of Vaisala is strictly
prohibited. All specifications — technical included — are subject