Vaisala GMW115 Technical data

www.vaisala.com
GMW115 Carbon Dioxide Transmitter for Demand-controlled Ventilation
from the stable reference provided by the electrically tunable Fabry-Perot Interferometer (FPI).
The tunable FPI lter measures CO absorption, and simultaneously a reference wavelength. This internal reference measurement compensates effectively for any changes in the
The Vaisala CARBOCAP® Carbon Dioxide Transmitter GMW115 is a wall-mounted CO
2
Features/Benefits
Compact, wall-mounted
transmitter for demand­controlled ventilation
Incorporates Vaisala
CARBOCAP®, the silicon based NDIR sensor with unique internal referencing
Advanced, single-beam, dual
wavelength measurement with no moving parts
Excellent long-term stability
Ideal for ventilation control in
all types of occupied spaces
Most of us spend 90 % of our time indoors. Consequently, good indoor air quality is important to our wellbeing. All human beings produce carbon dioxide gas by respiration, thus the carbon dioxide level can be used as an indicator for indoor human presence. A high CO sign of poor ventilation and often an indication of other unpleasant odors in the air. In many buildings the ventilation need varies throughout the day. Demand controlled ventilation is an economical way to ensure good air quality.
The Vaisala CARBOCAP sensors have been proven to be accurate and durable. They have an excellent long-term stability, which decreases maintenance. The superior performance of Vaisala CARBOCAP
®
sensors results largely
®
CO2
level is a
2
optical path, such as light source intensity changes and contamination. In the HVAC market, this type of reference measurement is a unique feature to Vaisala CARBOCAP products, distinguishing them from competitors’ comparative products that do not have a reference measurement at all, or have an indirect reference measurement, which is based on an assumed back­ground CO around-the-clock occupancy (e.g. hospitals, work-places, residential buildings, retirement homes), the assumed background CO reference is simply not applicable. The true internal reference measurement of Vaisala CARBOCAP CO
transmitters provides years of
2
stable CO
The GMW115 Transmitter is designed especially for DCV (Demand Controlled Ventilation) applications with two optional CO 0…2000 ppm and 0…5000 ppm.
levels. In buildings with
2
measurements.
2
measurement ranges of
2
level
2
2
®
®
66.3
60
60
Ø 4.2
66.7
85.3
83.4
85.2
R2.1
124
120.9
25.8
84
R3.5
Technical data
Performance
CO2-measurement range 0 ... 2000 ppm
0.....5000 ppm
Accuracy (including repeatability, non­linearity and calibration uncertainty)
±(2 % of range + 2 % of
reading) Long-term stability ± 5 % of range/5 years Response time T90 1 min Temperature dependence, typical -0,35 % of reading / °C Pressure dependence, typical +0,15 % of reading/hPa Warm-up time 1 min, 10 min for full.
specification
Product lifetime > 10 years
Operating environment
Temperature -5 ... +45 °C (23 ... 113 °F) Humidity 0 ... 85 % RH Pressure 700 ... 1200 hPa Electromagnectic compatibility
Complies with EMS standard EN61326-1, Generic Environment
Inputs and outputs
Operating voltage 24 V (±20 %) AC/DC Power consumption <2 W Outputs 4 … 20 mA, 0 … 10 V,
RS-485, 2-wire, non-isolated
Dimensions
Dimensions in mm
Housing
Material: ABS plastics Colour: Cycolac 233599/NCS 0502-G50Y Fire resistance: UL94 HB Ingress protection: IP30
For more information, visit www.vaisala.com or contact us at sales@vaisala.com
Ref. B210568EN-D ©Vaisala 2009
This material is subject to copyright protection, with all copyrights retained by Vaisala and its individual partners. All rights reserved. Any logos and/or product names are trademarks of Vaisala or its individual partners. The reproduction, transfer, distribution or storage of information contained in this brochure in any form without the prior written consent of Vaisala is strictly prohibited. All specifications — technical included — are subject to change without notice.
Loading...