Universal Enterprise HA1 Installation Manual

Page 1
INSTRUCTION MANUAL
HA1
1-800-547-5740 • Fax: (503) 643-6322
www.ueitest.com • email: info@ueitest.com
Hermetic Compressor Analyzer
Page 2
Introduction
The HA1 analyzes and tests hermetic compressors at up to 25 amps of running current. Connects directly to the compressor motor eliminating the
ation system start capacitor.
refriger
Features include
• 3 Ranges of 250 V AC starting capacitors between 88-301 MFD
• Dual voltage oper
ation of 120/240 V AC
• Indicates continuity & ground faults in motor windings with LED lights
• Free locked rotors by reversing motor action
• Convenient breakout jacks for measuring voltage and resistance
Safety Notes
Before using this instrument, read all safet this manual the word "WARNING" is used to indicate conditions or actions that may pose physical hazards to the user. The word "CAUTION" is used to indicate conditions or actions that may damage this instrument.
• Do not attempt to measure any voltage that exceeds the category based rating of this meter
• Do not attempt to use this instrument if either the meter or the test leads have been damaged. Turn it in for repair at a qualified repair facility
• Ensure instrument leads are fully seated by making a quick continuity check of the leads prior to making voltage measurements
• Keep your fingers away from the test lead’s metal probe contacts when making measurements. Always grip the leads behind the finger guards molded into the probes
• Use a current clamp adapter when measuring current that may exceed 10 amps. See the accessories in UEi’s full-line catalog
• Do not open the instrument to replace batteries or fuses while the probes are connected
y information carefully. In
• In the event of electrical shock, ALWAYS bring the victim to the emergency room for evaluation, regardless of the victim’s apparent recovery - Electrical shock can cause an unstable heart rhythm that may need medical attention
• Higher voltages and currents require greater awareness of
al safety hazards - Before connecting the test leads; turn
physic
wer to the circuit under test; set the instrument to the
off po desired function and range; connect the test leads to the instrument first, then to the circuit under test. Reapply power
• If any of the following indications occur during testing, turn
off the power source to the circuit under test:
• Arcing
• Flame
• Smoke
• Extreme Heat
• Smell of Burning Materials
• Discoloration or Melting of Components
CAUTION!
Do not attempt to remove the instruments leads from the circuit under test. The leads, the meter, or the cir
cuit under test may have degraded to the point that they no longer provide protection from the voltage and current applied. If any of these erroneous readings are observed, disconnect power immediately and recheck all settings and connections
Controls and Indicators
7
6
5
WARNING!
Exceeding the specified limits of this instrument is dangerous and can expose the user to serious or possibly fatal injury.
• Voltages above 60 volts DC or 25 volts AC may constitute a serious shock hazard
• Always turn off power to a circuit (or assembly) under test before cutting, unsoldering, or breaking the current path ­Even small amounts of current c Always disconnect the live test lead before disconnecting the
an be dangerous
common test lead from a circuit
HA1-MAN
2
1
3
8
4
9
1. PWR Breaker: This is a combination 25A circuit breaker and a POWER ON switch.
2. CAP 100/300/200: Selects one of the three starting capacitor ranges:
osition
P
FD 88-108MFD
00M
1
Range
200MFD 161-193MFD 300MFD 249-301MFD
P. 1
Page 3
EV/OFF/FWD:
3. R the compressor. In the “ compressor motor run winding, and the start capacitor is connected to the ST applied to the compressor motor start winding and the start capacitor is connected to the RUN cable. In the “ the power circuit to the motor is broken.
This switch determines the mode of oper
FWD” position, power is applied to the
ART cable. In the “REV” position, po
OFF” position,
ation of
wer is
est Jacks:
9. T cable of the corresponding color: GROUND = yellow, START = red, and RUN = black. The purpose of the test jacks is to facilitate resistance and voltage readings by enabling voltmeter/ohm meter test leads to be connected to the compressor motor circuit by inserting them into the appropriate jack at the HA1 front panel.
The four test jacks are connected directly to the test
COMMON = white,
REV” position is momentary. The “OFF” and “FWD
The “ positions are sustained.
4. FAULT/CONT./START: This is a multi-function switch. The FAU LT” (momentary action) position is used to check for shorts between the “COM” and the “RUN/START” windings. The CONT.” (sustained action) position is used to check for GROUND, RUN and START continuity. In the “ (momentary action) position the start capacitor is connected to the compressor motor through the “
5. Ground Test (Yellow): Push-button switch tests for ground continuity between system ground and the frame of the appliance being tested.
The HA1 introduces an “artificial ground” to make possible the testing for short circuits between the motor winding and the frame of appliances which may not be directly grounded. For example, units with two wire power cords would not be connected to systems ground (unless a separate ground connection were present).
6. Start Test (Red): Push-button switch tests two conditions, depending on the position of the “FUALT/CONT./START” switch.
Switch Position Condition Tested FAU LT Short between START winding and frame CONT. Continuity of START winding
7. Run Test (Black): Push-button switch tests two conditions, depending on the position of the “FUALT/CONT./START” switch.
REV/OFF/FWD” switch.
START
*Since this cable is an “artificial” ground line it is colored yellow instead of green.
Operating Instructions
NOTE: Every effort has been made to make the HA1 a safe and versatile tester. However, under some circumstances line voltage may be present on the HA1 test cables when the control switches are in the OFF position. For this reason it is very important to read and become familiar with the section on operation.
The following procedures have been detailed so a thorough understanding of the operation sequence may be gained. In practice, the following tests may be performed very quickly.
110 V AC Operation
CAUTION!
The HA1 is wired so that the white COMMON test cable is connected to the neutral side of the line. The red START and black RUN cables are connected to the hot side of the line by the “POWER BREAKER” switch and the “REV/OFF/FWD” switch. If the 110 V AC receptacle has been accidently reverse wired, the white as soon as the HA1 is plugged into the power receptacle. To warn against such a condition, the red REV LINE indicator will light as soon as the HA1 is plugged into a grounded receptacle. In this case follow procedure B for reversed line condition.
COMMON cable will be “hot”
Switch Position Condition Tested FAU LT Short between RUN winding and frame CONT. Continuity of RUN winding
8. Indicator Lights: LINE NORM (white)/REV (red). These lights are used to indicate the condition of the power source to which the HA1 is connected.
Line Voltage Indicator Light Status
110 V AC NORM on/REV off Normal
REV on/NORM off Neutral and line wires
reversed at po receptacle. Refer to section on “110 V AC” operation.
V
M and R
NOR on (half intensity) or not connected at
220 V AC NORM and REV Normal
on (full intensity)
E
System ground open
power receptacle.
wer
A. Normal Test Procedure
1. The “REV/OFF/FWD” switch must be in the “OFF” position.
Plug the HA1 into a grounded 110 V AC receptacle and turn on
2.
R
E
W
PO
the “ white NORM LINE indicator should light.
NOTE: If the receptacle is ungrounded, both the “NORM” and the
EV LINE”
R of a g from being made.
IMPORTANT: Verify that the receptacle is not also reverse wired by measuring the voltage between the white COM cable and a ground connection. A reversed line will measure 110 V AC. A normal line will measure zero volts. If the receptacle is reverse wired, follow procedure B.
3. Remove power to the unit which is to be tested.
Remove and identif
4. and run terminals of the compressor motor
” switch. This is a push-on and push-off switch. The
indicator will lig
ounded line will not pr
r
y the connectors going to the common, start,
ht, but at half intensity. The absence event an
y of the following tests
.
HA1-MAN
P. 2
Page 4
5. Connect the test cables of the HA1 to the compressor motor. ellow “GROUND
A. Y B. Red “
START” cable to the start terminal. C. Black “RUN” cable to the run terminal. D. Leave the white “
step 7.
6. Push the “FAULT/CONT./START” switch to the “FAULT” position and hold it there while pressing the red “START TEST” and black “
RUN TEST” switches in turn. If either the “START” indicator or RUN” indicator lights, there is a short between that winding and
“ the frame. STOP the test and replace the unit.
7. Connect the white “ of the compressor motor.
8. Press, in turn, the “
” switches. The appropriate indicator will light indicating
TEST
continuity in the circuit being tested.
able to compressor motor frame.
” c
COMMON” cable disconnected until
COMMON” cable to the common terminal
GROUND TEST, START TEST, and RUN
Reversed Line Operation
B.
10 V AC receptacle is reverse wired the main thing to
If the 1 remember is that the white “COMMON” cable will be HOT regardless of any HA1 switch setting. Therefore, exercise extreme care.
ollow the same procedure as for Normal Operation (A) steps 1
F through 6, but keep the white “COMMON” cable isolated to prevent accidental contact with it.
Before doing step 7, unplug the HA1 from the power receptacle, connect the white “COMMON” cable to the common terminal of the motor, and then plug the HA1 into the power receptacle.
Proceed with the tests outlines in steps 8 though 12, section A.
220 V AC Operation
NOTE: To test for ground continuity the appliance must be plugged into a grounded 110 V AC receptacle or be grounded through an external connection
If either the run start winding indicator open, stop the test and replace the unit.
9. Select the appropriate motor start capacitor.
10. Press the “FAULT/CONT./START” switch to the “START” position and, holding it there, throw the “REV/OFF/FWD” switch to the “FWD” position. If the compressor starts, release the “START” switch. The compressor will continue to run. The compressor may be stopped by returning the “REV/OFF/FWD” switch to the “OFF” position.
If the compressor does not start immediately, the rotor may be locked. Release the “START” switch and return the “REV/OFF/FWD” switch to the “OFF” position.
11. To “ Bump” the compressor, press the “FAULT/CONT./START” switch to the “START” position and holding it there, throw the “REV/OFF/FWD” switch to the “REV” position. If the compressor starts immediately, then release both switches. Repeat step 10 to assure that the compressor will run in the forwards direction.
If the compressor does not start immediately in reverse, then release both switches. A locked rotor will result in excessive current being drawn by the compressor.
12. Steps 10 and 11 may be repeated a few times in an attempt to free a locked rotor, but care should be taken not to overheat the motor windings. If the compressor still does not start, then it should be replaced.
13. Push the “POWER BREAKER” switch OFF. Disconnect the HA1 test cables from the motor.
CAUTION!
The white COM cable will be hot as soon as the HA1 line cord is con­nected to 220 V AC. Always make sure that power to the HA1 is shut off before connecting the HA1 cables to the compressor motor on 220 V AC operation.
1. The “REV/OFF/FWD” switch and the “POWER BREAKER” switch must be in the off position.
2. Remove power to the unit which is to be tested.
3. Some compressor units have fans mounted in the same housing as the compressor. If possible turn down the thermostat, or disconnect the fan, so that the fan will not operate during the compressor tests. The fan noise could make it difficult to listen to the action of the compressor.
4. Remove and identify the connectors going to the common, start, and run terminals of the compressor motor.
5. Connect the test cables of the HA1 to the compressor motor.
A. Yellow “ B. Red “S C. Black “RUN” cable to the run terminal. D. Leave the white “COMMON” cable disconnected until
6. Use an adapter cord of at least #14 AWG wire size to connect the HA1 to the 2
7. Turn on the power to the HA1.
NOTE: Remember to keep the white “COM” cable out of the way. It will have 110 V AC on the clip.
8. Push the “POWER BREAKER” switch to the “ON” position. Both “LINE NORM/REV” indicators will light on.
Push the “FAU
9. and hold it there while pressing the red “SRUN TEST” switches in sequence. If either the “START
ator or “RUN
indic winding and the frame. Stop the test and replace the unit.
GROUND” cable to compressor motor frame.
T
AR
step 1
T
0.
2
able to the start terminal.
” c
AC input terminals.
0 V
NT./START
T/CO
L
ator lights, there is a short between that
” indic
” switch to the “F
T
AU
ART TEST
T
L
” position
” and black
HA1-MAN P. 3
Page 5
0. Turn off the 220 V AC power source to the HA1. Connect the
1
white “COM” cable to the common terminal of the compressor motor.
11. Turn Power back on andPress, in turn, the “GROUND, TEST,
TART TEST
S
tor will light indicating continuity in the circuit being tested. If either the run or start winding indicate open, stop the test and replace the unit.
12. Select the appropriate motor start capacitor.
13. Press the “FAULT/CONT./START” switch to the “START” position and, holding it there, throw the “
FWD” position. If the compressor starts, release the
to the “ “START” switch. The compressor will continue to run. The compressor may be stopped by returning the “REV/OFF/FWD” switch to the “OFF” position.
If the compressor does not start immediately, the rotor may be locked. Release the “SREV/OFF/FWD” switch to the “OFF” position.
14. To “Bump” the compressor, press the “FAULT/CONT./START” switch to the “START” position and, holding it there, throw the “REV/OFF/FWD” switch to the “REV” position. If the compressor starts immediately then release both switches. Repeat step 13 to assure that the compressor will run in the forwards direction.
If the compressor does not start immediately in reverse, then release both switches. A locked rotor will result in excessive current being drawn by the compressor.
15. Steps 13 and 14 may be repeated a few times in an attempt to free a locked rotor, but care should be taken not to overheat the motor windings. If the compressor still does not start, then it should be replaced.
, and R
UNTEST
” switches. The appropriate indic
TART
” switch and return the
REV/OFF/FWD” switch
Maintenance
eriodic Service
P
a
WARNING!
Repair and service of this instrument is to be performed by qualified personnel only
radation of the meter. This could alter the protection from
deg electrical shock and personal injury this meter provides to the operator. Perform only those maintenance tasks that you are qualified to do.
These guidelines will help you attain long and reliable service from your meter:
• Calibrate your meter annually to ensure it meets original performance specifications
• Keep your meter dry. If it gets wet, wipe dry immediately. Liquids can degrade electronic circuits
• Whenever practical, keep the meter away from dust and dirt that can cause premature wear
• Although your meter is built to withstand the rigors of daily use, it can be damaged by severe impacts. Use reasonable caution when using and storing the meter
Cleaning
Periodically clean your meter’s case using a damp cloth. DO NOT use abrasive, flammable liquids, cleaning solvents, or strong detergents as they may damage the finish, impair safety, or affect the reliability of the structural components.
. Improper repair or service could result in physical
16. Turn off the 220 V AC power source to the HA1. Disconnect the HA1 test cables from the motor.
HA1-MAN
P. 4
Page 6
HA1
Hermetic Compressor Analyzer
Limited Warranty
The HA1 is warranted to be free from defects in materials and workmanship for a period of three years from the date of purchase. If within the warranty period your instrument should become inoperative from such defects, the unit will be repaired or replaced at UEi’s option. This warranty covers normal use and does not cover damage which occurs in ship­ment or failure which results from alteration, tampering, accident, misuse, abuse, neglect or improper maintenance. Batteries and consequential damage resulting from failed batteries are not covered by warranty.
Any implied warranties, including but not limited to implied warranties of merchantability and fitness for a particular purpose, are limited to the express warranty. UEi shall not be liable for loss of use of the instrument or other incidental or consequential damages, expenses, or economic loss, or for any claim or claims for such damage, expenses or economic loss. A purchase receipt or other proof of original purchase date will be required before warranty repairs will be rendered. Instruments out of warranty will be repaired (when repairable) for a service charge. Return the unit postage paid and insured to:
1-800-547-5740 • FAX: (503) 643-6322
www.ueitest.com • Email: info@ueitest.com
This warranty gives you specific legal rights. You may also have other rights which vary from state to state.
PLEASE
RECYCLE
Copyright © 2007 UEi
HA1-MAN 1/07
Loading...