C100ACOPBX • Combustion Efficiency Analyzer
Copyright © 2007 UEi Specifications are subject to change without notice. L538 Z 1/07
Distributed By:
1-800-547-5740 • Fax: (503) 643-6322
www.ueitest.com • Email: info@ueitest.com
IN CANADA
Vancouver: Phone: 1-877-475-0648 • (604) 278-4511 • Fax: (604) 278-8299
Toronto: Phone: 1-877-475-0648 • Fax: (905) 238-5117
IN EUROPE
Phone: +44 1707 375550 • Fax: +44 1707 393277
Specifications
The C100ACOPBX enables HVAC professionals to test
and service all residential combustion appliances as well
as diagnose and repair heating equipment. Equipped with
the professional accuracy expected in today’s combustion
efficiency analyzers, the C100ACOPBX also has convenient
features to streamline the task at hand. Like the extra large
backlit LCD which displays three parameters at one time
allowing users to make burner adjustments without having
to change the instrument settings. The C100ACOPBX can
store, retrieve, view and print up to 99 test results, and has
an infrared printer port for printing test results on the spot
to an optional printer.
The C100ACOPBX
has the following features:
• Measures O2, CO, differential pressure, stack and ambient temperatures
• Calculates CO2, gross/net efficiency and excess air
• Poison Index, CO/CO2 ratio
• Protective boot with integral magnet
• Inlet temperature probe
• Backlit triple display allows technician to view 3
parameters simultaneously.
• 99 memory locations to store and recall test results
• Infrared printer port
• Three year limited warranty on analyzer/two year limited
warranty on all sensors
Optional upgrades:
• AC73 - Soft Carrying Case capable of holding C100A/COPBX
probe and accessories, optional KMIRP2 printer, and extra
printing supplies.
• KMIRP2 - Infrared remote thermal printer
• AC power supply
Standard Accessories:
Particle filter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .17631
Optional Accessories:
AC adapter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . AACA4
Infrared printer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . KMIRP2
Paper roll . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16646
*1 Using dry gases at Standard Temperature and Pressure. *2 Calculated.
PLEASE
RECYCLE
Parameter Resolution Accuracy Range
Temperature
Flue Temperature 1°F/°C ±5°F (2°C) 32-1112°F
±0.3% reading (0-600°C)
Inlet Temperature 1˚F/˚C 1˚F/˚C 32-1112°F
±0.3% reading (0-100°C)
Temp (Net)
*2
1˚F/˚C ±5°F (2°C) 32-1112°F
±0.3% reading (0-600°C)
Gas Measurement
Oxygen 0.1% ±0.2% 0-21%
Carbon Monoxide
*2
1 ppm -10 ppm <100 ppm
* 1
0-2000 PPM
±0.5% reading
Carbon Dioxide
*2
0.1% ±0.3% reading 0-30%
Efficiency
*2
0.1% ±1.0% reading 0-99.9%
Excess Air
*2
0.1% ±0.2% 0-250%
Poison Index
*2
0.1% ±0.5% reading 0-99.9%
CO/CO2 ratio
*2
0.001% ±0.5% reading 0-0.999%
Pressure (differential) 0.004 in WG ±1% of full scale 0-19.999 in WG
0.01 in WG 20-40 in WG
1.0 mbar 0-100 mbar
Pre-programmed Fuels Natural Gas, Light Oil, Propane, Butane, LPG
Dimensions
Weight 2.2lb (1kg)
Handset 8" (200mm) x 2" (45mm) x 3.5" (90mm)
Probe L 12" (300mm) x Dia 0.25" (6mm)
with 8" (200mm)
long stainless steel shaft, type K
thermocouple and 9ft
(3m) long neoprene hose
Ambient Operating 32-104°F (0° to 40°C)
Range 10% to 90% RH non-condensing
Battery Life Standard "AA" (x4)
>8 hours continuous use
AC adapter (optional) Input: 110V AC/220V AC nominal
Output: 9V DC regulated 500mA minimum