Triton T90xr Installation And Operating Instructions Manual

Installation and
operating
instructions
2180574G February 2009
Installers please note these InstructIons are to be left wIth the user
T90xr pumped
electric shower
Under *NO circumstances must
this shower be connected directly
to a mains water supply.
It is designed for GRAVITY FED
COLD WATER systems ONLY !
*
Failure to comply may invalidate product warranty
T90xr pumped electric shower
Important safety information .......................................................... 1
Introduction
................................................................................... 2
Specifications
.................................................................................. 2
Advice to users
............................................................................... 2
Main components
.......................................................................... 3
Electrical requirements
.................................................................... 4
Water requirements
........................................................................ 6
Siting of the shower
....................................................................... 7
Fitting the shower to the wall
......................................................... 9
Plumbing connections
................................................................... 11
Electrical connections
.................................................................... 12
Commissioning
.............................................................................. 13
Operating the shower.................................................................... 16
Operating functions
....................................................................... 18
Instructions for installers and service engineers only
...................... 19
Spare parts
.................................................................................... 20
Fault finding
...............................................................................21 - 22
Guarantee, service policy, etc.
..................................................rear cover
CONTENTS PageCONTENTS Page
To check the product suitability for commercial and multiple installations, please contact Triton’s specification advisory service before installation.
Telephone:
Facsimile:
E mail:
0844 980 0730
0844 980 0744
technical@tritonshowers.co.uk
1
T90xr pumped electric shower
  
Products manufactured by Triton are safe and without risk provided they are installed, used and maintained in good working order in accordance with our instructions and recommendations.
WARNING: DO NOT operate shower if frozen, or suspected of being frozen. It must thaw out before using.
DO NOT operate the unit if the showerhead or spray hose becomes damaged. DO NOT restrict flow out of shower by placing showerhead in direct contact with your body. DO NOT operate the shower if water ceases to flow during use or if water has entered inside
the unit because of an incorrectly fitted cover.
WARNING: If restarting the shower immediately after stopping, be aware that a slug of hot water will be expelled for the first few seconds.
PLEASE READ THIS IMPORTANT SAFETY INFORMATION
A-001-A
1
1.1
1.2
1.3
1.4
1.5
1.6
a)
b)
c)
1.7
1.8
1.9
2
2.1
2.2
2.3
2.4
2.5
2.6
3
3.1
3.2
3.3
3.4
GENERAL
Isolate the electrical and water supplies before removing the cover.
Read all of these instructions and retain them for later use.
DO NOT take risks with plumbing or electrical equipment.
Isolate electrical and water supplies before proceeding with the installation.
The unit must be mounted onto the finished wall surface (on top of the tiles). Do not tile up to unit after fixing to wall.
Contact Customer Service (see back page), if any of the following occur:
If it is intended to operate the shower at pressures above the maximum or below the minimum stated.
If the unit shows a distinct change in performance.
If the shower is frozen. If it is intended to operate the shower in areas
of hard water (above 200 ppm temporary hardness), a scale inhibitor may have to be fitted. For advice on the Triton Scale Inhibitor, contact Triton Customer Service.
The showerhead must be cleaned regularly with descalent to remove scale and debris, otherwise restrictions to the flow on the outlet of the unit will result in higher temperatures and could also cause the Pressure Relief Device in the unit to operate.
This product is not suitable for mounting into steam rooms or steam cubicles.
PLUMBING
The plumbing installation must comply with Water Regulations, Building Regulations or any particular regulations as specified by Local Water Company or Water Undertakers and should be in accordance with BS 6700.
The supply pipe must be flushed to clear debris before connecting to the shower unit.
DO NOT solder pipes or fittings within
300mm of the shower unit, as heat can transfer along the pipework and damage components.
DO NOT fit any form of outlet flow control as the outlet acts as a vent for the heater can.
DO NOT use excessive force when making connections to the flexible hose or showerhead, finger tight is sufficient.
All plumbing connections must be completed before making the electrical connections.
ELECTRICAL
The installation must comply with BS 7671 ‘Requirements for electrical installations’ (IEE wiring regulations), building regulations or any particular regulations as specified by the local Electrical Supply Company.
This appliance MUST be earthed. In accordance with ‘The Plugs and Sockets etc.
(Safety) Regulations 1994’, this appliance is intended to be permanently connected to the fixed wiring of the electrical mains system.
Make sure all electrical connections are tight to prevent overheating.
Fuses do not give personal protection against electric shock. A 30mA residual current device (RCD) MUST be installed in all UK electric and pumped shower circuits. This may be part of the consumer unit or a separate unit.
Switch off immediately at isolating switch if water ceases to flow during use.
Other electrical equipment i.e. extractor fans, pumps must not be connected to the circuits within the unit.
Switch off at isolating switch when not in use. This is a safety procedure recommended with all electrical appliances.
As with all electrical appliances it is recommended to have the shower and installation checked at least every two years by a competent electrician to ensure there is no deterioration due to age and usage.
3.5
3.6
3.7
3.8
3.9
3.10
2
T90xr pumped electric shower
This book contains all the necessary fitting and operating instructions for your Triton pumped electric shower. Take time to read this book thoroughly and familiarise yourself with all instructions before installing. Please keep it for future reference.
The shower installation must be carried out in the sequence of this instruction book.
Do not attempt any electrical or plumbing work necessary to install this product unless you have good practical experience and adequate understanding of the IEE regulations and water regulations
Care taken during the installation will provide a long, trouble-free life from your shower.
Meets with Compliance with European Community Directives (CE).
The following points will help you understand how the shower operates:
a.
The electric heating elements operate at a
constant rate at your chosen power setting. It is the rate of the water passing through the heater unit which determines the shower temperature at any given setting. (The slower the flow the hotter the water becomes, and the faster the flow the cooler the water.)
b.
During winter, mains water supply will
be cooler than in summer. Therefore, the temperature of the shower will vary between seasons on any one setting of the temperature control, e.g. if you have chosen setting number 6 as your preferred shower temperature in the summer, you will have to increase that number during winter by adjusting the temperature control clockwise (which in effect slows the water flow).
c. If for any reason there is a sudden rise in water
temperature, the unit has thermal cut-out devices built-in (see items 3 and 4 under ‘Fault Finding’).
d. Switch off immediately at the isolating switch
if water ceases to flow. Press the Start/Stop button and contact Customer Service for advice.
If ever the water becomes too hot and you cannot obtain cooler water, first check that the sprayplate in the showerhead has not become blocked.
DO NOT place items such as soap or shampoo bottles on top of the unit. Liquid could seep through the joint between the cover and backplate, and possibly damage the sealing rubber.
Electrical Nominal power Nominal power
rating at 240V rating at 230V
8.5kW – (40A MCB rating) 7.9kW – (40A MCB rating)
9.5kW – (40A MCB rating) 8.7kW – (40A MCB rating)
Pump motor rating 120 Watt − single phase.
Water Inlet connection – 15mm diameter Outlet connection – ½” BSP male thread
Entry Points
Water – top, bottom, back Cable – top, bottom, back
Materials
Backplate, cover, controls, showerhead – ABS Sprayplate – Acetal Elements – Minerally insulated corrosion resistant metal sheathing
Dimensions (mm) Height – 268, Width – 330, Depth – 104
Standards and Approvals
Splashproof rating IPX4
Complies with the requirements of current British and European safety standards for household and similar electrical appliances.
Complies with requirements of the British Electrotechnical Approvals Board (BEAB).
Advice to users
ADVICE TO USERS
Introduction
INTRODUCTION
Specifications
SPECIFICATIONS
Y-003-A
Replacement parts can be ordered from Customer Service. See ‘spare parts’ for details and part numbers.
This product is rated at:
15 minutes on / 45 minutes off.
3
T90xr pumped electric shower
1. Top pipe / cable entry
2. Motor assembly
3. Pump assembly
4. Bleed screw
5. Wall screw fixing
6. Power selector assembly
7. Thermal cut-out (main)
8. Terminal block
9. Can and element assembly
10. Area for bottom and back pipe/cable entry
11. Pressure switch
12. Temperature valve
13. Solenoid valve
14. Earth connection
15. Inlet pipe
16. Filter
17. Thermal cut-out (outlet)
18. Outlet pipe
19. Trimplate
Other items
Screw fixing kit
Instructions, guarantee, etc.
Main components
MAIN COMPONENTS
268 mm
330 mm
157 mm
49 mm
58 mm
NOTE: Not all wiring shown for reasons of clarity
Inside unit (fig.1)
I-001-A
IMPORTANT: When first installed the unit
will be empty. It is essential the unit should contain water before the elements are switched on. It is vital that the commissioning procedure is followed. Failure to carry out this operation will result in damage to the unit and will invalidate the guarantee.
Fig.1
1
2
16
3
18
17
4
5
6
7
8
9
10
11
12
13
14
15
5
5
5
19
5
4
T90xr pumped electric shower
ELECTRICAL REQUIREMENTS
The installation, supply cable and circuit protection must conform with BS 7671 (IEE wiring regulations) and be sufficient for the amperage required. The following notes are for guidance only:
1 The shower must only be connected to a
230-240V ac supply. If you are installing a shower with a kilowatt rating above 9kW, it is advisable to contact the local electricity supply company.
1.1 The electrical rating of the shower is shown on the rating label (Fig.3) within the unit.
2 Before making any sort of electrical
connection within the installation make sure that no terminal is live. If in any doubt, switch off the whole installation at the mains supply and remove the correct fuse.
3 The shower must be connected to its own
independent electrical circuit. IT MUST NOT be connected to a ring main, spur, socket outlet, lighting circuit or cooker circuit.
3.1 The electrical supply must be adequate for the loading of the unit and existing circuits.
4 Check your consumer unit (main fuse box)
has a main switch rating of 80A or above and that it has a spare fuse way which will take the fuse or Miniature Circuit Breaker (MCB) necessary for the shower (Fig.4).
4.1 If your consumer unit has a rating below 80A or if there is no spare fuse way, then the installation will not be straightforward and may require a new consumer unit serving the house or just the shower.
4.2 You will need to contact the local electricity company. They will check the supply and carry out what is necessary.
5 For close circuit protection DO NOT use a
rewireable fuse. Instead use a suitably rated Miniature Circuit Breaker (MCB) or cartridge fuse (see Table A).
Meter
Incoming
supply
fuse
Meter
tails
Consumer
unit
Pull cord
isolating switch
Shower
unit
Fuse or
MCB
RCD
(can be part of
consumer unit)
80A or 100A
main switch
Shepperton Park,
Triton Road, Nuneaton,
Warwickshire, CV11 4NR
Table A
MCB
30/32A
32A
40A
40A
40A
40/45A
45A
cartridge
fuse
30A
35A
35A
45A
45A
45A
45A
unit
rating
7.0kW
7.5kW
8.0kW
8.5kW
9.0kW
9.5kW
10.5kW
CIRCUIT PROTECTION
Fig.3 Schematic of installation circuit
Fig.2
W-006-A
WARNING!
THIS APPLIANCE MUST BE EARTHED
(Fig.2)
(Fig.3).
5
T90xr pumped electric shower
Table B
Note: Cable selection is dependent on
derating factors
Twin and earth PVC insulated cable
Current carrying capacity
In conduit
trunking
6 mm²
38A
10 mm²
52A
16 mm²
69A
Installed in an insulated wall
6 mm²
32A
10 mm²
43A
16 mm²
57A
Clipped direct
or buried in a non-insulated
wall
6 mm²
46A
10 mm²
63A
16 mm²
85A
E-002-A
installation will not be straightforward and may require a new consumer unit serving the house or just the shower.
4.2 You will need to contact the local electricity company. They will check the supply and carry out what is necessary.
5 For close circuit protection DO NOT use a
rewireable fuse. Instead use a suitably rated Miniature Circuit Breaker (MCB) or cartridge fuse (see Table A).
5.1 A 30mA residual current device (RCD) must be installed in all UK electric and pumped shower circuits. This may be part of the consumer unit or a separate unit.
6 A 45 amp double pole isolating switch with
a minimum contact gap of 3 mm in both poles must be incorporated in the circuit.
6.1 It must have a mechanical indicator showing when the switch is in the OFF position, and the wiring must be connected to the switch without the use of a plug or socket outlet.
6.2 The switch must be accessible and clearly identifiable, but out of reach of a person using a fixed bath or shower, except for the cord of a cord operated switch, and should be placed so that it is not possible to touch the switch body while standing in a bath or shower cubicle. It should be readily accessible to switch off after using the shower.
7 Where shower cubicles are located in any
rooms other than bathrooms, all socket outlets in those rooms must be protected by a 30mA RCD.
8 The current carrying capacity of the cable
must be at least that of the shower circuit protection (see Table B).
8.1 To obtain full advantage of the power provided by the shower, use the shortest cable route possible from the consumer unit to the shower.
8.2 It is also necessary to satisfy the disconnection time and thermal constraints which means that for any given combination of current demand, voltage drop and cable size, there is a maximum permissible circuit length.
9 The shower circuit should be separated from
other circuits by at least twice the diameter of the cable or conduit.
9.1 The current rating will be reduced if the cabling is bunched with others, surrounded by thermal loft or wall insulation or placed in areas where the ambient temperature is above 30°C. Under these conditions, derating factors apply and it is necessary to select a larger cable size.
E-002-A
5.1 A 30mA residual current device (RCD) must be installed in all UK electric and pumped shower circuits. This may be part of the consumer unit or a separate unit.
6 A 45 amp double pole isolating switch with
a minimum contact gap of 3 mm in both poles must be incorporated in the circuit.
6.1 It must have a mechanical indicator showing when the switch is in the OFF position, and the wiring must be connected to the switch without the use of a plug or socket outlet.
6.2 The switch must be accessible and clearly identifiable, but out of reach of a person using a fixed bath or shower, except for the cord of a cord operated switch, and should be placed so that it is not possible to touch the switch body while standing in a bath or shower cubicle. It should be readily accessible to switch off after using the shower.
7 Where shower cubicles are located in any
rooms other than bathrooms, all socket outlets in those rooms must be protected by a 30mA RCD.
8 The current carrying capacity of the cable
must be at least that of the shower circuit protection (see Table B).
8.1 To obtain full advantage of the power provided by the shower, use the shortest cable route possible from the consumer unit to the shower.
8.2 It is also necessary to satisfy the disconnection time and thermal constraints which means that for any given combination of current demand, voltage drop and cable size, there is a maximum permissible circuit length.
9 The shower circuit should be separated from
other circuits by at least twice the diameter of the cable or conduit.
9.1 The current rating will be reduced if the cabling is bunched with others, surrounded by thermal loft or wall insulation or placed in areas where the ambient temperature is above 30°C. Under these conditions, derating factors apply and it is necessary to select a larger cable size.
9.2 In the majority of installations, the cable will unavoidably be placed in one or more of the above conditions. This being so, it is strongly recommended to use a minimum of 10mm cabling throughout the shower installation.
9.3 In any event, it is essential that individual site conditions are assessed by a competent electrician in order to determine the correct cable size and permissible circuit length.
6
T90xr pumped electric shower
Mains water supply
Gate valve
Stop
valve
Cold water
cistern
Mains electric supply
(via double pole switch)
Double pole isolating switch
Separate permanently
connected supply
from consumer unit
Shower
unit
Minimum capacity 114 litres (25 gallons)
8 cm (3")
minimum
Fig.4 Diagrammatic view (not to scale)
WATER REQUIREMENTS
The installation must be in accordance with the Water Regulations/Bylaws.
To ensure activation of the heating elements, the shower must be connected to a cold water supply which is gravity fed from a static cold water storage cistern with a minimum capacity of 114 litres (25 gallons).
There must be a maximum head of water of 10 metres and a minimum head of 8 cm as measured between the bottom of the cistern and the top of the shower unit. There must be no other cold water draw-offs between the cistern and the unit and the pipe must not supply water to any other tap or fitting at a lower level.
Note: The supply pipe from the cistern should be on the opposite side to the float operated valve to prevent air being drawn into the pipe when the cistern is filling.
If it is intended to operate the shower in hard water areas (above 200 ppm temporary hardness) a scale inhibitor should be fitted.
Fig.4 shows a typical system layout.
DO NOT use jointing compounds on any pipe fittings for the installation.
WARNING!
Under no circumstances must this
shower be connected directly to the
mains water supply.
7
T90xr pumped electric shower
Outline of bath,
shower tray
or cubicle
Cold water supply
from cistern
(top, bottom or back)
Shower can be mounted
either side of
the riser rail
Ceiling
Height of
showerhead
and shower
to suit user’s
requirement
Shower unit
must not be within
an area 1 metre
from base
Fig.5 Diagrammatic view (not to scale)
W-008-A
WARNING!
The shower must not be positioned
where it will be subjected to freezing
conditions.
SITING OF THE SHOWER
IMPORTANT: If installing onto a tiled wall always mount the unit on the surface of the tiles. NEVER tile up to the unit.
Refer to fig.5 for correct siting of the shower.
Position the unit where it will
NOT be in direct
contact with water from the showerhead. Position the shower unit vertically.
Allow enough room between the ceiling and the shower to access the cover top screws.
Note: Water regulations require the showerhead be ‘constrained by a fixed or sliding attachment
so that it can only discharge water at a point not less than 25 mm above the spill-over level of the relevant bath, shower tray or other fixed appliance’. The use of the supplied soap dish will
in most cases meet this requirement, but if the showerhead can be placed within a bath, basin or shower tray, then a double check valve, or similar, must be fitted in the supply pipework to prevent back-flow.
Allow enough room between the ceiling and the
shower to access the cover top screws.
Pressure relief safety device
A pressure relief device (PRD) is designed into the shower unit which complies with European standards. The PRD provides a level of appliance protection should an excessive build up of pressure occur within the shower.
DO NOT operate the shower with a damaged or kinked shower hose, or a blocked showerhead which can cause the PRD to operate.
When commissioning, the showerhead must be removed from the flexible hose. Failure to follow this procedure may also result in causing the PRD to operate.
Make sure the shower is positioned over a bath or shower tray because if the PRD operates, then water will eject from the bottom of the unit.
Should this happen, turn off the electricity and water supplies to the shower at the isolating switch and stopvalve. Contact Customer Service for advice on replacing the PRD.
Two PRD screws
PRD
Outlet pipe
Two outlet pipe screws
Fig.6
Loading...
+ 20 hidden pages