Triton T550i Installation And Operating Instructions Manual

Installers please note these InstructIons are to be left wIth the user
2180149I February 2009
Installation and
operating instructions
T550i power shower pump
CONTENTS Page
Plumbing and electrical notes ......................1
Introduction ................................................2
Safety warnings ........................................... 2
Key to main components ............................3
Water requirements .....................................4
Electrical requirements .................................5
Siting of the pump ...................................... 5
Installation ................................................... 6
Variable speed control .................................9
Commissioning ............................................9
Spare parts .................................................11
Fault finding ............................................... 12
Guarantee, Service Policy, Etc. .............. Rear cover
To check the product suitability for commercial and multiple installations, please contact Triton’s specification advisory service before installation.
Telephone:
Facsimile:
E mail:
0844 980 0730
0844 980 0744
technical@tritonshowers.co.uk
1
1 PLUMBING NOTES
1.1 All installations must comply with Water
Regulations/Byelaws.
1.2 Supply pipes must be flushed thoroughly to clear debris before connecting to the pump and shower.
1.3 DO NOT connect the pump unit to the mains cold water supply as it would damage the unit and also, the installation would be in breach of the guidance notes contained in ‘1’ above.
1.4 DO NOT use excessive force when making connections to the flexible connector hoses.
1.5 DO NOT turn on the electrical supply to the pump until the plumbing connections and commissioning procedure have been completed. The pump must not be
operated dry without water.
1.6 DO NOT solder pipes or fittings within
300mm of the pump, as heat transfer can damage the components.
1.7 A dedicated cold water supply must be taken directly from the cold water cistern to the pump. This draw-off must be on the opposite side of the cistern to the float operated valve.
1.8 The action of the pump is to increase the flow rate. If the supply pipework cannot handle the resulting flow rate then:
1.8.1 The anticipated flow rate may not be achieved.
1.8.2 Air may be drawn into the hot supply from the vent pipe causing spluttering and temperature fluctuations at the sprayhead.
1.9 A high level hot feed pipe run must not rise above the level of water in the cistern. To reduce the risk of air locks pipes should be run level with or below the base of the cistern.
1.10 Standard gate valves or full way lever valves MUST be fitted on the hot and cold water supplies to the pump as an independent means of isolating the water supplies should maintenance or servicing be necessary.
DO NOT use stop taps or ball-o-fix type
valves which restrict flow.
1.11 If the pump unit is installed on a common supply which feeds an adjacent tap, the maximum static inlet pressure for the unit will, under certain circumstances be exceeded. The action of closing the tap can cause a pulse in the supply pressure which may result in damage to the unit. This can be resolved by the installation of a suitably sized mini expansion vessel, sited as close as possible to the tap and pressurised to 50kPa (0.5 bar).
2 ELECTRICAL NOTES
2.1 The installation must comply with BS 7671
‘Requirements for electrical installations’ (IEE wiring regulations). Ensure the incoming hot and cold water supplies to the pump are adequately earth bonded.
2.2 DO NOT turn on the electrical supply to the pump until the plumbing connections have been completed. The pump must
not be operated dry without water.
2.3 The mains supply must be 230-240V, at
50Hz, connected to the pump via a double pole switched 3 Amp fused connection unit (not supplied) with a minimum 3mm contact separation gap in each pole.
2.4 In accordance with ‘The Plugs and Sockets etc. (Safety) Regulations 1994’, the pump is intended to be permanently connected to the fixed electrical wiring of the mains system.
2.5 To enhance electrical safety a 30mA residual current device (RCD) should be installed in all UK electric and pumped shower circuits. This may be part of the consumer unit or a separate unit.
Replacement parts can be ordered from Triton Customer Service. See ‘spare parts’ for details.
2
INTRODUCTION
This book contains all the necessary fitting and operating instructions for your Triton twin impeller power shower pump. Please read them carefully.
This product is rated at:
15 minutes on / 60 minutes off.
Care taken during the installation will ensure a long and trouble free life from your unit.
IMPORTANT: All plumbing connections must be completed before making the electrical connections.
Please read through the whole of this book before beginning your installation.
SAFETY WARNINGS
a. Under no circumstances must this pump
be connected to a mains cold water supply. Failure to comply will invalidate the guarantee.
b. The shower pump MUST NOT be used if
suspected of being frozen.
c. The pump must be earthed. d. Switch off immediately at isolating switch if
water ceases to flow during use.
e. DO NOT operate the unit outside the
guidelines laid out in “site requirements”.
f. This pump is to be used for providing water
to a shower only.
In the interest of electrical safety a 30mA residual current device (RCD) should be installed in all UK electric and pumped shower circuits. This may be part of the consumer unit or a separate unit.
3
KEY TO MAIN COMPONENTS
Pump (fig.1)
1 Inlet connector hose
2 Outlet connector hose
3 Integral flow switch
4 Variable speed control
5 PCB cover
Fig.1
1
1
2
2
3
5
4
3
Loading...
+ 11 hidden pages