Triton t150z Installation And Operating Instructions Manual

Installation and
operating
instructions
2180759D September 2009
Installers please note these InstructIons are to be left wIth the user
T150Z
pumped
electric shower
! IMPORTANT !
Under *NO circumstances must
this shower be connected directly
to a mains water supply.
It is designed for GRAVITY FED
COLD WATER systems ONLY !
*
Failure to comply may invalidate product warranty
T150Z pumped thermostatic electric shower
CONTENTS Page
To check the product suitability for commercial and multiple installations, please contact Triton’s specification advisory service before installation.
Telephone:
Facsimile:
E mail:
0844 980 0730
0844 980 0744
technical@tritonshowers.co.uk
CONTENTS
PAGE
Important safety information ..........................................................1
Introduction
...................................................................................2
Specifications
.................................................................................. 2
Advice to users
............................................................................... 2
Main components
....................................................................... 3 - 4
Electrical requirements ................................................................. 5 - 6
Water requirements
........................................................................ 7
Siting of the shower
........................................................................ 8
Fitting the shower to the wall ......................................................... 9
Plumbing connections
............................................................... 10 - 11
Electrical connections
....................................................................12
Shower drain pumps (not supplied) ............................................ 13 - 14
Commissioning
.......................................................................... 15 - 16
PCB Dip Switch settings ................................................................. 17
Replacing the cover
....................................................................... 18
Operating the shower/Operating functions................................ 19 - 21
Instructions for installers and service engineers only
....................... 22
Spare parts
................................................................................ 23 - 24
Fault finding
.............................................................................. 25 - 26
BEAB CARE requirements ........................................................... 27 - 31
Guarantee, etc.
........................................................................ rear cover
1
T150Z pumped thermostatic electric shower
  
Products manufactured by Triton are safe and without risk provided they are installed, used and maintained in good working order in accordance with our instructions and recommendations.
WARNING: DO NOT operate shower if frozen, or suspected of being frozen. It must thaw out before using.
DO NOT operate the unit if the showerhead or spray hose becomes damaged. DO NOT restrict flow out of shower by placing showerhead in direct contact with your body. DO NOT operate the shower if water ceases to flow during use or if water has entered inside
the unit because of an incorrectly fitted cover.
PLEASE READ THIS IMPORTANT SAFETY INFORMATION
A-001-A
1
1.1
1.2
1.3
1.4
1.5
1.6
a)
b)
c)
1.7
1.8
1.9
2
2.1
2.2
2.3
2.4
2.5
2.6
3
3.1
3.2
3.3
3.4
GENERAL
Isolate the electrical and water supplies before removing the cover.
Read all of these instructions and retain them for later use.
DO NOT take risks with plumbing or electrical equipment.
Isolate electrical and water supplies before proceeding with the installation.
The unit must be mounted onto the finished wall surface (on top of the tiles). Do not tile up to unit after fixing to wall.
Contact Customer Service (see back page), if any of the following occur:
If it is intended to operate the shower at pressures above the maximum or below the minimum stated.
If the unit shows a distinct change in performance.
If the shower is frozen. If it is intended to operate the shower in areas
of hard water (above 200 ppm temporary hardness), a scale inhibitor may have to be fitted. For advice on the Triton Scale Inhibitor, contact Triton Customer Service.
The showerhead must be cleaned regularly with descalent to remove scale and debris, otherwise restrictions to the flow on the outlet of the unit will result in higher temperatures and could also cause the Pressure Relief Device in the unit to operate.
This product is not suitable for mounting into steam rooms or steam cubicles.
PLUMBING
The plumbing installation must comply with Water Regulations, Building Regulations or any particular regulations as specified by Local Water Company or Water Undertakers and should be in accordance with BS 6700.
The supply pipe must be flushed to clear debris before connecting to the shower unit.
DO NOT solder pipes or fittings within
300mm of the shower unit, as heat can transfer along the pipework and damage components.
DO NOT fit any form of outlet flow control as the outlet acts as a vent for the heater can.
DO NOT use excessive force when making connections to the flexible hose or showerhead, finger tight is sufficient.
All plumbing connections must be completed before making the electrical connections.
ELECTRICAL
The installation must comply with BS 7671 ‘Requirements for electrical installations’ (IEE wiring regulations), building regulations or any particular regulations as specified by the local Electrical Supply Company.
This appliance MUST be earthed. In accordance with ‘The Plugs and Sockets etc.
(Safety) Regulations 1994’, this appliance is intended to be permanently connected to the fixed wiring of the electrical mains system.
Make sure all electrical connections are tight to prevent overheating.
Fuses do not give personal protection against electric shock. A 30mA residual current device (RCD) MUST be installed in all UK electric and pumped shower circuits. This may be part of the consumer unit or a separate unit.
Switch off immediately at isolating switch if water ceases to flow during use.
Other electrical equipment i.e. extractor fans, pumps must not be connected to the circuits within the unit.
Switch off at isolating switch when not in use. This is a safety procedure recommended with all electrical appliances.
As with all electrical appliances it is recommended to have the shower and installation checked at least every two years by a competent electrician to ensure there is no deterioration due to age and usage.
3.5
3.6
3.7
3.8
3.9
3.10
2
T150Z pumped thermostatic electric shower
INTRODUCTION
This book contains all the necessary fitting and operating instructions for your electric shower.
Take time to read this book thoroughly and familiar­ise yourself with all instructions before commencing installation. Please keep it for future reference.
The shower installation must be carried out by a suitably qualified person and in the sequence of this instruction book.
Care taken during the installation will provide a long, trouble-free life from your shower.
SPECIFICATIONS
Electrical
Nominal power Nominal power rating at 240V rating at 230V
8.5kW – (40A MCB rating) 7.8kW – (40A MCB rating)
9.5kW – (40A MCB rating) 8.7kW – (40A MCB rating)
Pump motor rating 120 Watt − single phase.
Water
Inlet connection – 15 mm diameter. Outlet connection – ½” BSP male thread.
Entry Points
Water – bottom, back and top. Cable – bottom, back and top.
Materials
Backplate, cover, controls, showerhead – ABS. Sprayplate – Acetal. Elements – Minerally insulated corrosion resistant metal sheathing.
Dimensions
Height − 300 mm Width − 316 mm Depth − 90 mm
Standards and Approvals
Splashproof rating IPX4. Complies with the requirements of current British
and European safety standards for household and similar electrical appliances.
Complies with requirements of the British Electrotechnical Approvals Board (BEAB) and BEAB CARE mark (BEAB).
Meets with Compliance with European Community Directives (CE).
ADVICE TO USERS
The following points will help you understand how the shower operates:
a)
Temperature/flow rate
The temperature control can be adjusted to
provide shower temperatures between 35°C and 47°C.
Alternatively, adjusting a temperature stop
mechanism inside the unit to 38°C, 41°C or 43°C maximum can restrict the shower temperature.
Important
: To comply with BEAB care
mark requirements the unit must not be able to run hotter than 41°C (this is used in healthcare or special needs environments).
The T150Z pumped unit is factory set at
47°C (see page 16) on how to adjust the MAXIMUM temperature stop to 41°C
or below.
At a selected showering temperature the unit
will provide the optimum flow rate possible.
Note the maximum flow rate for the given
temperature will be greater in the summer than in the winter because of the variance in the ambient mains water supply.
Should water pressure/flow to the shower be
insufficient for optimum performance then the unit will operate at a reduced power level and provide the highest flow rate possible for the given shower temperature.
b)
Temperature stabilisation
The shower will maintain temperature in
accordance with the BEAB care mark.
If ever the water becomes too hot, and you cannot obtain cooler water, first check that the sprayplate in the showerhead has not become blocked.
DO NOT place items such as soap or shampoo bottles on top of the unit. Liquid could seep through the joint between the cover and backplate, and possibly damage the sealing rubber.
Important: When first installed the unit will be empty. It is essential the unit should contain water before the elements are switched on. It is vital that the commissioning procedure is followed. Failure to carry out this operation will result in damage to the unit and will invalidate the guarantee.
3
T150Z pumped thermostatic electric shower
This product is rated at:
30 minutes on / 30 minutes off.
Note: Wires have not been shown for reasons of clarity.
1
2
16
17
3
18
15
4
5
6
12
9
14
10
7
8
11
13
Inside unit (fig.1)
1. Top cable/pipe entry
2. Wall screw fixings
3. Cover screw fixings
4. Thermal safety cut-out
5. Power printed circuit board
6. Can and element assembly
7. Flow switch assembly
8. Temperature Control
9. Terminal block
10. Earth connection
11. Solenoid valve
12. Water inlet
13. Pressure relief device (PRD)
14. Shower outlet
15. Filter
16. Pump motor
17. Pump
18. Trimplate
19. Bottom cable/pipe entry
MAIN COMPONENTS
2
2
2
3 3
3
19
Fig.1
4
T150Z pumped thermostatic electric shower
Inside Cover (fig.2)
20. Stop/start switch - Inside
21. Control printed circuit board - Inside
22. Front cover - T150Z pumped
Other items
- Instructions, guarantee, etc.
MAIN COMPONENTS (continued)
20
21
22
Fig.2
5
T150Z pumped thermostatic electric shower
Meter
Incoming
supply
fuse
Meter
tails
Consumer
unit
Pull cord
isolating switch
Shower
unit
Fuse or
MCB
RCD
(can be part of
consumer unit)
80A or 100A
main switch
Schematic of installation circuit
ELECTRICAL REQUIREMENTS
Shepperton Park,
Triton Road, Nuneaton,
Warwickshire, CV11 4NR
The installation, supply cable and circuit protection must conform with BS 7671 (IEE wiring regulations) and be sufficient for the amperage required. The following notes are for guidance only:
1 The shower must only be connected to a
230-240V ac supply. If you are installing a shower with a kilowatt rating above 9kW, it is advisable to contact the local electricity supply company.
1.1 The electrical rating of the shower is shown on the rating label (Fig.3) within the unit.
2 Before making any sort of electrical
connection within the installation make sure that no terminal is live. If in any doubt, switch off the whole installation at the mains supply and remove the correct fuse.
3 The shower must be connected to its own
independent electrical circuit. IT MUST NOT be connected to a ring main, spur, socket outlet, lighting circuit or cooker circuit.
3.1 The electrical supply must be adequate for the loading of the unit and existing circuits.
4 Check your consumer unit (main fuse box)
has a main switch rating of 80A or above and that it has a spare fuse way which will take the fuse or Miniature Circuit Breaker (MCB) necessary for the shower (Fig.4).
4.1 If your consumer unit has a rating below 80A or if there is no spare fuse way, then the installation will not be straightforward and may require a new consumer unit serving the house or just the shower.
4.2 You will need to contact the local electricity company. They will check the supply and carry out what is necessary.
5 For close circuit protection DO NOT use a
rewireable fuse. Instead use a suitably rated Miniature Circuit Breaker (MCB) or cartridge fuse (see Table A).
5.1 A 30mA residual current device (RCD) must be installed in all UK electric and pumped shower circuits. This may be part of the consumer unit or a separate unit.
W-006-A
WARNING!
THIS APPLIANCE MUST BE EARTHED
Fig.3
Fig.4
6
T150Z pumped thermostatic electric shower
Table A
Table B
MCB
30/32A
32A
40A
40A
40A
40/45A
45A
cartridge
fuse
30A
35A
35A
45A
45A
45A
45A
unit
rating
7.0kW
7.5kW
8.0kW
8.5kW
9.0kW
9.5kW
10.5kW
CIRCUIT PROTECTION
E-002-A
80A or if there is no spare fuse way, then the installation will not be straightforward and may require a new consumer unit serving the house or just the shower.
4.2 You will need to contact the local electricity company. They will check the supply and carry out what is necessary.
5 For close circuit protection DO NOT use a
rewireable fuse. Instead use a suitably rated Miniature Circuit Breaker (MCB) or cartridge fuse (see Table A).
5.1 A 30mA residual current device (RCD) must be installed in all UK electric and pumped shower circuits. This may be part of the consumer unit or a separate unit.
6 A 45 amp double pole isolating switch with
a minimum contact gap of 3 mm in both poles must be incorporated in the circuit.
6.1 It must have a mechanical indicator showing when the switch is in the OFF position, and the wiring must be connected to the switch without the use of a plug or socket outlet.
6.2 The switch must be accessible and clearly identifiable, but out of reach of a person using a fixed bath or shower, except for the cord of a cord operated switch, and should be placed so that it is not possible to touch the switch body while standing in a bath or shower cubicle. It should be readily accessible to switch off after using the shower.
7 Where shower cubicles are located in any
rooms other than bathrooms, all socket outlets in those rooms must be protected by a 30mA RCD.
8 The current carrying capacity of the cable
must be at least that of the shower circuit protection (see Table B).
8.1 To obtain full advantage of the power provided by the shower, use the shortest cable route possible from the consumer unit to the shower.
8.2 It is also necessary to satisfy the disconnection time and thermal constraints which means that for any given combination of current demand, voltage drop and cable size, there is a maximum permissible circuit length.
9 The shower circuit should be separated from
other circuits by at least twice the diameter of the cable or conduit.
9.1 The current rating will be reduced if the cabling is bunched with others, surrounded by thermal loft or wall insulation or placed in areas where the ambient temperature is above 30°C. Under these conditions, derating factors apply and it is necessary to select a larger cable size.
E-002-A
fuse (see Table A).
5.1 A 30mA residual current device (RCD) must
be installed in all UK electric and pumped shower circuits. This may be part of the consumer unit or a separate unit.
6 A 45 amp double pole isolating switch with
a minimum contact gap of 3 mm in both poles must be incorporated in the circuit.
6.1 It must have a mechanical indicator showing when the switch is in the OFF position, and the wiring must be connected to the switch without the use of a plug or socket outlet.
6.2 The switch must be accessible and clearly identifiable, but out of reach of a person using a fixed bath or shower, except for the cord of a cord operated switch, and should be placed so that it is not possible to touch the switch body while standing in a bath or shower cubicle. It should be readily accessible to switch off after using the shower.
7 Where shower cubicles are located in any
rooms other than bathrooms, all socket outlets in those rooms must be protected by a 30mA RCD.
8 The current carrying capacity of the cable
must be at least that of the shower circuit protection (see Table B).
8.1 To obtain full advantage of the power provided by the shower, use the shortest cable route possible from the consumer unit to the shower.
8.2 It is also necessary to satisfy the disconnection time and thermal constraints which means that for any given combination of current demand, voltage drop and cable size, there is a maximum permissible circuit length.
9 The shower circuit should be separated from
other circuits by at least twice the diameter of the cable or conduit.
9.1 The current rating will be reduced if the cabling is bunched with others, surrounded by thermal loft or wall insulation or placed in areas where the ambient temperature is above 30°C. Under these conditions, derating factors apply and it is necessary to select a larger cable size.
9.2 In the majority of installations, the cable will unavoidably be placed in one or more of the above conditions. This being so, it is strongly recommended to use a minimum of 10mm cabling throughout the shower installation.
9.3 In any event, it is essential that individual site conditions are assessed by a competent electrician in order to determine the correct cable size and permissible circuit length.
Circuit Protection
Note: Cable selection is dependent on
derating factors
Twin and earth PVC insulated cable
Current carrying capacity
In conduit
trunking
6 mm²
38A
10 mm²
52A
16 mm²
69A
Installed in an insulated wall
6 mm²
35A
10 mm²
47A
16 mm²
63A
Clipped direct
or buried in a non-insulated
wall
6 mm²
47A
10 mm²
64A
16 mm²
85A
7
T150Z pumped thermostatic electric shower
Mains water supply
Isolating valve
Stop
valve
Cold water
cistern
Mains electric supply (via double pole switch)
Double pole isolating switch
Separate permanently
connected supply
from consumer unit
Shower
unit
Minimum capacity 114 litres (25 gallons)
8 cm (3") minimum
The installation must be in accordance with Water Regulations/Bylaws.
WATER REQUIREMENTS
Supply Source ............................................ Gravity fed cold water only
Minimum Head
.......................................... 8cm
Maximum static pressure ........................... 100 kPa (1 bar) or (10m Head)
Maximum inlet temperature
...................... 28°C
Minimum inlet temperature
....................... 2°C
To ensure activation of the heating elements, the shower must be connected to a cold water supply which is Gravity Fed Only from a static cold water storage cistern with a minimum capacity of 114 litres (25 gallons).
There must be a maximum head of water of 10 metres and a minimum head of 8 cm as measured between the bottom of the cistern and the top of the shower unit. There must be no other cold water draw-offs between the cistern and the unit and the pipe must not supply water to any other tap or fitting at a lower level.
Note: The supply pipe from the cistern should be on the opposite side to the float operated valve to prevent air being drawn into the pipe when the cistern is filling.
If it is intended to operate the shower in hard water areas (above 200 ppm temporary hardness) a scale inhibitor should be fitted.
Fig.5 shows a typical system layout.
DO NOT use jointing compounds on any pipe fittings for the installation.
WARNING!
Under no circumstances must
this shower be connected directly
to the mains water supply.
Fig.5
Diagrammatic view (not to scale)
Important: To comply with BEAB care mark in service testing procedure the isolating valve should be located close to the shower unit.
8
T150Z pumped thermostatic electric shower
Outline of shower tray
Gravity cold
water supply
(either top, bottom
or back entry)
Shower unit
can be mounted
either side
of riser rail
Height of
shower should
be a
minimum of 1 metre from base
Spillover level
Height of
sprayhead and shower to suit user's requirement
SITING OF THE SHOWER
For ease of servicing, the unit must always be mounted on the surface of tiled walls. Never tile up to the unit.
Refer to (Fig.6) for correct siting of shower. Position the unit where it will not be in direct contact with water from the showerhead. Position the shower unit vertically.
Allow enough room between the ceiling and the shower to access the cover top screws.
Note: Water Regulations (shower hose connections) requires the showerhead be ‘constrained by a fixed or sliding attachment so that it can only discharge water at a point not less than 25mm above the spill-over level of the relevant bath, shower tray or other fixed appliance’. The use of the supplied soap dish will in most cases meet this requirement, but if the showerhead can be placed within a bath, basin or shower tray, then a double check valve, or similar, must be fitted in the supply pipework to prevent back-flow.
Pressure relief safety device
A pressure relief device (PRD) is designed into the shower unit which complies with European standards. The PRD provides a level of appliance protection should an excessive build up of pressure occur within the shower.
Do not operate the shower with a damaged or kinked shower hose, or a blocked showerhead which can cause the PRD to operate.
When commissioning, the showerhead must be removed from the flexible hose. Failure to follow this procedure may also cause the PRD to operate.
Make sure the shower is positioned over a bath or shower tray because if the PRD operates, then water will eject from the bottom of the unit.
Should this happen, turn off the electricity and water supplies to the shower at the isolating switch and stopvalve. Contact Customer Service for advice on replacing the PRD.
WARNING!
The shower must not be
positioned where it will be subjected
to freezing conditions.
Fig.6
Diagrammatic view (not to scale)
I-002-A
IMPORTANT: The unit must be mounted on
a flat surface which covers the full width and length of the backplate. It is important that the wall surface is flat otherwise difficulty may be encountered when fitting the cover and subsequent operation of the unit may be impaired.
9
T150Z pumped thermostatic electric shower
Note: The control knobs are an integral part of the cover – DO NOT attempt to remove them.
Unscrew the two top and bottom two retaining screws (fig.7) and lift the cover from the backplate.
Entry positions for the mains water and electric cable are from the top, bottom, or from the back.
Note: Deviations from the designated entry points will invalidate product approvals.
If bottom entry has been chosen, fit the appropriate cut-out in the top of the backplate (fig.8).
If top entry has been chosen, fit the appropriate cut-out in the bottom of the cover (fig.9).
After choosing the site for the shower, use the Installation Template supplied to mark the four fixing holes, the position of which are shown in (fig.7).
Drill and plug the wall.
(An appropriate drill bit should be used. If the wall is brick, plasterboard or a soft building block, appropriate wall plugs and screws should be fitted).
Screw the top two fixing screw into position leaving the base of the screw head protruding 6mm out from the wall.
Hook the backplate over the top of the two screw and fit the other fixing screws into position.
DO NOT fully tighten the screws at this stage, as the fixing holes are elongated to allow for out of square adjustment after the plumbing connections have been completed.
FITTING THE SHOWER TO THE WALL
Fig.7
Fig.8
Fig.9
10
T150Z pumped thermostatic electric shower
PLUMBING CONNECTIONS
Plumbing to be carried out before wiring
DO NOT use jointing compounds on any pipe fittings for the installation.
DO NOT solder fittings near the shower unit as heat can travel along pipework and damage components.
Compression fittings Must be used to connect to the inlet of the shower.
Note: An additional stopvalve (complying with Water Regulations) Must be fitted in the water supply to the shower as an independent means of isolating the water in order to carry out maintenance or servicing.
Important: Before completing the connection of the water supply to the inlet of the shower, flush out the pipework to remove all swarf and system debris. This can be achieved by connecting a hose to the pipework and turning on the water supply long enough to clear the debris to waste.
Procedure
Turn off the water supply isolating stopvalve. Connect the water supply to the Inlet of the shower via 15mm copper, stainless steel or plastic pipe using a 15mm x 15mm compression fitting, see (fig.10) for advice on Rear Entry fitting.
Note: If installing a feed pipe from the back, the use of a soldered Elbow connector is recommended. It should be positioned approximately 105mm from the inlet connector centre. The centre of the inlet valve to the wall surface is 21mm.
Fig.10
105mm
21mm
Centre of Soldered Elbow
Centre of Water Inlet
Wall
Loading...
+ 25 hidden pages