Only qualified personnel should install and service the equipment. The installation, starting up, and
servicing of heating, ventilating, and air-conditioning equipment can be hazardous and requires specific
knowledge and training. Improperly installed, adjusted or altered equipment by an unqualified person could
result in death or serious injury. When working on the equipment, observe all precautions in the literature
and on the tags, stickers, and labels that are attached to the equipment.
January 2013UV-SVN03F-EN
“A” and later Design Sequence
750 cfm—1500 cfm
SAFETY WARNING
Warnings, Cautions and Notices
Warnings, Cautions, and Notices. Note that
warnings, cautions, and notices appear at appropriate
intervals throughout this manual. Warnings are provide to
alert installing contractors to potential hazards that could
result in death or personal injury. Cautions are designed to
alert personnel to hazardous situations that could result in
personal injury, while notices indicate a situation that
could result in equipment or property-damage-only
accidents.
Your personal safety and the proper operation of this
machine depend upon the strict observance of these
precautions.
Read this manual thoroughly before operating or servici ng
this unit.
ATT EN TI ON : Warnings, Cautions, and Notices appear at
appropriate sections throughout this literature. Read
these carefully:
WARNING
CAUTIONs
NOTICE:
Indicates a potentially hazardous
situation which, if not avoided, could
result in death or serious injury.
Indicates a potentially hazardous
situation which, if not avoided, could
result in minor or moderate injury. It
could also be used to alert against
unsafe practices.
Indicates a situation that could result in
equipment or property-damage only
Important
Environmental Concerns!
Scientific research has shown that certain man-made
chemicals can affect the earth’s naturally occurring
stratospheric ozone layer when released to the
atmosphere. In particular, several of the identified
chemicals that may affect the ozone layer are refrigerants
that contain Chlorine, Fluorine and Carbon (CFCs) and
those containing Hydrogen, Chlorine, Fluorine and
Carbon (HCFCs). Not all refrigerants containing these
compounds have the same potential impact to the
environment. Trane advocates the responsible handling of
all refrigerants-including industry replacements for CFCs
such as HCFCs and HFCs.
Responsible Refrigerant Practices!
Trane believes that responsible refrigerant practices are
important to the environment, our customers, and the air
conditioning industry. All technicians who handle
refrigerants must be certified. The Federal Clean Air Act
(Section 608) sets forth the requirements for handling,
reclaiming, recovering and recycling of certain
refrigerants and the equipment that is used in these
service procedures. In addition, some states or
municipalities may have additional requirements that
must also be adhered to for responsible management of
refrigerants. Know the applicable laws and follow them.
WARNING
Contains Refrigerant!
System contains oil and refrigerant under high
pressure. Recover refrigerant to relieve pressure before
opening the system. See unit nameplate for refrigerant
type. Do not use non-approved refrigerants, refrigerant
substitutes, or refrigerant additives.
Failure to follow proper procedures or the use of nonapproved refrigerants, refrigerant substitutes, or
refrigerant additives could result in death or serious
injury or equipment damage.
WARNING
Proper Field Wiring and Grounding
Required!
All field wiring MUST be performed by qualified
personnel. Improperly installed and grounded field
wiring poses FIRE and ELECTROCUTION hazards. To
avoid these hazards, you MUST follow requirements for
field wiring installation and grounding as described in
NEC and your local/state electrical codes. Failure to
follow code could result in death or serious injury.
WARNING
Personal Protective Equipment (PPE)
Required!
Installing/servicing this unit could result in exposure to
electrical, mechanical and chemical hazards.
•Before installing/servicing this unit, technicians
MUST put on all PPE required for the work being
undertaken. ALWAYS refer to appropriate MSDS
sheets and OSHA guidelines for proper PPE.
•When working with or around hazardous chemicals,
ALWAYS refer to the appropriate MSDS sheets and
OSHA guidelines for information on allowable
personal exposure levels, proper respiratory
protection and handling instructions.
•If there is a risk of arc or flash, technicians MUST put
on all PPE in accordance with NFPA 70E or other
country-specific requirements for arc flash
protection, PRIOR to servicing the unit.
Failure to follow instructions could result in death or
serious injury.
Never solder, braze or weld on refrigerant lines or any
unit components that are above atmospheric pressure
or where refrigerant may be present. Always remove
refrigerant by following the guidelines established by
the EPA Federal Clean Air Act or other state or local
codes as appropriate. After refrigerant removal, use dry
nitrogen to bring system back to atmospheric pressure
before opening system for repairs. Mixtures of
refrigerants and air under pressure may become
combustible in the presence of an ignition source
leading to an explosion. Excessive heat from soldering,
brazing or welding with refrigerant vapors present can
form highly toxic gases and extremely corrosive acids.
Failure to follow all proper safe refrigerant handling
practices could result in death or serious injury.
Introduction
Important: Equipment is shipped FOB (Free On Board)
at the manufacturer. Therefore, freight
claims for damages against the carrier must
be initiated by the receiver.
Warnings, Cautions and Notices
Trademarks
ComfortLink, EarthWise, Rover, Tracer, Tracer Summit,
Trane, and the Trane logo are trademarks or registered
trademarks of Trane in the United States and other
countries. All trademarks referenced in this document are
the trademarks of their respective owners.
BACnet is a registered trademark of American Society of
Heating, Refrigerating and Air-Conditioning Engineers
(ASHRAE); Echelon, LonTalk, and L
trademarks of Echelon Corporation; Energizer is a
registered trademark of Eveready Battery Company, Inc.;
National Electrical Code, National Fire Protection
Association, and NEC are registered trademarks of the
National Fire Protection Association.
1= Return Air Front / Fresh Air Back
2= 100% Return Air Front
3= 100% Fresh Air Back
4= Dynamic Air Barrier
5= ERS-Compatible w/RH
Connection
6= ERS-Compatible w/LH
Connection
Digit 14 — Preheat / Reheat /
Changeover
A = 4-Pipe Preheat (RH Clg/LH Htg)
B =4-Pipe Preheat (LH Clg/RH Htg)
C =4-Pipe Reheat (RH Clg/LH Htg)
D = 4-Pipe Reheat (LH Clg/RH Htg)
E =2-Pipe (RH Connections)
F= 2-Pipe (LH Connections)
Digit 15 — Cooling / 2-Pipe Coil
0=None
B =2-Row, 12 F.P.I.
C =2-Row, 16 F.P.I.
D = 3-Row, 12 F.P.I.
E =3-Row, 16 F.P.I.
F= 4-Row, 12 F.P.I.
G =4-Row, 14 F.P.I.
H = 3-Row, 16 F.P.I, EarthWise™ Coil
J= 3-Row, DX (R-410A) Cooling Coil
Digit 16 — Heating Coil
0=None
A = 1-Row, 12 F.P.I.
B =2-Row, 12 F.P.I.
C =2-Row, 16 F.P.I.
D = 3-Row, 12 F.P.I.
E =3-Row, 16 F.P.I.
F= 4-Row, 12 F.P.I.
G =4-Row, 14 F.P.I.
H = 3-Row, 16 F.P.I, EarthWise Coil
K=Steam Low
L=Steam High
M =Electric Heat - Low
N =Electric Heat - Med
P =Electric Heat - High
1= Deluxe Beige
2= Cameo White
3=Soft Dove
4= Stone Gray
5= Driftwood Gray
UV-SVN03F-EN7
General Information
Unit Description
Unit Nameplate. The unit nameplate is located in the
left hand end pocket, behind the control box. It includes the
unit model number, serial number, electrical
characteristics, and other pertinent unit data.
Factory Shipment. Before shipment, each unit is leak-
tested and run-tested for proper control operation.
Access. A three-panel front access of the unit ventilator
allows for speedy set-up during field commissioning. This
design allows for the end pocket of the unit ventilator to be
open while the fan (airside) section stays closed.
End Pockets. Access for piping and controls is made
through the unit ventilator’s end pockets.
Coil Connections. The coil headers and drain
connections are made within the unit chassis to allow a
tight seal and help prevent air leakage around the coil. The
connection sizes vary dependent upon type of coil
combination specified.
Coil type
Hydronic cooling (main) coil or
Heating/cooling changeover coil
Heating (auxiliary) coil
Steam heating coil1 in. FNPT
Direct expansion coil
Unit Drain Pan. The drain pan is dual-sloped for
effective condensate removal. It is made from a noncorrosive material to help eliminate issues associated to
leaking or standing water. It may be easily removed for
cleaning. The drain pan connection size for all Trane VUVE
models is 7/8
in. OD.
Motor. Motors for the VUVE model do not include an
external fan bearing on the end of the fan shaft. This helps
avoid issues related to fan bearing maintenance (oiling is
not needed), and/or bearing replacement.
Filters. Filter sizing for the unit ventilator are an off-the-
shelf design to reduce or help eliminate local stocking of
the filters. Options include throwaway filters, MERV 8, and
MERV 13 filters.
Sliding Fan Deck. Convenient access to the fan motor
and wheels for maintenance and serviceability may be
made through Trane’s easy-slide fan deck design.
Note: Ground wire must be reconnected if removed for
service of fan deck.
Outside-Air/Return-Air Dampers. The outside-air/
return-air damper is a one piece, linkage free design
resulting in a superior air-tight seal.
Size (in.)
3/4 in. nominal
7/8 in. ID
1/2 in. nominal
5/8 in. ID
3/8 in. OD liquid
7/8 in. OD suction
Options
Field-Installed Controls (Option). The unit comes
equipped with a fan speed switch, damper blade (only),
and an optional low temperature detection.
will incorporate a pre-wired, selected control components
to a terminal strip for wiring a field-provided controller and
temperature sensor.
Note: For controller operation malfunction of any non-
Tracer ZN520 Control Package (Option). The Tracer
ZN520 electronic digital controller is a factory installed,
tested and commissioned LonTalk
may be used in a stand-alone control scheme, or as part of
a building automation system. The controller is pre-wired
to Trane selected control components best suited for room
comfort. For more information on the Tracer ZN520 unit
controller operation and service issues, refer to
CNT-SVX04A-EN (Installation, Operation, and Programming Guide: Tracer ZN520 Unit Controller), or the
most recent version.
Tracer UC400 Control Package (Option). The Tracer
UC400 electronic digital controller is a factory installed,
tested and commissioned BACnet® certified design. The
Tracer UC400 operates as a single zone VAV controller and
ramps fan speed based on space load. It may be used in a
stand-alone control scheme, or as part of a building
automation system. The controller is mounted, pre-wired,
and pre-programmed to selected control components
best suited for room comfort. For more information on the
Tracer UC400 unit controller operation and service issues,
refer to BAS-SVX48B-EN (Installation, Operation, and
Programming Manual: Tracer UC400 Programmable
Controller), or the most recent version.
OA/RA Actuator (Option). The OA/RA actuator
provides true spring-return operation for positive close-off
of the OA/RA damper. The spring return system of the
actuator closes the outside damper if power is lost to the
building. When ordered with factory controls, the actuator
is a 3-point floating design. A 2 to 10 Vdc actuator is
available when other than Trane controls are specified.
Refer to Table 1, p. 9 for OA/RA technical data.
Note: Because the damper actuator is a spring return
Units containing the end device control design
Trane, field installed controls, consult the literature
or technical support of the controls manufacturer.
®
certified design. It
type an inner spring will close the damper upon
loss of power. If the need to service or replace the
actuator is required, the spring must be “loaded”
for the damper to function properly. The term
loaded means that the blade must be held in the
return air position upon replacement of the
actuator.
8 UV-SVN03F-EN
General Information
Power supply24 Vac ±20% 50/60 Hz
24 Vac ±10%
Power consumptionRunning: 2.5 W
Holding: 1 W
Transformer sizing5 VA (class 2-power source)
Overload protection Electronic throughout 0° to 95° rotation
Control signal2 to 10 Vdc
3-point floating with Trane controls
Angle of rotationMaximum 95°
Adjustable with mechanical stop
Torque35 in·lb
Direction of rotation Spring return reversible with cw/ccw
mounting
Position indicationVisual indicator, 0° to 95°
Noise levelRunning: 30 dB
Power supply24 Vac ± 20% 50/60 Hz
24 Vac
± 10%
Power consumption2 W
Transformer sizing3 VA (class 2-power source)
Angle of rotationMaximum 95-degree
Adjustable with mechanical stop
Torque35 in./lb
Direction of rotation Reversible with switch L/R
Position indicationClip-on indicator
Manual overrideExternal push button
Noise levelLess than 35 dB
Control signal3-point floating
Power supply24 Vac -50/60 Hz
Power consumption4 W
Max. duty cycle15%
Operating ambient temp. 0 to 65°C
bypass damper actuator incorporates a direct couple
design. It provides electronic protection against overload.
A limit switch is not included, nor required as part of the
design. When reaching the damper end position, the
actuator automatically stops. The gears can be manually
disengaged with a button on the housing. Refer to Table 2,
p. 9 for face and bypass actuator specifications.
Modulating Water Valves (Option). The modulating
control valve provides optimum control of hot and chilled
water flow in various heating and cooling applications.
They are designed to provide sinusoidal valve actuator
travel and operate silently, resisting water hammer.
The actuator on the valve is a 24V, 3-point floating type.
Refer to Tabl e 3 for modulating water valve specifications.
Isolation Valve (Option). The isolation valve is a two
position 24V, spring return type valve. It provides added
control in heating and cooling applications when used in
conjunction with the face and bypass damper.
On heating coils, and two-pipe changeover applications,
the valve is normally open to help prevent the coil from
freezing in-case of power loss.
For cooling, the valve is normally closed and opens when
there is a call for cooling. Refer to Tab l e 4 , p. 9 for isolation
valve specifications.
Table 2.Face-bypass actuator specification
Table 3.Mod. water valve specification
Table 1.OA/RA actuator specification
UV-SVN03F-EN9
Table 4.Isolation valve specification
ECM Application Notes
The new Trane BLDC system has some notable differences
to traditional designs.
RPM Mode
The motors are programmed from the factory to run in
rpm mode and will not change rpm based on external
static pressure, except at the performance limits of the
motor/controller. For ducted units, the units are shipped
with the rpm set for 0.2 in. ESP for High, Medium, and Low
speeds. The speeds can for high, medium, and low
operation, but should not be changed for the electric heat
actuation speeds.
Generally, the fans deliver less cfm for the same rpm, if the
static is increased and the power will decrease. The fan will
deliver more cfm for the same rpm, if the static is
decreased and the fan power will increase. A unit with high
static configuration should not be used to free-deliver air
(i.e., with no ducting attached).
Field Power Wiring
Note: This product uses an electronic variable speed
motor control, which includes a line reactor to
minimize power line harmonic currents. It is
recommended that good wiring practices be
followed to manage building electrical power
system harmonic voltages and currents to avoid
electrical system problems or other equipment
interaction.
Performance Boundaries
While the speeds of the fan motors can be adjusted, never
program a fan speed higher than 1700 rpm, or lower than
450 rpm. In many cases, units configured for high-static
operation will not achieve the desired rpm if the ESP of the
unit is too low, or the unit is allowed to “free-discharge.”
The ECM engine contains settings that will limit the output
power of the motor under these overload conditions. If the
motors cannot achieve rpm close to the target for a specific
period of time, the unit will disable electric heat and fanstatus indicators.
perform the function of a two 3-pole contactors.
Figure 1.Sample arrangement: electric heat relay
Troubleshooting Other Unit Functions
In some cases, the normal or abnormal operation of the
BLDC system may interact with other components in the
system. Generally, verification of the engine and adapter
boards’ wiring and configuration should be checked if
there are unexplained abnormalities in other areas of the
unit:
1. Valve operation
2. Electric Heat operation
3. Changeover sensor operation
4. Damper operation
5. Condensate overflow switch
A high degree of protection is provided on electric heat
nits. If electric heat fails to actuate, it may be because of
u
one of the following events:
1. Fans are failing to meet target speed. If a second motor
is not present, all settings for speeds for Motor 2
should be set to 0000.
2. Hot water may be available in the changeover coil.
3. The connection to analogue input 1 on the Tracer ZN
controlle
4. Target speeds for motor
a. The parameter may be set incorrectly.
b. The
r may be reversed in polarity.
s may be set too high:
parameter may be set incorrectly.
MCA/MFS and Power Draw
The Trane BLDC motors have variable output but are
shipped at specific settings to deliver proper performance
and reliability. The power draw indicated in the catalogue
indicates the power consumed when applied properly (as
shipped and with the nominal ESP applied). However, the
nameplate of the unit indicates the maximum input draw
of the motor, as the motor settings can be changed to draw
more power.
Electric Heat Relays
For quiet operation, the new BLDC units employ power
relays instead of definite purpose contactors for electric
heat actuation. The coils of multiple relays are hooked in
parallel to simulate a multi-pole contactor, as shown in
Figure 1. In Figure 1, two sets of three relays are used to
10 UV-SVN03F-EN
Dimensions and Weights
Unit Location and Clearances
Locate the unit in an indoor area. The ambient
temperature surrounding the unit must not be less than
45°F. Do not locate the unit in areas subject to freezing.
Electrocution and Fire Hazards with
Improperly Installed and Grounded Field
Wiring!
NOTICE:
Equipment Damage!
Do not locate the unit in areas subject to freezing. Pipes
could burst at lower temperature resulting in
equipment damage.
Attention should be given to service clearance and
technician safety. The unit should contain enough space
for service personnel to perform maintenance or repair.
Provide sufficient room to make water, and electrical
connection(s).
Table 5.VUVE general data
Description
Unit length w/o end covers (in.)698193105
Unit depth - standard (in.)16-5/816-5/816-5/816-5/8
Unit depth - with false back (in.)21-1/421-1/421-1/421-1/4
Unit height - standard (in.)30303030
Shipping weight (lb)320405450470
Nominal filter size (in.) and quantity14 x 20 x 1 (2)14 x 24 x 1 (1)14 x 20 x 1 (2)14 x 24 x 1 (2)
Dynamic air filter nominal size (in.) and quantity 7 x 42 x 1 (1)7 x 54 x 1 (1)7 x 66 x 1 (1)7 x 78 x 1 (1)
Drain connection size (in.)7/8 I.D. hose7/8 I.D. hose7/8 I.D. hose7/8 I.D. hose
Fan type / quantityFC / 2FC / 2FC / 4FC / 4
Motor data
Improperly installed and grounded field wiring poses
FIRE & ELECTROCUTION hazards. To avoid these
hazards, you MUST follow requirements for field wiring
installation and grounding as described in NEC and
your local/state electrical codes. All field wiring MUST
be performed by qualified personnel.
Failure to follow these requirements could result in
death or serious injury.
A 36-inch clearance at the unit front is sufficient for
maintenance and service of the equipment.
Unit size
14 x 30 x 1 (1)14 x 24 x 1 (1)14 x 30 x 1 (1)
WARNING
Table 6.Control Methodology
Fan Speed
FSS3 or infinite
CSTI 3 or infinite
ZN520 3
UC400Infinite
(a) With a field-supplied 2–10 Vdc controller.
UV-SVN03F-EN11
(a)
(a)
Table 7.Control Sequences
Fan Speeds
(b)
(a)
(b)
(a)
1
1
2
2
DX operation
Electric heat operation
Sidewall Exhaust
ERSA
(a) Fan speed during sequence operation.
(b) Unit Ventilator when operating with option.
Dimensions and Weights
UNIT SIZE
075
100
125
150
NO. FANS
2
2
4
4
A
69"
81"
93"
105"
B
42"
54"
66"
78"
NOTE:
1. THE UNIT LENGTH DOES NOT INCLUDE 5/8" END PANELS.
2. THE POWER CONNECTION IS MADE IN THE LEFT HAND
END POCKET FOR ALL OPTIONS BUT ELECTRIC HEAT.
3. THE POWER CONNECTION FOR ELECTRIC HEAT OPTION
IS MADE IN THE RIGHT HAND END POCKET.
8 1/8"
B
A
(4)K.O. FOR PIPING
OR ELECTRICAL
FRESH AIR OPENING (OPTIONAL)
5 3/4"
5"
21/4"
13 1/2"
9"
12 1/2"
22 5/8"
3/4"
3 3/4"
BACK VIEW
12 1/4"
FRONT OF UNIT
GRILLE
RETURN AIR
(OPTIONAL)
UNIT MOUNTED
FAN SWITCH
(OPTIONAL)
2"
21/4"
16 5/8"
(2)9" x 9"[229mm x 229mm]
KNOCKOUTS IN BOTTOM
10 7/8"
3 3/4"
TOP VIEW
13"
5 1/4"
9 1/4"
14 3/8"
7"
21/4"
21/2"
23/8"
30"
SIDE VIEW
7/8" O.D.
AUX.
DRAIN CONN.
(optional)
PIPE
CHASE
11"
"
7/8" O.D.
DRAIN CONN.
16 5/8"
Figure 2.Standard depth unit
9 1/4
12 UV-SVN03F-EN
Figure 3.Falseback unit
UNIT SIZE
075
100
125
150
NO. FANS
2
2
4
4
A
69"
81"
93"
105"
B
42"
54"
66"
78"
C
25" to 29"
25" to 29"
25" to 29"
25" to 29"
NOTE:
1. THE UNIT LENGTH DOES NOT INCLUDE 5/8" END PANELS.
2. THE POWER CONNECTION IS MADE IN THE LEFT HAND
END POCKET FOR ALL OPTIONS BUT ELECTRIC HEAT.
3. THE POWER CONNECTION FOR ELECTRIC HEAT OPTION
IS MADE IN THE RIGHT HAND END POCKET.
14 3/8"
21/4"
21/2"
16 5/8"
23/8"
30"
21 1/4"
SIDE VIEW
Depicting Step-down
Falseback
18"
C
STEP-DOWN
IS IN 1"
INCREMENTS
21/4"
21/2"
16 5/8"
23/8"
30"
21 1/4"
SIDE VIEW
18"
5 1/4"
7"
PIPECHASE
14 3/8"
11"
9 1/4"
/
3
0
PIPE
CHAS
7/8" O.D.
DRAIN CONN.
7/8" O.D.
AUX.
DRAIN CONN.
(optional)
FRONT OF UNIT
RETURN AIR
(OPTIONAL)
FALSEBACK
A
(4)K.O. FOR PIPING
OR ELECTRICAL
5 3/4"
5"
9"
12 1/2"
22 5/8"
21/4"
BACK VIEW
8 1/8"
12 1/4"
B
FRESH AIR OPENING (OPTIONAL)
13 1/2"
3/4"
3 3/4"
STEP-DOWN
FALSEBACK
FOR RETROFIT
APPLICATIONS
WHERE WINDOW
SEAL MAY INTERFERE
WITH UNIT INSTALLATION
(OPTIONAL)
STEP-DOWN
FALSEBACK
4. THE UNIT SHOWN INCLUDES THE INSULATED HORIZONTAL
BAFFLE OPTION.
2"
21/4"
(2)9" x 9"[229mm x 229mm]
KNOCKOUTS IN BOTTOM
10 7/8"
3 3/4"
TOP VIEW
13"
FALSEBACK
Dimensions and Weights
E
"
UV-SVN03F-EN13
Dimensions and Weights
UNIT SIZE
075
100
125
150
NO. FANS
2
2
4
4
A
69"
81"
93"
105"
B
42"
54"
66"
78"
NOTE:
1. THE UNIT LENGTH DOES NOT INCLUDE 5/8" END PANELS.
2. THE POWER CONNECTION IS MADE IN THE LEFT HAND
END POCKET FOR ALL OPTIONS BUT ELECTRIC HEAT.
3. THE POWER CONNECTION FOR ELECTRIC HEAT OPTION
IS MADE IN THE RIGHT HAND END POCKET.
21/2"
16 5/8"
23/8"
30"
21 1/4"
SIDE VIEW
7"
PIPE
CHASE
14 3/8"
21/4"
5 1/4"
11"
9 1/4"
3/8
9 1/
2/2
3
0"CHASE
7/8" O.D.
DRAIN CONN.
7/8" O.D.
AUX.
DRAIN CONN.
(optional)
B
A
(4)K.O. FOR PI PING
OR ELECTRICAL
FRESH AIR OPENING
5 3/4"
5"
21/4"
13 1/2"
9"
12 1/2"
22 5/8"
3/4"
3 3/4"
RETURN AIR OPENING
BACK VIEW
8 1/8"
12 1/4"
FALSEBACK
BARRIER
2"
21/4"
13"
(2)9" x 9"[229mm x 229mm]
KNOCKOUTS IN BOTTOM
10 7/8"
3 3/4"
TOP VIEW
FALSEBACK
Figure 4.Dynamic air barrier unit
4"
14 UV-SVN03F-EN
Figure 5.End covers
Dimensions and Weights
UV-SVN03F-EN15
Dimensions and Weights
Figure 6.Wall boxes
16 UV-SVN03F-EN
Figure 7.Crossover piping
16 5/8" DEPTH UNIT
FLUSH
7/8" I.D. FIELD
CONN. W/ SHUT
OFF VALVE
RS
Dimensions and Weights
1 1/2"
RETURN
3"
SUPPLY
TOP VIEW
21 1/4" DEPTH UNIT
FLUSH
TOP VIEW
Note: 1-3/8 in. OD and 2-1/8 in. ID crossover piping
1. Crossover piping is available for all 2- or 4-pipe coils
selections. Trane provides the crossover for the hot
water only. The crossover pipe is factory insulated with
3/8 in.-thick insulation.
2. Expansion compensation between the factory piping
package and the crossover piping is achieved using a
flex hose rated at 250 psi working pressure. Flex hose
s only available with factory mounted piping
i
packages.
3. Expansion compensation for the
must be handled external to the unit ventilator.
4. Crossover connections term
pocket as the heating coil on all 2- and 4-pipe coils.
crossover piping
inate in the same end
3 1/2"
4 1/2"
7/8" I.D. FIELD
CONN. W/ SHUT
OFF VALVE
RS
3 1/2"
4 1/2"
SIDE VIEW
1 1/4"
8 1/4"
10"
SIDE VIEW
19 3/8"
3 5/8"
5 3/8"
24"
RETURN
3"
SUPPLY
24"
19 3/8"
UV-SVN03F-EN17
Receiving and Handling
The unit ventilator is packaged in clear stretch wrap and
protective cardboard.
Note: Before unwrapping, make a visual inspection of the
unit for any damage that may have occurred during
shipping. All orders are shipped FOB (Freight on
Board) from the factory, therefore any claims must
be made with the delivering carrier.
Following visual inspection, carefully begin the following
procedures:
1. Carefully remove the stretch wrap and the top
cardboard cover.
2. Remove remaining cardboard blocking.
3. Remove the bottom access panel with a 7/32-in. Allen
h.
wrenc
4. Verify nameplate sales order number is correct.
5. Remove shipping bracket from the lower rear corners
f the unit and shipping skid. Access to the screws
o
holding unit to the skid is obtained inside the unit.
Figure 8.Shipping skid removal
6. Rotate fan wheels manually. Wheels should move
freely and be in proper alignment. Visually inspect the
fan area for obstructions or shipping damage.
7. Remove all applicable knock-outs for coil piping and
electrical connections
Figure 4, p. 14).
18 UV-SVN03F-EN
(see Figure 2, p. 12 through
Pre-Installation
Jobsite Inspection
Always perform the following checks before accepting a
unit:
1. Verify that the nameplate data matches the data on the
sales order and bill of lading (including electrical data).
2. Verify that the power supply complies with the unit
nameplate specifications.
3. Visually inspect the exterior
shipping damage. Do not sign the bill of lading
accepting the unit(s) until inspection has been
completed. Check for damage promptly after the
unit(s) are unloaded. Once the bill of lading is signed at
the jobsite, the unit(s) are now the property of the
SOLD TO party and future freight claims MAY NOT be
accepted by the freight company.
Jobsite Storage
This unit is intended for indoor use only. To protect the unit
from damage due to the elements, and to prevent possible
IAQ contaminant sources from growing.
1. Place the unit(s) on a dry surface or raise above the
ground to assure adequate air circulation beneath the
unit.
2. Cover the unit(s) with a water proof tarp to protect
from the elements.
them
of the unit, for signs of
NOTICE:
Microbial Growth!
Wet interior unit insulation can become an
amplification site for microbial growth (mold), which
may cause odors and damage to the equipment and
building materials. If there is evidence of microbial
growth on the interior insulation, the insulation should
be removed and replaced prior to operating the system.
3. Make provisions for continuous venting of the covered
units to prevent moisture from standing on the unit(s)
surfaces.
4. Do not stack units.
UV-SVN03F-EN19
Installation—Mechanical
Grout
Weep
Holes
Rubber
Seals
Unit
Outside
Wall
Floor
Interior Wall
w/ sheetrock
Water dam sloped
toward exterior
Weep
Holes
Caulking
Outside
Wall
Rubber
Seals
Unit
Interior Wall
w/ sheetrock
Water dam sloped
toward exterior
Flanged
wallbox
Wall Box Installation
The following instructions are general recommendations
for installing wall intake boxes. Consult the architectural
plans for specific requirements.
Additional materials required to complete any specific
installations (such as duct connections, metal mounting
plates, or flanges) are not furnished by Trane.
For best results, all air intake boxes should be removable
from outside of the building. Weep holes must be at the
bottom to permit free drainage. A positive air and
moisture seal should be provided around all edges.
General Instructions. Trane wall boxes are illustrated in
the dimensional section of this manual. Dimensions are
actual, and may be used to define the wall opening.
Vertical louvers in the wall intake box provide extra
strength for a high load bearing capacity. The lintel may be
omitted on masonry wall installations.
Weep holes are provided in the outside face of the bottom
channel in the wallbox frame. Install all wall boxes to
permit free drainage through the weep holes to the
outside of the building.
All wallboxes are furnished with diamond pattern
expanded aluminum bird screen.
Note: V1 and V2 (vertical) wall models are all unflanged.
H2, V3, and V6 are flanged.
Figure 9.Masonry wall installation
Figure 10. Flanged wall box installation in 2-in. curtain
wall
Installation in Masonry Walls. A typical method of
installing the wall box in a masonry wall opening is shown
in Figure 9.
Grout the top and bottom of the wall box frame as noted.
A sloped water dam located in the space between the unit
and wall facilitates moisture drainage. Grouting at the
ends of the intake box will complete the seal between the
wall box frame and the masonry opening.
Installation in Curtain Walls. In all cases, the wall
intake box should be caulked to provide a tight,
weatherproof seal (see Figure 10).
Note: A minimum of 2-1/8 in. of clearance must be
maintained between the exterior wall and back of
the unit. Failure to provide this gap will not allow
the wall box to fit properly.
20 UV-SVN03F-EN
General Installation Checks
The checklist below is a summary of the steps required to
successfully install a unit. This checklist is intended to
acquaint the installing personnel with procedures
required in the installation process. It does not replace the
detailed instructions called out in the applicable sections
of this manual.
1. Carefully remove the stretch wrap and top cardboard
cover. Check the unit for shipping damage and material
shortage; file a freight claim and notify appropriate
sales representation. If end panels have been ordered, the panel will already be mounted to the unit.
Note: The unit ventilator is packaged in clear stretch
wrap to allow for immediate visual inspection.
A protective cardboard cover helps prevent
scratching and other cosmetic blemishes
during transport.
2. Remove remaining cardboard blocking.
3. Remove the unit’s left front panel
sales order number is correct. It is located behind the
control box.
to verify nameplate/
Installation—Mechanical
4. Remove shipping bracket from the lower rear corners
of the unit to separate the unit from the skid. Access to
the screws holding the bracket to the skid is obtained
inside the unit.
5. Rotate the fan wheels manually
move freely and be in proper alignment. Visually
inspect the fan area for obstructions or shipping
damage.
6. Remove all applicable knockouts for coil
electrical connections.
. The wheels should
piping and
Location Considerations
Selecting the appropriate location for installing a unit is
very important. The following factors should be
considered:
WARNI NG
Heavy Object!
Floor structure must be strong enough to support the
weight of the unit. Consult the structural plans, and
have a structural engineer ensure the floor can
withstand the weight of the unit. Inadequate structural
support could result in unit falling.
Failure to follow recommendations could result in
death or serious injury.
5. Internal access to the unit is pr
front panel. Sufficient space should be allowed to lift
the panel for maintenance purposes.
Note: All wall intake boxes should be installed prior to
mounting the unit ventilator. Refer to p. 20 for wall
box installation instructions.
The 1/2 in. mounting or anchoring holes are located on the
back of the unit on each end (see Figure 11, p. 22).
Note: All mounting fasteners are to be provided by the
installer.
1. Floor design must have sufficient structure to
withstand the weight of the unit while allowing for
openings in the floor for a return air duct, electrical and
piping supply lines fed through the floor. Refer to
“Dimensions and Weights,” p. 11 for unit weights.
2. Wall space design should allow the unit to be mounted
the wall securely. The wall surface behind the unit
to
should be smooth and level. Wall and floor moldings
should be removed prior to installation. A wall slightly
out of level may cause problems with unconditioned
air leaking into the room. Remove any object
projecting more then 1/8 in. (0.3175 cm) from the wall
surface.
Note: Ad
3. There are two removable knock
unit, on either end, for piping and electrical supply
lines. A pipe chase is located in the upper back portion
of the unit for crossover piping. The outside air
opening is located in the lower back of the unit and the
path to the wallbox on the outside wall should be
unobstructed.
4. The physical layout of the
any accessories ordered with the unit. Conditioned air
is distributed through the grille on top of the unit and
returned through the return air grille on the bottom of
the unit. Avoid placing any objects that may obstruct
either grille or interfere with airflow.
ditional gasket or furr strips may be installed
to accommodate for an uneven wall.
-outs in the rear of the
room should accommodate
UV-SVN03F-EN21
Installation—Mechanical
A
B
C
D
E
F
C
B
Figure 11. Mounting hole location
075Standard unit (no falseback)1.3113.502.7566.3910.3845.64
Standard falseback1.002.1326.0067.0010.0047.00
29 in. stepdown falseback1.002.1324.4467.0010.0047.00
28 in. stepdown falseback1.002.1323.4467.0010.0047.00
27 in. stepdown falseback1.002.1322.4467.0010.0047.00
26 in. stepdown falseback1.002.1321.4467.0010.0047.00
25 in. stepdown falseback1.002.1320.4467.0010.0047.00
100Standard unit (no falseback)1.3113.502.7578.3910.3857.64
Standard falseback1.002.1326.0079.0010.0059.00
29 in. stepdown falseback1.002.1324.4479.0010.0059.00
28 in. stepdown falseback1.002.1323.4479.0010.0059.00
27 in. stepdown falseback1.002.1322.4479.0010.0059.00
26 in. stepdown falseback1.002.1321.4479.0010.0059.00
25 in. stepdown falseback1.002.1320.4479.0010.0059.00
125Standard unit (no falseback)1.3113.502.7590.3910.3869.64
Standard falseback1.002.1326.0091.0010.0071.00
29 in. stepdown falseback1.002.1324.4491.0010.0071.00
28 in. stepdown falseback1.002.1323.4491.0010.0071.00
27 in. stepdown falseback1.002.1322.4491.0010.0071.00
26 in. stepdown falseback1.002.1321.4491.0010.0071.00
25 in. stepdown falseback1.002.1320.4491.0010.0071.00
150Standard unit (no falseback)1.3113.502.75102.3910.3881.64
Standard falseback1.002.1326.00103.0010.0083.00
29 in. stepdown falseback1.002.1324.44103.0010.0083.00
28 in. stepdown falseback1.002.1323.44103.0010.0083.00
27 in. stepdown falseback1.002.1322.44103.0010.0083.00
26 in. stepdown falseback1.002.1321.44103.0010.0083.00
25 in. stepdown falseback1.002.1320.44103.0010.0083.00
ABCDE F
falseback metal. Use these holes rather than the holes
WARNI NG
Improper Unit Lift!
Test lift unit approximately 24 inches to verify proper
center of gravity lift point. To avoid dropping of unit,
reposition lifting point if unit is not level. Failure to
properly lift unit could result in death or serious injury
or possible equipment or property-only damage.
located in the unit’s end pockets.
Note: Ensure the unit is level. Coils and drain pans
inside the unit are pitched properly for draining
before shipment.
9. Ensure the unit rests tightly ag
proper seal and that air does not leak underneath the
unit.
ainst the wall. Check for
7. Set the unit into selected location and adjust leveling
legs if necessary to ensure level fit.
Note: Care
should be taken when handling the unit to
ensure that the front return air grille does not
bend.
8. Push the unit tightly against
the wall to compress the
seal on the back edge of the unit and intake opening.
Subbase (Option)
A subbase may be used to increase the unit height and aid
in leveling the unit. The subbase is shipped separately for
field installation. Slots and leveling screws are provided
on the subbase.
1. Remove the leveling legs provided with the unit (see
Figure 12).
Anchor the unit by using the 1/2 in. mounting holes in
th end pockets.
bo
Units containing a falsebac
k: The falseback unit
ventilator contains mounting holes located on the
22 UV-SVN03F-EN
Figure 12. Subbase with leveling legs
Unit Base
Installation—Mechanical
Weld
Nuts
2"- 6"
Subbase
For leveling legs
2. Set the unit on the subbase and fasten with four, 3/8 in.
x 16 ft x 1 in. hex head cap screws and 3/8 in. lock
washers.
Note: Hex
screws and lock washers are provided by
the factory. They are located in a baggy and are
used to attach the base to the unit ventilator.
Pre-drilled slots in the subbase flange will line
up with the weld nuts in the bottom of the unit.
3. The bottom of the subbase has weld nuts in four slots.
Place the leveling le
gs in those slots and level the unit.
End Panels
When ordered as an option, end covers ship already
attached to the vertical unit ventilator. The following
section is for installing end covers purchased as an addon.
It is recommended end panels be installed on the unit
ventilator after all piping, wiring and accessory installation
is completed. To install the end panel:
1. Insert the four factory provided metal studs into the
four pre-mounted nuts on the inside of the panel.
2. Align each stud with the four pre-drilled holes on the
de of the unit.
si
3. Secure the panel to the unit by fastening wit
factory provided nuts.
4. Do not overtighten screws.
h the four
NOTICE:
Equipment Damage!
Do not run units for any length of time without all
panels and filters properly installed. Failure to do so
could result in equipment failure.
UV-SVN03F-EN23
Installation—Piping
Piping Installation
Before installation of piping package, the shipping bracket
holding the piping in place, must be removed.
Proper installation of piping is necessary to provide
efficient coil operation and to prevent damage during
operation. Follow standard piping practices and include all
accessories as necessary.
Piping connection knockouts are shown in “Dimensions
and Weights,” p. 11. Field connection types and sizes for
unit coils are listed in Tab le 8. These sizes are provided for
field piping connection.
Table 8.Coil data for field piping
Coil typeConnection location Field connection size
4-pipe chilled water /
hot water
2-pipe changeover coil Left or right7/8 in. OD
Hot water onlyLeft or right7/8 in. OD
SteamLeft or right1 in. MPT
Chilled water / electric
heat
Chilled water / steam Left or right7/8 in. OD / 1 in. MPT
DXLeft7/8 in. suction, 3/8 in.
DX / hot waterLeft cooling / right
DX / steamLeft cooling / right
DX / electric heatLeft cooling / right
A 7/8 in. OD condensate drain connection is provided on
the chilled water supply end of the unit.
1. Attach a flexible condensate drain hose over the drain
pan connection and secure with a hose clamp.
The drain pan on the vertical is vacuum-molded with a
drain connection and P-trap on the cooling coil,
connection side.
Note: Condensate removal to the main system
should be made through the bottom of the unit
ventilator. If other location for condensate
removal is desired, a specific field cut-out for
the connection should be made in the back of
the unit ventilator. To help avoid cold air
infiltration, the field cut-out should only be
large enough to allow for the condensate hose
to exit the unit.
To field reverse the slope of a vertical unit drain pan:
2. Slide out fan deck (disconnecting the condensate line and fan plug will release fan deck for sliding).
3. Remove pipe clamp that hold
pan.
4. Remove clips that hold the drain pan in-place.
5. Lift and rotate the drain pan.
Left or right (opposite
ends)
Left cooling7/8 in. OD
heating
heating
heating
7/8 in. OD / 5/8 in. OD
7/8 in. suction,
3/8 in. / 5/8 in. OD
7/8 in. suction,
3/8 in. / 1 in. MPT
7/8 in. suction,
3/8 in. / NA
the p-trap to the drain
6. Reconnect p-trap to the drai
n pan and replace clips to
secure the pan to the fan deck.
7. After the condensate drain piping has been completed,
heck water flow to ensure the system properly carries
c
and away all condensate accumulation.
Note: A P
-trap is factory supplied in every vertical unit
ventilator.
Trane Piping Packages (Option). Trane Standard
Piping Package includes a 2- or 3-way valve with bypass
balance valve, ball valves, Pete’s plugs and unions. A
strainer and circuit balancing valve are optional.
All union connections should be tightened in the field.
Units are shipped with union connections hand tightened
only in the factory.
Note: All connections made in the field should be sweat
connections.
Piping packages are not shipped insulated. Any insulation
should be provided in the field by the installing contractor.
The auxiliary drain pan (optional) is the main condensate
connection to the unit when specified. The chilled water or
DX coil drain pan will empty into the auxiliary drain pan if
a factory-installed, auxiliary pan is ordered. All field-piping
condensate connections should be made at the auxiliary
drain pan.
Installation Crossover Piping
Crossover piping is available for all hydronic coils. It is
either 1-3/8 in. \[34.9\] or 2-1/8 in. \[54\] in diameter (OD) as
specified by the customer. Crossover piping can be found
in either the left or right hand end pocket. Refer to
“Dimensions and Weights,” p. 11 for dimensional data.
On 4-pipe coils, crossover piping connects to the main
cooling coil.
Factory insulation is provided on all crossover piping.
When a Trane piping package is ordered, it is installed with
the connections made to the supply and return of both the
coil and the crossover piping. However, supply and return
connections must be made in the field when a piping
package is furnished by the installer.
The crossover piping is located at the back of the unit along
the wall and the ends of the piping are flush with the end
of the unit.
Expansion compensation between the piping package and
the crossover piping is achieved using flex hoses rated at
250 psi working pressure. Expansion compensation for
the crossover piping must be handled external to the unit
ventilator.
Split System Units
The following refrigerant piping and interconnecting
wiring instructions apply to unit ventilators with direct
expansion type cooling coils used in conjunction with aircooled condensing units. Reference must also be made to
24 UV-SVN03F-EN
Installation—Piping
Vacuum Equalizer
H= 12"
minimum
F&T Trap
See text for sizing
Gravity flow to
vented receiver
Coil
To Condensate
return
Temp. Regulating Valve
the condensing unit installation and wiring manuals which
are shipped with the condensing unit.
Note: The ETL listing mark applied to a unit ventilator
does not apply to any associated refrigerant
condensing unit.
Refrigerant Piping
WARNI NG
Hazard of Explosion and Deadly Gases!
Never solder, braze or weld on refrigerant lines or any
unit components that are above atmospheric pressure
or where refrigerant may be present. Always remove
refrigerant by following the guidelines established by
the EPA Federal Clean Air Act or other state or local
codes as appropriate. After refrigerant removal, use dry
nitrogen to bring system back to atmospheric pressure
before opening system for repairs. Mixtures of
refrigerants and air under pressure may become
combustible in the presence of an ignition source
leading to an explosion. Excessive heat from soldering,
brazing or welding with refrigerant vapors present can
form highly toxic gases and extremely corrosive acids.
Failure to follow all proper safe refrigerant handling
practices could result in death or serious injury.
Unit ventilators with direct expansion cooling contain a
nitrogen holding charge in the evaporator coils.
Connections are “pinched-off” at the factory.
To connect the condensing unit lines, cut off the stubouts
and swage. The condensing unit lines can then be brought
into the swage and brazed. Trane recommends the use of
nitrogen purge when brazing refrigerant lines to prevent
formation of oxides in the lines.
Install the refrigerant suction and liquid lines as described
in the condensing unit installation instructions. The TXV is
factory installed on the unit ventilator. Piping should be
run straight out through the back of the unit. Access piping
knockouts are located in the rear panels of the unit, as
shown “Dimensions and Weights,” p. 11.
Recommended refrigerant line connections for various
unit combinations are given in Table 8, p. 24. Typical
Superheat Charging Charts are shown in the Trane Service
Facts found in the condensing unit section manual.
Refrigerant charge weights can also be determined with
your local Trane sales engineer using a valid Trane
Selection Program.
There are detailed methods for determining condensate
load under various operating conditions. However, in
most cases this is not necessary if the coils are piped as
shown in Figure 13. Follow the procedure documented in
the ASHRAE Systems Handbook, Steam Systems.
Figure 13. Steam piping
Modulating Water Valves (Option)
The actuator on the valve is a 24V, 3-point floating valve.
The actuator can be easily removed from the valve body
by pressing in on the locking tab and rotating the actuator
45° counter-clockwise (see Figure 14). The 2-way valves
are bi-directional flow; the 3-way valves can be mixing or
diverting (see Figure 15, p. 26).
Note: The actuator must be removed if soldering is being
conducted near the valve. High heat may cause
damage to the actuator’s plastic body/
mechanisms.
Figure 14. Remove modulating valve actuator by
pressing in tab (inset) and turning actuator
45° counterclockwise
Steam Piping
When air, water or another product is heated, the
temperature or heat transfer rate can be regulated by a
modulating steam pressure control valve. Since pressure
and temperature do not vary at the same rate as load, the
steam trap capacity, which is determined by the pressure
differential between the trap inlet and outlet, may be
adequate at full load, but not some lesser load.
UV-SVN03F-EN25
Installation—Piping
2-way valve3-way valve
Figure 15. Steam piping: 2- and 3-way valves
Closed
Open
B
AB
B
A
A
A
AB<->B
B
AB<->A
AB
On applications without the optional, factory installed
piping packages, it is important to remove the cartridge
assembly from the valve body with the provided tool (see
Figure 16).
Figure 16. Cartridge removal tool
Plumbing the Valve
The valve may be plumbed in any angle but preferably not
with the actuator below horizontal level of the body. Make
sure there is enough room around the actuator for
servicing or replacement.
For use in diverting applications, the valve is installed with
the flow water entering through the bottom AB port and
diverting through end ports A or B. In mixing applications
the valve is installed with inlet to A or B and outlet through
AB.
Mount directly to the tube or pipe. Do not grip the actuator
while making or tightening plumbing connections. Either
hold valve body by hand or attach an adjustable spanner
(38 mm/1-1/2”) across the hexagonal or flat faces on the
valve body (see Figure 17).
Figure 17.Proper plumbing technique for modulating
valves
Use the following steps to complete cartridge assembly
removal:
1. Remove valve actuator.
2. Remove the cartridge assembly from the valve body
with the enclosed tool.
3. Solder the valve in accordance with
practices.
4. Re-install the cartridge after
until it bottoms out. The top surface of the cartridge will
be flush with the top edge of the body casting.
NOTICE:
Over-tightening!
Do not over-tighten. Maximum torque is 40 in·lb.
Overtightening could result in equipment damage.
Manually Opening Valve
The manual opener can be manipulated only when in the
up position. The A port can be manually opened by firmly
pushing the white manual lever down to the midway
position and pushing the lever in. In this position, both A
and B ports are open. This “manual open” position may be
used for filling, venting and draining the system or
opening the valve during power failure.
The valve can be closed by depressing the white lever
lightly and then pulling the lever outward. The valve and
actuator will return to the automatic position when power
is restored.
Note: If the valve is powered open, it cannot be manually
closed, unless the actuator is removed.
normal soldering
soldering by tightening
5. Replace valve actuator and wire in accordance with
instructions.
26 UV-SVN03F-EN
Installation—Piping
Wiring the Valve
WARNI NG
Electrocution and Fire Hazards with
Improperly Installed and Grounded
Field Wiring!
Improperly installed and grounded field wiring poses
FIRE & ELECTROCUTION hazards. To avoid these
hazards, you MUST follow requirements for field wiring
installation and grounding as described in NEC and
your local/state electrical codes. All field wiring MUST
be performed by qualified personnel.
Failure to follow these requirements could result in
death or serious injury.
A controller and a separate transformer is required to
operate each valve (see Figure 18 and Figure 19, p. 27).
Port A “open” and “closed” denote valve open and closed
positions.
Figure 18. Wiring for modulating valve actuator
enough room to remove actuator cover for servicing.
Mount the valve on the tube or pipe.
Note: Ensure the flow through the valve is in the direction
indicated by the arrow stamped on the valve body.
Figure 20. Proper mounting for isolation valves
Servicing/Removal of Valves
The actuator can be removed from the valve body.
Removing the actuator is recommended if soldering is
being conducted near the valve. To remove the actuator:
1. Place the manual operating lever to the Open position
(see Figure 21, p. 27).
2. Depress the locking button and lift actuator until it
separates from the valve body.
To install the actuator
3. Align the slot on the shaft of the
body notch on side of body (see Figure 22, p. 28).
to the valve body:
valve with the valve
Figure 19. Wiring for modulating valve actuator
The typical floating controller is an SPDT controller with a
center-off position. On a change in temperature from the
set point, the controller will close the normally open (NO)
or normally closed (NC) contacts, driving the valve to an
intermediate position until a further change at the
controller.
The valve is set between the limits of the controller to
satisfy various load requirements. In the event of power
failure, the valve will stay in the position it was in before
loss of power. When power is restored, the valve will again
respond to controller demand.
Isolation Valves Installation
The valve can be mounted in any position on a vertical line.
If the valve is mounted horizontally, the actuator must be
even with or above the center line. Make sure there is
Figure 21. Removing valve actuator
UV-SVN03F-EN27
Installation—Piping
Figure 22. Installing isolation valve
4. Install body valve into pipe.
WARNI NG
Electrocution and Fire Hazards with
Improperly Installed and Grounded Field
Wiring!
Improperly installed and grounded field wiring poses
FIRE & ELECTROCUTION hazards. To avoid these
hazards, you MUST follow requirements for field wiring
installation and grounding as described in NEC and
your local/state electrical codes. All field wiring MUST
be performed by qualified personnel.
Failure to follow these requirements could result in
death or serious injury.
Figure 23. Preparation for soldering
3. Sweat the joints, keeping outer surface free from
solder.
Note: Do not use silver solder due to high
temperature requirements.
Heating Coils with Direct Expansion
Cooling
Heating options for direct expansion cooling in the unit
ventilator are hot water, steam or electric heat.
These coils facilitate direct expansion cooling with
standard capacities. The supply and return connections
are located in the right-hand end pocket. Hot water field
connections are made with a 5/8 in. \[15.9\] OD male
sweated joint, while steam coils have a 1 in. \[25.4\] male
pipe thread (MPT) connection. Refer to Table 8, p. 24 for
coil connection sizes.
Electric heat coils provide a third way to supply heating to
the direct expansion cooling. The coil utilizes three to six
preheat elements which are factory-wired.
5. Wiring connections may be made either before or after
actuator installed on body.
6. Place the manual operating leve
OPEN position.
7. Align actuator coupling to slot on the shaf
body and fit the head onto the valve body to ensure the
shaft seats correctly (see Figure 20, p. 27).
8. Press the actuator and valve body until it secures
together
.
r on the actuator in the
t of the valve
Soldering Procedures
1. Remove actuator as stated earlier.
2. Place valves on the pipe. Rotate valve stem so the shaf
slot points at the notch in the side of the body (90° to
flow direction). This protects the plug inside the valve
by removing it from the seat (see Figure 23).
Reference the wall-mounted zone sensor dimensions in
Figure 36, p. 30. Position the sensor on an inside wall three
to five feet above the floor and at least 18 inches from the
nearest outside wall. Installing the sensor at a lower height
may give the advantage of monitoring the temperature
closer to the zone, but it also exposes the sensor to airflow
obstructions. Ensure that air flows freely over the sensor.
Figure 36. Wall-mounted wired and wireless zone
sensor dimensions
Figure 34. Wireless temp sensor with display
(SP, OCC/UNOCC, COMM)
Figure 35. Wireless temp sensor with display
(SP, OCC/UNOCC, COMM)
30 UV-SVN03F-EN
1. 0.31 in
2. TYP R.07 in (R1.9)
3. TYP 0.24 in)
4. 2.9 in
5. 1.08 in
6. 0.12 in
7.3.39 in
8. 4.68 in
9. 2.48 in
10. 0.6 3 in
11. 1.45 in
12. 2.62 in
Sensor
When selecting a sensor location, avoid the following:
•Areas of direct sunlight
•Areas in the direct airstream of air diffusers
•Exterior walls and other walls that have a
differential between the two sides
temperature
Loading...
+ 81 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.