Trane VUV 750 CFM, VUV 1500 CFM User Manual

Installation Owner Maintenance
Vertical Unit Ventilator
Classroom Unit Ventilator Model VUV
Models
VUVE
750 CFM
“A” and later Design Sequence
1500 CFM
UV-SVN03D-ENOctober 2007
Notice
NOTICE:
Warnings and Cautions appear at appropriate sections throughout this manual. Read these carefully.
WARNING – Indicates a potentially hazardous situation
!
which, if not avoided, could result in death or serious injury.
!
CAUTION – Indicates a potentially hazardous situation which, if not avoided, may result in minor or moderate injury. It may also be used to alert against unsafe practices.
CAUTION – Indicates a situation that may result in equipment or property-damage-only accidents.
Important!
Equipment is shipped FOB (Free on Board) at the manufacturer. Therefore, freight claims for damages against the carrier must be initiated by the receiver.
© 2007 American Standard All rights reserved. UV-SVN03D-EN
Contents
Installation/Startup/Commissioning
Pre-installation Checklist
General Information
Dimensions/Weights
Installation Instructions
Electrical Requirements
Pre-Startup Checklist
Maintenance
Warranty Information
Troubleshooting Checklist
Unit Wiring
4
4
5
7
14
24
26
27
30
31
33
UV-SVN03D-EN 3
Pre-installation Checklist
Jobsite Inspection
Always perform the following checks before accepting a unit:
1. Verify that the nameplate data matches the data on the sales order and bill of lading (including electrical data).
2. Verify that the power supply complies with the unit nameplate specifications.
3. Visually inspect the exterior of the unit, for signs of shipping damage. Do not
sign the bill of lading accepting the unit(s) until inspection has been com pleted. Check for damage promptly after the unit(s) are unloaded. Once the bill of lading is signed at the jobsite, the unit(s) are now the property of the SOLD TO party and future freight claims MAY NOT be accepted by the freight company.
Microbial Growth!
Wet interior unit insulation can become an amplification site for microbial growth (mold), which may cause odors and damage to the equipment and building materials. If there is evidence of microbial growth (mold) on the interior insulation, the insulation should be removed and replaced prior to operating the system.
-
Jobsite Storage
This unit is intended for indoor use only. To protect the unit from damage due to the elements, and to prevent possible IAQ contaminant sources from growing.
1. Place the unit(s) on a dry surface or raise above the ground to assure ade­quate air circulation beneath the unit.
2. Cover the unit(s) with a water proof tarp to protect them from the elements.
3. Make provisions for continuous venting of the covered units to prevent moisture from standing on the unit(s) surfaces. Wet interior unit insulation can become an amplification site for microbial growth (mold) which can be a cause of odors and possible indoor air quality problems.
4. Do not stack units.
4 UV-SVN03D-EN
General Information
Unit Nameplate
The unit nameplate is located in the left hand end pocket, behind the con­trol box. It includes the unit model number, serial number, electrical char­acteristics, and other pertinent unit da­ta.
Factory Shipment
Before shipment, each unit is leak test­ed, and run tested for proper control operation.
Access
A three panel front access of the unit ventilator allows for speedy set-up during field commissioning. This de­sign allows for the end pocket of the unit ventilator to be open while the fan (airside) section stays closed.
End Pockets
Access for piping and controls is made through the unit ventilator’s end pock­ets.
Coil Connections
The coil headers and drain connec­tions are made within the unit chassis to allow a tight seal and help prevent air leakage around the coil. The con­nection sizes vary dependent upon type of coil combination specified.
Coil Type Size (in.) Hydronic Cooling (Main) Coil or
Heating/Cooling Changeover Coil Heating (Auxiliary) Coil Steam Heating Coil 1" FNPT Direct Expansion Coil
3/4" Nominal
7/8" I.D.
1/2" Nominal
5/8" I.D.
3/8" O.D. Liquid
7/8" O.D. Suction
Unit Drain Pan
The drain pan is dual-sloped for effec­tive condensate removal. It is made from a non-corrosive material to help eliminate issues associated to leaking or standing water. It may be easily re moved for cleaning. The drain pan connection size for all Trane VUVE models is 7/8" O.D.
Motor
Motors for the VUVE model do not in­clude an external fan bearing on the end of the fan shaft. This helps avoid issues related to fan bearing mainte
-
nance (oiling is not needed), and/or bearing replacement.
Filters
Filter sizing for the unit ventilator are an off-the-shelf design to reduce or help eliminate local stocking of the fil­ters.
Sliding Fan Deck
Convenient access to the fan motor and wheels for maintenance and ser viceability may be made through Trane’s easy-slide fan deck design.
Outside/Return-Air Dampers
The outside-air/return-air damper is a one piece, linkage free design result­ing in a superior air-tight seal.
Field Installed Controls
(Option)
The unit comes equipped with a fan speed switch, damper blade (only), and an optional low temperature de­tection.
End Device Control Package
(Option)
Units containing the End Device con­trol design will incorporate a pre­wired, selected control components to a terminal strip for wiring a field pro vided controller and temperature sen­sor.
Note: for controller operation malfunc­tion of any non-Trane, field installed controls, consult the literature or tech­nical support of the controls manufac­turer.
Tracer™ ZN520 Control Package
(Option)
The ZN520 electronic digital controller is a factory installed, tested and com­missioned LonTalk™ certified design. It may be used in a stand-alone control scheme, or as part of a building auto
­mation system. The controller is pre-
wired to Trane selected control com ponents best suited for room comfort. For more information on the ZN520 unit controller operation and service issues, refer to CNT-SVX04A-EN (ZN520 control manual).
-
-
-
-
UV-SVN03D-EN 5
General Information
OA/RA Actuator (Option)
Table 1: OA/RA actuator specification
Table 2: Face-bypass actuator specification
The OA/RA actuator provides true spring return operation for positive close-off of the OA/RA damper. The spring return system of the actuator closes the outside damper if power is lost to the building. When ordered with factory controls, the actuator is a 3-point floating design. A 2 to 10 VDC actuator is available when other than Trane controls are specified. See Table 1 for OA/RA technical data.
Note: Because the damper actuator is a spring return type an inner spring will close the damper upon loss of power. If the need to service or replace the actuator is required, the spring must be "loaded" for the damper to function properly. The term loaded means that the blade must be held in the return air position upon replace ment of the actuator.
Power Supply
Power Consumption
Transformer Sizing
Overload Protection Control Signal 2 to 10 VDC
Angle of Rotation
Torque 35-inch/lb Direction of Rotation Position
Indication Run Time
-
(nominal) Noise Level Running: 30 dB
24 VAC ± 20% 50/60 HZ 24 VAC ± 10%
Running: 2.5 W Holding: 1 W
5 VA (class 2-power source)
Electronic throughout 0 to 95-degree rotation
3-point floating with Trane controls Maximum 95-degree
Adjustable with mechanical stop
Spring return reversible with CW/ CCW mounting Visual indicator, 0 to 95-degrees
90-second constant (independent of load)
Power Supply
Power Consumption
Transformer Sizing Angle of Rotation Torque 35-inch/lb Direction of Rotation Position Indication Run Time (nominal) Manual Override Noise Level Less than 35 dB Control Signal 3-point floating
24 VAC ± 20% 50/60 HZ 24 VAC ± 10%
2 W
3 VA (class 2-power source)
Maximum 95-degree Adjustable with mechanical stop
Reversible with switch L/R
Clip-on indicator
90-second constant
External push button
Face and Bypass Actuator (Option)
The face and bypass damper actuator
Table 3: Mod. water valve specification.
Table 4: Isolation valve specification.
incorporates a direct couple design. It provides electronic protection against overload. A limit switch is not includ
­ed, nor required as part of the design. When reaching the damper end posi­tion, the actuator automatically stops. The gears can be manually disen
­gaged with a button on the housing. See Table 2 for face and bypass actua tor specifications.
Modulating Water Valves (Option)
The modulating control valve provides optimum control of hot and chilled wa ter flow in various heating and cooling applications. They are designed to provide sinusoidal valve actuator trav
Power Supply
Power Consumption Max. Duty Cycle 15%
-
Nominal Timing 120 sec. Operating Ambient
Temp. Min./Max. Fluid Temp. 1 to 95°C
Operating Pressure
-
Differential Pressure Rating Static - 20 bar (300 psi)
Flow Characteristic Linear
-
24 VAC - 50/60 HZ
4 W
0 to 65°C 32 to 150°F
34 to 203°F Max. - 4 bar (60 psi)
Burst - 100 bar (1500 psi)
Power Supply
Power Consumption
Max. Fluid Temp. 94°C
Min. Fluid Temp. 1°C
Max. Operating Pressure 300 psi Max. Close-off Pressure 1/2" = 30 psi
24 VAC - 50/60 HZ
5 W
200°F
34°F
3/4" = 20 psi 1" = 15 psi
el and operate silently, resisting water hammer. The actuator on the valve is a 24V, 3­point floating type. See Table 3 for modulating water valve specifications.
Isolation Valve (Option)
The isolation valve is a two position 24V, spring return type valve. It pro vides added control in heating and cooling applications when used in
On heating coils, and two-pipe changeover applications, the valve is normally open to help prevent the coil from freezing in-case of power loss.
­For cooling, the valve is normally closed and opens when there is a call for cool-
ing. See Table 4 for isolation valve specifications.
conjunction with the face and bypass damper.
6 UV-SVN03D-EN
Dimensions/Weights/ Clearance
!
WARNING
Improper Unit Lift!
Test lift unit approximately 24 inches to verify proper center of gravity lift point. To avoid dropping of unit, reposition lifting point if unit is not level. Failure to properly lift unit could result in death or serious injury or possible equipment or property-only damage.
Table G1: VUVE general data
Description Unit Size
0750 1000 1250 150 0 Unit Length w/o end covers (inches) Unit Depth - Standard (inches) Unit Depth - with false back (inches) Unit Height - Standard (inches) Shipping Weight (Lbs.) Nominal Filter Size and Quantity (inches) Dynamic Air Filter Nominal Size (inches) & Qty. Drain Connection Size (inches) Fan Type / Quantity Motor Data
Quantity 1 1 2 2
Horsepower (ea) 1/4 1/4 1/10 1/10
Number of Fan Speeds (Standard)
If DX or electric heat used 1 1 1 1
Number of Fan Speed (ZN520)
If exhaust fan or ERSA used 2 2 2 2
If DX or electric heat used 1 1 1 1
Coil Volume (gal.)
Coil Type A 0.178 0.228 0.277 0.327
B 0.311 0.410 0.510 0.610 C 0.311 0.410 0.510 0.610 D 0.444 0.571 0.704 0.931
E 0.444 0.571 0.704 0.931
F 0.610 0.809 1. 014 1. 21 3 G 0.610 0.809 1. 014 1.213 H 0.395 0.593 0.742 0.837
69 81 93 105 16 5/8 16 5/8 16 5/8 16 5/8 21 1/4 21 1/4 21 1/4 21 1/4
30 30 30 30
320 405 450 470
14 x 20 x 1 (2) 14 x 24 x 1 (1) 14 x 20 x 1 (2) 14 x 24 x 1 (2)
7 x 42 x 1 (1) 7 x 54 x 1 (1) 7 x 66 x 1 (1) 7 x 78 x 1 (1)
7/8 ID Hose 7/8 ID Hose 7/8 ID Hose 7/8 ID Hose
FC / 2 FC / 2 FC / 4 FC / 4
3 3 3 3
3 3 3 3
14 x 30 x 1 (1) 14 x 24 x 1 (1) 14 x 30 x 1 (1)
Unit Location and Clearances
Locate the unit in an indoor area. The ambient temperature surrounding the unit must not be less than 45°F. Do not locate the unit in areas subject to freezing.
Attention should be given to service clearance and technician safety. The unit should contain enough space for
UV-SVN03D-EN 7
service personnel to perform mainte­nance or repair. Provide sufficient room to make water, and electrical connection(s). Local and national codes should be followed in providing electrical power connections. A 36" clearance at the unit front is sufficient for maintenance and service of the equipment.
Dimensions
Standard Depth Unit
8 UV-SVN03D-EN
Dimensions
Falseback Unit
UV-SVN03D-EN 9
Dimensions
Dynamic Air Barrier Unit
10 UV-SVN03D-EN
Dimensions
End Covers
UV-SVN03D-EN 11
Dimensions
Wall Boxes
12 UV-SVN03D-EN
16 5/8" DEPTH UNIT
FLUSH
Dimensions
Crossover Piping
7/8" I.D. FIELD
CONN. W/ SHUT
RS
OFF VALVE
1 1/2"
RETURN
3"
SUPPLY
TOP VIEW
21 1/4" DEPTH UNIT
FLUSH
TOP VIEW
Notes: 1-3/8" o.d. and 2-1/8" o.d. crossover piping
3 1/2" 4 1/2"
7/8" I.D. FIELD
CONN. W/ SHUT
OFF VALVE
RS
3 1/2" 4 1/2"
SIDE VIEW
1 1/4"
8 1/4" 10"
SIDE VIEW
19 3/8"
3 5/8" 5 3/8"
24"
RETURN
3"
SUPPLY
24"
19 3/8"
1 Crossover piping is available for all 2 or 4-pipe coils selections. Trane pro-
vides the crossover for the cold water only. The crossover pipe is factory in­sulated with 3/8"-thick insulation.
2 Expansion compensation between the factory piping package and the cross-
over piping is achieved using a flex hose rated at 250 psi working pressure. flex hose is only available with factory mounted piping packages.
3 Expansion compensation for the crossover piping must be handled external
to the unit ventilator.
4 Crossover connections terminate in the same end pocket as the main coil con-
nection. The main coil connection for 2-pipe systems is the heating coil. the main coil connection for 4-pipe systems is the cooling coil.
UV-SVN03D-EN 13
Installation
Wall Box Installation
The following instructions are general recommendations for installing wall intake boxes. Consult the architectural plans for specific requirements.
Additional materials required to com­plete any specific installations (such as duct connections, metal mounting plates, or flanges) are not furnished by Trane.
For best results, all air intake boxes should be removable from outside of the building. Weep holes must be at the bottom to permit free drainage. A positive air and moisture seal should be provided around all edges.
General Instructions Trane wall boxes are illustrated in the dimensional section of this manual. Dimensions are actual, and may be used to define the wall opening.
Vertical louvers in the wall intake box provide extra strength for a high load bearing capacity. The lintel may be omitted on masonry wall installations.
Weep holes are provided in the out­side face of the bottom channel in the wallbox frame. Install all wall boxes to permit free drainage through the weep holes to the outside of the building.
All wallboxes are furnished with dia­mond pattern expanded aluminum bird screen.
Note: V1 and V2 (vertical) wall models are all unflanged. H2, V3 and V6 are flanged.
Installation in Masonry Walls
A typical method of installing the wall box in a masonry wall opening is shown in Figure 1.
Grout the top and bottom of the wall box frame as noted. A sloped water dam located in the space between the unit and wall facilitates moisture drainage. Grouting at the ends of the intake box will complete the seal be
­tween the wall box frame and the ma­sonry opening.
Installation in Curtain Walls In all cases, the wall intake box should be caulked to provide a tight, weather proof seal, Figure 2.
Note: A minimum of 2-1/8” of clear­ance must be maintained between the exterior wall and back of the unit. Fail­ure to provide this gap will not allow the wall box to fit properly.
Interior Wall w/ sheetrock
Outside Wall
Grout
Weep Holes
-
Unit
Rubber Seals
Water dam sloped toward exterior
Figure 1: Masonry wall installation
Interior Wall w/ sheetrock
Outside Wall
Caulking
Rubber Seals
Flanged wallbox
Weep Holes
Water dam sloped toward exterior
Figure 2: Flanged wall box installation
in 2" curtain wall
Floor
Unit
14 UV-SVN03D-EN
Installation
General Installation Checks
The checklist below is a summary of the steps required to successfully in­stall a unit. This checklist is intended to acquaint the installing personnel with procedures required in the installation process. It does not replace the de tailed instructions called out in the ap­plicable sections of this manual.
1 Carefully remove the stretch wrap
and top cardboard cover. Check the unit for shipping damage and material shortage; file a freight claim and notify appropriate sales representation. If end panels have
been ordered, the panel will al ready be mounted to the unit.
Note: The unit ventilator is pack­aged in clear stretch wrap to allow for immediate visual inspection. A protective cardboard cover helps prevent scratching and other cos metic blemishes during transport.
2 Remove remaining cardboard
blocking.
-
-
Location Considerations
Selecting the appropriate location for installing a unit is very important. The following factors should be consid ered:
1 Floor design must have sufficient
structure to withstand the weight of the unit while allowing for openings in the floor for a return air duct, electrical and piping sup ply lines fed through the floor. See page 7 for unit weights.
2 Wall space design should allow the
unit to be mounted to the wall se curely. The wall surface behind the unit should be smooth and lev­el. Wall and floor moldings should be removed prior to installation. A wall slightly out of level may cause problems with unconditioned air leaking into the room. Remove
-
any object projecting more then 1/8” (.3175cm) from the wall sur­face. Note: Additional gasket or
furr strips may be installed to ac­commodate for an uneven wall.
5 Internal access to the unit is pro-
vided by the removable front pan­el. Sufficient space should be
-
-
-
allowed to lift the panel for mainte nance purposes.
6 Ensure the floor surface is level.
Note: The unit leveling legs can be adjusted to accommodate slight out-of-level installation surfaces.
Unit Mounting
Note: All wall intake boxes should be installed prior to mounting the unit ventilator. Refer to Page 14 for wall
box installation instructions.
The 1/2” mounting or anchoring holes are located on the back of the unit on each end. See Figures 3.
Note: All mounting fasteners are to be provided by the installer.
-
3 Remove the unit’s left front panel
to verify nameplate/sales order number is correct. It is located be hind the control box.
4 Remove shipping bracket from the
lower rear corners of the unit to separate the unit from the skid. Ac cess to the screws holding the bracket to the skid is obtained in­side the unit.
5 Rotate the fan wheels manually.
The wheels should move freely and be in proper alignment. Visu ally inspect the fan area for ob­structions or shipping damage.
6 Remove all applicable knockouts
for coil piping and electrical con nections.
UV-SVN03D-EN 15
3 There are two removable knock-
outs in the rear of the unit, on ei
-
-
-
-
ther end, for piping and electrical supply lines. A pipe chase is locat ed in the upper back portion of the unit for crossover piping. The out­side air opening is located in the lower back of the unit and the path to the wallbox on the outside wall should be unobstructed.
4 The physical layout of the room
should accommodate any accesso­ries ordered with the unit. Condi­tioned air is distributed through the grille on top of the unit and re­turned through the return air grille on the bottom of the unit. Avoid placing any objects that may ob struct either grille or interfere with airflow.
-
-
-
A
Figure 3: Mounting hole location
Installation
075
100
125
150
E
C
C
F
B
B
D
ABCDE F
Standard Unit (no Falseback) 1.31 13.50 2.75 66.39 10.38 45.64 Standard falseback 1.00 2.13 26.00 67.00 10.00 47.00 29" stepdown falseback 1.00 2.13 24.44 67.00 10.00 47.00 28" stepdown falseback 1.00 2.13 23.44 67.00 10.00 47.00 27" stepdown falseback 1.00 2.13 22.44 67.00 10.00 47.00 26" stepdown falseback 1.00 2.13 21.44 67.00 10.00 47.00 25" stepdown falseback 1.00 2.13 20.44 67.00 10.00 47.00 Standard Unit (no Falseback) 1.31 13.50 2.75 78.39 10.38 57.64 Standard falseback 1.00 2.13 26.00 79.00 10.00 59.00 29" stepdown falseback 1.00 2.13 24.44 79.00 10.00 59.00 28" stepdown falseback 1.00 2.13 23.44 79.00 10.00 59.00 27" stepdown falseback 1.00 2.13 22.44 79.00 10.00 59.00 26" stepdown falseback 1.00 2.13 21.44 79.00 10.00 59.00 25" stepdown falseback 1.00 2.13 20.44 79.00 10.00 59.00 Standard Unit (no Falseback) 1.31 13.50 2.75 90.39 10.38 69.64 Standard falseback 1.00 2.13 26.00 91.00 10.00 71.0 0 29" stepdown falseback 1.00 2.13 24.44 91.00 10.00 71.00 28" stepdown falseback 1.00 2.13 23.44 91.00 10.00 71.00 27" stepdown falseback 1.00 2.13 22.44 91.00 10.00 71.00 26" stepdown falseback 1.00 2.13 21.44 91.00 10.00 71.00 25" stepdown falseback 1.00 2.13 20.44 91.00 10.00 71.00 Standard Unit (no Falseback) 1.31 13.50 2.75 102.39 10.38 81.64 Standard falseback 1.00 2.13 26.00 103.00 10.00 83.00 29" stepdown falseback 1.00 2.13 24.44 103.00 10.00 83.00 28" stepdown falseback 1.00 2.13 23.44 103.00 10.00 83.00 27" stepdown falseback 1.00 2.13 22.44 103.00 10.00 83.00 26" stepdown falseback 1.00 2.13 21.44 103.00 10.00 83.00 25" stepdown falseback 1.00 2.13 20.44 103.00 10.00 83.00
16 UV-SVN03D-EN
Installation
Unit Mounting
Note: All wall intake boxes should be installed prior to mounting the unit ventilator. Refer to Page 14 for wall
box installation instructions.
The 1/2” mounting or anchoring holes are located on the back of the unit on each end. See Figure 3.
1 Note: All mounting fasteners are to
be provided by the installer. Check the gasket on the rear of the unit and around the fresh air open­ing. Gaps around the openings can lead to outside air leaks into the room.
2 Remove all electrical and piping
knockouts where required for in­stallation.
!
WARNING
Improper Unit Lift!
Test lift unit approximately 24 inches to verify proper center of gravity lift point. To avoid drop­ping of unit, reposition lifting point if unit is not level. Failure to properly lift unit could result in death or serious injury or possible equipment or property-only dam age.
3 Set the unit into selected location
and adjust leveling legs if neces sary to ensure level fit.
Note: Care should be taken when handling the unit to ensure that the front return air grille does not bend.
4 Push the unit tightly against the
wall to compress the seal on the back edge of the unit and intake opening. Anchor the unit by using the 1/2” mounting holes in both end pockets.
Units containing a falseback; The falseback unit ventilator contains mounting holes located on the falseback metal. Use these holes
-
-
rather than the holes located in the unit’s end pockets.
Note: Ensure the unit is level. Coils and drain pans inside the unit are pitched properly for draining before shipment.
5 Ensure the unit rests tightly
Subbase (option) A subbase may be used to increase the unit height and aid in leveling the unit. The subbase is shipped separately for field installation. Slots and leveling screws are provided on the subbase.
1 Remove the leveling legs provided
2"- 6"
Figure 4: Subbase with leveling legs
2 Set the unit on the subbase and
against the wall. Check for proper seal and that air does not leak un derneath the unit.
with the unit. See Figure 4.
Unit Base
Weld Nuts
Subbase
For leveling legs
fasten with four, 3/8” x 16’ x 1” hex head cap screws and 3/8" lock washers.
Note: Hex screws and lock wash­ers are provided by the factory. They are located in a baggy and are used to attach the base to the unit ventilator. Pre-drilled slots in the subbase flange will line up with the weld nuts in the bottom of the unit.
3 The bottom of the subbase has
weld nuts in four slots. Place the leveling legs in those slots and lev el the unit.
End Panels When ordered as an option, end cov­ers ship already attached to the verti­cal unit ventilator. The following section is for installing end covers pur­chased as an add-on.
It is recommended end panels be in­stalled on the unit ventilator after all piping, wiring and accessory installa tion is completed. To install the end
-
panel:
1 Insert the four factory provided
metal studs into the four pre­mounted nuts on the inside of the panel.
2 Align each stud with the four pre-
drilled holes on the side of the unit.
3 Secure the panel to the unit by fas-
tening with the four factory pro­vided nuts.
4 Do not overtighten screws.
CAUTION
Equipment Damage!
Do not run units for any length of time without all panels and filters properly installed. Failure to do so may result in equipment failure.
-
-
UV-SVN03D-EN 17
Installation
Piping Installation
Before installation of piping package, the shipping bracket holding the pip­ing in place, must be removed.
Proper installation of piping is neces­sary to provide efficient coil operation and to prevent damage during opera tion. Follow standard piping practices and include all accessories as neces
-
sary.
Piping connection knockouts are shown pages 8 to 10. Field connection types and sizes for unit coils are listed in Table 5. These sizes are provided for field piping connection.
A 7/8’’ OD condensate drain connec­tion is provided on the chilled water supply end of the unit.
1 Attach a flexible condensate drain
hose over the drain pan connec­tion and secure with a hose clamp.
The drain pan on the vertical is vacu­um molded with a drain connection and P-Trap on the cooling coil, connec­tion side.
Note: Condensate removal to the main system should be made through the bottom of the unit ventilator. If other location for condensate removal is de sired, a specific field cut-out for the connection should be made in the back of the unit ventilator. To help avoid cold air infiltration, the field cut-out should only be large enough to allow for the condensate hose to exit the unit.
To field reverse the slope of a vertical unit drain pan.
2 Slide out fan deck (disconnecting
the condensate line and fan plug will release fan deck for sliding).
3 Remove pipe clamp that hold the
p-trap to the drain pan.
4 Remove clips that hold the drain
pan in-place.
5 Lift and rotate the drain pan.
6 Reconnect p-trap to the drain pan
and replace clips to secure the pan to the fan deck.
7 After the condensate drain piping
has been completed, check water flow to ensure the system proper ly carries and away all condensate accumulation.
Note: A P-trap is factory supplied in ev-
-
ery vertical unit ventilator.
Trane Piping Packages (Option) Trane Standard Piping Package in­cludes a 2-way or 3-way valve with by­pass balance valve, ball valves, Pete’s plugs and unions. A strainer and cir­cuit balancing valve are optional.
1 All union connections should be
tightened in the field. Units are shipped with union connections hand tightened only in the factory.
Note: All connections made in the field should be sweat connections.
Piping packages are not shipped insu­lated. Any insulation should be provid­ed in the field by the installing contractor.
The auxiliary drain pan (optional) is the main condensate connection to the unit when specified. The chilled water or DX coil drain pan will empty into the auxiliary drain pan if a factory
-
installed, auxiliary pan is ordered. All field piping condensate connections should be made at the auxiliary drain pan.
Installation Crossover Piping
Crossover piping is available for all hy-
-
dronic coils. It is either 1 3/8’’ \[34.9\] or 2 1/8’’ \[54\] in diameter (O.D.) as spec ified by the customer. Crossover pip­ing can be found in either the left or right hand end pocket. See crossover submittal drawings page 13 for dimen sional data.
On 4-pipe coils, crossover piping con­nects to the main cooling coil.
Factory insulation is provided on all crossover piping.
When a Trane piping package is or­dered, it is installed with the connec­tions made to the supply and return of both the coil and the crossover piping. However, supply and return connec­tions must be made in the field when a piping package is furnished by the in­staller.
The crossover piping is located at the back of the unit along the wall and the ends of the piping are flush with the end of the unit.
Expansion compensation between the piping package and the crossover pip­ing is achieved using flex hoses rated at 250 psi working pressure. Expan­sion compensation for the crossover piping must be handled external to the unit ventilator.
Table 7: Coil data for field piping
Coil Type Connection Locat ion Field Connection Size 4-Pipe Chilled Water/Hot Water Left or Right (opposite ends) 7/8" OD/5/8" OD 2-Pipe Changeover Coil Left or Right 7/8" OD Hot Water Only Left or Right 7/8" OD Steam Left or Right 1" MPT Chilled Water/Electric Heat Left Cooling 7/8" OD Chilled Water/Steam Left or Right 7/8" OD/1" MPT DX Left 7/8" Suction, 3/8" Discharge DX/Hot Water Left Cooling/Right Heating 7/8" Suction, 3/8" Discharge/5/8" OD DX/Steam Left Cooling/Right Heating 7/8" Suction, 3/8" Discharge/1" MPT DX/Electric Heat Left Cooling/Right Heating 7/8" Suction, 3/8" Discharge/NA Electric Heat Right NA
Notes:
1. Supply and return connections are located on the same end of each coil.
2. All Trane piping packages have union connections; all units with piping packages by others have sweat connections.
3. Coil connections are sweat except steam coils, which are threaded.
-
-
18 UV-SVN03D-EN
Installation
Split System Units
The following refrigerant piping and interconnecting wiring instructions apply to unit ventilators with direct ex pansion type cooling coils used in con­junction with air-cooled condensing units. Reference must also be made to the condensing unit installation and wiring manuals which are shipped with the condensing unit.
Note: The ETL listing mark applied to a unit ventilator does not apply to any associated refrigerant condensing unit.
Refrigerant Piping
Unit ventilators with direct expansion cooling contain a nitrogen holding charge in the evaporator coils. Con
­nections are ‘‘pinched-off’’ at the fac­tory.
To connect the condensing unit lines, cut off the stubouts and swage. The condensing unit lines can then be brought into the swage and brazed. Trane recommends the use of nitro
­gen purge when brazing refrigerant lines to prevent formation of oxides in the lines.
Install the refrigerant suction and liq­uid lines as described in the condens­ing unit installation instructions. The TXV is factory installed on the Unit Ventilator. Piping should be run straight out through the back of the unit. Access piping knockouts are lo
­cated in the rear panels of the unit, as shown in dimensional section of this manual.
Recommended refrigerant line con­nections for various unit combinations are given in Table 7. Typical Superheat Charging Charts are shown in the Trane Service Facts found in the con densing unit section manual. Refriger­ant charge weights can also be determined with your local Trane sales engineer using a valid Trane Se lection Program.
Steam Piping When air, water or another product is heated, the temperature or heat trans-
-
fer rate can be regulated by a modulat­ing steam pressure control valve. Since pressure and temperature do not vary at the same rate as load, the steam trap capacity, which is deter mined by the pressure differential be­tween the trap inlet and outlet, may be adequate at full load, but not some lesser load.
There are detailed methods for deter­mining condensate load under various operating conditions. However, in most cases this is not necessary if the coils are piped as shown in Figure 5. Follow the procedure documented in the ASHRAE Systems Handbook, Steam Systems.
Temp. Regulating Valve
Coil
To Condensate
return
Vacuum Equalizer
F&T Trap
See text for sizing
Gravity flow to
vented receiver
Figure 5: Steam piping
-
-
-
H= 12" minimum
UV-SVN03D-EN 19
Installation
Modulating Water Valves (Option)
The actuator on the valve is a 24V, 3­point floating valve. The actuator can be easily removed from the valve body by pressing in on the locking tab and rotating the actuator 45° counter­clockwise (See Figure 6a). The 2-way valves are bi-directional flow. The 3­way valves can be mixing or diverting (See Figure 6b).
Note: The actuator must be removed if soldering is being conducted near the valve. High heat may cause damage to the actuator’s plastic body/mecha
-
nisms.
Figure 6a: Remove modulating valve
actuator by pressing in tab (inset) and turning actuator 45° counterclockwise.
Figure 6b: Steam piping
Closed
A
A
B
Open
B
2-way valve
AB<->B
B
AB
AB<->A
A
3-way valve
AB
On applications without the optional, factory installed piping packages, it is important to remove the cartridge as sembly from the valve body with the provided tool (Figure 7).
Figure 7: Cartridge removal tool
Use the following steps to complete cartridge assembly removal:
1 Remove valve actuator.
2 Remove the cartridge assembly
from the valve body with the en­closed tool.
3 Solder the valve in accordance with
normal soldering practices.
4 Re-install the cartridge after solder-
ing by tightening until it bottoms out. The top surface of the car­tridge will be flush with the top edge of the body casting.
Note: Do not overtighten. Maxi­mum torque is 40 in-lb.
5 Replace valve actuator and wire in
accordance with instructions.
Plumbing the Valve
The valve may be plumbed in any an­gle but preferably not with the actua­tor below horizontal level of the body. Make sure there is enough room around the actuator for servicing or re placement.
For use in diverting applications, the valve is installed with the flow water entering through the bottom AB port and diverting through end ports A or B. In mixing applications the valve is
-
installed with inlet to A or B and outlet through AB.
Mount directly to the tube or pipe. Do not grip the actuator while making or tightening plumbing connections. Ei ther hold valve body by hand or attach an adjustable spanner (38mm/1-1/2”) across the hexagonal or flat faces on the valve body. See Figure 8.
-
-
Figure 8: Proper plumbing technique for modulating valves
20 UV-SVN03D-EN
Installation
Manually Opening Valve
The manual opener can be manipulat­ed only when in the up position. The A port can be manually opened by firmly pushing the white manual lever down to the midway position and pushing the lever in. In this position, both A and B ports are open. This “manual open” position may be used for filling, venting and draining the system or opening the valve during power fail ure.
The valve can be closed by depressing the white lever lightly and then pulling the lever outward. The valve and actu­ator will return to the automatic posi­tion when power is restored.
Note: If the valve is powered open, it cannot be manually closed, unless the actuator is removed.
Wiring
A controller and a separate transform­er is required to operate each valve. See Figures 9 and 10. Port A “open” and “closed” denote valve open and closed positions.
-
the normally open (NO) or normally closed (NC) contacts, driving the valve to an intermediate position until a fur ther change at the controller.
The valve is set between the limits of the controller to satisfy various load requirements. In the event of power failure, the valve will stay in the posi tion it was in before loss of power. When power is restored, the valve will again respond to controller demand.
Isolation Valves Installation
The valve can be mounted in any posi­tion on a vertical line. If the valve is mounted horizontally, the actuator must be even with or above the center line. Make sure there is enough room to remove actuator cover for servicing. Mount the valve on the tube or pipe.
Note: Ensure the flow through the valve is in the direction indicated by the arrow stamped on the valve body.
Figure 12: Removing valve actuator
-
-
To install the actuator to the valve body:
3 Align the slot on the shaft of the
valve with the valve body notch on side of body. See Figure 13.
Figure 9: Wiring for modulating valve
actuator
Figure 11: Proper mounting for
isolation valves.
Servicing/Removal of Valves
The actuator can be removed from the valve body. Removing the actuator is recommended if soldering is being conducted near the valve. To remove
Figure 10: Wiring for modulating valve
actuator
The typical floating controller is an SPDT controller with a center-off posi tion. On a change in temperature from the set point, the controller will close
UV-SVN03D-EN 21
the actuator:
1 Place the manual operating lever
to the Open position, Figure 12
2 Depress the locking button and lift
­actuator until it separates from the
valve body.
Figure 13: Installing isolation valve
4 Install body valve into pipe.
5 Wiring connections may be made
either before or after actuator in­stalled on body.
6 Place the manual operating lever
on the actuator in the OPEN posi­tion.
7 Align actuator coupling to slot on
the shaft of the valve body and fit the head onto the valve body to ensure the shaft seats correctly, Figure 11.
8 Press the actuator and valve body
until it secures together.
Installation
Soldering procedures are as follows:
1 Remove actuator as stated earlier.
2 Place valves on the pipe. Rotate
valve stem so the shaft slot points at the notch in the side of the body (90° to flow direction). This pro tects the plug inside the valve by removing it from the seat, Figure
14.
3 Sweat the joints, keeping outer
surface free from solder.
Note: Do not use silver solder due to high temperature require­ments.
Figure 14: Preparation for soldering
Heating Coils with Direct Expansion Cooling
Heating options for direct expansion cooling in the unit ventilator are hot water, steam or electric heat.
These coils facilitate direct expansion cooling with standard capacities. The supply and return connections are lo cated in the right hand end pocket. Hot water field connections are made with a 5/8’’ \[15.9\] OD male sweated joint, while steam coils have a 1’’ \[25.4\] male pipe thread (MPT) connection. See Table 7 for coil connection sizes.
Electric heat coils provide a third way to supply heating to the direct expan sion cooling. The coil utilizes three to six preheat elements which are factory wired.
-
-
-
Wiring
All classroom unit ventilators have 115V motor power. Motor data can be found in Tables G1.
Control Power
!
WARNING
Hazardous Voltage!
Disconnect all electric power, in­cluding remote disconnects be­fore servicing. Follow proper lockout/tagout procedures to en­sure the power can not be inad­vertently energized. Failure to disconnect power before servic­ing could result in death or seri­ous injury.
CAUTION
Equipment Damage!
-Wiring diagrams provided in this manual are for reference only. Ac­tual wiring for particular options/ units may vary. Refer to the dia gram provided on the equipment for specific information. Failure to do so may result in equipment fail ure.
-When installing field provided controls, do not alter or remove any built-in unit safeties. Tamper ing with unit safeties may cause unit overheating and possible fire hazard.
-Do not remove or alter the wiring of the Time Delay Relay (DL). Do ing so may result in premature motor failures.
Unit ventilator controls and control wiring can be factory mounted or field installed.
Wiring diagrams illustrate the stan­dard unit motors with one and two speed control. Terminal wiring is pro­vided by Trane and the actual compo­nents used for a particular installation may differ. Control and line diagrams for the exact control system used are provided with each unit.
-
Supply Power
CAUTION
Use Copper Conductors Only!
Unit terminals are not designed to accept other types of conductors. Failure to use copper conductors may result in equipment damage.
Power supply wiring is to be connect­ed to terminals 1 and 2 at the junction box in the left end pocket, below the discharge air grille.
Electric Heat (option)
Supply Power
Supply power wiring is to be connect­ed to the following line terminals in the right hand end pocket:
208V or 240V, 3-phase, 3 wire system: L1, L2 and L3.
480V, 3-phase, 4 wire system: L1, L2, L3 and N (neutral)
See Page 34 for a typical unit line and interconnecting wiring diagram for
-
Electric Heat Coils.
CAUTION
Equipment Damage!
-
480 V/3-Wire is NOT compatible with Trane Classroom Unit Venti­lator equipment. There must be a 4-wire system with a separate ground. Failure to provide a 4-wire
-
system may result in equipment damage.
Note: The supply neutral wire must be connected to the neutral terminal block.
Operational controls and an electric heating safety device are factory mounted. The safety device is a high temp cut-out which de-energizes elec tric heating elements through the K1 safety contactor.
-
22 UV-SVN03D-EN
!
WARNING
Hazardous Voltage!
Disconnect all electric power, in­cluding remote disconnects be­fore servicing. Follow proper lockout/tagout procedures to en­sure the power can not be inad­vertently energized. Failure to disconnect power before servic­ing could result in death or seri­ous injury.
Installation
IMPORTANT:
INSTALLER MUST MOUNT THERMAL EXPANSION VALVE BULB AND FROST PROTECTION BULB (if suppled) TO SUCTION LINE AFTER CONNECTION OF FIELD REFRIGERANT PIPING
X39001939010A
Wiring (continued)
DX System
A typical unit ventilator with DX coil in­cludes an outside air thermostat, a frost prevention thermostat and a 24V transformer for condensing unit con trol.
Wire sizing is the same as given for the thermostat wiring in the condensing unit installation instructions, or may be obtained from the nameplate. The condensing unit must be controlled by the same room thermostat that also controls the unit ventilator.
Split System Start-Up After all piping and wiring has been completed, follow the instructions provided with the condensing unit for control testing and system start-up. If sweat type field-piped systems are be ing used, then pressure testing, evacu­ation and refrigerant charging will be required.
Two bulbs will also be shipped with a split system unit:
-
9:00
8:00
MOUNT BULB IN HORIZONTAL PLANE
Figure 15: Frost stat/TXV valve
installation tag
Note: Depending on the controls pack­age ordered with the unit, not all in­stallations will require mounting the frost stat bulb.
-
RECOMMENDED BULB PLACEMENT
X
12
93:00
3
6
4:00
X
Frost stat bulb
TXV valve (used with R410a).
Both components are to be field in­stalled using the installation kit shipped with the unit. For complete in stallation instructions and locations, refer to the tag attached to the installa tion kit within the unit. See Figure 15 for an example of the installation tag.
UV-SVN03D-EN 23
-
-
Electrical Requirements
Table E1: VUV 075-150, Electrical Performance
Unit Motor Motor No. of Heating Heat Heat Total Circuit Protective
Model No. Voltage FLA (ea) HP Fan Motor Elements kW Amps FLA Ampacity Device
VUVE075 115/60/1 3.0 1/4 1 0 0.00 0.00 3.00 3.8 15
208/60/1 1.6 1/4 1 0 0.00 0.00 1.60 2.0 15 208/60/1 1.6 1/4 1 3 4.39 21.10 22.70 28.4 30 208/60/1 1.6 1/4 1 4 5.86 28.20 29.80 37.3 40 208/60/1 1.6 1/4 1 6 8.79 42.30 43.90 54.9 60 208/60/3 1.6 1/4 1 0 0.00 0.00 1.60 2.0 15 208/60/3 1.6 1/4 1 3 4.39 12.20 13.80 17.3 20 208/60/3 1.6 1/4 1 4 5.86 18.69 20.29 25.4 30 208/60/3 1.6 1/4 1 6 8.79 24.40 26.00 32.5 35 230/60/1 1.6 1/4 1 0 0.00 0.00 1.60 2.0 15 230/60/1 1.6 1/4 1 3 5.85 24.40 26.00 32.5 35 230/60/1 1.6 1/4 1 4 7.80 32.50 34.10 42.6 45 230/60/1 1.6 1/4 1 6 11.70 48.80 50.40 63.0 70 230/60/3 1.6 1/4 1 0 0.00 0.00 1.60 2.0 15 230/60/3 1.6 1/4 1 3 5.85 14.10 15.70 19.6 20 230/60/3 1.6 1/4 1 4 7.80 21.49 23.09 28.9 30 230/60/3 1.6 1/4 1 6 11.70 28.10 29.70 37.1 40 265/60/1 1.0 1/4 1 0 0.00 0.00 1.00 1.3 15 265/60/1 1.0 1/4 1 3 5.82 21.00 22.00 27.5 30 265/60/1 1.0 1/4 1 4 7.80 28.20 29.20 36.5 40 265/60/1 1.0 1/4 1 6 11.70 42.20 43.20 54.0 60 460/60/3 1.0 1/4 1 0 0.00 0.00 1.00 1.3 15 460/60/3 1.0 1/4 1 3 5.85 7.00 8.00 10.0 15 460/60/3 1.0 1/4 1 4 7.80 14.10 15.10 18.9 20 460/60/3 1.0 1/4 1 6 11.70 14.10 15.10 18.9 20
VUVE100 115/60/1 3.0 1/4 1 0 0.00 0.00 3.00 3.8 15
208/60/1 1.6 1/4 1 0 0.00 0.00 1.60 2.0 15 208/60/1 1.6 1/4 1 3 5.86 28.20 29.80 37.3 40 208/60/1 1.6 1/4 1 4 7.81 37.50 39.10 48.9 50 208/60/1 1.6 1/4 1 6 11.72 56.30 57.90 72.4 80 208/60/3 1.6 1/4 1 0 0.00 0.00 1.60 2.0 15 208/60/3 1.6 1/4 1 3 5.86 16.30 17.90 22.4 25 208/60/3 1.6 1/4 1 4 7.81 24.79 26.39 33.0 35 208/60/3 1.6 1/4 1 6 11.72 32.50 34.10 42.6 45 230/60/1 1.6 1/4 1 0 0.00 0.00 1.60 2.0 15 230/60/1 1.6 1/4 1 3 7.80 32.50 34.10 42.6 45 230/60/1 1.6 1/4 1 4 10.40 43.30 44.90 56.1 60 230/60/1 1.6 1/4 1 6 15.60 65.00 66.60 83.3 90 230/60/3 1.6 1/4 1 0 0.00 0.00 1.60 2.0 15 230/60/3 1.6 1/4 1 3 7.80 18.80 20.40 25.5 30 230/60/3 1.6 1/4 1 4 10.40 28.66 30.26 37.8 40 230/60/3 1.6 1/4 1 6 15.60 37.50 39.10 48.9 50 265/60/1 1.0 1/4 1 0 0.00 0.00 1.00 1.3 15 265/60/1 1.0 1/4 1 3 7.80 28.20 29.20 36.5 40 265/60/1 1.0 1/4 1 4 10.40 37.50 38.50 48.1 50 265/60/1 1.0 1/4 1 6 15.60 56.30 57.30 71.6 80 460/60/3 1.0 1/4 1 0 0.00 0.00 1.00 1.3 15 460/60/3 1.0 1/4 1 3 7.80 9.40 10.40 13.0 15 460/60/3 1.0 1/4 1 4 10.40 18.80 19.80 24.80 25 460/60/3 1.0 1/4 1 6 15.60 18.80 19.80 24.8 25
Blower Blower Number of Electric Electric Minimum Overcurrent
24 UV-SVN03D-EN
Electrical Requirements
Table E1: VUV 075-150, Electrical Performance (continued)
Unit Motor Motor No. of Heating Heat Heat Total Circuit Protective
Model No. Voltage FLA (ea) HP Fan Motor Elements kW Amps FLA Ampacity Device
VUVE125 115/60/1 2.0 1/10 2 0 0.00 0.00 4.00 4.5 15
208/60/1 1.0 1/10 2 0 0.00 0.00 2.00 2.3 15 208/60/1 1.0 1/10 2 3 7.32 35.20 37.20 46.3 50 208/60/1 1.0 1/10 2 4 9.76 46.90 48.90 60.9 70 208/60/1 1.0 1/10 2 6 14.65 70.40 72.40 90.3 100 208/60/3 1.0 1/10 2 0 0.00 0.00 2.00 2.3 15 208/60/3 1.0 1/10 2 3 7.32 20.30 22.30 27.6 30 208/60/3 1.0 1/10 2 4 9.76 31.03 33.03 41.0 45 208/60/3 1.0 1/10 2 6 14.65 40.70 42.70 53.1 60 230/60/1 1.0 1/10 2 0 0.00 0.00 2.00 2.3 15 230/60/1 1.0 1/10 2 3 9.75 40.60 42.60 53.0 60 230/60/1 1.0 1/10 2 4 13.00 54.20 56.20 70.0 80 230/60/1 1.0 1/10 2 6 19.50 81.30 83.30 103.9 110 230/60/3 1.0 1/10 2 0 0.00 0.00 2.00 2.3 15 230/60/3 1.0 1/10 2 3 9.75 23.50 25.50 31.9 35 230/60/3 1.0 1/10 2 4 13.00 35.82 37.82 47.0 50 230/60/3 1.0 1/10 2 6 19.50 46.90 48.90 60.9 70 265/60/1 0.9 1/10 2 0 0.00 0.00 1.80 2.0 15 265/60/1 0.9 1/10 2 3 9.75 35.20 37.00 46.0 50 265/60/1 0.9 1/10 2 4 13.00 46.90 48.70 60.7 70 265/60/1 0.9 1/10 2 6 19.50 70.40 72.20 90.0 100 460/60/3 0.9 1/10 2 0 0.00 0.00 1.80 2.0 15 460/60/3 0.9 1/10 2 3 9.75 11.70 13.50 16.6 20 460/60/3 0.9 1/10 2 4 13.00 23.50 25.30 31.40 35 460/60/3 0.9 1/10 2 6 19.50 23.50 25.30 31.4 35
VUVE150 115/60/1 2.0 1/10 2 0 0.00 0.00 4.00 4.5 15
208/60/1 1.0 1/10 2 0 0.00 0.00 2.00 2.3 15 208/60/1 1.0 1/10 2 3 8.56 41.20 43.20 53.8 60 208/60/1 1.0 1/10 2 4 11.42 54.90 56.90 70.9 80 208/60/1 1.0 1/10 2 6 17.13 82.40 84.40 105.3 110 208/60/3 1.0 1/10 2 0 0.00 0.00 2.00 2.3 15 208/60/3 1.0 1/10 2 3 8.56 23.80 25.80 32.0 35 208/60/3 1.0 1/10 2 4 11.42 36.36 38.36 47.7 50 208/60/3 1.0 1/10 2 6 17.13 47.50 49.50 61.6 70 230/60/1 1.0 1/10 2 0 0.00 0.00 2.00 2.3 15 230/60/1 1.0 1/10 2 3 11.40 47.50 49.50 61.9 70 230/60/1 1.0 1/10 2 4 15.20 63.30 65.30 81.4 90 230/60/1 1.0 1/10 2 6 22.80 95.00 97.00 121.0 125 230/60/3 1.0 1/10 2 0 0.00 0.00 2.00 2.3 15 230/60/3 1.0 1/10 2 3 11.40 27.40 29.40 36.5 40 230/60/3 1.0 1/10 2 4 15.20 41.87 43.87 54.6 60 230/60/3 1.0 1/10 2 6 22.80 54.80 56.80 70.8 80 265/60/1 0.9 1/10 2 0 0.00 0.00 1.80 2.0 15 265/60/1 0.9 1/10 2 3 11.40 41.20 43.00 53.5 60 265/60/1 0.9 1/10 2 4 15.20 54.90 56.70 70.7 80 265/60/1 0.9 1/10 2 6 22.80 82.30 84.10 104.9 110 460/60/3 0.9 1/10 2 0 0.00 0.00 1.80 2.0 15 460/60/3 0.9 1/10 2 3 11.40 13.70 15.50 19.1 20 460/60/3 0.9 1/10 2 4 15.20 27.40 29.20 36.30 40 460/60/3 0.9 1/10 2 6 22.80 27.40 29.20 36.3 40
Blower Blower Number of Electric Electric Minimum Overcurrent
UV-SVN03D-EN 25
Pre-Start Checklist
Pre-Start-up Checklist
Before energizing the unit, the following system devices must be checked:
____ Is the high voltage power supply correct and in accordance with the nameplate ratings?
____ Is the field wiring and circuit protection the correct size?
____ Is the low voltage control circuit wiring correct per the unit wiring diagram?
____ Is the piping system clean/complete and correct?
____ Is unit serviceable? (See clearance specifications on page 7).
____ Are all the unit access panels secure and in place?
____ Is the water flow established and circulating through all the units?
____ Is the condensate line properly sized, run, trapped and pitched?
____ Does the indoor blower turn freely without rubbing?
____ Has all work been done in accordance with applicable local and national codes?
____ Has heat transfer fluid been added in the proper mix to prevent freezing if required?
26 UV-SVN03D-EN
Maintenance
!
WARNING
Hazardous Service Procedures!
The maintenance and trouble­shooting procedures recommend­ed in this section of the manual could result in exposure to electri cal, mechanical or other potential safety hazards. Always refer to the safety warnings provided throughout this manual concern ing these procedures. When possi­ble, disconnect all electrical power including remote discon­nects before servicing. Follow proper lockout/tagout procedures to ensure the power can not be in advertently energized. When nec­essary to work with live electrical components, have a qualified li­censed electrician or other indi­vidual who has been trained in handling live electrical compo­nents perform these tasks. Failure to follow all of the recommended safety warnings provided, could result in death or serious injury.
-
Periodic Maintenance
The following maintenance sugges­tions apply to all types of unit ventila­tors, chilled water, hot water, split systems and electric. Additional infor­mation for controls not supplied by The Trane Company should be ob tained from the controls manufactur-
-
er.
Split system unit ventilators include a condensing unit and the instructions provided with the condensing unit will apply to the entire refrigerant system.
Filters The air filters supplied with Trane UV’s are specially designed for high lint content. Depending upon room condi-
-
tions, these filters will normally need to be replaced every 4 to 8 weeks. To assure proper unit operation, inspect the filters monthly and clean or re place as required.
Overloaded filters will reduce unit air handling capacity, which may result in insufficient heating during the morn ing warm-up period and loss of natural cooling capacity during mild weather.
Cleaning of the Drain Pan The unit ventilators drain pan is re­movable for periodic cleaning or easy access for maintenance/drainage is sues. Use Figure 16, and the steps be­low for removing the drain pan.
­1 Turn off power to the unit and re-
move the front panel.
2 Disconnect the condensate drain
line from the P-trap.
3 Disconnect fan plug.
4 Remove (4) pan clips located at
each end of the pan’s front.
5 Slide out fan board.
6 Remove drain pan for cleaning.
­7 When reinstalling, reverse se-
quence.
-
-
Service Access
To access the unit for water balancing, motor access or other start-up and maintenance functions, use one of the following methods:
1 Remove the end pocket front
panel.
2 Remove the return air grille by re-
leasing the mounting screws.
3 If there is no shelving or other ob-
structions, removing the end panel may allow more access.
Filter Replacement The air filter on the vertical unit is lo­cated near the bottom of the unit Filter sizing may be found on Table G1. . 1 To remove the filters, take-off the
air section’s front panel.
2 Slide the filter out of the filter rack
on the bottom of the unit.
3 Replace old filter with new filter
and re-attach front panel.
CAUTION
1
2
Figure 16: Removal of drainpan
Slide out fanboard
3
4
Equipment Damage!
Do not operate unit without filters or grilles in place. Failure to do so may cause equipment failure
UV-SVN03D-EN 27
Maintenance
!
WARNING
Hazardous Service Procedures!
The maintenance and trouble­shooting procedures recommend­ed in this section of the manual could result in exposure to electri cal, mechanical or other potential safety hazards. Always refer to the safety warnings provided throughout this manual concern ing these procedures. When possi­ble, disconnect all electrical power including remote discon­nects before servicing. Follow proper lockout/tagout procedures to ensure the power can not be in advertently energized. When nec­essary to work with live electrical components, have a qualified li­censed electrician or other indi­vidual who has been trained in handling live electrical compo­nents perform these tasks. Failure to follow all of the recommended safety warnings provided, could result in death or serious injury.
Access to Fanboard & Motor
The unit ventilator fan board can be re­moved for service to the blower motor and fan wheels. The fan board must also be removed for easier access to the unit coils for cleaning and mainte nance. Utilize the following steps for proper removal of the fanboard.
1 Turn off power to the unit and re-
move the front panel.
2 Disconnect P-trap from drain pan.
-
CAUTION
Equipment Damage!
Support the fanboard to prevent the deck from sliding too far for ward and falling out of the unit. Failure to do so may cause equip­ment damage.
-
5 When reinstalling, use the same
steps in reverse order.
Motor The fan motor is a permanent split ca­pacitor type motor with voltage specif­ic power. See Table E1 through E3 for electrical performance and motor volt age.
­Table E3: Motor Voltage
Unit Voltage Motor Voltage
115-60-1 115-60-1 208-60-1 208/230-60-1 230-60-1 208/230-60-1 208-60-3 208/230-60-1 460-60-3 265-60-1 265-60-1 265-60-1 230-60-3 208/230-60-1
If a replacement motor is required, it should be ordered from The Trane Company. To replace the fan motor, complete the following steps:
-
6 Complete steps for removal of
fan board.
7 Disconnect the motor ground
wire.
8 Using a 7/16” Allen wrench, loos-
en the coupling on the fan shaft.
11 Attach new motor to fan shaft
and reverse steps to complete in stallation.
-
-
Figure 17: Fan board removal for fan/
motor access
Figure 18: Loosen screws
-
3 Disconnect fan plug.
4 Slide fan board by pulling deck
forward, Figure 17.
28 UV-SVN03D-EN
9 Loosen the screw on the motor
clamp until it allow the motor to be lifted off the base, Figure 18.
10 Lift the motor and pull forward
until fan shaft separates from the motor, Figure 19.
Figure 19: Lift/pull motor forward
Maintenance
!
WARNING
Hazardous Service Procedures!
The maintenance and trouble­shooting procedures recommend­ed in this section of the manual could result in exposure to electri cal, mechanical or other potential safety hazards. Always refer to the safety warnings provided throughout this manual concern ing these procedures. When possi­ble, disconnect all electrical power including remote discon­nects before servicing. Follow proper lockout/tagout procedures to ensure the power can not be in advertently energized. When nec­essary to work with live electrical components, have a qualified li­censed electrician or other indi­vidual who has been trained in handling live electrical compo­nents perform these tasks. Failure to follow all of the recommended safety warnings provided, could result in death or serious injury.
-
Note: These hydronic valves are de­signed and tested for silent operation. However, water noise may occur as a result of high water velocity. Piping noises may also occur in high temper ature (over 212° F) systems with insuf­ficient water pressure.
Note: Do not use petroleum-based or
-
mineral oil type boiler additives. Com pounds with a 50% water dilution that can be used are diethylene glycol, etheylene glycol and propylene glycol.
Coil Cleaning
Periodically the hydronic coils should be cleaned from dirt accumulation that could reduce the unit performance. To clean the equipment coil:
-
1 Remove the unit’s front panel.
2 Remove the unit’s front nosing.
3 Removed the coil’s solid steel
front cover.
4 Vacuum the dust/particles from
the coil face.
-
-
Modulating Valves
The valve should be serviced by a trained, experienced technician. For detailed installation and removal steps, refer to Pages 18-20 in this man ual.
For general servicing or malfunction, follow one of the appropriate steps:
1 If the valve is leaking, drain system
OR isolate valve from the system. DO NOT remove valve body from plumbing.
2 Ensure the cartridge needs to be
replaced. If so, follow appropriate steps explained for cartridge as sembly removal.
3 If the motor or other internal parts
of the actuator is damaged, replace the entire actuator assembly.
UV-SVN03D-EN 29
5 Reverse order for re-installation.
Preventive Maintenance A comprehensive preventive mainte­nance program should be established
­for a unit ventilator system. The fol-
lowing are several key elements:
Inspect the filters monthly. Follow
the Filter Replacement instruc-
tions.
Inspect and clean the drain pan
every three months.
Check the coils for ‘‘dirt’’ accumu-
-
lation every three to six months.
Clean the coils at least once each year.
Inspect the unit ventilator insula-
tion every three months; thor­oughly clean as needed.
Warranty Information
Warranty Information
Standard Warranty
The standard unit ventilator warranty is Trane’s parts-only warranty, running 12-months from startup, not to exceed 18-months from shipment.
Extended Warranty
The optional extended warranty is a second through fifth year warranty. The time starts at the end of standard 1-year coverage through the fifth year.
These extended warranties apply only to new equipment installed in domestic Trane Commercial Systems Group sales territories and must be ordered prior to start-up.
30 UV-SVN03D-EN
Trouble Shooting Checklist
!
WARNING
Hazardous Service Procedures!
The maintenance and trouble shooting procedures recommended in this section of the manual could result in exposure to electrical, mechanical or other potential safety hazards. Always refer to the safety warnings pro­vided throughout this manual concerning these procedures. When possible, disconnect all electrical power including remote disconnects before servicing. Follow proper lockout/tagout procedures to ensure the power can not be inadvertently energized. When necessary to work with live electrical components, have a qualified licensed electrician or other individual who has been trained in handling live electrical components per these tasks. Failure to follow all of the recommended safety warnings provided, could result in death or serious in­jury.
If operating difficulties are encountered, refer to page 31 and 32 for probable causes and corrective measures. If suggested corrective measures have been taken, and the trouble still persists, contact the control supplier or the local Trane Sales Of­fice.
Problem Heating Cooling Cause Correction
X Main power off Check fuses X Room sensor is not properly set Reset room sensor temperature
Start the warm-up cycle earlier in the morning to provide appropriate time­frame to increase room temperature prio r to space occupation.
Relocate sensor.
Replace malfunctioning component, or contact the control’s contra ctor , or if Trane controls, see CNT-SVX04A-EN for more information concerning Tracer™ controls.
Replace malfunctioning component, or contact the control’s contra ctor , or if Trane controls, see CNT-SVX04A-EN for more information concerning Tracer™ controls.
Ensure OA damper is in the open position.
Check flow of hot water through the control valve.
Check the boiler reset schedule to determine if the loop temperature can be decreased.
The economics of the unit ventilator selection dictate that, in most cases, the unit will be sized to provide adequate natural (ventilation) cooling without outside temperatures up to 60-65 F. Above this point, a changeover should be made to the mechanical cooling cycle.
Room too warm
(outside air temperature is below 35° F)
Room too warm
(outside air temperature is above 35° F)
Room too warm
(outside air temperature is above 35° F) Unit utilizes Wall Fin auxiliary radiation:
X
X
X
X Room sensor is not properly set Reset room sensor temperature
X
X OA damper is in the closed position X Clogged filter Replace filter X Control valve is malfunctioning
XBoiler
X Steam Check the operation of the control valves
X Outside air temperature is above 60 to 65° F
Room sensor is providing a false reading due to walls being cold from the night temperature setting.
Sensor is mounted on a block wall that is leaking cold air into the room through the mounting holes.
Face and bypass damper, or coil valve is malfunctioning.
Face and bypass damper or coil control valve is malfunctioning.
UV-SVN03D-EN 31
Trouble Shooting Checklist
Problem Heating Cooling Cause Correction
X Room sensor is not properly set Reset room sensor temperature X Clogged filter Replace filter
Replace malfunctioning component, or contact the control’s contract or, o r if Trane controls, see CNT-SVX04A-EN for more information concerning Tracer™ controls.
Ensure OA damper is in the closed or minimum outside air position.
On hot water and steam type units, check the boiler pressure or temperat ure to ensure that the requirements are being met.
Check the operation of the wall fin controls.
Replace malfunctioning component, or contact the control’s contract or, o r if Trane controls, see CNT-SVX04A-EN for more information concerning Tracer™ controls.
Ensure OA damper is in the minimum outside air position.
Check the temperature of the water leaving the chiller to ensure that it meets design requirements.
Check the unit switch to ensure it is in the ON position.
Check for loose switch or motor connection.
Room too cool
Room too cool
Unit utilizes Wall Fin auxiliary radiation:
Room too hot
Motor
Face and bypass damper, or coil valve is
X
malfunctioning.
X OA damper is in the open position
Boiler pressure or temperature de sign
X
requirements not being met
X Radiation controls malfunctioning X Room sensor is not properly set Reset room sensor temperature
X Clogged filter Replace filter
Face and bypass damper, or coil valve is
X
malfunctioning.
X OA damper is in the open position
Chiller temperature design requirements not
X
being met If the motor fails to start, and other motors on
X
the same circuit are functioning If the motor fails to start, and other motors on
X
the same circuit are functioning
32 UV-SVN03D-EN
120V/1 PH - 3-Speed
Unit Wiring
Field Installed Wiring
UV-SVN03D-EN 33
120V/1 PH - 3-Speed, DX/Hot Water
Unit Wiring
End Device Controls
34 UV-SVN03D-EN
Unit Wiring
End Device Package
480V/3 PH - 3-Speed, Chilled Water/Electric Heat (6-Element) -page 1
UV-SVN03D-EN 35
Unit Wiring
End Device Package
480V/3 PH - 3-Speed, Chilled Water/Electric Heat (6-Element) -page 2
36 UV-SVN03D-EN
Unit Wiring
End Device Package
120V/1 PH - 3-Speed, 4-Pipe Hot Water/Chilled Water
UV-SVN03D-EN 37
Unit Wiring
Tracer ZN520
120V/1 PH - 3-Speed, 4-Pipe Hot Water/Chilled Water
38 UV-SVN03D-EN
UV-SVN03D-EN 39
Trane A business of American Standard Companies www.trane.com
Literature Order Number UV-SVN03D-EN
Date October 2007
Supersedes UV-SVN03C-EN May 2006
For more information, contact your local district office or e-mail us at comfort@trane.com
Trane has a policy of continuous product and data improvement and reserves the right to change design and specifications without notice.
Loading...