Trane VUV 750 CFM, VUV 1500 CFM User Manual

Installation Owner Maintenance
Vertical Unit Ventilator
Classroom Unit Ventilator Model VUV
Models
VUVE
750 CFM
“A” and later Design Sequence
1500 CFM
UV-SVN03D-ENOctober 2007
Notice
NOTICE:
Warnings and Cautions appear at appropriate sections throughout this manual. Read these carefully.
WARNING – Indicates a potentially hazardous situation
!
which, if not avoided, could result in death or serious injury.
!
CAUTION – Indicates a potentially hazardous situation which, if not avoided, may result in minor or moderate injury. It may also be used to alert against unsafe practices.
CAUTION – Indicates a situation that may result in equipment or property-damage-only accidents.
Important!
Equipment is shipped FOB (Free on Board) at the manufacturer. Therefore, freight claims for damages against the carrier must be initiated by the receiver.
© 2007 American Standard All rights reserved. UV-SVN03D-EN
Contents
Installation/Startup/Commissioning
Pre-installation Checklist
General Information
Dimensions/Weights
Installation Instructions
Electrical Requirements
Pre-Startup Checklist
Maintenance
Warranty Information
Troubleshooting Checklist
Unit Wiring
4
4
5
7
14
24
26
27
30
31
33
UV-SVN03D-EN 3
Pre-installation Checklist
Jobsite Inspection
Always perform the following checks before accepting a unit:
1. Verify that the nameplate data matches the data on the sales order and bill of lading (including electrical data).
2. Verify that the power supply complies with the unit nameplate specifications.
3. Visually inspect the exterior of the unit, for signs of shipping damage. Do not
sign the bill of lading accepting the unit(s) until inspection has been com pleted. Check for damage promptly after the unit(s) are unloaded. Once the bill of lading is signed at the jobsite, the unit(s) are now the property of the SOLD TO party and future freight claims MAY NOT be accepted by the freight company.
Microbial Growth!
Wet interior unit insulation can become an amplification site for microbial growth (mold), which may cause odors and damage to the equipment and building materials. If there is evidence of microbial growth (mold) on the interior insulation, the insulation should be removed and replaced prior to operating the system.
-
Jobsite Storage
This unit is intended for indoor use only. To protect the unit from damage due to the elements, and to prevent possible IAQ contaminant sources from growing.
1. Place the unit(s) on a dry surface or raise above the ground to assure ade­quate air circulation beneath the unit.
2. Cover the unit(s) with a water proof tarp to protect them from the elements.
3. Make provisions for continuous venting of the covered units to prevent moisture from standing on the unit(s) surfaces. Wet interior unit insulation can become an amplification site for microbial growth (mold) which can be a cause of odors and possible indoor air quality problems.
4. Do not stack units.
4 UV-SVN03D-EN
General Information
Unit Nameplate
The unit nameplate is located in the left hand end pocket, behind the con­trol box. It includes the unit model number, serial number, electrical char­acteristics, and other pertinent unit da­ta.
Factory Shipment
Before shipment, each unit is leak test­ed, and run tested for proper control operation.
Access
A three panel front access of the unit ventilator allows for speedy set-up during field commissioning. This de­sign allows for the end pocket of the unit ventilator to be open while the fan (airside) section stays closed.
End Pockets
Access for piping and controls is made through the unit ventilator’s end pock­ets.
Coil Connections
The coil headers and drain connec­tions are made within the unit chassis to allow a tight seal and help prevent air leakage around the coil. The con­nection sizes vary dependent upon type of coil combination specified.
Coil Type Size (in.) Hydronic Cooling (Main) Coil or
Heating/Cooling Changeover Coil Heating (Auxiliary) Coil Steam Heating Coil 1" FNPT Direct Expansion Coil
3/4" Nominal
7/8" I.D.
1/2" Nominal
5/8" I.D.
3/8" O.D. Liquid
7/8" O.D. Suction
Unit Drain Pan
The drain pan is dual-sloped for effec­tive condensate removal. It is made from a non-corrosive material to help eliminate issues associated to leaking or standing water. It may be easily re moved for cleaning. The drain pan connection size for all Trane VUVE models is 7/8" O.D.
Motor
Motors for the VUVE model do not in­clude an external fan bearing on the end of the fan shaft. This helps avoid issues related to fan bearing mainte
-
nance (oiling is not needed), and/or bearing replacement.
Filters
Filter sizing for the unit ventilator are an off-the-shelf design to reduce or help eliminate local stocking of the fil­ters.
Sliding Fan Deck
Convenient access to the fan motor and wheels for maintenance and ser viceability may be made through Trane’s easy-slide fan deck design.
Outside/Return-Air Dampers
The outside-air/return-air damper is a one piece, linkage free design result­ing in a superior air-tight seal.
Field Installed Controls
(Option)
The unit comes equipped with a fan speed switch, damper blade (only), and an optional low temperature de­tection.
End Device Control Package
(Option)
Units containing the End Device con­trol design will incorporate a pre­wired, selected control components to a terminal strip for wiring a field pro vided controller and temperature sen­sor.
Note: for controller operation malfunc­tion of any non-Trane, field installed controls, consult the literature or tech­nical support of the controls manufac­turer.
Tracer™ ZN520 Control Package
(Option)
The ZN520 electronic digital controller is a factory installed, tested and com­missioned LonTalk™ certified design. It may be used in a stand-alone control scheme, or as part of a building auto
­mation system. The controller is pre-
wired to Trane selected control com ponents best suited for room comfort. For more information on the ZN520 unit controller operation and service issues, refer to CNT-SVX04A-EN (ZN520 control manual).
-
-
-
-
UV-SVN03D-EN 5
General Information
OA/RA Actuator (Option)
Table 1: OA/RA actuator specification
Table 2: Face-bypass actuator specification
The OA/RA actuator provides true spring return operation for positive close-off of the OA/RA damper. The spring return system of the actuator closes the outside damper if power is lost to the building. When ordered with factory controls, the actuator is a 3-point floating design. A 2 to 10 VDC actuator is available when other than Trane controls are specified. See Table 1 for OA/RA technical data.
Note: Because the damper actuator is a spring return type an inner spring will close the damper upon loss of power. If the need to service or replace the actuator is required, the spring must be "loaded" for the damper to function properly. The term loaded means that the blade must be held in the return air position upon replace ment of the actuator.
Power Supply
Power Consumption
Transformer Sizing
Overload Protection Control Signal 2 to 10 VDC
Angle of Rotation
Torque 35-inch/lb Direction of Rotation Position
Indication Run Time
-
(nominal) Noise Level Running: 30 dB
24 VAC ± 20% 50/60 HZ 24 VAC ± 10%
Running: 2.5 W Holding: 1 W
5 VA (class 2-power source)
Electronic throughout 0 to 95-degree rotation
3-point floating with Trane controls Maximum 95-degree
Adjustable with mechanical stop
Spring return reversible with CW/ CCW mounting Visual indicator, 0 to 95-degrees
90-second constant (independent of load)
Power Supply
Power Consumption
Transformer Sizing Angle of Rotation Torque 35-inch/lb Direction of Rotation Position Indication Run Time (nominal) Manual Override Noise Level Less than 35 dB Control Signal 3-point floating
24 VAC ± 20% 50/60 HZ 24 VAC ± 10%
2 W
3 VA (class 2-power source)
Maximum 95-degree Adjustable with mechanical stop
Reversible with switch L/R
Clip-on indicator
90-second constant
External push button
Face and Bypass Actuator (Option)
The face and bypass damper actuator
Table 3: Mod. water valve specification.
Table 4: Isolation valve specification.
incorporates a direct couple design. It provides electronic protection against overload. A limit switch is not includ
­ed, nor required as part of the design. When reaching the damper end posi­tion, the actuator automatically stops. The gears can be manually disen
­gaged with a button on the housing. See Table 2 for face and bypass actua tor specifications.
Modulating Water Valves (Option)
The modulating control valve provides optimum control of hot and chilled wa ter flow in various heating and cooling applications. They are designed to provide sinusoidal valve actuator trav
Power Supply
Power Consumption Max. Duty Cycle 15%
-
Nominal Timing 120 sec. Operating Ambient
Temp. Min./Max. Fluid Temp. 1 to 95°C
Operating Pressure
-
Differential Pressure Rating Static - 20 bar (300 psi)
Flow Characteristic Linear
-
24 VAC - 50/60 HZ
4 W
0 to 65°C 32 to 150°F
34 to 203°F Max. - 4 bar (60 psi)
Burst - 100 bar (1500 psi)
Power Supply
Power Consumption
Max. Fluid Temp. 94°C
Min. Fluid Temp. 1°C
Max. Operating Pressure 300 psi Max. Close-off Pressure 1/2" = 30 psi
24 VAC - 50/60 HZ
5 W
200°F
34°F
3/4" = 20 psi 1" = 15 psi
el and operate silently, resisting water hammer. The actuator on the valve is a 24V, 3­point floating type. See Table 3 for modulating water valve specifications.
Isolation Valve (Option)
The isolation valve is a two position 24V, spring return type valve. It pro vides added control in heating and cooling applications when used in
On heating coils, and two-pipe changeover applications, the valve is normally open to help prevent the coil from freezing in-case of power loss.
­For cooling, the valve is normally closed and opens when there is a call for cool-
ing. See Table 4 for isolation valve specifications.
conjunction with the face and bypass damper.
6 UV-SVN03D-EN
Dimensions/Weights/ Clearance
!
WARNING
Improper Unit Lift!
Test lift unit approximately 24 inches to verify proper center of gravity lift point. To avoid dropping of unit, reposition lifting point if unit is not level. Failure to properly lift unit could result in death or serious injury or possible equipment or property-only damage.
Table G1: VUVE general data
Description Unit Size
0750 1000 1250 150 0 Unit Length w/o end covers (inches) Unit Depth - Standard (inches) Unit Depth - with false back (inches) Unit Height - Standard (inches) Shipping Weight (Lbs.) Nominal Filter Size and Quantity (inches) Dynamic Air Filter Nominal Size (inches) & Qty. Drain Connection Size (inches) Fan Type / Quantity Motor Data
Quantity 1 1 2 2
Horsepower (ea) 1/4 1/4 1/10 1/10
Number of Fan Speeds (Standard)
If DX or electric heat used 1 1 1 1
Number of Fan Speed (ZN520)
If exhaust fan or ERSA used 2 2 2 2
If DX or electric heat used 1 1 1 1
Coil Volume (gal.)
Coil Type A 0.178 0.228 0.277 0.327
B 0.311 0.410 0.510 0.610 C 0.311 0.410 0.510 0.610 D 0.444 0.571 0.704 0.931
E 0.444 0.571 0.704 0.931
F 0.610 0.809 1. 014 1. 21 3 G 0.610 0.809 1. 014 1.213 H 0.395 0.593 0.742 0.837
69 81 93 105 16 5/8 16 5/8 16 5/8 16 5/8 21 1/4 21 1/4 21 1/4 21 1/4
30 30 30 30
320 405 450 470
14 x 20 x 1 (2) 14 x 24 x 1 (1) 14 x 20 x 1 (2) 14 x 24 x 1 (2)
7 x 42 x 1 (1) 7 x 54 x 1 (1) 7 x 66 x 1 (1) 7 x 78 x 1 (1)
7/8 ID Hose 7/8 ID Hose 7/8 ID Hose 7/8 ID Hose
FC / 2 FC / 2 FC / 4 FC / 4
3 3 3 3
3 3 3 3
14 x 30 x 1 (1) 14 x 24 x 1 (1) 14 x 30 x 1 (1)
Unit Location and Clearances
Locate the unit in an indoor area. The ambient temperature surrounding the unit must not be less than 45°F. Do not locate the unit in areas subject to freezing.
Attention should be given to service clearance and technician safety. The unit should contain enough space for
UV-SVN03D-EN 7
service personnel to perform mainte­nance or repair. Provide sufficient room to make water, and electrical connection(s). Local and national codes should be followed in providing electrical power connections. A 36" clearance at the unit front is sufficient for maintenance and service of the equipment.
Dimensions
Standard Depth Unit
8 UV-SVN03D-EN
Dimensions
Falseback Unit
UV-SVN03D-EN 9
Dimensions
Dynamic Air Barrier Unit
10 UV-SVN03D-EN
Dimensions
End Covers
UV-SVN03D-EN 11
Dimensions
Wall Boxes
12 UV-SVN03D-EN
Loading...
+ 28 hidden pages