Only qualified personnel should install and service the equipment. The installation, starting up, and servicing
of heating, ventilating, and air-conditioning equipment can be hazardous and requires specific knowledge and
training. Improperly installed, adjusted or altered equipment by an unqualified person could result in death or
serious injury.When working on the equipment, observe all precautions in the literature and on the tags,
stickers, and labels that are attached to the equipment.
February 2015
RSP-SVN001A-EN
Page 2
Introduction
Read this manual thoroughly before operating or servicing
this unit.
Warnings, Cautions, and Notices
Safety advisories appear throughout this manual as
required.Your personal safety and the proper operation of
this machine depend upon the strict observance of these
precautions.
The three types of advisories are defined as follows:
WARNING
Proper Field Wiring and Grounding
Required!
Failure to follow code could result in death or serious
injury. All field wiring MUST be performed by qualified
personnel. Improperly installed and grounded field
wiring poses FIRE and ELECTROCUTION hazards. To
avoid these hazards, you MUST follow requirements for
field wiring installation and grounding as described in
NEC and your local/state electrical codes.
WARNING
CAUTIONs
NOTICE
Indicates a potentially hazardous
situation which, if not avoided, could
result in death or serious injury.
Indicates a potentially hazardous
situation which, if not avoided, could
result in minor or moderate injury. It
could also be used to alert against
unsafe practices.
Indicates a situation that could result in
equipment or property-damage only
accidents.
Important Environmental Concerns
Scientific research has shown that certain man-made
chemicals can affect the earth’s naturally occurring
stratospheric ozone layer when released to the
atmosphere. In particular, several of the identified
chemicals that may affect the ozone layer are refrigerants
that contain Chlorine, Fluorine and Carbon (CFCs) and
those containing Hydrogen, Chlorine, Fluorine and
Carbon (HCFCs). Not all refrigerants containing these
compounds have the same potential impact to the
environment.Trane advocates the responsible handling of
all refrigerants-including industry replacements for CFCs
such as HCFCs and HFCs.
Important Responsible Refrigerant
Practices
Trane believes that responsible refrigerant practices are
important to the environment, our customers, and the air
conditioning industry. All technicians who handle
refrigerants must be certified.The Federal Clean Air Act
(Section 608) sets forth the requirements for handling,
reclaiming, recovering and recycling of certain
refrigerants and the equipment that is used in these
service procedures. In addition, some states or
municipalities may have additional requirements that
must also be adhered to for responsible management of
refrigerants. Know the applicable laws and follow them.
WARNING
Personal Protective Equipment (PPE)
Required!
Installing/servicing this unit could result in exposure to
electrical, mechanical and chemical hazards.
•Before installing/servicing this unit, technicians
MUST put on all PPE required for the work being
undertaken (Examples; cut resistant gloves/sleeves,
butyl gloves, safety glasses, hard hat/bump cap, fall
protection, electrical PPE and arc flash clothing).
ALWAYS refer to appropriate Material Safety Data
Sheets (MSDS)/Safety Data Sheets (SDS) and OSHA
guidelines for proper PPE.
•When working with or around hazardous chemicals,
ALWAYS refer to the appropriate MSDS/SDS and
OSHA/GHS (Global Harmonized System of
Classification and Labelling of Chemicals) guidelines
for information on allowable personal exposure
levels, proper respiratory protection and handling
instructions.
•If there is a risk of energized electrical contact, arc, or
flash, technicians MUST put on all PPE in accordance
with OSHA, NFPA 70E, or other country-specific
requirements for arc flash protection, PRIOR to
servicing the unit. NEVER PERFORM ANY
SWITCHING, DISCONNECTING, OR VOLTAGE
TESTING WITHOUT PROPER ELECTRICAL PPE AND
ARC FLASH CLOTHING. ENSURE ELECTRICAL
METERS AND EQUIPMENT ARE PROPERLY RATED
FOR INTENDED VOLTAGE.
Failure to follow instructions could result in death or
serious injury.
This document and the information in it are the property of
Trane, and may not be used or reproduced in whole or in
part without written permission. Trane reserves the right
to revise this publication at any time, and to make changes
to its content without obligation to notify any person of
such revision or change.
Trademarks
All trademarks referenced in this document are the
trademarks of their respective owners.
All models that have ReliaTel™ controls installed. To
identify if ReliaTel™ controls are installed, validate digit 9
of the model number is an “R.”
Precedent™ 3 to 10Tons
All models that have ReliaTel™ controls installed (where
digit 9 of the model number is an “R’”) except
Precedent™ A cabinets, which include the following:
To identify the type of Precedent™ cabinet for older
models, view the letter after the model number on the
nameplate. For newer models, it is the 30
model number.
Figure 1.Cabinet identification on nameplate, older
models
th
digit of the
Figure 2.Cabinet identification on nameplate, newer
models
RSP-SVN001A-EN5
Page 6
General Information
The information provided in this manual is intended for
use when adding human interface support to a Precedent
or Voyager™ Light Commercial unit that has ReliaTel™
controls.The work involved in this upgrade consists of the
following:
•Updating to the latest ReliaTel™ Refrigeration Module
(RTRM) to MOD02617
•Installing theTD-5 human interface mounting bracket
•Mounting aTD-5 display to the human interface
mounting bracket
•Connecting theTD-5 human interface cable to the
RTRM
TheTD-5 human interface allows you to view historic
alarms, reports, graph specific data, create setpoints, and
save graph data to a USB device for further diagnosis.
Detailed information on the capabilities of theTD-5 can be
found in theTracer™TD-5 Display for ReliaTel™ Controller
Installation, Operation and Maintenance Guide (RTSVX49*-EN).
A number of setpoints can be changed by using the
different potentiometers on each control board.To change
the setpoint, use a screw driver to turn the potentiometers
to a specific value.
Figure 3.Example of changing potentiometer value on
the RTOM
If theTD-5 human interface is disconnected from the
ReliaTel™ Refrigeration Module, the local setpoints from
the potentiometer are used. Note that setpoints created
from a building automation system (BAS) take precedence
over setpoints created by theTD-5.
Additional modules are available as options that have the
capability to create setpoints. Table 2 defines these
optional modules:
Table 2.Optional setpoints
Option
17 SEERDigit 6 = 7
Economizer
Model No.
IdentificationSetpoint
Digit 14 = C, D, E,
F, G, or H
Supply fan
adjustment
Economizer
reference enthalpy
Economizer dry bulb
enabled
Supported
Control
Module
RTOM
MOD02554
RTEM
MOD02618
Note: This does not mean that older RTOM and RTEM
modules are unusable.TheTD-5 human interface
can still gather data from older RTOM and RTEM
boards in addition to having the ability to create
setpoints.The latest revisions of the RTOM and
RTEM boards require an upgrade to receive the
setpoint functionality described in Table 2.The
revision list of all ReliaTel™ boards is located in the
ReliaTel™ Controller Installation, Operation, and
Maintenance Guide (RT-SVX49*-EN)
This manual refers to other pieces of literature at various
points.The referenced literature is not included in the
upgrade package unless noted. It is available for download
from through the online literature repository.
If you need technical assistance during installation,
contact Light CommercialTechnical Service in Clarksville,
TN. Ensure installation is performed by a qualified service
technician.
Part Identification
The following tables provides part identification
information.
Table 3.Voyager™ Light Commercial (KIT17429)
Aftermarket
Part #DescriptionQty
MOD02617
CNT07131
To view all potentiometer setpoint values, put theTD-5
human interface in Read mode by going to Settings >
Setup > Display Read Only Mode.
In Writer mode, the TD-5 can override the setpoint values
created from the potentiometers, making setpoint
configuration easier.
4. Mount the TD-5 human interface bracket as follows:
WARNING
Hazardous Voltage w/Capacitors!
Failure to disconnect power and discharge capacitors
before servicing could result in death or serious injury.
Disconnect all electric power, including remote
disconnects and discharge all motor start/run
capacitors before servicing. Follow proper lockout/
tagout procedures to ensure the power cannot be
inadvertently energized. For variable frequency drives or
other energy storing components provided by Trane or
others, refer to the appropriate manufacturer’s literature
for allowable waiting periods for discharge of
capacitors. Verify with an appropriate voltmeter that all
capacitors have discharged.
For additional information regarding the safe discharge
of capacitors, see PROD-SVB06A-EN
1. Turnoff the main power disconnect to the unit and then
follow the correct lockout/tagout safety procedures to
ensure that main power to the machine cannot be
inadvertently restored.
2. Open the control cabinet door panel to locate the
RTRM board.
• For standard panels, remove the two screws at the
bottom of the control door panel.
• Depending on the model, you may need to remove
the high voltage sheet metal that is attached by
recessed screws.
a. Pre-drill holes for the TD-5 human interface
mounting bracket (BRK04519). Voyager™ Light
Commercial models manufactured after January
2014 already have pre-drilled holes for the TD-5
human interface mounting bracket. If the model
was manufactured before January 2014, pre-drilled
holes are required.
b. Place theTD-5 human interface mounting bracket
BRK04519 directly below the control compartment
against the inside of the unit. Use theTD-5
mounting bracket BRK04519 as a template to mark
the holes of the bracket.
c. Beforedrilling the holes, ensure that nothing will be
damaged on the other side of the sheet metal.Then
pre-drill the marked holes, using a 1/8" drill bit.
d. Fasten theTD-5 mounting bracket, using a 5/16" nut
driver and the 10-16 UNC x ½" screws.
e. Fasten the stop bumpers (IRT0 0017) around the
bottom screw thread.
Figure 5.Installing the TD-5 human interface
mounting bracket (BRK04519)
Figure 4.Voyager™ Light Commercial - RTRM board
3. Replace the RTRM as follows:
a. Detach the cables from the RTRM board that go to
a thermostat and sensors.
b. Once all cables/wires are detached, remove the
existing RTRM board from the back of the cabinet
and attach the newer RTRM board.
c. Reconnectall cables/wires that were removed from
the existing module to the new module.
To view detailed information on each connection of the
RTRM board, refer to the ReliaTel™ Microprocessor
Controls Service Diagnostics Manual (RT-SVD03*-EN).
5. Mount theTD-5 human interface(CNT07131) to bracket
BRK04416, as follows:
a. The notches on bracket BRK04416 must be located
at the top and bottom of theTD-5.
b. Use a Phillips screw driver and 4 of the 4M 8 mm
screws to fasten theTD-5 human interface onto
BRK04416.
6. Place theTD-5 human interface and BRK04416 onto the
TD-5 mounting bracket BRK04519, using the TD-5
mounting bracket eyelets. At any time, theTD-5 human
interface can be held for navigational purposes.Two
optional screws are included to fasten the two
mounting brackets.
Figure 7.Mount the TD-5 human interface on the
eyelet bracket (BRK04519
Figure 8.TD-5 Human Interface Schematic (2313-1548)
3.0
TRIM
SCHEMATIC - HUMAN INTERFACE
CBLHI
RED
1
J10-1
RTRM-P10
BLACK
2
J10-2
J10-3
J10-4
RTRM-P10
BLUE
3
RTRM-P10
4
GRAY
RTRM-P10
HI
2313-1548-0100
2.0
TRIM
RTRM
9. Optional: If the RTOM board was purchased, which
allows the ability to create the Supply Fan Adjustment
setpoint, remove the older RTOM board and replace it
with the newer RTOM board as follows:
a. Ensure that the newer RTOM board’s local
potentiometer values are identical to the replaced
RTOM board.
b. Once all cables/wires are detached, remove the
existing RTOM board from the back of the cabinet
and attach the newer RTOM board.
c. Reconnectall cables/wires that were removed from
the existing module to the new module.
To view detailed information on each connection of the
RTOM board, refer to the ReliaTel™ Microprocessor
Controls Service Diagnostics Manual (RT-SVD03*-EN).
Figure 9.RTOM Board
7. Run theTD-5 cord through the control compartment
base floor hole.
8. Insert the TD-5 cord into the J10 connection on the
RTRM board, ensuring that the cord is not pulled tight
against any sheet metal edges that could cause
damage to the cord.
10. Optional: If the RTEM board was purchased, which
allows the ability to create the economizer reference
enthalpy and economizer dry bulb enabled setpoint,
remove the RTEM board and replace it with the newer
RTEM board as follows:
a. Ensure the newer RTEM board’s local
potentiometer values are identical to the replaced
RTEM board.
b. Once all cables are detached, remove the existing
RTEM from the unit and attach the newer RTEM
board.
c. Reconnectall cables/wires that were removed from
the existing module to the new module.
To view detailed information on each connection of the
RTEM board, refer to the ReliaTel™ Microprocessor
Controls Service Diagnostics Manual (RT-SVD03*-EN).
11. Turn on the unit by turning the disconnect to the on
position.
12.To start the unit, press the Auto button in the upper
right hand corner of theTD-5 human interface.
10RSP-SVN001A-EN
Page 11
Precedent™ Unit Installation Instructions
3. Replace the RTRM as follows:
WARNING
Hazardous Voltage w/Capacitors!
Failure to disconnect power and discharge capacitors
before servicing could result in death or serious injury.
Disconnect all electric power, including remote
disconnects and discharge all motor start/run
capacitors before servicing. Follow proper lockout/
tagout procedures to ensure the power cannot be
inadvertently energized. For variable frequency drives or
other energy storing components provided by Trane or
others, refer to the appropriate manufacturer’s literature
for allowable waiting periods for discharge of
capacitors. Verify with an appropriate voltmeter that all
capacitors have discharged.
For additional information regarding the safe discharge
of capacitors, see PROD-SVB06A-EN
1. Turnoff the main power disconnect to the unit and then
follow the correct lockout/tagout safety procedures to
ensure that main power to the machine cannot be
inadvertently restored.
2. Open the control cabinet door panel to locate the
RTRM board.
• For standard panels, remove the two screws at the
bottom of the control door panel.
Figure 10. Precedent™ E Cabinet - RTRM board
a. Detach the cables from the RTRM board that go to
a thermostat and sensors.
b. Once all cables are detached, remove the existing
RTRM board from the back of the cabinet and attach
the new RTRM board.
c. Reconnectall cables/wires that were removed from
the existing module to the new module.
To view detailed information on each connection of the
RTRM board can be viewed in the ReliaTel™
Microprocessor Controls Service Diagnostics Manual
(RT-SVD03*-EN).
d. Insert the TD-5 cord into the J10 connection on the
RTRM board.
e. Place theTD-5 on top of the unit while mounting the
bracket.
Figure 12. TD-5 Human Interface Schematic (2313-1548)
3.0
TRIM
SCHEMATIC - HUMAN INTERFACE
RED
1
J10-1
RTRM-P10
BLACK
2
J10-2
J10-3
J10-4
RTRM-P10
BLUE
3
RTRM-P10
4
GRAY
RTRM-P10
2.0
TRIM
RTRM
CBLHI
HI
2313-1548-0100
4. Optional: If the RTOM board was purchased, which
allows the ability to create the supply fan adjustment
setpoint, remove the older RTOM board and replace it
with the newer RTOM board as follows:
The RTOM board will be located in either the indoor fan
section or the control panel compartment depending
on the Precedent™ model.
Figure 13. Precedent™ E Cabinet - RTOM board
Figure 11. Precedent™ B Cabinet - RTRM board
RSP-SVN001A-EN11
Page 12
Precedent™ Unit Installation Instructions
Figure 14. Precedent™ B Cabinet - RTOM board
a. Ensure the newer RTOM board's local
potentiometer values are identical to the replaced
RTOM board.
b. Once all cables/wires are detached, remove the
existing RTOM board from the back of the cabinet
and attach the newer RTOM board.
c. Reconnectall cables/wires that were removed from
the existing module to the new module.
To view detailed information on each connection of the
RTOM board can be viewed in the ReliaTel
Microprocessor Controls Service Diagnostics Manual
(RT-SVD03*-EN).
5. Mount the TD-5 human interface bracket as follows:
a. Place theTD-5 human interface mounting bracket in
the front of the control compartment. Use the TD-5
human interface mounting bracket as a template to
mark the holes. For units that have the gas/heat
option and a voltage of either 450/60/3 or 575/60/3
an additional sensor and transformer may be
attached in this area.
b. Before drilling the holes, ensure that nothing will be
damaged on the other side of the sheet metal.Then
pre-drill the marked holes with a 1/8" drill bit.
c. Fasten theTD-5 mounting bracket, using a 5/16" nut
driver and the 10-16 UNC x ½” screws.
d. Fasten the stop bumpers (IRT00017) around the
bottom screw thread.
6. Mount theTD-5 display (CNT07131) to theTD-5 human
interface mounting bracket.
This bracket gives the user the ability to hold the TD-5
human interface in their hand while diagnosing issues.
a. Fasten 3 of the 4M 8 mm screws into the top two
holes and bottom left hand hole of theTD-5 human
interface making sure 1 mm is left to place the
TD-5 human interface into the recessed screw
holes. Loctite can be optionally used when
fastening the screws.
b. TheTD-5 can be permanently fastened by installing
the 4th screw in the bottom right hand hole once the
TD-5 human interface is mounted.
Figure 15. Precedent™ E Cabinet - TD-5 Human
Interface
Figure 16. Precedent™ B Cabinet - TD-5 Human
Interface
c. Using the plastic zip tie, (fastened to the hole in the
right hand leg of the TD-5 bracket) bundle theTD-5
cord to ensure it is isolated from the other controls.
Do not pull the cord tight against any sheet metal
edges.This could cause damage to the cord.
7. Optional: If the RTEM board was purchased, which
allows the ability to create the economizer reference
enthalpy and economizer dry bulb enabled setpoint,
remove the RTEM board and replace it with the newer
RTEM board as follows:
a. Ensure the newer RTEM board's local
potentiometer values are identical to the replaced
RTEM board.
b. Once all cables are attached remove the existing
RTEM from the unit and attach the newer RTEM
board.
c. Reconnectall cables/wires that were removed from
the existing module to the new module.
To view detailed information on each connection of the
RTEM board, refer to the ReliaTel™ Microprocessor
Controls Service Diagnostics Manual (RT-SVD03*-EN).
12RSP-SVN001A-EN
Page 13
Figure 17.Precedent™ E Cabinet - RTEM Location
8. Turn on the unit by turning the disconnect to the on
position.
9. To start the unit, press the Auto button in the upper
right hand corner of theTD-5 human interface.
Precedent™ Unit Installation Instructions
RSP-SVN001A-EN13
Page 14
Page 15
Page 16
The manufacturer optimizes the performance of homes and buildings around the world. A business of Ingersoll Rand,
the leader in creating and sustaining safe, comfortable and energy efficient environments,the manufacturer offers a
broad portfolio of advanced controls and HVAC systems, comprehensive building services, and parts. For more
information, visit www.IRCO.com.
The manufacturer has a policy of continuous product and product data improvement and reserves the right to change design and specifications without notice.