Table 2. List of factory installed options (FIOPs)
2” MERV 8 or MERV 13 Pleated Filters w/ Filter Removal
Tool
Black Epoxy Pre-Coated Coil Horizontal Side Access with Disconnect Switch
Barometric Relief
BACnet™ Communication Interface (BCI) Motor Shaft Grounding Ring
Clogged Filter/Fan Failure Switch
Condensate Overflow Switch Powered or Unpowered Convenience Outlet
DCV Harness Stainless Steel Drain Pan
Discharge Air Sensing Kit
Economizer - Standard, Downflow
Economizer - Low Leak, Downflow
Electric Heaters Tool-less Hail Guard
Frostat™
High Efficiency Motors Two Speed Fan Provision
High Short Circuit Current Rated (SCCR) Electrical
Subsystem
Hinged Access Panels
(a)Most Factory Installed Options are available for downflow air discharge units only. Verify with ordering
system for availability.
(b)Requires an Economizer.
(c) Some field set up required.
(d)Available with Two Speed Fan or Variable Speed Fan.
(e) Requires ReliaTel Options Module.
(f) Must be ordered with Through the Base Electrical op tion or Horizontal Si de Access, and either Un it Mounted
Disconnect switch or Circuit Breaker.
(g)TCI is for use with non-VariTrac™ systems and VariTrac systems.
(b) (c)
(e)
(e)
(e)
(c)
Through the Base Electrical with Circuit Breaker
(c)
Through the Base Electrical with Disconnect Switch
(a)
Horizontal Side Access with Circuit Breaker
LonTalk® Communication Interface (LCI)
Oversized Motors
Supply & Return Air Smoke Detectors
Trane® Communication Interface (TCI)
Variable Speed Fan Provision for Single Zone VAV
(d)
(f)
(e)
(g)
2
Table 3. 12.5-20 ton packaged rooftop performance data (heat pump)
Nominal Size (Tons) 12.5 15 20
Cooling Performance
Supply Air (cfm)
Tot / Sens Cap (MBh) 153.1/107.3 186.2/138.9 267.8/189.7
(b)
EER
IEER (One Speed Fan / Two or
Variable Speed Fan)
Heating Performance
High Temperature Btuh Rating 136,000 170,000 210,000
COP 3.2 3.2 3.2
Low Temperature Btuh Rating 75,000 90,000 120.000
COP 2.1 2.1 2.1
Other information
Net Weight (Lbs) 1978 1982 2107
Roofcurb BAYCURB027B
Unit Cabinet Size C C+
(d)
Filters
Number Size Recommended
Downflow (4) 20x20x2
Horizontal (8) 20x25x2 (8) 20x25x2 (12) 20x20x2
(a)ARI rated airflow.
(b)EER is rated at ARI conditions and in accordance with DOE test procedures.
(c) Integrated Energy Efficiency Ratio (IEER) is rated in accordance with AHRI standard
210/240 or 360.
(d)Optional 2” MERV 8 and MERV 13 filters also available.
(a)
(c)
- Type Furnished
5,000 5,300 6,400
12.0/13.5 12.0/13.5 11.5/12.0
Throwaway Throwaway Throwaway
(4) 20x25x2
Standard Efficiency
10.6 10.6 9.7
(4) 20x20x2
(4) 20x25x2
(8) 20x20x2
(4) 20x16x2
3
Table 4. 12.5-20 ton unit indoor fan data (heat pump)
STANDARD
150 208-230/3
460/3 3 - 1740 5 - 3450
575/3
180 208-230/3
460/3 3 - 1740 5 - 3450
575/3
240 208-230/3
460/3 5 - 3450 7.5 - 3470
575/3
HP - RPM
Table 5. Unit MCA & MOP electrical data (standard indoor fan motor)
WS* Volts MCA MOP
150 208-230/3 68 80
180 208-230/3 74 90
240 208-230/3 116 150
460/3 32 40
575/3 25 30
460/3 36 45
575/3 30 35
460/3 56 70
575/3 45 60
OVERSIZE
HP - RPMWS* Volts
3
Table 6. Unit dimensional data
Cabinet Size
Unit Length UL 122 5/16 122 5/16
Unit Width UW 84 3/16 84 3/16
Unit Height UH 54 64 1/8
Clearance C1 60 60
Clearance C2 48 48
Clearance C3 36 1/8 36 1/8
Clearance C4 38 38
Clearance C5 72 72
Curb Length CL 116 7/8 116 7/8
Curb Width CW 81 81
Supply Length SL
Supply Width SW
Return Length RL
Return Width RW
(a) Dimensions are for curb openings and not duct inserts.
Reference the product catalog for duct insert dimensions.
(a)
(a)
(a)
(a)
CC+
28 9/16 28 9/16
69 1/2 69 1/2
22 1/4 22 1/4
77 77
4
RL
RW
SW
CL
SL
CW
The manufacturer optimizes the performance of homes and buildings around the world. A business of Ingersoll Rand, the leader
in creating and sustaining safe, comfortable and energy efficient environments, the manufacturer offers a broad portfolio of
advanced controls and HVAC systems, comprehensive building services, and parts. For more information, visit www.IRCO.com.
The manufacturer has a policy of continuous product and product data improvement and reserves the right to change design and
specifications without notice.
© 201 4 Trane All rights reserved
RT-PRC052E-EN 23 May 2014
Supersedes RT-PRC052D-EN (14 Jan 2014)
We are committed to using environmentally
conscious print practices that reduce waste.