Trane R Series, RTHD Installation Operation & Maintenance

Page 1
Installation Operation Maintenance
Series R Helical Rotary Liquid Chillers
© American Standard Inc. 2006
Models RTHD 175-450 ton units (60 Hz) 125-450 ton units (50 Hz)
November 2006 RTHD-SVX01D-EN
Page 2
NOTICE: Warnings and Cautions appear at appropriate sections through-
out this literature. Read these carefully.
WARNING: Indicates a potentially hazardous situation which, if not
avoided, could result in death or serious injury.
CAUTION: Indicates a potentially hazardous situation which, if not
avoided, may result in minor or moderate injury. It may also be used to alert against unsafe practices.
CAUTION: Indicates a situation that may result in equipment or property­damage only accidents.
Important Environmental Concerns!
Scientific research has shown that certain man-made chemicals can affect the earth’s naturally occurring stratospheric ozone layer when released to the atmosphere. In particular, several of the identified chemicals that may affect the ozone layer are refrigerants that contain Chlorine, Fluorine and Carbon (CFCs) and those containing Hydrogen, Chlorine, Fluorine and Carbon (HCFCs). Not all refrigerants containing these compounds have the same potential impact to the environment. Trane advocates the responsible handling of all refrigerants—including industry replacements for CFCs such as and HCFCs and HFCs.
Responsible Refrigerant Practices!
Trane believes that responsible refrigerant practices are important to the environment, our customers, and the air conditioning industry. All technicians who handle refrigerants must be certified. The Federal Clean Air Act (Section 608) sets forth the requirements for handling, reclaiming, recovering and recycling of certain refrigerants and the equipment that is used in these service procedures. In addition, some states or municipalities may have additional requirements that must also be adhered to for responsible management of refrigerants. Know the applicable laws and follow them.
WARNING Contains Refrigerant!
System contains oil and refrigerant under high pressure. Recover refrigerant to relieve pressure before opening the system. See unit nameplate for refrigerant type. Do not use non-approved refrigerants, refrigerant substitutes, or refrigerant additives.
Failure to follow proper procedures or the use of non-approved refrigerants, refrigerant substitutes, or refrigerant additives could result in death or serious injury or equipment damage.
2 RTHD-SVX01D-EN
Page 3
Table of Contents
General Information..................................................................................... 5
Literature Change History ................................................................................. 5
Unit Identification - Nameplates ........................................................................ 5
Unit Inspection .................................................................................................. 6
Inspection Checklist .......................................................................................... 6
Loose Parts Inventory ....................................................................................... 6
Unit Description................................................................................................. 6
Model Number Coding System......................................................................... 7
Unit Model Number ........................................................................................ 7
Installation Overview....................................................................................... 12
Installation Mechanical.............................................................................. 19
Storage ............................................................................................................ 19
Location Requirements ................................................................................... 19
Moving and Rigging......................................................................................... 21
Lifting Procedure ............................................................................................. 25
Isolation Pads .................................................................................................. 29
Unit Leveling ................................................................................................... 30
Water Piping.................................................................................................... 31
Water Pressure Drop Data .............................................................................. 39
Condenser Water Regulating Valve................................................................. 49
Water Treatment ............................................................................................. 50
Water Pressure Gauges and Thermometers................................................... 51
Water Pressure Relief Valves.......................................................................... 51
Flow Sensing Devices ..................................................................................... 51
Refrigerant Pressure Relief Valve Venting ...................................................... 52
Thermal Insulation ........................................................................................... 54
Installation Electrical ................................................................................. 57
General Recommendations............................................................................. 57
Power Supply Wiring....................................................................................... 57
Compressor Motor Phase Sequencing ........................................................... 59
Correcting Improper Electrical Phase Sequence ............................................. 60
Application Of Solid-State Starters ........................................................................... 63
Module Connections for Interconnecting Wiring ............................................ 66
Interconnecting Wiring (Field Wiring Required)............................................... 66
Operating Principles Mechanical .............................................................. 75
General ............................................................................................................ 75
Refrigeration (Cooling) Cycle ........................................................................... 75
Compressor Description.................................................................................. 78
Oil Management System ................................................................................ 80
Oil Cooler......................................................................................................... 82
Operator Interface Controls ...................................................................... 83
CH530 Communications Overview ................................................................. 83
Controls Interface............................................................................................ 83
DynaView Interface ......................................................................................... 84
Display Screens............................................................................................... 85
Keypad/Display Lockout Feature ..................................................................... 86
Main Screen .................................................................................................... 87
Reports Screen................................................................................................ 92
RTHD-SVX01D-EN 3
Page 4
Table of Contents
Settings Screen ............................................................................................... 94
Diagnostic Screen ........................................................................................... 96
TechView .................................................................................................... 97
Minimum PC requirements to install and operate TechView .......................... 98
Unit View......................................................................................................... 99
Status View ................................................................................................... 100
Setpoint View ................................................................................................ 103
Manual Override View................................................................................... 107
Diagnostics View........................................................................................... 109
Software View............................................................................................... 113
Binding View ................................................................................................. 114
Software Download....................................................................................... 115
Unit Start-up............................................................................................. 117
Power Up ...................................................................................................... 117
Power Up to Starting..................................................................................... 117
Stopped to Starting: ...................................................................................... 119
Seasonal Unit Start-Up Procedure................................................................. 121
Unit Shutdown......................................................................................... 125
Normal Shutdown to Stopped....................................................................... 125
Seasonal Unit Shutdown ............................................................................... 126
Periodic Maintenance .............................................................................. 127
Overview ....................................................................................................... 127
Weekly Maintenance and Checks ................................................................. 127
Monthly Maintenance and Checks................................................................ 127
Annual Maintenance...................................................................................... 128
Scheduling Other Maintenance..................................................................... 129
Maintenance Procedures ......................................................................... 133
Cleaning the Condenser ................................................................................ 133
Mechanical Cleaning Procedure .................................................................... 133
Chemical Cleaning Procedure ....................................................................... 136
Cleaning the Evaporato ................................................................................. 137
Compressor Oil ............................................................................................. 137
Oil Sump Level Check .................................................................................... 137
Removing Compressor Oil ............................................................................ 139
Oil Charging Procedure .................................................................................. 139
Replacing the Main Oil Filt e (Hot Filter)......................................................... 140
Replacing the Gas Pump Oil Filter................................................................. 141
Refrigerant Charge ......................................................................................... 141
Refrigerant Charging ..................................................................................... 142
Diagnostics ............................................................................................... 145
Wiring Schematics ................................................................................... 159
Unit Electrical Data ........................................................................................ 159
4 RTHD-SVX01D-EN
Page 5
General Information
Literature Change History
RTHD-SVX01D-EN Additional configurations available for 50 hz units. (Nov.
2006) RTHD-SVX01C-EN New control panel design. (May 2005) RTHD-SVX01B-EN New Evap/Cond configuration C2F2F3 and change to
minimum flow rates. (June 2004) RTHD-SVX01A-EN New manual describes installation, operation, and
maintenance of RTHD units. (May 2003)
Unit Identification - Nameplates
When the unit arrives, compare all nameplate data with ordering, submittal, and shipping information. A typical unit nameplate is shown in Figure 1.
Figure 1 Typical Unit Nameplate
Unit Nameplates
The RTHD “unit” nameplate is applied to the exterior surface of the starter/ control panel. The “compressor” nameplate is applied to the compressor. The starter/control panel nameplate is located inside the panel.
The unit nameplate provides the following information:
Unit model
Unit Serial Number
Unit device number.
– Identifies unit electrical requirements – Lists correct operating charges of HFC-134a and refrigerant oil – Lists unit test pressures and maximum working pressures.
The starter/control panel nameplate provides the following information:
Panel model number
Rated load amps
•Voltage
• Electrical characteristics - starter type, wiring
• Options included. The compressor nameplate provides the following information:
RTHD-SVX01D-EN 5
Page 6
General Information
Compressor model descriptor
Compressor serial number
Compressor device number
Motor serial number
Compressor electrical characteristics
Refrigerant.
Unit Inspection
When the unit is delivered, verify that it is the correct unit and that it is prop­erly equipped.
Inspect all exterior components for visible damage. Report any apparent dam­age or material shortage to the carrier and make a “unit damage” notation on the carrier’s delivery receipt. Specify the extent and type of damage found and notify the appropriate Trane Sales Office.
Do not proceed with installation of a damaged unit without sales office approval.
Inspection Checklist
To protect against loss due to damage incurred in transit, complete the fol­lowing checklist upon receipt of the unit.
Inspect the individual pieces of the shipment before accepting the unit. Check for obvious damage to the unit or packing material.
Inspect the unit for concealed damage as soon as possible after delivery and before it is stored. Concealed damage must be reported within 10 days after receipt.
If concealed damage is discovered, stop unpacking the shipment. Do not remove damaged material from the receiving location. Take photos of the damage, if possible. The owner must provide reasonable evidence that the damage did not occur after delivery.
Notify the Trane sales representative and arrange for repair. Do not repair the unit, however, until damage is inspected by the transportation repre­sentative.
Loose Parts Inventory
Check all items against the shipping list. Water vessel drain plugs, isolation pads, rigging and electrical diagrams, service literature and the starter/control panel wire pullbox (required on some starters) are shipped unassembled in the starter control panel.
Unit Description
The RTHD units are single compressor, helical-rotary type, water-cooled liquid chillers designed for installation indoors. Each unit is a completely assembled, hermetic package that is factory-piped, wired, leak-tested, dehydrated, charged (optional), and tested for proper control operation before shipment.
Figure 2 and Figure 3 show a typical RTHD unit and its components. Water
inlet and outlet openings are covered before shipment. The oil tank is factory charged with the proper amount of refrigeration oil. The unit can be factory charged with refrigerant.
6 RTHD-SVX01D-EN
Page 7
General Information
Digit 1-4 Basic product line
RTHD Water-Cooled Series R
Digit 5 Manufacturing Plant
U Water Chiller Business Unit,
Pueblo CO USA
E Epinal Business Unit, Charmes
France
C China Business Unit
Digit 6 - Compressor Frame
B B compressor C C compressor DD compressor
E E compressor
Digit 7 - Compressor Capacity
1 Small capacity for frame 2 Large capacity for frame
3 For 50 hz units
Digit 8 - Unit power supply
A 200V/60Hz/3Ph power C 230V/60Hz/3Ph power D 380V/60Hz/3Ph power R 380V/50Hz/3Ph power T 400V/50Hz/3Ph power U 415V/50Hz/3Ph power F 460V/60Hz/3Ph power
H 575V/60Hz/3Ph power
Digit 9 - Design Specials
X None C Specials denoted elsewhere
S Specials not denoted elsewhere
Digit 10,11 - Design sequence
** First design, etc. increments
when parts are affected for service
purposes.
Digit 12 - Agency listing
X No agency listing U C/UL listing
3 CCC- Chinese Compulsor y Code
Digit 13 - Pressure vessel code
A ASME pressure vessel code L Chinese code
S Special
Digit 14 - Evaporator
B B evaporator C C evaporator D D evaporator E E evaporator F F evaporator
G G evaporator
Digit 15 - Evaporator Capacity
1 Tube count #1 2 Tube count #2 3 Tube count #3 4 Tube count #4 5 Tube count #5
6 Tube count #6
Digit16 - Evap Tube type
A Enhanced Fin Copper
Digit 17 - Evaporator passes
2 2 Pass evaporator 3 3 Pass evaporator
4 4 Pass evaporator
Digit 18 Evaporator water connection
L Left hand evaporator
connection
R Righ t hand evaporator connection
Digit 19 Evaporator connection type
A Standard grooved pipe
S Special
Digit 20 Evaporator water side pressure
L 150 PSI / 10.5 Bar evaporator
water pressure
H 300 PSI / 21 Bar evaporator
water
pressure
Digit 21 - Condenser
BB Frame DD Frame EE Frame FF Frame
GG Frame
Digit 22 - Condenser Capacity
1 Tube count #1 2 Tube count #2 3 Tube count #3 4 Tube count #4
5 Tube count #5
Digit 23 -Condenser tube type
A Enhanced fin - copper B Smooth bore - copper
C Smooth bore - 90/10 Cu/Ni
Digit 24 - Condenser passes
22 Pass
Digit 25 -Condenser water connection
L Left hand condenser
connection
R Right hand condenser connection
Digit 26 -Condenser connection type
A Standard grooved pipe C Marine
S Special
Digit 27 Condenser water side pressure
L 150 PSI / 10.5 Bar condenser
water pressure
H 300 PSI / 21 Bar condens er water
pressure
Digit 28 Condenser Leaving Water Temp
A St andard (<45 deg C)
Digit 29 - Refrigerant specialties
X No refrigerant isolation valves
V Refrigerant isolation valves
Digit 30 - Oil Cooler
X without oil cooler
C with oil cooler
Model Number Coding System
The model numbers for the unit and the compressor are composed of num­bers and letters that represent features of the equipment. Shown in the three tables following are samples of typical unit, compressor, and panel model numbers, followed by the coding system for each.
Each position, or group of positions, in the model number is used to repre­sent a feature. For example, in the first table, position 08 of the unit model number, Unit Voltage, contains the letter “F”. An F in this position means that the unit voltage is 460/60/3.
Unit Model Number
RTHD-SVX01D-EN 7
Page 8
General Information
Digit 31 -Thermal Insulation
X No insulation
Q Factory insulation cold parts
Digit 32 -Sound Attenuator
X No insulation
A Standard attenuator
Digit 33 -Control, Label, and Literature
C Spanish E English
FFrench
Digit 34 -Safety Devices
X Standard
Digit 35 -Shipping Charge
A Full Factory Charge (R134a)
B Nitrogen
Digit 36 -Shipping Package
A No skid (standard) B Shrink Wrap CSkid D Skid + Shrink Wrap
J Special
Digit 37 -Flow Switch
X Without A Evap (NEMA-1) B Evap & Cond (NEMA-1) C Evap (Vapor/NEMA -4)
D Evap & Cond (Vapor/NEMA -4)
Digit 38 -Factory Performance Test
X Without C Witness test D Performance test w/report
S Special
Digit 39 -Starter type
Y Wye-delta closed transition
starter
A Solid State starter
Digit 40, 41, 42 Design RLA (for starter)
*** Selection RLA
Digit 43 Power line connection type
A Terminal block connection for
incoming line(s) B Mechanical disconnect switch D Circuit breaker F High interrupt circuit breaker H Ground fault circuit breaker
J Ground fault high interrupt circuit
breaker
Digit 44 -Enclosure type
F
NEMA 1 - MRLA207
G NEMA 1 - MRLA277 H
NEMA 1 - MRLA300
J NEMA 1 - MRLA364 K
NEMA 1 - MRLA397
L NEMA 1 - MRLA476 M NEMA 1 - MRLA500 N NEMA 1 - MRLA598
P NEMA 1 - MRLA779
Digit 45 -Under/over voltage protection
X No under/over voltage
protection
U Under/over voltage protection
Digit 46 -Unit operator interface
A Dyna-View/English B Dyna-View/French C Dyna-View/Italian D Dyna-View/Spanish E Dyna-View/German F Dyna-View/Dutch G Dyna-View/Trad.Chinese H Dyna-View/Simp.Chinese J Dyna-View/Japanese K Dyna-View/Portugese(Brazil) L Dyna-View/Korean
M Dyna-View/Thai
Digit 47 Remote Interfaces (digital comm)
X No remote digital comm 4 Tracer Comm 4 Interface
5 Tracer Comm 5 LCI-C (LonTalk )
Digit 48 External Chilled Water & Current Limit Setpoint
X None 4 4-20 mA input
2 2-10 Vdc input
Digit 49 External Base Loading
X None 4 4-20 mA input
2 2-10 Vdc input
Digit 50 -Icemaking
X None A Icemaking with relay
B Icemaking without relay
Digit 51 -Programmable Relays
X None
R Programmable Relay
Digit 52 Chilled water reset
X No Sensor (return water CHW
reset standard)
T Chilled water reset - outdoor air
temp
Digit 53 - Control Outputs
X None V Condenser reg. Valve out & %
RLA out
P Condenser Pressure (%HPC) &
% RLA out
D Chiller Delta P & %RLA out
Digit 54 -Refrigerant Monitor Input
X None A 100 ppm / 4-20 maA B 1000 ppm / 4-20 mA C 100 ppm / 2-10 Vdc
D 1000 ppm / 2-10 Vdc
8 RTHD-SVX01D-EN
Page 9
General Information
Compressor Model Number (located on compressor nameplate):
Table 1 Compressor Model Number
Selection Category M/N Digit M/N Code Description of Selection
Compressor Series 1-4 CHHC Semi-Hermetic Heli-Rotor Compressor
Design Control 5 1 Pueblo
Compressor Frame 6 B B Frame
CC Frame
DD Frame
EE Frame
Compressor Capacity 7 1 Smaller capacity (minor)
2 Larger capacity (major)
3 Special 50 Hz capacity
Motor 8 A 200V/60Hz/3
C 230V/60Hz/3
D 380V/60Hz/3
F 460V/60Hz/3 or 400V/50Hz/3
H 575V/60Hz/3
Specials 9 O No Specials
C Specials Denoted Elsewhere
S Uncategorized Special not denoted elsewhere
Design Sequence 10-11 AO 1st Design (Factory Input)
RTHD-SVX01D-EN 9
Page 10
General Information
DynaView or EasyView Interface
Starter/Control Panel
Evaporator
Liquid Level Sensor
Gas Pump
Figure 2 Component Location for Typical RTHD Unit
Evaporator Water Outlet
Oil Separator
Relief Valves
Oil Sump
Condenser Water Outlet
Condenser Water Inlet
10 RTHD-SVX01D-EN
Page 11
General Information
el)
Oil Filter (Cold) Hot Oil Filt er is hidden from view.
Relief Valves
Condenser
Service Valves (With Refrigerant Isolation Valve Option Only)
Oil Separators
Compressor
Discharge Line
Unit Nameplate (On side of starter/control pan
EXVs
Evaporator Water Inlet
Oil Sump (The oil distribution system is located between the condenser and the evaporator.)
Figure 3 Component Location for Typical RTHD Unit (Back View)
RTHD-SVX01D-EN 11
Page 12
General Information
Installation Overview
For convenience, Table 2 summarizes responsibilities that are typically asso­ciated with the RTHD chiller installation process.
Table 2 Installation Responsibility Chart for RTHD Units
Trane-supplied,
Requirement
Rigging Safety chains
Isolation Isolation pads Isolation pads
Electrical Circuit breakers or non-fused
Water piping Flow switches (may be field-
Pressure Relief Relief valves Vent line and flexible connector
Insulation Insulation (optional) Insulation
Trane-installed
disconnects (optional)
Unit-mounted starter Temperature sensor (optional
Trane-supplied, Field-installed
Circuit breaker or non-fused disconnect handle
outdoor air)
Flow switches (may be field­supplied)
Condenser water regulating valve controller (optional: may be field­supplied)
supplied)
Condenser water regulating valve controller (optional: may be field­supplied)
Field-supplied, Field-installed
Clevis connectors - Lifting beam
Circuit breakers or fusible discon­nects (optional)
Terminal lugs
Ground connection(s)
Jumper bars
BAS wiring (optional)
IPC wiring
Control voltage wiring
High condenser pressure interlock wiring
Chilled water pump contactor and wiring
Condenser water pump contactor and wiring
Optional relays and wiring
Thermometers
Water flow pressure gauges
Isolation and balancing valves water piping
Vents and drain valves
Pressure relief valves (for water boxes as required)
Refer to the Installation Mechanical and Installation Electrical sections of this manual for detailed installation instructions.
Locate and maintain the loose parts, e.g. isolators, temperature sensors,
Install the unit on a foundation with flat support surfaces, level within
Install the unit per the instructions outlined in the Mechanical Installation
12 RTHD-SVX01D-EN
flow sensors or other factory-ordered, field-installed options, for installa­tion, as required. Loose parts are located in the starter/control panel.
1/4” (6.35 mm) and of sufficient strength to support concentrated load­ing. Place the manufacturer-supplied isolation pad assemblies under the unit.
Page 13
General Information
section.
Complete all water piping and electrical connections.
NOTE: Field piping must be arranged and supported to avoid stress on the equipment. It is strongly recommended that the piping contractor provide at least 3 feet (914 mm) of clearance between the pre-installation piping and the planned location of the unit. This will allow for proper fit-up upon arrival of the unit at the installation site. All necessary piping adjustments can be made at that time. Refer to the current engineering bulletin for further details on instal­lation.
Where specified, supply and install valves in the water piping upstream and downstream of the evaporator and condenser water boxes, to isolate the shells for maintenance and to balance/trim the system.
Supply and install condenser water control valve(s) per Trane Engineering
Bulletin -Water Cooled Series R
Supply and install flow switches or equivalent devices in both the chilled water and condenser water piping. Interlock each switch with the proper pump starter and CH530, to ensure that the unit can only operate when water flow is established.
Supply and install taps for thermometers and pressure gauges in the water piping, adjacent to the inlet and outlet connections of both the evaporator and the condenser.
Supply and install drain valves on each water box.
Supply and install vent cocks on each water box.
Where specified, supply and install strainers ahead of all pumps and auto­matic modulating valves.
Supply and install refrigerant pressure relief piping from the pressure relief to the atmosphere.
If necessary, supply enough HCFC-134 refrigerant and dry nitrogen (75 psig) for pressure testing.
Start the unit under supervision of a qualified service technician.
Where specified, supply and insulate the evaporator and any other por­tion of the unit, as required, to prevent sweating under normal operating conditions.
For unit-mounted starters, cutouts are provided at the top of the panel for line-side wiring.
Supply and install the wire terminal lugs to the starter.
Supply and install field wiring to the line-side lugs of the starter.
Condenser Water Control.
RTHD-SVX01D-EN 13
Page 14
General Information
Table 3 General Data
Unit Designator (corresponds to digits 6, 7, 14, 15, 21, 22 of unit model number)
D1D1E1 D1F1F2 D1G1G1 D1G2G2 D2D2E2 D2F2F3 D2G3G3
General
Refrigerant Type HFC-134a HFC-134a HFC-134a HFC-134a HFC-134a HFC-134a HFC-134a
Refrigerant Charge (lb (kg))
Oil Charge (gal (l)) 6 (23) 10 (38) 11 (42) 11 (42) 6 (23) 10 (38) 11 (42)
Operating Weight (lb (kg))
Shipping Weight (lb (kg))
Length (in(mm))*
Width (in (mm))*
Height (in (mm))*
Water Storage (gal (l))
Minimum Flow (gpm (l/s)) Water
Minimum Flow (gpm (l/s))Brine
Maximum Flow (gpm (l/s))
Water Storage (gal (l))
Minimum Flow (gpm (l/s))Water
Minimum Flow (gpm (l/s))Brine
Max Flow (gpm (l/s))
475 (216) 625 (284) 700 (318) 700 (318) 475 (216) 625 (284) 700 (318)
15385 (6978) 17537 (7955) 20500 (9299) 21065 (9555) 15570 (7063) 18220 (8265) 21641
(9816)
14443 (6551) 16187 (7342) 18600 (8437) 19107 (8667) 14562 (6605) 16820 (7630) 19508
(8849)
Overall Dimensions
126 (3189) 144 (3669) 146 (3712) 146 (3712) 126 (3189) 144 (3669) 146 (3712)
68 (1717) 68 (1716) 70 (1771) 70 (1771) 68(1717) 68 (1716) 70 (1771)
76 (1717) 76 (1716) 80 (2033) 80 (2033) 76 (1937) 76 (1936) 80 (2033)
Evaporator
69 (261) 102 (386) 136 (515) 144 (545) 74 (280) 107 (405) 159 (602)
415 (26) for 2-pass
275 (17) for 3-pass
498 (31) for 2-pass
330 (21) for 3-pass
1812 (114) for 2-pass
1206 (76) for 3-pass
563 (36) 2-pass
376 (24) 3-pass
676 (43) 2-pass
454 (29) 3-pass
2478 (156) for 2-pass
1655 (104) for 3-pass
505 (35) 3 pass
379 (24) 4 pass
606 (38) 3 pass
454 (29) 4 pass
2218 3 pass
1666 4 pass
550 (35) for 3-pass
411 (26) for 4-pass
660 (42) for 3-pass
492 (31) for 4-pass
2413 (152) for 3-pass
1807 (114) for 4-pass
450 (28) for 2-pass
300 (20) for 3-pass
541 (34) for 2-pass
357 (23) for 3-pass
1980 (125) for 2-pass
1320 (83) for 3-pass
604 (38) for 2-pass
404 (25) for 3-pass
725 (46) for 2-pass
487 (31) for 3-pass
2667 (168) for 2-pass
1780 (112) for 3-pass
622 (39) for 3-pass
466 (29) for 4-pass
747 (47) for 3-pass
557 (35) for 4-pass
2732 (172) for 3-pass
2050 (129) for 4-pass
Condenser (all are 2-pass)
44 (166) 57 (216) 79 (299) 91 (344) 47 (178) 61 (231) 97 (367)
291 (18) 355 (22) 444 (28) 535 (34) 316 (20) 385 (24) 589 (37)
350 (22) 430 (27) 530 (33) 650 (41) 380 (24) 460 (29) 710 (45)
1280 (81) 1560 (98) 1960 (124) 2360 (149) 1390 (88) 1700 (107) 2600 (164)
All weights ±3%, include standard 150 psig water boxes. Operating weights include refrigerant, oil, and water charges. If oil cooler is installed, add 1/4 gal (1 liter) to the oil charge value given for B family units; add 1.0 gal (4 liters) for all other units. Overall dimensions are based on 3-pass evap/2 pass cond and LH/RH water connections. Refer to submittals for exact job conf.
14 RTHD-SVX01D-EN
Page 15
General Information
Table 4 General Data
Unit Designator (corresponds to digits 6, 7, 14, 15, 21, 22 of unit model number)
D2G2G1 D3D2E2 D3F2F3 D3G2G1 D3G3G3 E3D2E2 E3F2F3 E3G2G1 E3G3G3
General
Refrigerant Type HFC-134a HFC-134a HFC-134a HFC-134a HFC-134a HFC-134a HFC-134a HFC-134a HFC-134a
Rfgt Chg (lb (kg)) 700 (318) 475 (216) 625 (284) 700 (318) 700 (318) 475 (216) 625 (284) 700 (318) 700 (318)
Oil Charge (gal (l)) 11 (42) 6 (23) 10 (38) 11 (42) 11 (42) 6 (23) 10 (38) 11 (42) 11 (42)
Operating Weight (lb (kg))
Shipping Weight (lb (kg))
Length (in (mm))
Width (in (mm))
Height (in (mm))
Water Storage (gal (l))
Minimum Flow (gpm (l/s))Water
Minimum Flow (gpm (l/s))Brine
Max Flow (gpm (l/s))
Water Storage (gal (l))
Minimum Flow (gpm (l/s))Water
Min Flow (gpm (l/s))Brine
Max Flow (gpm(l/s))
20700 (9389)
18700 (8482)
15570 (7063)
14562 (6605)
18220 (8265)
16820 (7630)
20700 (9389)
18700 (8482)
21641 (9816)
19508 (8849)
15728 (7134)
14720 (6677)
18356 (8326)
16956 (7695)
20800 (9435)
18800 (85528)
21786 (9882)
19653 (8915)
Overall Dimensions
146 (3712) 126 (3189) 144 (3669) 146 (3712) 146 (3712) 126 (3189) 144 (3669) 146 (3712) 146 (3712)
70 (1771) 68 (1717) 68 (1716) 70 (1771) 70 (1771) 68 (1717) 67 (7716) 70 (1771) 70 (1771)
80 (2033) 76 (1937) 76 (1936) 80 (2033) 80 (2033) 76 (1937) 76 (1936) 80 (2033) 80 (2033)
Evaporator
144 (545) 74 (280) 107 (405) 144 (545) 159 (602) 74 (280) 107 (405) 144 (545) 159 (602)
550 (35) 3-pass
411 (26) 4-pass
660 (42) 3-pass
492 (31) 4-pass
2413 (152) for 3-pass
1807 (114) for 4-pass
405 (28) for 2-pass
300 (19) for 3-pass
541 (34) for 2-pass
357 (23) for 3-pass
1980 (125) for 2-pass
1320 (83) for 3-pass
604 (38) 2-pass
404 (25) 3-pass
725 (46) 2-pass
487 (31) 3-pass
2667 (168) for 2-pass
1780 (112) for 3-pass
550 (35) 3-pass
411 (26) 4-pass
660 (42) 3-pass
492 (31) 4-pass
2413 (152) for 3-pass
1807 (114) for 4-pass
622 (39) 3-pass
466 (29) 4-pass
747 (47) 3-pass
557 (35) 4-pass
2732 (172) for 3-pass
2050 (129) for 4-pass
405 (28) 2-pass
300 (19) 3­pass
541 (34) 2­pass
357 (23) 3-pass
1980 (125) 2-pass
1320 (83) for 3-pass
604 (38) 2-pass
404 (25) 3-pass
725 (46) 2-pass
487 (31) 3-pass
2667 (168) for 2-pass
1780 (112) for 3-pass
550 (35) 3-pass
411 (26) 4-pass
660 (42) 3-pass
492 (31) 4-pass
2413 (152) for 3-pass
1807 (114) for 4-pass
622 (39) 3-pass
466 (29) 4-pass
747 (47) 3-pass
557 (35) 4-pass
2732 (172) for 3-pass
2050 (129) for 4-pass
Condenser (all are 2-pass)
79 (299) 47 (178) 61 (231) 79 (299) 97 (367) 47 (178) 61 (231) 79 (299) 97 (367)
444 (28) 316 (20) 355 (22) 444 (28) 589 (37) 316 (20) 355 (22) 444 (28) 589 (37)
530 (33) 380 (24) 460 (29) 530 (33) 710 (45) 380 (24) 460 (29) 530 (33) 710 (45)
1960 (124) 1390 (88) 1700 (107) 1960 (124) 2600 (164) 1390 (88) 1700 (107) 1960 (124) 2600
(164)
All weights ±3%, include standard 150 psig water boxes. Operating weights include refrigerant, oil, and water charges. If oil cooler is installed, add 1/4 gal (1 liter) to the oil charge value given for B family units; add 1.0 gal (4 liters) for all other units. Overall dimensions are based on 3-pass evap/2 pass cond and LH/RH water connections. Refer to submittals for exact job configurations
RTHD-SVX01D-EN 15
Page 16
Table 5 General Data
Refrigerant Type
Refrigerant Charge (lb (kg))
Oil Charge (gal (l))
Operating Weight (lb (kg))
Shipping Weight (lb (kg))
Length (in (mm))*
Width (in (mm))*
Height (in (mm))*
Water Storage (gal (l))
Minimum Flow (gpm (l/s)) Water
Minimum Flow (gpm (l/s)) Brine
Maximum Flow (gpm (l/s))
(all are 2-pass)
Water Storage (gal (l))
Minimum Flow (gpm (l/s)) Water
Minimum Flow (gpm (l/s)) Brine
Maximum Flow (gpm (l/s))
General Information
Unit Designator (corresponds to digits 6, 7, 14, 15, 21, 22 of unit model number)
C1D6E5 C1D5E4 C1E1F1 C2D4E4 C2D3E3
General
HFC-134a HFC-134a HFC-134a HFC-134a HFC-134a
490 (222) 490 (222) 525 (238) 490 (222) 490 (222)
6 (23) 6 (23) 10 (38) 6 (23) 6 (23)
13397 (6077) 13673 (6202) 15818 (7175) 13672 (6202) 15044 (6824)
12780 (5797) 12973 (5885) 14718 (6675) 12972 (5884) 14002 (6351)
Overall Dimensions
126 (3194) 126 (3194) 144 (3650) 126 (3194) 126 (3194)
68 (1717) 68 (1717) 68 (1715) 68 (1717) 68 (1717)
76 (1937) 76 (1937) 76 (1937) 76 (1937) 76 (1937)
Evaporator
45 (170) 52 (197) 82 (311) 52 (197) 78 (295)
293 (18) for 2-pass
196 (12) for 3-pass
352 (22) for 2-pass
233 (15) for 3-pass
1287 (81) for 2-pass
860 (54) for 3-pass
29 (110) 32 (121) 60 (226) 32 (121) 47 (178)
206 (13) 245 (15) 375 (24) 245 (15) 325 (21)
250 (16) 295 (19) 450 (28) 295 (19) 390 (25)
910 (57) 1080 (68) 1650 (104) 1080 (68) 1420 (90)
351 (21) for 2-pass
234 (15) or 3-pass
422 (27) for 2-pass
281 (18) or 3-pass
1542 (97)or 2-pass
1028 (65) or 3-pass
Condenser
450 (28) for 2-pass
300 (19) for 3-pass
487 (31) for 2-pass
357 (23) for 3-pass
1980 (125) for 2-pass
1320 (83) for 3-pass
351 (21) for 2-pass
234 (15) or 3-pass
422 (27) for 2-pass
281 (18) or 3-pass
1542 (97)or 2-pass
1028 (65) or 3-pass
465 (31) for 2-pass
324 (20) for 3-pass
584 (37) for 2-pass
389 (25) for 3-pass
2131 (134) for 2-pass
1417 (89) for 3-pass
All weights ±3%, include standard 150 psig water boxes. Operating weights include refrigerant, oil, and water charges. If oil cooler is installed, add 1/4 gal (1 liter) to the oil charge value given for B family units; add 1.0 gal (4 liters) for all other units. Overall dimensions are based on 3-pass evap/2 pass cond and LH/RH water connections. Refer to submittals for exact job
configurations
16 RTHD-SVX01D-EN
Page 17
Table 6 General Data
Refrigerant Type
Refrigerant Charge (lb (kg))
Oil Charge (gal (l))
Operating Weight (lb (kg))
Shipping Weight (lb (kg))
Length (in (mm))*
Width (in (mm))*
Height (in (mm))*
Water Storage (gal (l))
Minimum Flow (gpm (l/s)) Water
Minimum Flow (gpm (l/s)) Brine
Maximum Flow (gpm (l/s))
(all are 2-pass)
Water Storage (gal (l))
Minimum Flow (gpm (l/s)) Water
Minimum Flow (gpm (l/s)) Brine
Maximum Flow (gpm (l/s))
General Information
Unit Designator (corresponds to digits 6, 7, 14, 15, 21, 22 of unit model number)
C2F2F3 B1B1B1 B1C1D1 B2B2B2 B2C2D2
General
HFC-134a HFC-134a HFC-134a HFC-134a HFC-134a
700 (318) 410 (186) 490 ((222) 410 (186) 490 ((222)
11 (42) 4.5 (17.0) 4.5 (17.0) 4.5 (17.0) 4.5 (17.0)
17560 (7965) 9867 (4476) 10554 (4787) 10019 (4544) 10653 (4832)
16168 (7334) 9292 (4215) 9837 (4462) 9402 (4265) 9953 (4515)
Overall Dimensions
144 (3658) 124 (3160) 143 (3624) 124 (3160) 143 (3624)
68 (1727) 64 (1634) 64 (1634) 64 (1634) 64 (1634)
76 (1930) 73 (1849) 73 (1849) 73 (1849) 72 (1849)
Evaporator
107 (405) 41 (155) 55 (208) 45 (170) 58 (220)
604 (38) for 2-pass
404 (25) for 3-pass
725 (46) for 2-pass
487 (31) for 3-pass
2667 (168) for 2-pass
1780 (112) for 3-pass
61 (231) 28 (106) 31 (117) 29 (110) 34 (129)
355 (22) 193 (12) 193 (12) 212 (13) 212 (13)
460 (29) 230 (15) 230 (15) 255 (16) 255 (16)
1700 (107) 850 (54) 850 (54) 935 (59) 935 (59)
253 (16) for 2-pass
168 (11) for 3-pass
303 (19) for 2-pass
200 (13) for 3-pass
1104 (70) for 2-pass
736 (46) for 3-pass
Condenser
320 (18) for 2-pass
213 (12) for 3-pass
346 (22) for 2-pass
254 (16) for 3-pass
1412 (89) for 2-pass
941 (59) for 3-pass
288 (22) for 2-pass
192 (15) for 3-pass
346 (22) for 2-pass
233 (15) for 3-pass
1266 (80) for 2-pass
844 (53) for 3-pass
347 (22) for 2-pass
232 (15) for 3-pass
375 (24) for 2-pass
276 (17) for 3-pass
1531 (97) for 2-pass
1022 (65) for 3-pass
All weights ±3%, include standard 150 psig water boxes. Operating weights include refrigerant, oil, and water charges. If oil cooler is installed, add 1/4 gal (1 liter) to the oil charge value given for B family units; add 1.0 gal (4 liters) for all other units. Overall dimensions are based on 3-pass evap/2 pass cond and LH/RH water connections. Refer to submittals for exact job configurations
RTHD-SVX01D-EN 17
Page 18
General Information
18 RTHD-SVX01D-EN
Page 19
Installation Mechanical
Storage
If the chiller is to be stored more than one month prior to installation, observe the following precautions:
Do not remove the protective coverings from the electrical panel.
Store the chiller in a dry, vibration-free, secure area.
At least every three months, attach a gauge and manually check the pres­sure in the refrigerant circuit. If the refrigerant pressure is below 71 psig
o
at 70
F (or 46 psig at 50oF), call a qualified service organization and the
appropriate Trane sales office.
NOTE: Pressure will be approximately 20 psig if shipped with the optional nitrogen charge.
Location Requirements
Noise Considerations
Refer to Trane Engineering Bulletin -Series R Installation Guide.
for sound consideration applications.
Locate the unit away from sound-sensitive areas.
Install the isolation pads under the unit. Refer to “Unit Isolation.”
Install rubber vibration isolators in all water piping.
Use flexible electrical conduit for final connection to the CH530.
Seal all wall penetrations.
Chiller Sound Ratings and
NOTE: Consult an acoustical engineer for critical applications.
Foundation
Provide rigid, non-warping mounting pads or a concrete foundation of suffi­cient strength and mass to support the chiller operating weight (including completed piping and full operating charges of refrigerant, oil and water). Refer to Table 7 for unit operating weights.
Once in place, level the chiller within 1/4” (6.35 mm) over its length and width.
The Trane Company is not responsible for equipment problems resulting from an improperly designed or constructed foundation.
Vibration Eliminators
Provide rubber boot type isolators for all water piping at the unit.
Provide flexible conduit for electrical connections to the unit.
Isolate all pipe hangers and be sure they are not supported by main struc­ture beams that could introduce vibration into occupied spaces.
Make sure that the piping does not put additional stress on the unit.
NOTE: Do not use metal braided type eliminators on the water piping. Metal braided eliminators are not effective at the frequencies at which the unit will operate.
RTHD-SVX01D-EN 19
Page 20
Installation Mechanical
Clearances
Provide enough space around the unit to allow the installation and mainte­nance personnel unrestricted access to all service points. Refer to submittal drawings for the unit dimensions.
Allow adequate clearance for condenser and compressor servicing. A mini­mum of three feet is recommended for compressor service and to provide sufficient clearance for the opening of control panel doors. Refer to Figure 4 for minimum clearances required for condenser tube service. In all cases, local codes will take precedence over these recommendations.
NOTE: Required vertical clearance above the unit is 36” (914.4 mm). There should be no piping or conduit located over the compressor motor.
If the room configuration requires a variance to the clearance dimensions, contact your Trane sales office representative.
3'- 0" (914 mm) Servic e Clearance
3'- 0" (914 mm) Servic e Clearance (Opposi te Tube Removal)
Tu be Removal Clear ance ( Eit he r E nd )
EDE, DDE, CDE, BBB: 108" (27 43 m m)
E FF, DF F, CEF , BCD : 126" (32 00 m m)
EGG, DGG,CGG: 130" (33 02 m m)
36. 5" (927 mm) Radius
~
Swing
105
26.4" (671 mm) Radius
3'- 0" (914 m m) Se rvice Clearance
Figure 4 Recommended Operating and Service Clearances
20 RTHD-SVX01D-EN
3'-0" (914 mm) Ser vice Cleara nce
Page 21
Installation Mechanical
NOTE: Maximum clearances are given. Depending on the unit configu­ration, some units may require less clearance than others in the same category.
Ventilation
The unit produces heat even though the compressor is cooled by the refriger­ant. Make provisions to remove heat generated by unit operation from the equipment room. Ventilation must be adequate to maintain an ambient tem­perature lower than 122
Vent the evaporator, condenser and compressor pressure relief valves in accordance with all local and national codes. Refer to Table 11.
Make provisions in the equipment room to keep the chiller from being exposed to freezing temperatures (32
Water Drainage
Locate the unit near a large capacity drain for water vessel drain-down during shutdown or repair. Condensers and evaporators are provided with drain con­nections. Refer to “Water Piping.” All local and national codes apply.
Access Restrictions
Door clearances for the RTHD units are given in Figure 5. Refer to the unit submittals for specific “per unit” dimensional information.
Moving and Rigging
The Model RTHD chiller should be moved by lifting at designated lift points only. Refer to Figure 6 and Table 7 for typical unit lifting and operating weights. Refer to the rigging diagram that ships with each unit for specific “per unit” weight data.
o
F (50oC).
o
F/0oC).
WARNING Heavy Equipment!
Always use lifting equipment with a capacity exceeding unit lifting weight by an adequate safety factor. (+10%). Follow the procedures and diagrams in this manual and in the submittal. Failure to do so can result in death or serious injury.
RTHD-SVX01D-EN 21
Page 22
Installation Mechanical
C
D
B
=C.G.
X
A
Z
Y
Figure 5 Unit Weights and Dimensions for Rigging
Table 7 Unit Weights (lb (kg))
Location (points)
Unit Designator *
E3G3G3 5339
E3G2G1 5158
E3F2F3 4781
E3D2E2 3796
*Unit Designator (corresponds to digits 6, 7, 14, 15, 21, 22 of unit model number)
ABCD
(2422)
(2340)
(2169)
(1722)
4455 (2021)
4304 (1952)
3582 (1625)
2834 (1285)
4374 (1984)
4226 (1917)
3750 (1701)
3300 (1497)
22 RTHD-SVX01D-EN
5486 (2488)
5300 (2404)
4851 (2200)
4789 (2172)
Page 23
Installation Mechanical
Table 7 Unit Weights (lb (kg))
Location (points)
Unit Designator *
D3G3G3 5320
D3G2G1 5085
D3F2F3 4737
D3D2E2 3754
D2G3G3 5320
D2 G2G1 5085
D2F2F3 4737
D2D2E2 3754
D1G1G1 4981
D1G2G2 5216
D1F1F2 4526
D1D1E1 3728
C2F2F3 4649
C2D3E3 3612
C2D4E4 3374
C1E1F1 4205
C1D5E4 3375
C1D6E5 3330
B2C2D2 3162
B2B2B2 2522
B1C1D1 3136
B1B1B1 2495
ABCD
(2413)
(2307)
(2149)
(1703)
(2413)
(2307)
(2149)
(1703)
(2259)
(2366)
(2053)
(1691)
2109
(1638)
(1530)
(1907)
(1531)
(1510)
(1510)
(1144)
(1422)
(1132)
4451 (2019)
4255 (1930)
3563 (1616)
2818 (1278)
4451 (2019)
4255 (1930)
3563 (1616)
2818 (1278)
4148 (1882)
4344 (1970)
3452 (1566)
2758 (1251)
3496 1586
2738 (1242)
2479 (1124)
3046 (1382)
2479 (1124)
2430 (1102)
2297 (1042)
1996 (905)
2264 (1027)
1969 (893)
4327 (1963)
4136 (1876)
3722 (1688)
3269 (1483)
4327 (1963)
4136 (1876)
3722 (2176)
3269 (1483)
4041 (1833)
4231 (1919)
3615 (1640)
3236 (1468)
4707 2135
3148 (1428)
2876 (1305)
3196 (1450)
2876 (1305)
2825 (1281)
1767 (802)
1926 (874)
1739 (789)
1901 (862)
5140 (2331)
5171 (2346)
4797 (2176)
4720 (2141)
5140 (2331)
5171 (2346)
4797 (2176)
4720 (2141)
5076 (2302)
5316 (2411)
4594 (2084)
4694 (2129)
4707 2135
4503 (2043)
4243 (1925)
4271 (1937)
4243 (1925)
4195 (1903)
2726 (1237)
2958 (1342)
2698 (1224)
2928 (1328)
RTHD-SVX01D-EN 23
*Unit Designator (corresponds to digits 6, 7, 14, 15, 21, 22 of unit model number)
Page 24
Installation Mechanical
Table 8 Center of Gravity (in (mm))
Unit Configuration* X Y Z
E3G3G3 30.8 63.81 37.62
(782.32) (1621) (956)
E3G2G1 30.8 63.55 38.70
(782.32) (1614) (983)
E3F2F3 27.64 63.46 38.33
(702.056 (1612) (974)
E3D2E2 25.9 60.05 40.5
(658) (1525) (1029)
D3G3G3 30.85 63.48 37.44
(784) (1612) (951)
D3G2G1 30.58 68.56 37.79
(777) (1741) (960)
D3F2F3 27.7 63.4 38.14
(704) (1610) (969)
D3D2E2 25.97 59.95 40.31
(660) (1523) (1024)
D2G3G3 30.85 63.48 37.44
(784) (1612) (951)
D2G2G1 30.58 68.56 37.79
(777) (1741) (960)
D2F2F3 27.7 63.4 38.14
(704) (1610) (969)
D2D2E2 25.97 59.95 40.31
(660) (1523) (1024)
D1G1G1 30.58 68.56 37.79
(777) 1741) (960)
D1G2G2 30.77 63.55 37.72
(782) (1614) (958)
D1F1F2 27.92 63.47 38.7
(709) (1612) (9833)
D1D1E1 25.91 60 40.47
(658) (1524) (1028)
C2F2F3 27.92 63.47 38.7
(709) (1612) (9833)
C2D3E3 26.13 59.74 40.08
(664) (1517) (1018)
C2D4E4 26.13 59.74 40.08
(664) (1517) (1018)
C1E1F1 26.36 63.49 40.95
(670) (1613) (1040)
C1D5E4 26.13 59.74 40.08
(664) (1517) (1018)
C1D6E5 26.13 59.74 40.08
(664) (1517) (1018)
B2C2D2 22.4 58.29 33.51
(569) (1481) (851)
B2B2B2 22.88 58.11 35.43
(581) (1476) (900)
B1C1D1 22.32 58.23 33.65
(567) (1479) (855)
B1B1B1 22.84 58.13 35.59
(580) (1477) (904)
Designator corresponds to digits 6, 7, 14, 15, 21, 22 of model number
24 RTHD-SVX01D-EN
Page 25
Installation Mechanical
Lifting Procedure
CAUTION Equipment Damage!
Never use a forklift to move the unit. The skid is not designed to support the unit at any one point and using a forklift to move the equipment may cause unit damage. Always position the lifting beam so that cables do not contact the unit. Failure to do so may result in unit damage.
NOTE: If absolutely necessary, the chiller can be pushed or pulled across a smooth surface if it is bolted to wood shipping mounts.
WARNING Shipping Mounts!
Do not use the threaded holes in the compressor to lift or assist in lifting the unit. They are not intended for that purpose and could create a dangerous situation. Do not remove the wood mounts until the unit is in its final location. Removal of wood shipping mounts prior to unit final locating could result in death or serious injury or equipment damage.
1. When the unit is at its final location, remove the shipping bolts that secure the unit to the wood base mounts.
2. Rig the unit properly and lift from above or jack the unit (alternate moving method). Use the points shown on the rigging diagram that ships with the unit as shown in Figure 6. Remove the base mounts.
3. Install clevis connectors in lifting holes provided on the unit. Attach lifting chains or cables to clevis connectors as shown in Figure 6. Each cable alone must be strong enough to lift the chiller.
RTHD-SVX01D-EN 25
Page 26
Installation Mechanical
Table 9 Rigging
Unit Configuration*
E3G3G3 3658 3353 1621 20 661 610
E3G2G1 3658 3353 1621 20 661 610
E3F2F3 3658 3353 1612 29 615 610
E3D2E2 3048 2743 1525 116 612 610
D3G3G3 3658 3353 1612 99 654 610
D3G2G1 3658 3353 1612 99 654 610
D3F2F3 3658 3353 1610 101 617 610
D3D2E2 3048 2743 1523 188 614 610
D2G3G3 3658 3353 1612 99 654 610
D2G2G1 3658 3353 1612 99 654 610
D2F2F3 3658 3353 1610 101 617 610
D2D2E2 3048 2743 1523 188 614 610
D1G2G2 3658 3353 1614 97 661 610
D1G1G1 3658 3353 1612 99 654 610
D1F1F2 3658 3353 1612 99 622 610
D1D1E1 3048 2743 1524 187 612 610
C2F2F3 3658 3353 1610 101 617 610
C2D3E3 3048 2743 1517 225 618 610
C2D4E4 3048 2743 1523 219 584 610
Dimension (mm (in))
ABCDE F
(144.02) (132.01) (63.82) (0.79) (26.02) (24.02)
(144.02) (132.01) (63.82) (0.79) (26.02) (24.02)
(144.02) (132.01) (63.46) (1.14) (24.21) (24.02)
(120.00) (107.99) (60.04) (4.57) (24.09) (24.02)
(144.02) (132.01) (63.46) (3.90) (25.75) (24.02)
(144.02) (132.01) (63.46) (3.90) (25.75) (24.02)
(144.02) (132.01) (63.39) (3.98) (24.29) (24.02)
(120.00) (107.99) (59.96) (7.40) (24.17) (24.02)
(144.02) (132.01) (63.46) (3.90) (25.75) (24.02)
(144.02) (132.01) (63.46) (3.90) (25.75) (24.02)
(144.02) (132.01) (63.39) (3.98) (24.29) (24.02)
(120.00) (107.99) (59.96) (7.40) (24.17) (24.02)
(144.02) (132.01) (63.54) (3.82) (26.02) (24.02)
(144.02) (132.01) (63.46) (3.90) (25.75) (24.02)
(144.02) (132.01) (63.46) (3.90) (24.49) (24.02)
(120.00) (107.99) 60.00) (7.36) (24.09) (24.02)
(144.02) (132.01) 63.39) (3.98) (24.29) (24.02)
(120.00) (107.99) (59.72) (8.86) (24.33) (24.02)
(120.00) (107.99) (59.96) (8.62) (22.99) (24.02)
26 RTHD-SVX01D-EN
*Designator corresponds to digits 6, 7, 14, 15, 21, 22 of model number
Page 27
Installation Mechanical
Table 9 Rigging
Unit Configuration*
C1E1F1 3658 3353 1613 129 624 610
C1D5E4 3048 2743 1523 219 584 610
C1D6E5 3048 2743 1524 218 582 610
B2C2D2 3658 3353 1481 93 523 610
B2B2B2 3048 2743 1476 98 535 610
B1C1D1 3658 3353 1479 95 521 610
B1B1B1 3048 2743 1447 97 534 610
*Designator corresponds to digits 6, 7, 14, 15, 21, 22 of model number
Dimension (mm (in))
ABCDE F
(144.02) (132.01) (63.50) (5.08) (24.57) (24.02)
(120.00) (107.99) (59.96) (8.62) (22.99) (24.02)
(120.00) (107.99) (60.00) (8.58) (22.91) (24.02)
(144.02) (132.01) (58.31) (3.66) (20.59) (24.02)
(120.00) (107.99) (58.11) (3.86) (21.06) (24.02)
(144.02) (132.01) (58.23) (3.74) (20.51) (24.02)
(120.00) (107.99) (56.97) (3.82) (21.02) (24.02)
RTHD-SVX01D-EN 27
Page 28
Installation Mechanical
NOTES:
1. LIFTING CABLES(C HAIN S)WILL NOT BE THE SAMEL EN GTH. ADJUSTT OKEEP UNITL EVEL WHILEL IFTING.
2. ATTA CH ANTI- ROLLI NG CABL E (CH AIN) A S SHOWN WITHO UT T ENSION. NOT AS A LIFTING CABLE,BUT TO PREVENTU NIT FROM ROLLING.
3. DO NO T FORK LIFT UNI T.
4. WEIGHT S ARE T YPICAL FOR UNIT S WI TH R-13 4a CHARG E.
5. IFU NIT IS DISASSEMBLED, SEE SERVICEBULLETIN FORLIFTINGANDRIGGINGOFCOMPONENTS.
WARNING: DO NOT USE CABLES(CHAINS) OR SLINGSEXCEPT AS SHOWN. OTHER LIFTING ARRANGEMENTSMAY CAUSE EQUIPMENTD AMAG E OR SERIOUS P ERSONAL I NJURY.
F(MIN)
E
ANTI-ROLLING CABLE
ANTI-ROLLI NGCABLE
A
B
C
D
EYELET OR M16INTERNALT HREAD
ANTI-ROLLINGCABLE
COND EVAP
Figure 6 Lifting the Unit
LIFTING HOLES
44,5 MM TYP
n
STARTER C ONTROLS
UNIT M ODEL NUMBER LOCATI ON
EVAP
4. Attach cables to lifting beam. Total lifting weight, lifting weight distribution and required lifting beam dimensions are shown in the rigging diagram shipped with each unit and in Figure 6. The lifting beam crossbar must be positioned so the lifting cables do not contact unit piping or electrical panel enclosure.
WARNING Anti- rotation Strap!
Connect an anti-rotation strap between the lifting beam and compressor before lifting unit. Failure to do so may result in death or serious injury should a lifting cable fail.
COND
5. Connect an anti-rotation strap or cable loosely between the lifting beam
NOTE: The anti-rotation strap is not a lifting chain, but a safety device to ensure that the unit cannot tilt during lifting.
28 RTHD-SVX01D-EN
and the threaded coupling or eyelet provided at the top of the compres­sor. Use an eyebolt or clevis to secure the strap at the coupling or eyelet.
Page 29
Installation Mechanical
Alternate Moving Method
6. If it is not possible to rig from above as shown in the figures, the unit may also be moved by jacking each end high enough to move an equipment dolly under each tube sheet support. Once securely mounted on the dol­lies, the unit may be rolled into position.
Isolation Pads
The elastomeric pads shipped (as standard) are adequate for most instal­lations. For additional details on isolation practices, refer to
Trane Engineering Bulletin -Series R tion Guide., or consult an acoustical engineer for sound-sensitive installa-
tions.
7. During final positioning of the unit, place the isolation pads under the evaporator and condenser tube sheet supports as shown in Figure 7. Level the unit as described in the next main paragraph.
NOTE: Durometer values for isolator pads are a measure of resilience. See
Figure 7.
Note: Level unit to 1/4” (6.35 mm) across width and length
Chiller Sound Ratings and Installa-
B
A (hidden leg)
Durometer: 50 +/-5
0.31
Figure 7 Isolator Pad Placement
Typical Elastomeric Isolation Pad
D
C
Durometer: 40 +/-5 Durometer: 55 +/-10
Pads extend the full width of legs
0.31
0.31
RTHD-SVX01D-EN 29
Page 30
Oil Separator
Installation Mechanical
8. The unit is shipped with four spacers (only three on B family) on the com­pressor mount that protect the compressor isolation pads during shipping and in handling. Remove these spacers (Figure 8) before the unit is oper­ated.
9. Remove the shipping brackets from the bottom sides of the oil separa­tor(s) (see Figure 8).
NOTE: Once shipping bracket(s) is removed, the oil separator is only supported by the discharge line.
Compressor Housing
M20 bolt
Shipping Bracket
Figure 8 Oil Separator with Shipping Bracket and Compressor Shipping Spacer
Unit Leveling
NOTE: The electrical panel side of the unit is designated as the “front” of the unit.
1. Check unit level end-to-end by placing a level on the top surface of the evaporator shell.
2. If there is insufficient surface available on the top of the evaporator shell, attach a magnetic level to the bottom of the shell to level the unit. The unit should be level to within 1/4” (6.35 mm) over its length.
3. Place the level on the evaporator shell tube sheet support to check side­to-side (front-to-back) level. Adjust to within 1/4” (6.35 mm) of level front­to-back.
NOTE: The evaporator MUST be level for optimum heat transfer and unit performance.
4. Use full-length shims to level the unit.
Remove 4 Shipping
Spacers (only 3 on B family)
30 RTHD-SVX01D-EN
Page 31
Installation Mechanical
Water Piping
Piping Connections
CAUTION Equipment Damage!
To prevent equipment damage, bypass the unit if using an acidic flushing agent.
Make water piping connections to the evaporator and condenser. Isolate and support piping to prevent stress on the unit. Construct piping according to local and national codes. Insulate and flush piping before connecting to unit.
Use grooved pipe connectors for all water piping connections. Evaporator and condenser water inlet and outlet sizes and locations are shown by the unit submittals and in Figure 9 through Figure 14. The designation in the tables corresponds to the compressor frame code followed by the evaporator shell code followed by the condenser shell code as given in the unit model num­ber, digits 6, 7, 14, 15, 21 and 22. Table 10 gives additional water connection information.
Reversing Water Boxes
All water boxes may be reversed end-for-end. Do not rotate water boxes. Remove the sensors from the wells before removing the water box. Com­plete the water box switch and replace the sensors. See Figure 9 through Fig-
ure 14 for correct orientation of the water inlet and outlet.
If the water boxes are reversed, be sure to properly rewire the water temper­ature sensors in the control panel.
NOTE: Be certain to replace water boxes right-side-up to maintain proper baffle orientation. Use new o-rings.
RTHD-SVX01D-EN 31
Page 32
Installation Mechanical
75.0 [1905 mm]
OUT
28.59 [726mm]
EVAPORATOR
8. 38 [ 21 3 mm ]
8. 38 [ 21 3 mm ]
27.34 [694mm]
15.09 [383 mm]
8.94 [227 mm]
Standard 3Pass
107.66 [2734 mm]
6.87 [174 mm]
2 Pass Evap Connection Configuration
(left or right hand) Depending on Water Inlet
IN
13.84 [351 mm]
4.9 7 [ 126 m m] fo r 150 ps i
5.4 7 [ 139 m m] fo r 300 ps i
EVAPORATOR
10.23[260mm]
CONDENSER
70.30 [1786 mm]
OUT
23.50[597mm]
9.5 0 [ 241 m m]
13.35 [339 mm]
EVAP
IN
64.34 [1634 mm]
COND
IN
11.50[292mm]
13.50 [343 mm]
97.51 [2477 mm]
8.00 [203 mm]f or150 psi
8.50 [216 mm]f or300 psi
OIL S UM P
0.08 [2 mm]
Figure 9 Condenser and Evaporator Water Connections -BBB
32 RTHD-SVX01D-EN
Page 33
Installation Mechanical
(left or right hand) Depending on Water Inlet
75.0 [1905 mm]
8. 38 [ 21 3 m m]
OUT
28.59[726 mm]
27.34 [694 mm]
15.09 [383 mm]
8.94 [227 mm]
EV APO RAT OR
7.87 [174 mm]
St anda rd 3 Pa ss
125.91 [3198 mm]
IN
4.97 [126 mm] for 150 psi
8.38 [213 mm]
13.84[351mm]
5.47 [139 mm] for 300 psi
EV APO RAT OR
2 Pass Evap Connection Configuration
0.01[0 mm]
CONDENS ER
9.50 [241 mm]
70. 80 [ 1798 m m]
IN
13.35[339mm]
118. 00 [ 2997 m m]
EVAP
OIL SUM P
Figure 10 Condenser and Evaporator Water Connections -BCD
RTHD-SVX01D-EN 33
COND
IN
OUT
23.50 [597 mm]
64.34 [1634 mm]
13.50 [343mm]
11.50[292mm]
8.00 [203 mm]f or150 psi
8.50 [216 mm]f or300 psi
7.91 [201mm]
Page 34
Installation Mechanical
77.4 [1966 mm]
9.06 [230 mm]
30.1 3 [76 5 mm ]
OUT
St anda rd 3 Pa ss
EVAPORATOR
9. 06 [2 30 mm]
125. 91 [31 98 mm]
6.00 [153 mm] for 150 psi
IN
14.8 8 [37 8 m m]
6.50 [165 mm] for 300 psi
29.63 [753 mm]
EVAPORATOR
15.38 [391 mm]
9.42 [239 mm]
7.67 [195 mm]
2 Pass Evap Connection Configuration
(left or right hand) Depending on Water Inlet
3.07 [78 mm]
OIL SUM P
118. 00 [299 7 m m]
14.50 [ 368 mm]
73.44 [1865 mm]
OUT
25.8 8 [65 7 m m]
5.29 [134 mm]
IN
COND EVAP
IN
67.5 4 [17 15 mm]
14.13 [359 mm]
12.49[317mm]
CONDENSER
4. 84 [1 23 mm]
8. 00 [2 03 mm] for 1 50 ps i
8. 50 [2 16 mm] for 3 00 ps i
Figure 11 Condenser and Evaporator Water Connections - CEF
34 RTHD-SVX01D-EN
Page 35
Installation Mechanical
77.4 [ 196 6 mm]
OUT
30.13 [765 mm]
EVAPORATOR
8. 84 [2 25 m m]
9. 06 [2 30 m m]
Standard 3 Pass
107. 66 [273 4 mm ]
IN
14.88[378mm]
29.63 [753 mm]
15.38 [391 mm]
9.50 [241 mm]
7.67 [195 mm]
2 Pass Evap Connection Configuration
(left or right hand) Depending on Water Inlet
6. 00 [1 53 m m] fo r 15 0 p si
6. 50 [1 66 m m] fo r 30 0 p si
EVAPORATOR
7.59 [193 mm]
Figure 12 Condenser and Evaporator Water Connections - CDE/DDE/EDE
RTHD-SVX01D-EN 35
73. 44 [18 65 m m]
IN
IN
OUT
25.88[657mm]
5. 29 [134 mm]
14.5 0 [36 8 mm ]
EVAP
COND
67. 58 [17 17 m m]
12.49[317mm]
14.1 3 [35 9 m m]
97. 50 [24 77 mm]
8.0 0 [20 3 mm] for 1 50 ps i
8.5 0 [21 6 mm] for 3 00 ps i
OIL S UMP
CONDENSER
2.56 [65 m m]
Page 36
Installation Mechanical
77.0 [1956m m]
9.38 [238 mm]
OU T
EVA POR ATO R
9. 16 [2 33 mm]
28.43 [722 mm]
Standard 3 Pass
125. 91 [319 8 m m]
IN
11.4 3 [29 0 m m]
6. 15 [1 56 mm] for 1 50 ps i
27.30 [693 mm]
12.55 [319 mm]
10.88 [276 mm]
8.71 [221 mm]
2 Pass Evap Connection Configuration
(left or right hand) Depending on Water Inlet
EVAPORATOR
6. 65 [1 69 mm] for 3 00 ps i
OIL S UMP
Figure 13 Condenser and Evaporator Water Connections - DFF/EFF/CFF
36 RTHD-SVX01D-EN
73. 52 [18 67 m m]
IN
OUT
25.88[657mm]
3.59 [91 mm]
16.20[411mm]
CONDENSER
EVAP
IN
COND
14.13[359mm]
118.00 [2997 mm]
67.54[1716 mm]
4.87 [124 mm] 3.0 4 [77 m m]
12.49[317mm]
8.0 0 [20 3 mm ] for 150 ps i
8.5 0 [21 6 mm ] for 300 ps i
Page 37
Installation Mechanical
9.35 [238 mm]
81.0 [205 7 mm]
]m
]mm
m 1 2 3[
4 1
4
3[
6. 2
8
1
3. 2 1
]m
m 2 13 [ 92 . 21
2 Pass Evap Connection Configuration
(left or right hand) Depending on Water Inlet
EVAPORATOR
OUT
Standard 4 Pass
125.91 [3198 mm]
IN
7. 62 [ 194 mm ] fo r 30 0 ps i
7. 25 [ 184 mm ] fo r 15 0 ps i
]mm 928[ 46.23
EVAP OR ATOR
0.67 [17 mm]
11.39 [289 mm]
10. 88 [27 6 mm ]
33.89 [861 mm]
OILSUMP
77.29 [1963 mm]
18.63 [473mm]
22.50 [571mm]
1.18 [30 mm]
CONDENSER
EVAP
OUT
IN
COND
IN
OUT
129.80 [3297 mm]
69.72 [1771 mm]
Figure 14 Condenser and Evaporator Water Connections - DGG/EGG
RTHD-SVX01D-EN 37
3.22 [82 mm]
29.02[737mm]
14.73 [374mm]
14. 70 [37 3 mm ]
9.88 [251 mm]f or300 psi
9.13 [232 mm]f or150 psi
Page 38
Installation Mechanical
Table 10 Evaporator and Condenser Data
Compress or Frame Code (Digit 6,7 of Model No.)
E3 D2 26.5 8 8 - E2 22.0 8
D3 D2 26.5 8 8 - E2 22.0 8
D2 D2 26.5 8 8 - E2 22.0 8
D1 D1 26.5 8 8 - E1 22.0 8
C2 D3 26.5 8 8 - E3 22.0 8
C1 D6 26.5 8 8 - E5 22.0 8
B2 C2 23.0 - 6 - D2 18.75 6
B1 C1 23.0 - 6 - D1 18.75 6
Evap Shell Code (Digits 14, 15 of Model No.)
F2 29.0 8 8 - E2 22.0 8
G2 33.5 - 10 8 G1 25.75 8
G3 33.5 - 10 8 G3 25.75 8
F2 29.0 10 8 - F3 22.0 8
G2 33.5 - 10 8 G1 25.75 8
G3 33.5 - 10 8 G3 25.75 8
F2 29.0 10 8 - F3 22.0 8
G2 33.5 - 10 8 G1 25.75 8
G3 33.5 - 10 8 G3 25.75 8
F1 29.0 10 8 - F2 22.0 8
G1 33.5 - 10 8 G1 25.75 8
G2 33.5 - 10 8 G2 25.75 8
D4 26.5 8 8 E4 22.0 8
F2 29.0 10 8 - F3 22.0 8
D5 26.5 8 8 - E4 22.0 8
E1 33.5 8 8 - F1 22.0 8
B2 23.0 - 6 - B2 18.75 6
B1 23.0 - 6 - B1 18.75 6
Evap. Shell Diameter (in)
Nominal Connector size (NPS)*
2­Pass3-Pass4-Pass 2-Pass
Cond Shell Code (Digits 21,22 of Model No.)
Cond. Shell Diameter (in)
Nom. Conn. Size (NPS)*
Metric Conversion is:
6 NPS = 150 mm nominal
8 NPS = 200 mm nominal 10 NPS = 250 mm nominal
38 RTHD-SVX01D-EN
Page 39
Installation Mechanical
Water Pressure Drop Data
Evaporator Pressure Drop
G Frame - 3 Pass
50
45
40
35
O)
2
30
25
20
Delt-P (Ft H
15
10
5
0
0 500 1000 1500 2000 2500 3000
Flow (GPM)
G2
G1
Evaporator Pressure Drop
G Frame - 4 Pass
70
G2
G1
O)
2
60
50
40
G3
G3
30
Delt-P (Ft H
20
10
0
0 500 1000 1500 2000
RTHD-SVX01D-EN 39
Flow (GPM)
Page 40
Installation Mechanical
Evaporator Pressure Drop
F Frame - 2 Pass
35
30
25
O)
2
20
15
Delt-P (Ft H
10
5
0
0 500 1000 1500 2000 2500 3000
Flow (GPM)
F1
F2
Evaporator Pressure Drop
F Frame - 3 Pass
50
45
40
35
O)
2
30
25
20
Delt-P (Ft H
15
10
5
0
0 500 1000 1500 2000
Flow (GPM)
F1
F2
40 RTHD-SVX01D-EN
Page 41
Installation Mechanical
Evaporator Pressure Drop
E Frame - 2 Pass
40
35
30
O)
2
25
20
15
Delt-P (Ft H
10
5
0
0 500 1000 1500 2000
Flow (GPM)
Evaporator Pressure Drop
E Frame - 3 Pass
50
45
40
35
O)
2
30
25
20
Delt-P (Ft H
15
10
5
0
0 200 400 600 800 1000 1200 1400
Flow (GPM)
E1
E1
RTHD-SVX01D-EN 41
Page 42
Installation Mechanical
Evaporator Pressure Drop
D Frame - 2 Pass
40
35
D4 & D5
D6
O)
2
30
25
20
15
Delt-P (Ft H
10
5
0
0 500 1000 1500 2000 2500
Flow (GPM)
D1
D2
D3
Evaporator Pressure Drop
D Frame - 3 Pass
45
D4 & D5
D6
O)
2
40
35
30
25
20
15
Delt-P (Ft H
10
5
0
0 200 400 600 800 1000 1200 1400
Flow (GPM)
D1
D2
D3
42 RTHD-SVX01D-EN
Page 43
Installation Mechanical
Evaporator Pressure Drop
C Frame - 2 Pass
35
30
25
O)
2
20
15
Delt-P (Ft H
10
5
0
0 500 1000 1500
Flow (GPM)
C1
Evaporator Pressure Drop
C Frame - 3 Pass
50
45
40
35
O)
2
30
25
20
Delt-P (Ft H
15
10
5
0
0 200 400 600 800 1000
Flow (GPM)
C1
C2
C2
RTHD-SVX01D-EN 43
Page 44
Installation Mechanical
Evaporator Pressure Drop
B Frame - 3 Pass
45
40
35
O)
30
2
25
20
15
Delt-P (Ft H
10
5
0
0 200 400 600 800 1000
Flow (GPM)
B1
B2
Evaporator Pressure Drop
B Frame - 2 Pass
30
25
O)
20
2
15
10
Delt-P (Ft H
5
0
0 200 400 600 800 1000 1200 1400
Flow (GPM)
B1
B2
44 RTHD-SVX01D-EN
Page 45
Installation Mechanical
Condenser Pressure Drop
G Frame - 2 Pass
60
50
O)
40
2
30
20
Delt-P (Ft H
10
0
0 500 1000 1500 2000 2500 3000
Flow (GPM)
G1
G2
Condenser Pressure Drop
F Frame - 2 Pass
45
40
35
O)
30
2
25
20
15
Delt-P (Ft H
10
5
0
0 500 1000 1500 2000
Flow (GPM)
F2
G3
F1 & F3
RTHD-SVX01D-EN 45
Page 46
Installation Mechanical
Condenser Pressure Drop
E Frame - 2 Pass
40
35
30
O)
2
25
20
15
Delt-P (Ft H
10
5
0
0 500 1000 1500
Flow (GPM)
E5
E4
E1
E2
E3
Condenser Pressure Drop
D Frame - 2 Pass
45
40
35
O)
30
2
25
20
15
Delt-P (Ft H
10
5
0
0 200 400 600 800 1000
Flow (GPM)
D1
D2
46 RTHD-SVX01D-EN
Page 47
Installation Mechanical
Condenser Pressure Drop
B Frame - 2 Pass
40
35
30
O)
2
25
20
15
Delt-P (Ft H
10
5
0
0 200 400 600 800 1000
Flow (GPM)
Making Grooved Pipe Connections
CAUTION Equipment Damage!
B1
B2
To prevent damage to water piping, do not overtighten connections. To prevent equipment damage, bypass the unit if using an acidic flushing agent.
NOTE: Make sure that all piping is flushed and cleaned prior to starting the unit.
Vents and Drains
Install pipe plugs in evaporator and condenser water box drain and vent con­nections before filling the water systems.
To drain water, remove vent and drain plugs, install a NPT connector in the drain connection with a shutoff valve and connect a hose to it.
Evaporator Piping Components
NOTE: Make sure all piping components are between the shutoff valves, so that isolation can be accomplished on both the condenser and the evaporator.
RTHD-SVX01D-EN 47
Page 48
Installation Mechanical
“Piping components” include all devices and controls used to provide proper water system operation and unit operating safety. These components and their general locations are given below.
Entering Chilled Water Piping
Air vents (to bleed air from system)
Water pressure gauges with shutoff valves
Pipe unions
Vibration eliminators (rubber boots)
Shutoff (isolation) valves
Thermometers
Cleanout tees
Pipe strainer
Flow switch
Leaving Chilled Water Piping
Air vents (to bleed air from system)
Water pressure gauges with shutoff valves
Pipe unions
Vibration eliminators (rubber boots)
Shutoff (isolation) valves
Thermometers
Cleanout tees
Balancing valve
Pressure relief valve
CAUTION Evaporator Damage!
To prevent evaporator damage, do not exceed 150 psig (10.3 bar) evaporator water pressure for standard water boxes. Maximum pressure for high pressure water boxes is 300 psig (20.7 bar). Refer to digit 14 of the Model No. To prevent tube damage, install a strainer in the evaporator water inlet piping. To prevent tube corrosion, ensure that the initial water fill has a balanced pH.
Condenser Piping Components
“Piping components” include all devices and controls used to provide proper water system operation and unit operating safety. These components and their general locations are given below.
Entering condenser water piping.
Air vents (to bleed air from system)
Water pressure gauges with shutoff valves
48 RTHD-SVX01D-EN
Page 49
Installation Mechanical
Pipe unions
Vibration eliminators (rubber boots)
Shutoff (isolation) valves. One per each pass
Thermometers
Cleanout tees
Pipe strainer
Flow switch
Leaving condenser water piping.
Air vents (to bleed air from system)
Water pressure gauges with shutoff valves
Pipe unions
Vibration eliminators (rubber boots)
Shutoff (isolation) valve - one per each pass
Thermometers
Cleanout tees
Balancing valve
Pressure relief valve.
CAUTION Condenser Damage!
To prevent condenser damage, do not exceed 150 psig (10.3 bar) water pressure for standard water boxes. Maximum pressure for high pressure water boxes is 300 psig (20.7 bar). Refer to digit 18 of the Model No. To prevent tube damage, install a strainer in condenser water inlet piping. To prevent tube corrosion, ensure that the initial water fill has a balanced pH.
Condenser Water Regulating Valve
The Condenser Head Pressure Control Option provides for a 0-10VDC (maxi­mum range - a smaller range is adjustable) output interface to the customer's condenser water flow device. The condenser water flow device is typically a large butterfly type (6" or 8") automatic valve for 200 to 400 Ton chillers.
The following guidelines must be met in order to ensure adequate oil circula­tion throughout the system.
The RTHD must maintain a 23 psid system pressure differential at all load conditions in order to ensure adequate oil circulation.
The entering condenser water temperature must be above 55°F (12.8°C) or between 45°F (7.2°C) and 55°F (12.8°C) with a 1°F temperature rise per minute to 55°F (12.8°C).
RTHD-SVX01D-EN 49
Page 50
Installation Mechanical
Condenser leaving water temperature must be 17°F degrees higher than evaporator leaving water temperature within 2 minutes of startup. A 25°F diferential must be maintained thereafter.
If the above guidelines cannot be met, then some form of tower water con­trol must be used.
Condenser Water Regulating Valve Adjustment
A separate TechView Settings Menu tab entitled "Condenser Head Pressure Control - Setup" that is only visible if the configuration is selected, contain the following settings and manual overrides for user adjustments and commis­sioning all under one tab:
"Off State" Output Command (0-10 Vdc 0.1 volt increments, Default 2.0 Vdc)
Output Voltage @ Desired Minimum Flow (Adj: 0 to 10.0 in 0.1 volt incre­ments, Default 2.0 Vdc)
Desired Minimum Flow (Adj: 0- 100% of full flow in 1% intervals, Default 20%)
Output Voltage @ Desired Maximum Flow (Adj: 0 to 10.0 in .1 volt incre­ments (or finer), Default 10 Vdc)
Actuator Stroke Time (Min to Max Range Time) (Adj: 1 to 1000 seconds, in 1 second increments, Default 30s)
Damping Coefficient (adj: 0.1 to 1.8 , in .1 increments, Default .5)
Head Pressure Control Override (enumeration of: disabled (auto), "off" state, minimum, maximum (100%),) default :disabled (auto). When this setting is in "disabled (auto)"
Condenser Water Pump Prerun Time ( )
Water Treatment
CAUTION Proper Water Treatment!
The use of untreated or improperly treated water in a RTHD may result in scaling, erosion, corrosion, algae or slime. It is recommended that the services of a qualified water treatment specialist be engaged to determine what water treatment, if any, is required. The Trane Company assumes no responsibility for equipment failures which result from untreated or improperly treated water, or saline or brackish water.
Using untreated or improperly treated water in these units may result in inef­ficient operation and possible tube damage. Consult a qualified water treat­ment specialist to determine whether treatment is needed.
50 RTHD-SVX01D-EN
Page 51
Installation Mechanical
r
Water Pressure Gauges and Thermometers
Install field-supplied thermometers and pressure gauges (with manifolds, whenever practical) as shown in Figure 15. Locate pressure gauges or taps in a straight run of pipe; avoid placement near elbows, etc. Be sure to install the gauges at the same elevation on each shell if the shells have opposite-end water connections.
To read manifolded water pressure gauges, open one valve and close the other (depending upon the reading desired). This eliminates errors resulting from differently calibrated gauges installed at unmatched elevations.
Flow Switch
Shutoff
Isolation Valves
Evap Water Flow
Pressure Differential Gauge
Valves
Flow Switch
Manifold
Thermometers
Relief Valve
Relief Valve
Refer to Trane Engineering Bulletin -Series RChiller Sound Ratings and
Installation Guide for sound-sensitive applications.
Figure 15 Typical Thermometer, Valving, and Manifold Pressure Gauge Set-up
Water Pressure Relief Valves
CAUTION Shell Damage!
Shutoff Valves
Manifold
Thermometers
Cond Water
Reg. Valve (Opt.)
Isolation Valves
Pressure Differential Gauge
Cond
Wate
Flow
Install a pressure relief valve in both evaporator and condenser water systems. Failure to do so may result in shell damage.
Install a water pressure relief valve in one of the condenser and one of the evaporator water box drain connections or on the shell side of any shutoff valve. Water vessels with close-coupled shutoff valves have a high potential for hydrostatic pressure buildup on a water temperature increase. Refer to applicable codes for relief valve installation guidelines.
Flow Sensing Devices
The installer must provide flow switches or differential pressure switches with pump interlocks to sense system water flow. Flow switch locations are schematically shown in Figure 15.
To provide chiller protection, install and wire flow switches in series with the water pump interlocks, for both chilled water and condenser water circuits (refer to the Installation Electrical section). Specific connections and sche­matic wiring diagrams are shipped with the unit.
RTHD-SVX01D-EN 51
Page 52
Installation Mechanical
Flow switches must stop or prevent compressor operation if either system water flow drops off below the required minimum shown on the pressure drop curves. Follow the manufacturer’s recommendations for selection and installation procedures. General guidelines for flow switch installation are out­lined below.
Mount the switch upright, with a minimum of 5 pipe diameters straight, horizontal run on each side.
Do not install close to elbows, orifices or valves.
NOTE: The arrow on the switch must point in the direction of the water flow.
To prevent switch fluttering, remove all air from the water system
NOTE: The CH530 provides a 6-second time delay on the flow switch input before shutting down the unit on a loss-of-flow diagnostic. Contact a qualified service organization if nuisance machine shutdowns persist.
Adjust the switch to open when water flow falls below nominal. Refer to the General Data table in Section 1 for minimum flow recommendations for specific water pass arrangements. Flow switch contacts are closed on proof of water flow.
Refrigerant Pressure Relief Valve Venting
WARNING Hazardous Gases!
Consult local regulations for any special relief line requirements. Refrigerant vented into a confined equipment room could displace available oxygen to breathe, causing possible asphyxiation or other serious health risks. Failure to follow these recommendations could result in death or serious injury.
NOTE: Vent pipe size must conform to the ANSI/ASHRAE Standard 15 for vent pipe sizing. All federal, state, and local codes take precedence over any suggestions stated in this manual.
All relief valve venting is the responsibility of the installing contractor. All RTHD units use evaporator, compressor, and condenser pressure relief
valves (Figure 16) that must be vented to the outside of the building. Relief valve connection sizes and locations are shown in the unit submittals.
Refer to local codes for relief valve vent line sizing information.
Caution Equipment Damage!
Do not exceed vent piping code specifications. Failure to comply with specifications may result in capacity reduction, unit damage and/or relief valve damage.
52 RTHD-SVX01D-EN
Page 53
Installation Mechanical
Relief valve discharge setpoints and capacities rates are given in Table 11. Once the relief valve has opened, it will reclose when pressure is reduced to a safe level.
NOTE: Once opened, relief valves may have tendency to leak and must be replaced.
Discharge Pipes
*
*
Evaporator Shell
* Valve is hidden by pipe
Figure 16 Relief Valve Location
Table 11 Pressure Relief Valve Data
Discharge Setpoint
Valve Location
Evap - B1 200 1 48.0 1 1-5/16 -12
Evap - B2 200 1 48.0 1 1-5/16 -12
Evap -B3 200 1 48.0 1 1-5/16 -12
Evap -C1 200 1 48.0 1 1-5/16 -12
Evap - C2 200 1 48.0 1 1-5/16 -12
Evap - D1 200 1 48.0 1 1-5/16 -12
Evap - D2 200 1 48.0 1 1-5/16 -12
Evap - D3 200 1 48.0 1 1-5/16 -12
Evap - D4 200 1 48.0 1 1-5/16 -12
Evap - D5 200 1 48.0 1 1-5/16 -12
Evap - D6 200 1 48.0 1 1-5/16 -12
Evap - E1 200 1 48.0 1 1-5/16 -12
Evap - F1 200 1 48.0 1 1-5/16 -12
Evap - F2 200 1 48.0 1 1-5/16 -12
Evap - G1 200 1 78.8 1-1/4 1-5/8 - 12
Evap - G2 200 1 78.8 1-1/4 1-5/8 - 12
(psi)
Condenser Shell
Pressure relief valve discharge capacities will vary with shell diameter and length and also compressor displacement. Discharge venting capacity should be calculated as required by ASHRAE Standard 15-94. Do not adjust relief valve setting in the field.
Number of Valves
Rated Capacity per Relief Valve (lba/min.)
Field Connection Pipe Size (in NPT)
Factory Shell Side Connection(in)
RTHD-SVX01D-EN 53
Page 54
Installation Mechanical
Table 11 Pressure Relief Valve Data
Discharge Setpoint
Valve Location
Evap - G3 200 1 78.8 1-1/4 1-5/8 - 12
Cond - B1 200 2 48.0 1 1-5/16 -12
Cond - B2 200 2 48.0 1 1-5/16 -12
Cond - D1 200 2 48.0 1 1-5/16 -12
Cond - D2 200 2 48.0 1 1-5/16 -12
Cond - E1 200 2 48.0 1 1-5/16 -12
Cond - E2 200 2 48.0 1 1-5/16 -12
Cond - E3 200 2 48.0 1 1-5/16 -12
Cond - E4 200 2 48.0 1 1-5/16 -12
Cond - E5 200 2 48.0 1 1-5/16 -12
Cond - F1 200 2 48.0 1 1-5/16 -12
Cond - F2 200 2 48.0 1 1-5/16 -12
Cond - F3 200 2 48.0 1 1-5/16 -12
Cond - G1 200 2 48.0 1 1-5/16 -12
Cond - G2 200 2 48.0 1 1-5/16 -12
Cond - G3 200 2 48.0 1 1-5/16 -12
Comp - B1/B2* 200 2 78.8 1-1/4 1-5/8 - 12
Comp - C1/C2* 200 3 78.8 1-1/4 1-5/8 - 12
Comp - D1/D2/D3* 200 3 78.8 1-1/4 1-5/8 - 12
Comp -E3* 200 3 78.8 1-1/4 1-5/8 - 12
(psi)
Number of Valves
Rated Capacity per Relief Valve (lba/min.)
Field Connection Pipe Size (in NPT)
Factory Shell Side Connection(in)
* Only used with isolation valve option
Thermal Insulation
All RTHD units are available with optional factory installed thermal insulation. If the unit is not factory insulated, install insulation over the areas shaded in
Figure 17. Refer to Table 12 for types and quantities of insulation required.
NOTE: Liquid line filter, refrigerant charging valves, water temperature sensors, drain and vent connections when insulated must remain accessible for service.
NOTE: Use only water-base latex paint on factory-applied insulation. Failure to do so may result in insulation shrinkage.
NOTE: Units in environments with higher humidity or very low leaving water temperature may require thicker insulation
54 RTHD-SVX01D-EN
Page 55
Installation Mechanical
.
Figure 17 Typical RTHD Insulation Requirements
Table 12 Recommended Insulation Types
Location Type Sq. Feet
Evaporator 3/4” wall 90
Compressor 3/4” wall 25
All components and piping on low side of system (gas pump, return oil line, filter from pump)
3/4” wall 160
RTHD-SVX01D-EN 55
Page 56
Installation Mechanical
56 RTHD-SVX01D-EN
Page 57
Installation Electrical
General Recommendations
For proper electrical component operation, do not locate the unit in areas exposed to dust, dirt, corrosive fumes, or excessive humidity. If any of these conditions exist, corrective action must be taken.
WARNING Hazardous Voltage!
Disconnect all electric power, including remote disconnects and discharge all motor start/run capacitors before servicing. Follow proper lockout/tagout procedures to ensure the power cannot be inadvertently energized. Verify with an appropriate voltmeter that all capacitors have discharged. Failure to disconnect power and discharge capacitors before servicing could result in death or serious injury.
All wiring must comply with local and National Electric Codes. Minimum cir­cuit ampacities and other unit electrical data is on the unit nameplate. See the unit order specifications for actual electrical data. Specific electrical schemat­ics and connection diagrams are shipped with the unit.
Typical wiring diagrams are in the back of this manual.
CAUTION Use Copper Conductors Only!
Unit terminals are not designed to accept other types of conductors. Failure to use copper conductors may result in equipment damage.
Do not allow conduit to interfere with other components, structural members or equipment. All conduit must be long enough to allow compressor and starter removal.
NOTE: To prevent control malfunctions, do not run low voltage wiring (<30V) in conduit with conductors carrying more than 30 volts.
Power Supply Wiring
Model RTHD chillers are designed according to NEC Article 310-15; therefore, all power supply wiring must be sized and selected accordingly by the project engineer.
For a complete discussion on the use of conductors, see Trane Engineering Bulletin EB-MSCR-40.
Refer to Trane Engineering Bulletin CTV-EB-93 for power wire sizing.
Water Pump Power Supply
Provide power supply wiring with fused disconnect for both the chilled water and condenser water pumps.
RTHD-SVX01D-EN 57
Page 58
Installation Electrical
Electrical Panel Power Supply
Power supply wiring instructions for the starter/control panel are:
1. Run line voltage wiring in conduit to access opening(s) on starter/control panel or pull-box. See CTV-EB-93 for wire sizing and selection information and refer to Table 13 that show typical electrical connection sizes and locations. Always refer to submittal information for your actual unit speci­fications.
Table 13 Wire Selection Chart for Starter Panels
Min.
Supply Leads for All Starters (0 - 2000 Volts) Wire Size Copper
0
75
C
840******
652******
468******
360******
292******
1104******
0 120 192 252 360 384 360 480
00 140 224 294 420 448 420 560
000 160 256 336 480 512 480 640
0000 184 294 386 552 589 552 736
250 204 326 428 612 653 612 816
300 228 356 479 684 730 684 912
1 Conduit
3 Wire
1 Conduit 6 Wire
1 Conduit 9 Wire
2 Conduits 6 Wire
2 Conduits 12 Wire
3 Conduits 9 Wire
4 Conduits 12 Wire
350 248 397 521 744 794 744 992
400 268 429 563 804 858 804 1072
500 304 486 638 912 973 912 1216
Conductors to the starter and motor connected in parallel (electrically joined at both ends to form a single conductor) must be sized 0 (1/0) or larger per NEC 310-4. Each phase must be equally represented in each conduit.
58 RTHD-SVX01D-EN
Page 59
Installation Electrical
Figure 18 Electrical Installation
WARNING Live Electrical Components!
During installation, testing, servicing and troubleshooting of this product, it may be necessary to work with live electrical components. Have a qualified licensed electrician or other individual who has been properly trained in handling live electrical components perform these tasks. Failure to follow all electrical safety precautions when exposed to live electrical components could result in death or serious injury.
Compressor Motor Phase Sequencing
Always verify that proper rotation of the Series R compressor is established before the machine is started. Proper motor rotation requires confirmation of the electrical phase sequence of the power supply. The motor is internally connected for clockwise rotation with incoming power supply phased A, B, C.
To confirm the correct phase sequence (ABC), use a Model 45 Associated Research Phase indicator or equivalent.
Basically, voltages generated in each phase of a polyphase alternator or circuit are called phase voltages. In a three-phase circuit, three sine wave voltages are generated, differing in phase by 120 electrical degrees. The order in which the three voltages of a three-phase system succeed one another is called
RTHD-SVX01D-EN 59
Page 60
Installation Electrical
phase sequence or phase rotation. This is determined by the direction of rota­tion of the alternator. When rotation is clockwise, phase sequence is usually called “ABC,” when counterclockwise, “CBA.”
This direction may be reversed outside the alternator by interchanging any two of the line wires. It is this possible interchange of wiring that makes a phase sequence indicator necessary if the operator is to quickly determine the phase rotation of the motor.
Correcting Improper Electrical Phase Sequence
Proper compressor motor electrical phasing can be quickly determined and corrected before starting the unit. If using an Associated Research Model 45 Phase Sequence Indicator, follow this procedure:
1. Press the STOP button to insure the unit will not attempt to start the compressor.
2. Open the electrical disconnect or circuit protection switch that provides line power to the line power terminal block in the control panel (or to the unit-mounted disconnect).
3. Connect the phase sequence indicator leads to the line power terminal block (or the unit mounted disconnect) as follows:
Phase Seq. Lead 1TB1 Terminal
Black (Phase A) L1
Red (Phase B) L2
Yellow (Phase C) L3
4. Turn power on by closing the unit supply power disconnect switch.
5. Read the phase sequence on the indicator. The “ABC” indicator on the face of the phase indicator will glow if phase is “ABC”.
WARNING Hazardous Voltage!
Disconnect all electric power, including remote disconnects and discharge all motor start/run capacitors before servicing. Follow proper lockout/tagout procedures to ensure the power cannot be inadvertently energized. Verify with an appropriate voltmeter that all capacitors have discharged. Failure to disconnect power and discharge capacitors before servicing could result in death or serious injury.
6. If the “CBA” indicator glows instead, open the unit main power discon­nect and switch two line leads on the line power terminal block (or the unit mounted disconnect). Reclose the main power disconnect and recheck phasing.
7. Reopen the unit disconnect and disconnect the phase indicator.
60 RTHD-SVX01D-EN
Page 61
Installation Electrical
Terminal Lugs
Proper starter/control panel line-side lug sizes are specified on the starter submittals. These lug sizes must be compatible with conductor sizes speci­fied by the electrical engineer or contractor. Appropriate lug sizes are pro­vided.
Circuit Breakers and Non-Fused Disconnect Switches (factory installed Option)
Units that are ordered with factory installed Circuit Breakers or Non-Fused Disconnect Switches ship with the handle in the control panel. The handle must be installed prior to starting the unit.
The operating mechanism is already pre installed on the Disconnect/ Circuit Breaker frame.
The hole locations and shafts lengths have already been cut. And the shaft already installed.
WARNING Hazardous Voltage!
Disconnect all electric power, including remote disconnects and discharge all motor start/run capacitors before servicing. Follow proper lockout/tagout procedures to ensure the power cannot be inadvertently energized. Verify with an appropriate voltmeter that all capacitors have discharged. Failure to disconnect power and discharge capacitors before servicing could result in death or serious injury.
1. Attach the handel and gasket to the enclosure door and secure with the four bolts, lock washers and nut as shown in Figure 19. Tighten to 75 in- Lbs.
Note: there is an additional lexan spacer on the handel not shown in the
Figure 19, do not remove.
Figure 19 Handle on Door
2. Check that when the enclosure door is closed, the handle interlocks with
RTHD-SVX01D-EN 61
Page 62
Installation Electrical
the shaft in all handel positions except RESET/OPEN. To open the enclo­sure door when the breaker is in the ON position, rotate the screw slot on the handle plate counter -clockwise. Verify operation.
Table 14 Lug Sizes
Device Max. Current
RLA Circuit Breaker (copper)
0-200 (1) #6 - 350 MCM 250A
200.1-280 (2) 3/0-500 MCM 350A
280.1-320 (2) 3/0 - 500 MCM 400A
320.1-400 (2) 3/0 - 500 MCM 500A
400.1-476 (2) 3/0 - 500 MCM 600A
476.1-560 (4) 250 - 500 MCM 700A
560.1-640 (4) 250 - 500 MCM 800A
640.1-800 (4) 250 - 500 MCM 1000A
Rating
Non-Fused Disconnect
RLA
207, 277, 300 (2) 3/0 - 500 MCM 400A
360, 397 (2) 3/0 - 500 MCM 600A
476 (2) 3/0 - 500 MCM 600A
598 (2) 3/0 - 500 MCM 800A
500 (2) 3/0 - 500 MCM 800A
779 (4) 250 MCM - 500 MCM 1200A
Switch
RLA Main Lugs Only
1-476 (2) #6-500 MCM
500-598 (2) #4-500 MCM
760A
750A
Fused Disconnect Switches
Size fused disconnects in accordance with NEC Article 440-22(a).
Rated Load Amperage (RLA)
The compressor motor RLA for a particular chiller is determined by the field selection program and indicated on the compressor nameplate.
Minimum Circuit Ampacity (MCA)
The MCA is equal to 1.25 x the compressor RLA (on nameplate).
62 RTHD-SVX01D-EN
Page 63
Installation Electrical
Maximum Fuse/Circuit Breaker Size
The maximum fuse/circuit breaker size is equal to 2.25 x the compressor RLA in accordance with UL 1995, para. 36.15.See also NEC 440-22.
The recommended dual element (RDE) fuse size is equal to 1.75 x RLA in accordance with NEC Table 430-152.
For recommended field connection lug sizes (RTHD starters) see Table 14.
RTHD-SVX01D-EN 63
Page 64
Installation Electrical
Application Of Solid-State Starters
The RediStart MX motor starter is a microprocessor-controled started fot induction motors.
Viewing Parameter Values
Parameter view mode can be entered by:
1. At the default meter display, press the PARAM key to enter parameter mode. "P 1" will be displayed to indicate Parameter 1.
2. Use the UP and DOWN keys to scroll through the available parameters.
3. Pressing the UP key from "P 1" will advance to parameter "P 2".
4. Pressing the DOWN key from "P 1" will wrap around to the highest parameter.
5. The value of the parameter can be viewed by pressing the ENTER key.
6. To view another parameter without changing/saving the parameter, press the PARAM key to return to the parameter number display.
To return to the default meter display either:
1. Press the PARAM key while in the parameter number display mode.
2. Wait 60 seconds and the display will return to the default meter display
Parameter Settings
Parameter Description Setting Range Units Default
P1 Motor FLA 1-6400 A
P2 Maximum Motor Current 100-800 %FLA 225
P3 Ramp Time 0-300 Sec 1
P4 Rated RMS Voltage 200, 208, 220, 230, 240, 350,
380, 400, 415, 440, 460, 480, 500, 525, 575, 600
P5 CT Ratio (x:1) 72, 96, 144, 288, 864, 1320,
2640, 2880, 3900, 5760
P6 Software Part Number Display only - -
P7 Passcode 0-9999 - -
P8 Fault Log Display faults stored in Fault
log
rms
V
rms
- 288
--
10
480
64 RTHD-SVX01D-EN
Page 65
Installation Electrical
WARNING Electrical Shock!
Contacting any of the motor terminals, even with the motor off can cause a severe, potentially fatal, shock. Follow proper lockout/tagout procedures to ensure the power can not be inadvertently energized. Failure to disconnect power before servicing could result in death or serious injury.
NOTE: IMPORTANT! WHEN EVACUATING THE CHILLER’S REFRIG­ERANT SYSTEM, ALWAYS HAVE THE MAIN POWER DISCONNECT/ CIRCUIT BREAKER OPENED. Even when the compressor is not running, voltage is present at the compressor motor terminals, providing the potential for current to flow through a low impedance path. When removing refrigerant for the chiller both the condenser and chilled water pump must be operating to avoid freeze up.
As the chiller is evacuated below atmospheric pressure, the dielectric strength (resistance to arcing) of the gaseous atmosphere is significantly reduced. Because the SCRs are connected “inside the delta,” three of the motor terminals are connected directly to the line voltage. An “arc over” can occur between motor terminals under conditions seen in the evacuation pro­cess. If this occurs the circuit breaker (or other external protective devices) will trip in response to high fault currents, and motor damage may also occur. This can be avoided through being certain that the chiller is fully discon-
nected from all power sources before beginning pumpdown or evacua­tion procedures, as well as guaranteeing that the disconnect cannot be
accidentally closed while the chiller is in a vacuum.
RTHD-SVX01D-EN 65
Page 66
Installation Electrical
C T ' s
B BBA
M a i n P o w e r
1 2
A A
9 B 7 B
1 1 B
3
A A
B BBA
9 7
1 1
5 A
4 A
7 A
T 1
9 A
T 2
1 1 A
T 3
1 K 1 1 K 3
2 1
3
M A
M A M A
6 A
T 6
8 A
T 4
1 0 A
T 5
1 2 A
C B
C B
1 0
8
B A
C B
1 2
A B
1 0
1 2
1 K 4
1 0 C 1 2 C
8 C
A B
8
1 K 2
2 B 1 B
3 B
1 M 2 M
T o C o n t r o l s
3 M
Figure 20 Y-D Starter Panel Power Wire Routing
66 RTHD-SVX01D-EN
Page 67
Installation Electrical
C T ' s
1 2
F FFG
M a i n P o w e r
G G
T 1
1 G
T 2
2 G
T 3
3
3 G
7 C
T 6
9 C
T 4
1 1 C
1 1 C
T 5
T 3 T 2
S o l i d S t a t e S t a r t e r
L 3 L 2
3 2
F FFK
9 C 7 C
K
T 1
N o t e : S S S i n s t a l l e d i n p a n e l u p s i d e ­d o w n .
L 1
1
K
1 K
2 K
T o C o n t r o l s
3 K
Figure 21 Solid State Starter Panel Power Wire Routing
Module Connections for Interconnecting Wiring
All connectors can be unplugged or the wires can be removed from the screw assembly. If an entire plug is removed, make sure the plug and the associated jack are marked for proper location identification during reinstalla­tion.
CAUTION Equipment Damage!
Plugs and jacks must be clearly marked before disconnecting, because specific plugs will fit into other jacks. Possible damage to equipment may occur if the plugs are reversed with the jacks.
Interconnecting Wiring (Field Wiring Required)
NOTE: Important: Do not turn chiller on or off using the chilled water pump interlocks.
RTHD-SVX01D-EN 67
Page 68
Installation Electrical
When making field connections, refer to the appropriate field layout, wiring, schematics and controls diagrams that ship with the unit. The diagrams in this manual are typical only and may not match the unit.
Whenever a contact closure (binary output) is referenced, the electrical rating is:
At 120 VAC 7.2 amp resistive
2.88 amp pilot duty
1/3 hp, 7.2 FLA, 43.2 LRA
At 240 VAC 5.0 amp resistive
2.0 amp pilot duty
1/3 hp, 3.6 FLA, 21.6 LRA
Whenever a dry contact input (binary input) is referenced, the electrical rating is 24VDC, 12 mA.
Whenever a control voltage contact input (binary input) is referenced, the electrical rating is 120 VAC, 5mA.
NOTE: Asterisked connections require the user to provide an external source of power. The 115V control power transformer is not sized for additional load.
Chilled Water Pump Control
CH530 has a evaporator water pump output relay that closes when the chiller is given a signal to go into the Auto mode of operation from any source. The contact is opened to turn off the pump in the event of most machine level diagnostics to prevent the build up of pump heat. To protect against the build-up of pump heat for those diagnostics that do not stop and/or start the pump and to protect against the condition of a bad flow switch, the pump shall always be stopped when the evaporator pressure is seen to be close to the Low Side Evaporator Pressure relief valve setting.
Chilled Water Flow Interlock
CH530 has an input that will accept a contact closure from a proof-of-flow device such as a flow switch. The flow switch is to be wired in series with the chilled water pump starter's auxiliary contacts. When this input does not prove flow within 20 minutes relative to transition from Stop to Auto modes of the chiller, or if the flow is lost while the chiller is in the Auto mode of oper­ation, the chiller will be inhibited from running by a non-latching diagnos­tic.The flow switch input shall be filtered to allow for momentary openings and closings of the switch due to turbulent water flow. This is accomplished with a 6 seconds filtering time. The sensing voltage for the condenser water flow switch is 115/240 VAC
IMPORTANT! DO NOT cycle the chiller through starting and stopping the chilled water pump. This could cause the compressor to shut down fully loaded. Use the external stop/start input to cycle the chiller.
Condenser Water Pump Control
CH530 provides a contact closure output to start and stop the condenser water pump. If condenser pumps are arranged in a bank with a common header, the output can be used to control an isolation valve and/or signal another device that an additional pump is required.
68 RTHD-SVX01D-EN
Page 69
Installation Electrical
Condenser Water Pump Prestart time has been added to help with cold con­denser water problems. In very cold outdoor ambients, the cooling towers sump cold water would reach the chiller some time after the low system dif­ferential pressure protection had run through its ignore time, and result in an immediate shutdown and latching diagnostic. By simply starting the pump earlier, and allowing mixing of the warmer indoor loop with the cooling tower's sump, this problem can be avoided.
Condenser Water Flow Interlock
The CH530 shall accept an isolated contact closure input from a customer installed proof-of-flow device such as a flow switch and customer provided pump starter auxiliary contact for interlocking with condenser water flow. The input shall be filtered to allow momentary openings and closings of the switch due to turbulent water flow, etc. This shall be accomplished with a 6 seconds filtering time. The sensing voltage for the condenser water flow switch is 115/240 VAC.
On a call for cooling after the restart inhibit timer has timed out, the CH530 shall energize the condenser water pump relay and then check the condenser water flow switch and pump starter interlock input for flow confirmation. Startup of the compressor will not be allowed until flow has proven.
If flow is not initially established within 1200 seconds (20 minutes) of the con­denser pump relay energizing, an automatically resetting diagnostic "Con­denser Water Flow Overdue" shall be generated which terminates the prestart mode and de-energizes the condenser water pump relay This diag­nostic is automatically reset if flow is established at any later time.
Note: This diagnostic would never automatically reset if CH530 was in con­trol of the condenser pump through its condenser pump relay since it is com­manded off at the time of the diagnostic. It could however reset and allow normal chiller operation if the pump was controlled from some external source.
Chilled Water Reset (CWR)
The MP will reset the chilled water temperature setpoint based on either return water temperature, or outdoor air temperature. The Return Reset option is standard, Outdoor Reset is optional.
The following is selectable:
RESET TYPE Setpoint.
This can be set to: NO CWR, OUTDOOR AIR TEMPERATURE RESET, RETURN WATER TEMPERATURE RESET, or CONSTANT RETURN WATER TEMPERATURE RESET. The MP shall not permit more than one type of reset to be selected.
RESET RATIO Setpoints.
For outdoor air temp. reset, both positive and negative reset ratios will be allowed.
START RESET Setpoints.
MAXIMUM RESET Setpoints.
The maximum resets shall be with respect to the chilled water setpoint.
When the chiller is running, if any type of CWR is enabled, the MP will step the CWS toward the desired CWS' (based on the below equations and setup parameters) at a rate of 1 degree F every 5 minutes until the Active CWS equals the desired CWS'. When the chiller is not running the CWS will be
RTHD-SVX01D-EN 69
Page 70
Installation Electrical
fully reset immediately (within one minute). The chiller will then start at the Differential to Start value above a fully reset CWS or CWS' for Outdoor, Return, and Constant Return Reset.
Equations for calculating CWR
Equation used to get Degrees of Reset: Outdoor Air: Degrees of Reset = Reset Ratio * (Start Reset - TOD) Return Reset: Degrees of Reset = Reset Ratio * (Start Reset - (TWE - TWL)) Constant Return: Degrees of Reset = 100% * (Design Delta Temp - (TWE - TWL))
To obtain Active CWS from Degrees of Reset: Active CWS = Degrees of Reset + Previous CWS Note: Previous CWS can either be Front Panel, BAS, or External
Reset Ratio calculation: The Reset Ratio on the User Interface is displayed as a percentage. To use it
in the above equation it must be converted to its decimal form.
Reset Ratio percent / 100 = Reset Ratio decimal
Example of converting Reset Ratio: If the Reset Ratio displayed on the User Interface is 50% then use (50/100) = .5 in the equation
TOD = Outdoor Air Temp TWE = Evap Entering Water Temp TWL = Evap Leaving Water Temp
Programmable Relays (Alarm and Status) - Optional
CH530 provides a flexible alarm or chiller status indication to a remote loca­tion through a hard wired interface to a dry contact closure. Four relays are available for this function, and they are provided (generally with a Quad Relay Output LLID) as part of the Alarm Relay Output Option.
The events/states that can be assigned to the programmable relays are listed in the following table.
70 RTHD-SVX01D-EN
Page 71
Installation Electrical
Table 15 Chiller Events/Status Descriptions
Event/State Description
Alarm - Latching This output is true whenever there is any active diagnostic that requires a manual reset to
clear, that effects the Chiller, the Circuit, or any of the Compressors on a circuit. This classification does not include informational diagnostics.
Alarm - Auto Reset This output is true whenever there is any active diagnostic that could automatically clear, that
effects the Chiller, the Circuit, or any of the Compressors on a circuit. This classification does not include informational diagnostics. If all of the auto resetting diagnostics were to clear, this output would return to a false condition.
Alarm This output is true whenever there is any diagnostic effecting any component, whether
latching or automatically clearing. This classification does not include informational diagnostics.
Warning This output is true whenever there is any informational diagnostic effecting any component,
whether latching or automatically clearing.
Chiller Limit Mode This output is true whenever the chiller has been running in one of the Unloading types of
limit modes (Condenser, Evaporator, Current Limit or Phase Imbalance Limit) continuously for the last 20 minutes. A given limit or overlapping of different limits must be in effect continuously for 20 minutes prior to the output becoming true. It will become false, if no Unload limits are present for 1 minute. The filter prevents short duration or transient repetitive limits from indicating. The chiller is considered to be in a limit mode for the purposes of front panel display and annunciation, only if it is fully inhibiting loading by virtue of being in either the "hold" or "forced unload" regions of the limit control, excluding the "limited loading region". (In previous designs, the "limit load" region of the limit control was included in the criteria for the limit mode call out on the front panel and annunciation outputs)
Compressor Running
Chiller Head Pressure Relief Request Relay
The output is true whenever any compressors are started or running on the chiller and false when no compressors are either starting or running on the chiller. This status may or may not reflect the true status of the compressor in Service Pumpdown if such a mode exists for a particular chiller.
This relay output is energized anytime the chiller is running in one of the following modes; Ice Making Mode or Condenser Pressure Limit Control Mode continuously for the duration specified by the Chiller Head Relief Relay Filter Time. The Chiller Head Relief Relay Filter Time is a service setpoint. The relay output is de-energized anytime the chiller exits all above modes continuously for the duration specified by the same Chiller Head Relief Relay Filter Time.
RTHD-SVX01D-EN 71
Page 72
Installation Electrical
The CH530 Service Tool (TechView) is used to install and assign any of the above listed events or status to each of the four relays provided with this option.
The default assignments for the four available relays are listed below.
Table 16 Programable Relays
LLID Software
LLID Name
Relay Designation Output Name Default
Operating Status Programmable Relays
Relay 0 Status Relay 4, J2-1,2,3 Head Pressure Relief Request
Relay 1 Status Relay 3, J2-4,5,6 Chiller Limit Mode Relay
Relay 2 Status Relay 2, J2-7,8,9 Chiller Alarm Relay (latching or
nonlatching)
Relay 3 Status Relay 1, J2-10,11,12 Compressor Running Relay
Emergency Stop
The CH530 provides auxiliary control for a customer specified/installed latch­ing trip out. When this customer-furnished remote contact is provided, the chiller will run normally when the contact is closed. When the contact opens, the unit will trip off on a manually resettable diagnostic. This condition requires manual reset at the chiller switch on the front of the control panel.
External Auto/Stop
If the unit requires the external Auto/Stop function, the installer must provide leads from the remote contacts to the proper terminals of the LLID on the control panel.
The chiller will run normally when the contacts are closed. When the contact opens, the compressor(s), if operating, will go to the RUN:UNLOAD operating mode and cycle off. Unit operation will be inhibited. Re-closure of the con­tacts will permit the unit to automatically return to normal operation.
NOTE: A “panic” stop (similar to “emergency” stop) can be manually commanded by pressing the STOP button twice in a row, the chiller will immediately shut down, but without creating a latching diagnostic.
Soft Loading
Soft loading will prevent the chiller from going to full capacity during the pull­down period.
The CH530 control system has two soft loading algorithms running all of the time. They are capacity control soft loading and current limit soft loading. These algorithms introduce the use of a Filtered Chilled Water Setpoint and a Filtered Current Limit Setpoint. After the compressor has been started, the starting point of the filtered chilled water setpoint is initialized to the value of the Evap Leaving Water Temperature. The filtered current limit setpoint is ini­tialized to the value of the Current Limit Softload Starting Percent. These fil­tered setpoints allow for a stable pull-down that is user adjustable in duration. They also eliminate sudden transients due to setpoint changes during normal chiller operation.
Three settings are used to describe the behavior of soft loading. The setup for softloading can be done using TechView.
Capacity Control Softload Time: This setting controls the time constant of
72 RTHD-SVX01D-EN
the Filtered Chilled Water Setpoint. It is settable between 0 and 120 min.
Page 73
Installation Electrical
Current Limit Control Softload Time: This Setting controls the time con­stant of the Filtered Current Limit Setpoint. It is settable between 0 and 120 minutes.
Current Limit Softload Starting Percent: This setting controls the starting point of the Filtered Current Limit Setpoint. It is adjustable from 40 for RTHD to 100 percent RLA.
External Base Loading - Optional
Primarily for process control requirements, base loading provides for immedi­ate start and loading of a chiller up to an externally or remotely adjustable cur­rent limit setpoint without regard to differential to start or stop, or to leaving water temperature control. This allows the flexibility to prestart or preload a chiller in anticipation of a large load application. It also allows you to keep a chiller on line between processes when leaving water temperature control would normally cycle the unit.
When the base loading option is installed through TechView it will be control­lable through DynaView/TechView, External Hardware Interface or Tracer (if Tracer is installed). Order for precedence for all setpoints, DynaView/Tech­View then External then Tracer from lowest to highest priority. If one of the higher priority setpoints drops out due to a bad sensor or communication loss then base loading shall go to the next lowest priority of command and set­point. The command settings and control setpoints associated with base loading are explained below.
Base Loading Control setpoint
This setpoint has three possible sources, an External Analog Input, Dyna­View/TechView or Tracer.
DynaView/TechView Base Loading Control Setpoint
The range is 40 - 100 % Compressor Load (Max %RLA). The default is 50%.
Tracer Base Loading Control Setpoint
The range is 40 - 100 % Compressor Load (Max %RLA). The default is 50%.
External Base Loading Setpoint
This is an Analog Input that sets the base loading setpoint. This signal can be controlled by either a 2-10Vdc or 4-20ma Signal based on configuration information. The equations show the relationship between input and per­cent compressor load:
If the input is configured as a 4 - 20 mA: % Load = 3.75 * (mA Input) + 25
If the input is configured as a 2 - 10 Vdc: % Load = 7.5 * (Vdc Input) + 25
Summit Interface - Optional
CH530 provides an optional interface between the chiller and a Trane Summit BAS. A Communications interface LLID shall be used to provide "gateway" functionality between the Chiller and Summit.
RTHD-SVX01D-EN 73
Page 74
Installation Electrical
LonTalk Communication Interface - Optional
CH530 provides an optional LonTalk Communication Interface (LCI-C) between the chiller and a Building Automation System (BAS). An LCI-C LLID shall be used to provide "gateway" functionality between the LonTalk protocol and the Chiller.
Ice Making Contact - Optional
CH530 accepts a contact closure input to initiate Ice Building. When in the ice building mode, the compressor will be fully loaded (not given a low set­point) and will continue to operate until the ice contacts open or the return water temperature reaches the Ice Termination Setpoint. If terminated on return setpoint, CH530 will not allow the chiller to restart until the ice making contact is opened.
Ice Machine Control - Optional
CH530 provides an output contact closure that can be used as a signal to the system that ice building is in operation. This relay will be closed when ice building is in progress and open when ice building has been terminated by either CH530 or the remote interlock. It is used to signal the system changes required to convert to and from ice making.
External Chilled Water Setpoint - Optional
Ch530 will accept either a 2-10 VDC or a 4-20 mA input (J9-4, J9-5) signal, to adjust the chilled water setpoint from a remote location.
External Current Limit Setpoint - Optional
CH530 will accept either a 2-10VDC or a 4-20mA input (J7-11, J7-12) signal to adjust the current limit setpoint from a remote location.
Percent Condenser Pressure Output - Optional
CH530 provides a 2-10 VDC analog output to indicate percent High Pressure Cutout (HPC) condenser pressure.
Percent HPC = (Condenser Pressure/High Pressure Cutout Setpoint)*100
Compressor Percent RLA Output - Optional
CH530 provides a 2-10 Vdc analog output to indicate % RLA of compressor starter average phase current. 2 to 10 Vdc corresponds to 0 to 120% RLA.
74 RTHD-SVX01D-EN
Page 75
Operating Principles Mechanical
This section contains an overview of the operation and maintenance of Series R chillers equipped with microcomputer-based control systems. It describes the overall operating principles of the RTHD water chiller..
Following the section is information regarding specific operating instructions, detailed descriptions of the unit controls and options (Operator Interface ­Control Systems), and maintenance procedures that must be performed reg­ularly to keep the unit in top condition (Periodic Maintenance and Mainte­nance Procedures). Diagnostic information (Diagnostics) is provided to allow the operator to identify system malfunctions.
NOTE: To ensure proper diagnosis and repair, contact a qualified service organization if a problem should occur.
General
The Model RTHD units are single-compressor water-cooled liquid chillers. These units are equipped with unit-mounted starter/control panels.
The basic components of an RTHD unit are:
Unit-mounted panel containing starter and TracerCH530 controller and Input/Output LLIDS
Helical-rotary compressor
Evaporator
Electronic expansion valve
Water-cooled condenser with integral subcooler
Oil supply system
Oil cooler (application dependent)
Related interconnecting piping.
Refrigeration (Cooling) Cycle
The refrigeration cycle of the Series R chiller is conceptually similar to that of other Trane chiller products. It makes use of a shell-and-tube evaporator design with refrigerant evaporating on the shell side and water flowing inside tubes having enhanced surfaces.
The compressor is a twin-rotor helical rotary type. It uses a suction gas­cooled motor that operates at lower motor temperatures under continuous full and part load operating conditions. An oil management system provides an almost oil-free refrigerant to the shells to maximize heat transfer perfor­mance, while providing lubrication and rotor sealing to the compressor. The lubrication system ensures long compressor life and contributes to quiet operation.
Condensing is accomplished in a shell-and-tube heat exchanger where refrig­erant is condensed on the shell side and water flows internally in the tubes.
Refrigerant is metered through the flow system using an electronic expan­sion valve, that maximizes chiller efficiency at part load.
A unit-mounted starter and control panel is provided on every chiller. Micro­processor-based unit control modules (Tracer CH530) provide for accurate chilled water control as well as monitoring, protection and adaptive limit func­tions. The “adaptive” nature of the controls intelligently prevents the chiller from operating outside of its limits, or compensates for unusual operating conditions, while keeping the chiller running rather than simply tripping due to a safety concern. When problems do occur, diagnostic messages assist the operator in troubleshooting.
RTHD-SVX01D-EN 75
Page 76
Pressure
Operating Principles Mechanical
Cycle Description
The refrigeration cycle for the RTHD chiller can be described using the pres­sure-enthalpy diagram shown in Figure 22. Key State Points are indicated on the figure and are referenced in the discussion following. A schematic of the system showing the refrigerant flow loop as well as the lubricant flow loop is shown in Figure 25.
Liquid
3
4
2
5
Figure 22 Pressure /Enthalpy Curve
Evaporation of refrigerant occurs in the evaporator. A metered amount of refrigerant liquid enters a distribution system in the evaporator shell and is then distributed to the tubes in the evaporator tube bundle. The refrigerant vaporizes as it cools the water flowing through the evaporator tubes. Refriger­ant vapor leaves the evaporator as saturated vapor (State Pt. 1).
The refrigerant vapor generated in the evaporator flows to the suction end of the compressor where it enters the motor compartment of the suction-gas­cooled motor. The refrigerant flows across the motor, providing the neces­sary cooling, then enters the compression chamber. Refrigerant is com­pressed in the compressor to discharge pressure conditions. Simultaneously, lubricant is injected into the compressor for two purposes: (1) to lubricate the rolling element bearings, and (2) to seal the very small clearances between the compressor’s twin rotors. Immediately following the compression pro­cess the lubricant and refrigerant are effectively divided using an oil separator. The oil-free refrigerant vapor enters the condenser at State Pt. 2. The lubrica­tion and oil management issues are discussed in more detail in the compres­sor description and oil management sections that follow.
Baffles within the condenser shell distribute the compressed refrigerant vapor evenly across the condenser tube bundle. Cooling tower water, circulat­ing through the condenser tubes, absorbs heat from this refrigerant and con­denses it.
1
Gas
Enthalpy
76 RTHD-SVX01D-EN
Page 77
Operating Principles Mechanical
As the refrigerant leaves the bottom of the condenser (State Pt. 3), it enters an integral subcooler where it is subcooled before traveling to the electronic expansion valve (State Pt. 4). The pressure drop created by the expansion process vaporizes a portion of the liquid refrigerant. The resulting mixture of liquid and gaseous refrigerant then enters the Evaporator Distribution system (State Pt. 5). The flash gas from the expansion process is internally routed to compressor suction, and while the liquid refrigerant is distributed over the tube bundle in the evaporator.
The RTHD chiller maximizes the evaporator heat transfer performance while minimizing refrigerant charge requirements. This is accomplished by meter­ing the liquid refrigerant flow to the evaporator’s distribution system using the electronic expansion valve. A relatively low liquid level is maintained in the evaporator shell, which contains a bit of surplus refrigerant liquid and accumu­lated lubricant. A liquid level measurement device monitors this level and pro­vides feedback information to the CH530 unit controller, which commands the electronic expansion valve to reposition when necessary. If the level rises, the expansion valve is closed slightly, and if the level is dropping, the valve is opened slightly such that a steady level is maintained.
dual discharge lines only on C, D & E frame compressors
dual discharge lines
compressor
only on C, D & E frame compressors
EXV
evaporator
gas pump
Figure 23 Refrigerant Flow Diagram
s e p a r
a
t o r
condenser
s
e p a r a
t o
r
RTHD-SVX01D-EN 77
Page 78
Operating Principles Mechanical
Compressor Description
Unload
Solenoid
Load
Solenoid
Bearings
Piston Housing
Female Rotor
Male Rotor
Bearing Housing
Rotor Housing
Discharge Check Valve
Suction
Motor Housing
Oil Reclaim Port
Figure 24 Compressor Description
78 RTHD-SVX01D-EN
Unloader Piston
Bearing Lubricant Port
Rotor Injection Port
Discharge Plenum
Primary Mounting Holes
Slide Valve
Discharge Check Valve
Motor Stator
Page 79
Operating Principles Mechanical
The compressor used by the Series R chiller consists of three distinct sec­tions: the motor, the rotors and the bearing housing. Refer to Figure 24.
Compressor Motor
A two-pole, hermetic, squirrel-cage induction motor directly drives the com­pressor rotors. The motor is cooled by suction vapor drawn from the evapora­tor and entering the end of the motor housing (Figure 24) .
Compressor Rotors
Each Series R chiller uses a semi-hermetic, direct-drive helical rotary type compressor. Excluding the bearings, each compressor has only 3 moving parts: 2 rotors - “male” and “female” - provide compression, and a slide valve that controls capacity. See Figure 24. The male rotor is attached to, and driven by the motor, and the female rotor is, in turn, driven by the male rotor. Separately housed bearing sets are provided at each end of both rotors on the RTHD units. The slide valve is located below (and moves along) the rotors.
The helical rotary compressor is a positive displacement device. Refrigerant from the evaporator is drawn into the suction opening at the end of the motor section. The gas is drawn across the motor, cooling it, and then into the rotor section. It is then compressed and released directly into the discharge ple­num.
There is no physical contact between the rotors and compressor housing. Oil is injected into the bottom of the compressor rotor section, coating both rotors and the compressor housing interior. Although this oil does provide rotor lubrication, its primary purpose is to seal the clearance spaces between the rotors and compressor housing. A positive seal between these internal parts enhances compressor efficiency by limiting leakage between the high pressure and low pressure cavities.
Capacity control is accomplished by means of a slide valve assembly located in the rotor/bearing housing sections of the compressor. Positioned along the bottom of the rotors, the slide valve is driven by a piston/cylinder along an axis that parallels those of the rotors (Figure 24).
Compressor load condition is dictated by the coverage of the rotors by the slide valve. When the slide valve fully covers the rotors, the compressor is fully loaded. Unloading occurs as the slide valve moves away from the suc­tion end of the rotors. Slide valve unloading lowers refrigeration capacity by reducing the compression surface of the rotors.
Slide Valve Movement Movement of the slide valve piston (Figure 24) determines slide valve posi­tion which, in turn, regulates compressor capacity. Compressed vapor flow­ing in to and out of the cylinder governs piston movement, and is controlled by the load and unload solenoid valves.
The solenoid valves (both normally closed) receive “load” and “unload” sig­nals from the CH530, based on system cooling requirements. To load the compressor, the CH530 opens the load solenoid valve. The pressurized vapor flow then enters the cylinder and, with the help of the lower suction pressure acting on the face of the unloader valve, moves the slide valve over the rotors toward the suction end of the compressor.
The compressor is unloaded when the unload solenoid valve is open. Vapor “trapped” within the cylinder is drawn out into the lower-pressure suction area of the compressor. As the pressurized vapor leaves the cylinder, the slide valve slowly moves away from the rotors toward the discharge end of the rotors.
RTHD-SVX01D-EN 79
Page 80
Operating Principles Mechanical
When both solenoid valves are closed, the present level of compressor load­ing is maintained.
On compressor shutdown, the unload solenoid valve is energized. Springs assist in moving the slide valve to the fully-unloaded position, so the unit always starts fully unloaded.
Oil Management System
Oil Separator
The oil separator consists of a vertical cylinder surrounding an exit passage­way. Once oil is injected into the compressor rotors, it mixes with com­pressed refrigerant vapor and is discharged directly into the oil separator. As the refrigerant-and-oil mixture is discharged into the oil separator, the oil is forced outward by centrifugal force, collects on the walls of the cylinder and drains to the bottom of the oil separator cylinder. The accumulated oil then drains out of the cylinder and collects in the oil sump located near the top and in-between the evaporator and condenser shells.
80 RTHD-SVX01D-EN
Page 81
Operating Principles Mechanical
Oil that collects in the oil tank sump is at condensing pressure during com­pressor operation; therefore, oil is constantly moving to lower pressure areas.
Evaporator
Pressure
Transducer Pe
Master Oil Line
Solenoid
Optional Oil Cooler
Oil/Refrigerant
Mixture
Oil Recovery
Oil Filter
Oil Return
Gas Pump
Oil Return Filter
Manual Service Valve
Optical Oil
Detector
Evaporator
RTHD Oil System
Oil Pressure
Transducer
Manual Service Valve
Vent to
Condenser
Oil Sump
Drain Solenoid
Valve
To Bearings
Injection to
Rotors
Vent Line
Fill Solenoid
To Condenser
Pressure
restrictor
Compressor
Oil Separators
Oil Heaters
Liquid/Vapor
Refrigerant Mixture
Valve
Compressor
Discharge
Temperature
Sensor
Primary Oil System
Refrigerant & Oil Mixture-Oil Recovery System
Other
Condenser
Pressure
Transducer
Condenser
EXV
Figure 25 Oil Flow Diagram
Oil Flow Protection Oil flowing through the lubrication circuit flows from the oil sump to the com-
pressor (see Figure 25). As the oil leaves the sump, it passes through a ser­vice valve, an oil cooler (if used), oil filter, master solenoid valve, and another service valve. Oil flow then splits into two distinct paths, each performing a separate function: (1) bearing lubrication and cooling, and (2) compressor oil injection.
Oil flow and quality is proven through a combination of a number of sensors, most notably a pressure transducer and the optical oil level sensor.
RTHD-SVX01D-EN 81
Page 82
Operating Principles Mechanical
If for any reason oil flow is obstructed because of a plugged oil filter, closed service valve, faulty master solenoid, or other source, the oil pressure trans­ducer will read an excessively high pressure drop in the oil system (relative to the total system pressure) and shut down the chiller.
Likewise, the optical oil level sensor can detect the lack of oil in the primary oil system (which could result from improper oil charging after servicing, or oil logging in other parts of the system). The sensor will prevent the compressor from starting or running unless an adequate volume of oil is present. The combination of these two devices, as well as diagnostics associated with extended low system differential pressure and low superheat conditions, can protect the compressor from damage due to severe conditions, component failures, or improper operation.
If the compressor stops for any reason, the master solenoid valve closes; this isolates the oil charge in the sump during “off” periods. With the oil effi­ciently contained in the sump, oil is immediately available to the compressor at start-up. Such flows would otherwise purge oil from the lines and the oil sump, which is an undesirable effect.
To ensure the required system differential pressure is adequate to move oil to the compressor, the CH530 attempts to both control a minimum system differential pressure as well as monitor it. Based on readings from pressure transducers in both the evaporator and condenser , the EXV is modulated to maintain evaporator pressure at a minimum of 25 psid below the condenser pressure. Once the minimum is met, the EXV will return to normal liquid level control (see the paragraph on "Cycle Description". If the differential is significantly lower than required, the unit will trip and initiate a appropriate diagnostics and would enforce a compressor "cool down" period.
To ensure proper lubrication and minimize refrigerant condensation in the oil sump, heaters are mounted on the bottom of the oil sump. An auxilliary con­tact of the compressor starter, energizes these heaters during the compres­sor off cycle to maintain a proper elevation of the oil temperature. The heater element is continuously energized while the compressor is off and does not cycle on temperature.
Oil Filter
All Series R chillers are equipped with replaceable-element oil filters. Each removes any impurities that could foul the compressor internal oil supply gal­leries. This also prevents excessive wear of compressor rotor and bearing surfaces and promotes long bearing life. Refer to the Section 9 for recom­mended filter element replacement intervals.
Compressor Bearing Oil Supply
Oil is injected into the rotor housing where it is routed to the bearing groups located in the motor and bearing housing sections. Each bearing housing is vented to compressor suction so oil leaving the bearings returns through the compressor rotors to the oil separator.
Compressor Rotor Oil Supply
Oil flowing through this circuit enters the bottom of the compressor rotor housing. From there it is injected along the rotors to seal clearance spaces around the rotors and lubricate the contact line between the male and female rotors.
82 RTHD-SVX01D-EN
Page 83
Operating Principles Mechanical
Lubricant Recovery
Despite the high efficiency of the oil separators, a small percentage of oil will get past them, move through the condenser, and eventually end up in the evaporator. This oil must be recovered and returned to the oil sump. The function of active oil return is accomplished by a pressure-actuated pump referred to as the “gas pump.”
The gas pump, mounted just beneath the evaporator, is a cylinder with four ports controlled by two solenoids. The pump serves to return accumulating oil in the evaporator to the compressor at regular time intervals. As the refrig­erant-oil mixture enters the gas pump from the bottom of the evaporator, a fill solenoid opens to allow refrigerant vapor to be vented into the top of the evaporator, and is then closed. A second solenoid then opens to allow refrig­erant at condenser pressure to enter the gas pump. Simultaneously, a check valve prevents reverse flow back into the evaporator. A liquid refrigerant and oil mixture is displaced from the gas pump cylinder and is directed through a filter to the compressor. The oil then combines with oil injected into the com­pressor and returns to the oil sump via the oil separators.
Oil Cooler
The oil cooler is a brazed plate heat exchanger located near the oil filter. It is designed to transfer approximately one ton of heat from the oil to the suction side of the system. Subcooled liquid is the cooling source.
The oil cooler is required on units running at high condensing or low suction temperatures. The high discharge temperatures in these applications increase oil temperatures above the recommended limits for adequate lubri­cation and reduce the viscosity of the oil.
RTHD-SVX01D-EN 83
Page 84
Operating Principles Mechanical
84 RTHD-SVX01D-EN
Page 85
Operator Interface Controls
CH530 Communications Overview
The Trane CH530 control system that runs the chiller consists of several ele­ments:
The main processor collects data, status, and diagnostic information and communicates commands to the starter module and the LLID (for Low Level Intelligent Device) bus. The main processor has an integral display (DynaView).
Higher level modules (e.g. starter) exist only as necessary to support sys­tem level control and communications. The starter module provides con­trol of the starter when starting, running, and stopping the chiller motor. It also processes its own diagnostics and provides motor and compressor protection.
Low level intelligent device (LLID) bus. The main processor communi­cates to each input and output device (e.g. temperature and pressure sensors, low voltage binary inputs, analog input/output) all connected to a four-wire bus, rather than the conventional control architecture of signal wires for each device.
The communication interface to a building automation system (BAS).
A service tool to provide all service/maintenance capabilities.
Main processor and service tool (TechView) software is downloadable from www.Trane.com. The process is discussed later in this section under Tech­View Interface.
DynaView provides bus management. It has the task of restarting the link, or filling in for what it sees as “missing” devices when normal communications has been degraded. Use of TechView may be required.
The CH530 uses the IPC3 protocol based on RS485 signal technology and communicating at 19.2 Kbaud to allow 3 rounds of data per second on a 64­device network. A typical four-compressor RTAC will have around 50 devices.
Most diagnostics are handled by the DynaView. If a temperature or pressure is reported out of range by a LLID, the DynaView processes this information and calls out the diagnostic. The individual LLIDs are not responsible for any diagnostic functions. The only exception to this is the Starter module.
NOTE: It is imperative that the CH530 Service Tool (TechView) be used to facilitate the replacement of any LLID or reconfigure any chiller component. TechView is discussed later in this section.
Controls Interface
DynaView
Each chiller is equipped with the DynaView interface. DynaView has the capa­bility to display additional information to the advanced operator including the ability to adjust settings. Multiple screens are available and text is presented in multiple languages as factory-ordered or can be easily downloaded online.
TechView
TechView can be connected to the DynaView module and provides further data, adjustment capabilities, diagnostics information, downloadable soft­ware, and downloadable languages.
RTHD-SVX01D-EN 83
Page 86
Operator Interface Controls
DynaView Interface
The display on DynaView is a 1/4 VGA display with a resistive touch screen and an LED backlight. The display area is approximately 4 inches wide by 3 inches high (102mm x 60mm).
Figure 26 DynaView
Key Functions
In this touch screen application, key functions are determined completely by software and change depending upon the subject matter currently being dis­played. The basic touch screen functions are outlined below.
CAUTION Equipment Damage!
Putting excessive pressure on the touch screen could cause damage. It takes less that 15 lbs of force to break the screen.
Radio Buttons
Radio buttons show one menu choice among two or more alternatives, all vis­ible. (the AUTO button in Figure 26.) The radio button model mimics the but­tons used on old-fashioned radios to select stations. When one is pressed, the one that was previously pressed “pops out” and the new station is selected. In the DynaView, model the possible selections are each associated with a button. The selected button is darkened, presented in reverse video to indicate it is the selected choice. The full range of possible choices as well as the current choice is always in view.
Spin Value Buttons
Spin values are used to allow a variable setpoint to be changed, such as leav­ing water setpoint. The value increases or decreases by touching the incre­ment (+) or decrement (-) arrows.
84 RTHD-SVX01D-EN
Page 87
Operator Interface Controls
Action Buttons
Action buttons appear temporarily and provide the user with a choice such as
Enter or Cancel.
File Folder Tabs
File folder tabs are used to select a screen of data. Just like tabs in a file folder, these serve to title the folder/screen selected, as well as provide navi­gation to other screens. In DynaView, the tabs are in one row across the top of the display. The folder tabs are separated from the rest of the display by a horizontal line. Vertical lines separate the tabs from each other. The folder that is selected has no horizontal line under its tab, thereby making it look like a part of the current folder (as would an open folder in a file cabinet). The user selects a screen of information by touching the appropriate tab.
Display Screens
Basic Screen Format
The basic screen format appears as:
Main
File Folder Tabs
Page Scroll (up)
Fixed Display
Contrast control (lighter)
Reports
Line Scroll (up/down)
Settings
Page Scroll (down)
Contrast control (darker)
The file folder tabs across the top of the screen are used to select the various display screens.
The main body of the screen is used for description text, data, setpoints, or keys (touch sensitive areas). The Chiller Mode is displayed here.
The double up arrows cause a page-by-page scroll either up or down. The sin­gle arrow causes a line by line scroll to occur. At the end of the page, the appropriate scroll bar will disappear.
A double arrow pointing to the right indicates more information is available about the specific item on that same line. Pressing it will bring you to a sub­screen that will present the information or allow changes to settings.
The bottom of the screen (Fixed Display) is present in all screens and con­tains the following functions. The left circular area is used to reduce the con­trast/viewing angle of the display. The right circular area is used to increase the contrast/viewing angle of the display. The contrast may require re-adjust­ment at ambient temperatures significantly different from those present at last adjustment.
RTHD-SVX01D-EN 85
Page 88
Operator Interface Controls
The other functions are critical to machine operation. The AUTO and STOP keys are used to enable or disable the chiller. The key selected is in black (reverse video). The chiller will stop when the STOP key is touched and after completing the Run Unload mode.
Touching the AUTO key will enable the chiller for active cooling if no diagnos­tic is present. (A separate action must be taken to clear active diagnostics.)
The AUTO and STOP keys, take precedence over the Enter and Cancel keys. (While a setting is being changed, AUTO and STOP keys are recognized even if Enter or Cancel has not been pressed.)
The ALARMS button appears only when an alarm is present, and blinks (by alternating between normal and reverse video) to draw attention to a diagnos­tic condition. Pressing the ALARMS button takes you to the corresponding tab for additional information.
Keypad/Display Lockout Feature
DISPLAY AND TOUCH SCREEN ARE LOCKED
ENTER PASSWORD TO UNLOCK
321
653
987
Enter
NOTE: The DynaView display and Touch Screen Lock screen is shown below. This screen is used if the Display and touch screen and lock feature is enabled. Thirty minutes after the last keystroke, this screen is displayed and the Display and Touch Screen is locked out until the sequence “159 <ENTER>” is pressed.
Until the proper password is entered, there will be no access to the Dyna­View screens including all reports, setpoints, and Auto/Stop/Alarms/Inter­locks.
The password “159” can not be changed from either DynaView or TechView.
0
Cancel
86 RTHD-SVX01D-EN
Page 89
Operator Interface Controls
Main Screen
The Main screen is a summary of the chiller’s activity.The Main screen is the default screen. After an idle time of 30 minutes the CH530 will display the Main screen with the first data fields.
The remaining items (listed in the following table) are viewed by selecting the up/down arrow icons.
Figure 27. Main Screen
Table 17 Main Screen Items
Description Resolution Units
Chiller Mode (>> submodes) Text
Evap Ent/Lvg Water Temp X.X F / C
Cond Ent/Lvg Water Temp X.X F / C
Active Chilled Water Setpoint (>>source) X.X F / C
Average Line Current X % RLA
Active Current Limit Setpoint (>>source) X % RLA
Active Base Loading Setpoint (>>source) X %
Active Ice Termination Setpoint (>>source) X.X F / C
Outdoor Air Temperature X.X F / C
Software Type RTH Text
Software Version X.XX Text
RTHD-SVX01D-EN 87
Page 90
Operator Interface Controls
Chiller Operating Modes
The machine-operating mode indicates the operational status of the chiller. A sub-screen with additional mode summary information is provided by selec­tion of an additional information icon (>>). The operating mode line will remain stationary while the remaining status items scroll with the up/down arrow keys. The following is a list of all Top Level and Sub-modes.
Table 18 Operating Modes
Chiller Modes Description
MP Resetting
1
Stopped
1
The chiller is not running and cannot run without intervention. Further information is provided by the sub-mode:
Local Stop
2
Chiller is stopped by DynaView Stop button command- cannot be remotely overridden.
Panic Stop
2
Chiller is stopped by the DynaView Panic Stop (by pressing Stop button twice in succession) - previous shutdown was manually commanded to shutdown immediately without a run-unload or pumpdown cycle - cannot be remotely overridden.
2
Diagnostic Shutdown - Manual Reset
The chiller is stopped by a diagnostic that requires manual inter­vention to reset.
Other sub-modes are possible in conjunction with at least one of the above modes - See items below for their descriptions:
Diagnostic Shutdown - Auto Reset
Start Inhibited by External Source
Start Inhibited by BAS
2
Waiting for BAS Communications
Ice Building to Normal Transition
Ice Building is Complete
Waiting for Oil Level
Run Inhibit
1
2
2
2
2
2
2
The chiller is currently being inhibited from starting (and running*), but may be allowed to start if the inhibiting or diagnostic condition is cleared. Further information is provided by the sub-mode:
2
Diagnostic Shutdown - Auto Reset
The entire chiller is stopped by a diagnostic that may automatically clear.
Start Inhibited by External Source
2
The chiller is inhibited from starting (and running) by the "external stop" hardwired input.
Start Inhibited by BAS
2
The chiller is inhibited from starting (and running) by command from a Building Automation System via the digital communication link (com 4 or com 5).
1 - Top Level Mode 2 - Sub Level Mode
88 RTHD-SVX01D-EN
Page 91
Operator Interface Controls
Table 18 Operating Modes
Chiller Modes Description
Waiting for BAS Communications2 This is a transient mode - 15-min. max, and is only possible if the
chiller is in the Auto - Remote command mode. After a power up reset, it is necessary to wait for valid communication from a Building Automation System (Tracer) to know whether to run or stay inhibited. Either valid communication will be received from the Building Automation System (e.g. Tracer), or a communication diagnostic ultimately will result. In the latter case the chiller will revert to Local control.
2
Power Up Delay Inhibit min:sec
Ice Building to Normal Transition
Ice Building is Complete
2
2
Low Diff Rfgt Pres Cool-Down Time mn:sec
1
Auto
Waiting For Evap Water Flow
Waiting for Need to Cool
Waiting to Start
1
Waiting For Cond Water Flow
Waiting for Oil Level
2
Cond Water Pump PreRun Time
2
2
2
2
min:sec
1 - Top Level Mode 2 - Sub Level Mode
The compressor is currently being inhibited from starting as part of the power up start delay (or staggered start) feature. This feature is intended to prevent multiple chillers from all starting simulta­neously if power is restored to all chillers simultaneously.
The chiller is inhibited from running for a brief period of time if it is
commanded from active ice building mode into normal cooling mode via the ice building hardwired input or Tracer. This allows time for the external system load to "switchover" from an ice bank to the chilled water loop, and provides for a controlled pull down of the loop's warmer temperature. This mode is not seen if the ice making is automatically terminated on return brine temperature per the mode below.
The chiller is inhibited from running as the Ice Building process has been normally terminated on the return brine temperature. The chiller will not start unless the ice building command (hardwired input or Building Automation System command) is removed or cycled.(contact opened)
2
See oil flow protection spec
The chiller is not currently running but can be expected to start at any moment given that the proper conditions and interlocks are satisfied. Further information is provided by the sub-mode:
The chiller will wait up to 4 minutes in this mode for evaporator water flow to be established per the flow switch hardwired input.
The chiller will wait indefinitely in this mode, for an evaporator leaving water temperature higher than the Chilled Water Setpoint plus the Differential to Start.
The chiller is not currently running and there is a call for cooling but start is delayed by certain interlocks or proofs. Further information is provided by the sub-mode:
The chiller will wait up to 4 minutes in this mode for condenser water flow to be established per the flow switch hardwired input.
The chiller will wait up to 2 minutes in this mode for oil level to appear in the oil tank.
The chiller will wait up to 30 minutes (user adjustable) in this mode to allow the condenser water loop to equalize in temperature
RTHD-SVX01D-EN 89
Page 92
Operator Interface Controls
Table 18 Operating Modes
Chiller Modes Description
Compressor Restart Inhibit Time 2 min:sec
Waiting For EXV Preposition
Running
Unit is Building Ice
Establishing Min Capacity - High Disch Temp
Base Loaded
1
2
2
2
Capacity Control Softloading
Current Control Softloading
2
2
2
EXV Controlling Differential Pressure
Running - Limited
1
Capacity Limited by High Cond Press
Capacity Limited by Low Evap Rfgt
2
Temp
1 - Top Level Mode 2 - Sub Level Mode
The compressor is currently unable to start due to its restart inhibit timer. A given compressor is not allowed to start until 5 minutes (adj) has expired since its last start.
The Chiller will wait for the time it takes the EXV to get to its commanded pre-position prior to starting the compressor. This is typically a relatively short delay and no countdown timer is necessary (less than 15 seconds).
The chiller, circuit, and compressor are currently running. Further information is provided by the sub-mode:
The chiller is running in the Ice Building Mode, and either at or moving towards full capacity available. Ice mode is terminated either with the removal of the ice mode command or with the return brine temperature falling below the Ice Termination Setpoint.
The compressor is running and is being forced loaded, without regard to the leaving water temperature control, to prevent tripping on high compressor discharge temperature.
Chiller is running in "Base Load" operation where the capacity of the chiller is controlled to maintain a given current per an adjustable set point. The chiller is forced to run without regard to the chilled water temperatures and the differential to start and stop.
The chiller is running, but loading is influenced by a gradual 'pulldown" filter on the chilled water temperature setpoint The settling time of this filter is user adjustable as part of the softload control feature.
The chiller is running, but loading is influenced by a gradual filter on the current limit setpoint The starting current and the settling time of this filter is user adjustable as part of the softload control feature.
2
Liquid level control of the Electronic Expansion Valve has tempo­rarily been suspended. The EXV is being modulated to control for a minimum differential pressure. This control implies low liquid levels and higher approach temperatures, but is necessary to provide minimum oil flow for the compressor until the condenser water loop can warm up to approx 50F.
The chiller, circuit, and compressor are currently running, but the operation of the chiller/compressor is being actively limited by the controls. Further information is provided by the sub-mode.
2
The circuit is experiencing condenser pressures at or near the condenser limit setting. The compressor will be unloaded to prevent exceeding the limits.
The circuit is experiencing saturated evaporator temperatures at or near the Low Refrigerant Temperature Cutout setting. The compressors will be unloaded to prevent tripping.
90 RTHD-SVX01D-EN
Page 93
Operator Interface Controls
Table 18 Operating Modes
Chiller Modes Description
Capacity Limited by Low Liquid Level2The circuit is experiencing low refrigerant liquid levels and the EXV
is at or near full open. The compressor will be unloaded to prevent tripping.
Capacity Limited by High Current
2
Capacity Limited by Phase Unbalance
Note: Other normal running modes (see above) may also appear under this top level mode.
Shutting Down
Local Stop
Panic Stop
1
2
2
Diagnostic Shutdown - Manual Reset
Diagnostic Shutdown - Auto Reset
2
Compressor Unloading
Start Inhibited by External Source
Start Inhibited by BAS
Ice Building to Normal Transition
Ice Building is Complete
Evap Pump Off Delay
Service Override
1
Service Pumpdown
min:sec The compressor is in its "run - unload" state in which it is being
2
2
2
2
2
min:sec
2
1 - Top Level Mode 2 - Sub Level Mode
The compressor is running and its capacity is being limited by high currents. The current limit setting is 120% RLA (to avoid overcurrent trips).
2
The compressor is running and its capacity is being limited by excessive phase current unbalance.
The chiller is still running but shutdown is imminent. The chiller is going through a compressor run-unload. sequence. Shutdown is necessary due to one (or more) of the following sub-modes:
Chiller is in the process of being stopped by DynaView Stop button command.
Chiller is in the process of being stopped by DynaView Panic Stop command.
2
Chiller is in the process of being stopped by a Latching Diagnostic shutdown - Manual Reset is required to clear.
2
Chiller is in the process of being stopped by a Diagnostic shutdown
- Automatic clearing of the diagnostic is possible if condition clears.
continuously unloaded for 40 sec prior to shutdown.
Chiller is in the process of being stopped by the External Stop hardwired input.
The Chiller is in the process of shutdown due to a command from the Building Automation System (e.g. Tracer).
Chiller is in the process of being stopped by the transition from ice to normal cooling mode with the removal of the ice making command via the hardwired input or Building Automation System (e.g. Tracer).
Chiller is in the process of being stopped as the Ice Building process is being normally terminated on the return brine temperature.
The Chiller is in a Service Override mode
The chiller, circuit, and compressor is running via a manual command to perform a Service Pumpdown. Both evap and condenser water pumps are commanded to run. The EXV is held wide open, but the manual liquid line service valve should be closed.
RTHD-SVX01D-EN 91
Page 94
Operator Interface Controls
Reports Screen
The Reports tab allows a user to select from a list of reports headings. Each report will generate a list of status items as defined in the tables that follow.
Figure 28. Reports Screen
Chiller Log
Table 19 Report Screen Items
Description Resolution Units
Evaporator Evap Entering Water Temp ± XXX.X F / C
Evap Leaving Water Temp
Evap Sat Rfgt Temp
Evap Rfgt Pressure XXX.X psi / kPa
Evap Approach
Evap Water Flow Switch Status (Flow, No Flow) Text
Expansion Valve Position XXX.X Percent
Expansion Valve Position Steps XXXX Steps
Evaporator Liquid Level X.X in / mm
Condenser Cond Entering Water Temp ± XXX.X F / C
Cond Leaving Water Temp
Cond Sat Rfgt Temp
Cond Rfgt Pressure XXX.X psi / kPa
Cond Approach Temp
Cond Water Flow Switch Status (Flow, No Flow) Text
Cond Head Pressure Ctrl Command XXX %
± XXX.X F / C ± XXX.X F / C
± XXX.X F / C
± XXX.X F / C ± XXX.X F / C
± XXX.X F / C
92 RTHD-SVX01D-EN
Page 95
Operator Interface Controls
Table 19 Report Screen Items
Description Resolution Units
Outdoor Air Temperature ± XXX.X F / C
Compressor
Compressor Starts XXXX Integer
Compressor Running Time XXXX:XX hr:min
System Rfgt Diff Pressure XXX.X psi / kPa
Oil Pressure XXX.X psi / kPa
Compressor Rfgt Discharge Temp
Discharge Superheat
% RLA L1 L2 L3 XXX.X Percent RLA
Amps L1 L2 L3 XXXX Amps
Volts AB BC CA XXXX Volts
ASHRAE Chiller Log
Current Time/Date XX:XX mmm dd, yyyy Date / Time
Operating Mode: Text
Amps L1 L2 L3 XXXX Amps
Volts AB BC CA XXXX Volts
Active Chilled Water Setpoint XXX.X F / C
Active Current Limit Setpoint XXX.X F / C
Refrigerant Monitor XXX.X Ppm
Compressor Starts XXXX Integer
Compressor Running Time XX:XX Hours:Minute
Compressor Rfgt Discharge Temp XXX.X F / C
Evap Entering Water Temp XXX.X F / C
Evap Leaving Water Temp XXX.X F / C
Evap Sat Refrigerant Temp XXX.X F / C
Evap Rfgt Pressure XXX.X psi / kPa
Evap Approach Temp: XXX.X F / C
Evap Water Flow Switch Status Text
Cond Entering Water Temp XXX.X F / C
Cond Leaving Water Temp XXX.X F / C
Cond Sat Rfgt Temp XXX.X F / C
Cond Rfgt Pressure XXX.X psi / kPa
Condenser Approach Temp XXX.X F / C
Cond Water Flow Switch Status Text
± XXX.X F / C ± XXX.X F / C
RTHD-SVX01D-EN 93
Page 96
Operator Interface Controls
Settings Screen
The Settings screen provides the user the ability to adjust settings. The layout provides a list of sub-menus, organized by typical subsystem.
Figure 29. Settings Screen
Table 20 Settings Screen Items
Description Resolution or (Text), Default Units
Chiller Front Panel Chilled Water Setpt ± XXX.X (3)
Front Panel Current Limit Setpt XXX (4) Percent RLA
Front Panel Base Load Cmd On/Auto Text
Front Panel Base Load Setpt XXX Percent
Front Panel Ice Build Cmd On/Auto Text
Front Panel Ice Termn Setpt XXX.X F / C
Ice to Normal Cool Timer Setpt (0-10), 5 min Minutes
Differential to Start XXX.X F / C
Differential to Stop XXX.X F / C
Setpoint Source (BAS/Ext/FP, Ext/ Front Panel, Front Panel),
BAS/Ext/FP
Features
Chilled Water Reset (Constant, Outdoor, Return, Disable), Disable Text
Return Reset Ratio XXX Percent
Return Start Reset XXX.X F / C
Return Maximum Reset XXX.X F / C
Text
94 RTHD-SVX01D-EN
Page 97
Operator Interface Controls
Table 20 Settings Screen Items
Description Resolution or (Text), Default Units
Outdoor Reset Ratio XXX Percent
Outdoor Start Reset XXX.X F / C
Outdoor Maximum Reset XXX.X F / C
Ext Chilled Water Setpoint (Enable, Disable), Disable Text
Ext Current Limit Setpoint (Enable, Disable), Disable Text
Ice Building (Enable, Disable), Disable Text
Ext Base Loading Setpoint (Enable, Disable), Disable Text
Mode Overrides
Evap Water Pump (Auto, On), Auto Text
Cond Water Pump (Auto, On), Auto (8) Text
Expansion Valve Control (Auto, Manual) Auto Text
Slide Valve Control (Auto, Manual) Auto Text
Service Pumpdown Status: (Avail, Not Avail, Pumpdown) Text
Display Settings
Date Format ("mmm dd, yyy", "dd-mmm-yyyy"),
"mmm dd, yyy
Date Text
Text
Time Format (12-hour, 24-hour), 12-hour Text
Time of Day Text
Keypad/Display Lockout (Enable, Disable), Disable (5) Text
Display Units (SI, English) English Text
Pressure Units (Absolute, Gauge), Absolute Text
Language Selection Downloaded fron TechView Text
RTHD-SVX01D-EN 95
Page 98
Operator Interface Controls
Diagnostic Screen
Figure 30. Diagnostics Screen
The diagnostic screen is accessible by depressing the Alarms enunciator. A verbal description will be provided.
A scrollable list of the last (up to 10) active diagnostics is presented. Per­forming a “Reset Diags” will reset all active diagnostics regardless of type, machine or circuit. The scrollable list will be sorted by time of occurrence.
If a informational warning is present, the "Alarms" key will be present but not flashing. If a diagnostic shutdown (normal or immediate)has occurred, the "Alarm" key will display that is flashing. If no diagnostics exist, the "Alarm" key will not be present.
The "Operating Mode At Last Diagnostic" text above the most recent diagnos­tic will display a sub-screen listing the operating mode and submodes at the time of the last diagnostic.
96 RTHD-SVX01D-EN
Page 99
TechView
TechView is the PC (laptop) based tool used for servicing Tracer CH530 Chillers. Technicians that make any chiller control modification or service any diagnostic with Tracer CH530 must use a laptop running the software application “TechView.” TechView is a Trane application developed to minimize chiller downtime and aid the technicians' understanding of the chiller operation and service requirements.
NOTE: Important: Performing any Tracer CH530 service functions should be done only by a properly trained service technician. Please contact your local Trane service agency for assistance with any service requirements.
TechView software is available via Trane.com. (http://www.trane.com/commercial/software/tracerch530/) This download site provides a user the TechView installation software and
CH530 main processor software that must be loaded onto their PC in order to service a CH530 main processor. The TechView service tool is used to load software into the Tracer CH530 main processor.
RTHD-SVX01D-EN 97
Page 100
TechView
Minimum PC requirements to install and operate TechView
Pentium II or higher processor
128Mb RAM
1024 x 768 resolution of display
56K modem
9-pin RS-232 serial connection
Operating system - Windows 2000
Microsoft Office (MS Word, MS Access, MS Excel)
Parallel Port (25-pin) or USB Port
NOTE: TechView was designed for the preceding listed laptop configuration. Any variation will have unknown results. Therefore, support for TechView is limited to only those operating systems that meet the specific configuration listed here. Only computers with a Pentium II class processor or better are supported; Intel Celeron, AMD, or Cyrix processors have not been tested.
TechView is also used to perform any CH530 service or maintenance function. Servicing a CH530 main processor includes:
Updating main processor software
Monitoring chiller operation
Viewing and resetting chiller diagnostics
Low Level Intelligent Device (LLID) replacement and binding
Main processor replacement and configuration modifications
Setpoint modifications
Service overrides
98 RTHD-SVX01D-EN
Loading...