Trane RAU-SVX01B-E4 Installation Operation & Maintenance

Page 1
Installation Operation Maintenance
RAU Air Cooled Condensing Unit Sizes 190 – 260 – 300 – 350 – 400
450 – 500 – 600 – 700 – 800
To be used with the
manual of SMM module
Reference L80 IM 022 E
Page 2
© American Standard Inc. 2004
RAU-SVX01B-E4
General information
Foreword
These installation, operation and maintenance instructions are given as a guide to good practice in the installation, putting into service, operation, and maintenance by the user, of RAU Units. They do not contain full service procedures necessary for the continued successful operation of this equipment; The services of a qualified technician should be employed through the medium of a maintenance contract with a reputable service company.
Warranty
Warranty is based on the general terms and conditions of the constructor. The warranty is void if the equipment is repaired or modified without the written approval of Trane, if the operating limits are exceeded or if the control system or the electrical wiring is modified. Damage due to misuse, lack of maintenance or failure to comply with the manufacturer’s instructions or recommendations is not covered by the warranty obligation. If the user does not conform to the rules of chapter ”Maintenance”, it may entail cancellation of warranty and liabilities by the constructor.
Reception
On arrival, inspect the unit before signing the delivery note. Specify any damage on the delivery note, and send a registered letter of protest to the last carrier of the goods within 72 hours of delivery. Notify the local Sales Office at the same time. The unit should be totally inspected within 7 days of delivery. If any concealed damage is discovered, send a registered letter of protest to the carrier within 7 days of delivery and notify the local Office. Units are shipped with the refrigerant operating or holding charge and should be examined with an electronic leak detector to determine the hermetic integrity of the unit. The refrigerant charge is not included in the standard Warranty Cover.
General information
About this manual
Caution appears at appropriate places in this instruction manual. Your personal safety and the proper operation of this machine require that you follow them carefully. The constructor assumes no liability for installations or servicing performed by unqualified personnel.
About the unit
These RAU units are assembled, pressure tested, dehydrated, charged and run tested before shipment. The information contained in this manual applies to units designated.
Refrigerant
The refrigerant provided by the constructor meets all the requirements of our units. When using recycled or reprocessed refrigerant, it is advisable to ensure its quality is equivalent to that of a new refrigerant. For this, it is necessary to have a precise analysis made by a specialized laboratory. If this condition is not respected, the constructor warranty could be cancelled.
Page 3
RAU-SVX01B-E4
Contents
3
Foreword 2
Warranty 2
Reception 2
General 2
Refrigerant 2
Installation
Unit nameplate 4
Installation instructions 4
Handling 4
Refrigerant lines 5
Refrigerant charge 6
Oil charge 6
General unit characteristics 7
Electrical connections 10
General start-up
Preparation 11
Start-up 11
Operation
Control and unit operation 13
Seasonal shutdown and start-up 13
Weekly start up and week-end shutdown 13
Maintenance
Maintenance instructions 14
Installation checklist 15
Troubleshooting guide 16
Operating pressures 19
Control parameters of the SMM control module 26
Safety recommendations 28
Maintenance contract 28
Training 28
Page 4
4 RAU-SVX01B-E4
Installation
For minimum clearance, consult the certified submittals, which are available on request from your Trane Agency.
Unit nameplate
The unit nameplate gives the complete model reference numbers. The unit power rating is shown, and power supplies should not deviate by more than 5 % from the rated power. Compressor motor amperage is shown in box I.MAX. The customer’s electrical installation must be able to withstand this current.
Installation instructions
Foundations
No special foundations are required, provided the supporting surface is flat and level, and can withstand the weight or the unit.
Anti-vibration rubber pads
They are supplied as standard with the machine, and should be placed between the supporting floor and the unit to attenuate vibrations.
- 4 pads for the sizes 190 to 300
- 6 pads for the sizes 350 to 800
- Trane does not allow to install spring isolators.
Clearance
Respect recommended clearance around the unit to allow maintenance operation to take place without obstruction and recommended clearance around condenser.
Caution: Unit operation is function of the air temperature. Any recycling of the air fed out by the fans will increase the air intake temperature over the condenser fins and can result in high pressure cut-out. In this case the standard operating conditions are modified. Operation of the unit may be affected by an increase in air temperature on the condenser. When the units are positioned in a windy area, avoid all the risks of air­cooled recycling.
See submittals
Handling - Figure 2
Note: The plates welded at the end of the bases must not be used for handling.
Figure 2
Dimensions of recommended slings and swing-bar:
RAU 190 260 300 350 400 450 50 0 600 700 800 A (mm) 1500 1500 1500 1500 1500 1500 2400 2400 2300 2300 B (mm) 1800 1800 1800 1800 1800 1800 1800 1800 2200 2200 Weight - crated (kg) 555 625 691 869 959 985 1123 1251 1695 1754
A
B
Page 5
5RAU-SVX01B-E4
Refrigerant lines
Calculating and fixing the capacity of refrigerant lines is necessary to assure the oil return to the compressor, avoid refrigerant phase changes and limit pressure drop.
Liquid lines
Calculate capacity of liquid line, as per the following criteria.
1. Maximum load operating
conditions.
2. To avoid any evaporation risk:
- Consider the vertical risers
- Maximum pressure drop must
not exceed 1 to 2°C
3. Liquid circulation speed in a 0.5
to 2m/s range.
Discharge lines
Discharge lines should be calculated to obtain the gas displacement speed in horizontal and vertical lines required to drive compressor oil. Determine diameter of discharge lines as per the following criteria.
1. Speed above 2,5 m/s horizontally.
(Consider minimum speed at minimum load)
2. Speed above 5,0 m/s vertically
(Vertical risers, consider speed at minimum load)
3. Maximum speed 20 m/s.
4. Horizontal pipe run must be
pitched of 1cm/m in the same direction as the refrigerant circulation
5. An oil trap is necessary for
vertical risers greater than 3m. For major elevations add an intermediate oil trap every 5m.
6. Maximum pressure drop between
20 to 50 kPa
7. Install a filter drier adapted to
refrigerant capacity.
Insulation of refrigerant lines
Insulate refrigerant lines from building itself to avoid transmission to building structure of vibrations normally caused by pipework. Also avoid bypassing the unit's damping system by fixing the refrigerant lines or the electrical ducts very rigidly.Vibrations may propagate into building structure through rigidly fixed refrigerant lines.
Pressure tests. Leak detection
During operations, take the following precaution:
1. Neither oxygen nor acethylene should be used instead of refrigerant and nitrogen to detect leaks, otherwise a violent explosion may occur.
2. Always use valves and manometers to check the test pressure in system. Excessive pressure may either cause pipes to rupture, damage unit, or cause an explosion, causing possible physical injury.
Carry out liquid line and hot gas line pressure tests in accordance with current standards. The test pressures applied to the liquid line and the hot gas suction line must comply with the country's standards.
Caution: Do not go more than 0.7 bar above the high pressure switch setpoint.
Introduce enough refrigerant into circuit for 85 to 100 kPa pressure, pump-injecting dry nitrogen, and raise pressure to 100 kPa. Search for possible leaks using detector. This operation should be carried out with great care throughout the system. If leaks are detected, reduce system pressure, and repair defective component. Repeat test process, to check that the repair can withstand rated pressure.
Caution: Unit is delivered with a refrigerant holding charge and isolating valves.
Page 6
6 RAU-SVX01B-E4
Oil charge
Attention: The oil quantity necessary for the split system has also to be adjusted according to the diameter and the length of the refrigerant piping work.
Important note: These operations have to be performed by a specialist according to the rules of the art. The results have to be written on a start up record by the Trane engineer or the client's specialist who has performed this start up. The quantiy of refrigerant and oil added are at the client's charges.
Refrigerant charge (all split system types)
After system pressure and vacuum testing, fill up unit with refrigerant as per indicated in table Refrigerant Charge. The refrigerant complement will be charged according to the diameter and the length of the refrigerant piping work up to obtain the correct superheat and subcooling temperatures.
Refrigerant Charge
Size 190 260 300 350 400 450 500 600 700 800 Circuit A (kg) 9 10 13 9 13 13 10 13 24 24 Circuit B (kg) - - - 6 6 6 10 13 24 24
Page 7
7RAU-SVX01B-E4
Table 1 - R22 Units Characteristics
RAU 190 RAU 260 RAU 300 RAU 350 RAU 400 RAU 450 RAU 500 RAU 600 RAU 700 RAU 80 0
R22 R22 R22 R22 R22 R22 R22 R22 R22 R22
Performances (1)
Gross cooling capacity (1) (kW) 61,7 75,2 91,4 107,1 121,7 133,6 150,5 182,7 220,2 247,5 Power input in cooling (1) (kW) 18,6 25,6 30,5 33,3 39,1 45,5 51,2 60,8 70,8 83,4 Main Power supply 400/3/50 400/3/50 400/3/50 400/3/50 400/3/50 40 0/3/50 400/3/50 400/3/50 400/3/50 400/3/50 Sound Power Level (5) (dB(A)) 88 90 91 91 92 93 93 94 98 98
Units Amps
Nominal (4) (A) 34,4 43,7 53 60,9 70,2 79,5 87,4 106 121,8 140,4 Start-up Amps (A) 137 193 202 210 219 228 236 255 271 289 Max supply cable size (mm2)353535 50 50 95 95 95 150 150
Compressor
Number 2 2 2 3 33446 6 Type Scroll Scroll Scroll Scroll Scroll Scroll Scroll Scroll Scroll Scroll Model 10T+10T 10T+15T 2x15T 2x10T+15T 10T+2x15T 3x15T 2x(10T+15T) 4x15T 4x10T+2x15T 2x10T+4x15T Speeds number 1 1 1 1 11111 1 Motors Number 1 1 1 1 11111 1 Rated Amps (2)(4) (A) 30 42 50 55 65 75 84 101 109 130 Locked rotor Amps (2) (A) 120 175 175 175 175 175 175 175 175 175 Motor RPM (rpm) 2900 2900 2900 2900 2900 2900 2900 290 0 2900 2900 Sump Heater (2) (W) 50W - 40 0V 50W - 400V 50W - 400V 50W - 40 0V 50W - 400V 50W - 400V 50W - 400V 50W - 400V 50W - 400V 50W - 400V
Liquid and Suction connection
Suction connection brazed 1"5/8 1"5/8 1"5/8 1"5/8 1"5/8 1"5/8 1"5/8 1"5/8 2"1/8 2"1/8 Liquid connection brazed 7/8" 7/8" 7/8" 7/8" 7/8" 7/8" 7/8" 7/8" 1"1/8 1"1/8
Coil
Type Plate Fin Plate Fin Plate Fin Plate Fin Plate Fin Plate Fin Plate Fin Plate Fin Plate Fin Plate Fin Tube size (mm) 9,52 9,52 9,52 9,52 9,52 9,52 9,52 9,52 9,52 9,52 Tube type Smooth Smooth Smooth Smooth Smooth Smooth Smooth Smooth Smooth Smooth Height (mm) 1219 1219 1219 1219 1219 1219 1219 1219 1219 1219 Length (mm) 2743 2743 2743 3455 4115 4115 5486 5486 5486 5486 Face Area (m2) 3,34 3,34 3,34 4,21 5,02 5,02 6,69 6,69 6,69 6,69 Rows # 2,0 2,0 3,0 3,0 3,0 3,0 2,0 3,0 3,0 3,0 Fins per foot (fpf) # 156,0 156,0 156,0 156,0 156,0 156,0 156,0 156,0 156,0 156,0
Fan
Type Propeller Propeller Propeller Propeller Propeller Propeller Propeller Propeller Propeller Propeller Number 2 2 2 3 33446 6 Diameter (mm) 962 962 962 962 962 962 962 962 962 962 Drive type Direct Direct Direct Direct Direct Direct Direct Direct Direct Direct Speeds number 1 1 1 1 11111 1 Air flow (m3/h) 2700 0 27000 2530 0 3590 0 3790 0 3790 0 5400 0 50700 89100 89100 Motors Number 2 2 2 3 33446 6 Motor HP (2) (kW) 0,85 0,85 0,85 0,85 0,85 0,85 0,85 0,85 1,88 1,88 Rated Amps (2) (A) 2,4 2,4 2,4 2,4 2,4 2,4 2,4 2,4 4,2 4,2 Locked rotor Amps (2) (A) 6,8 6,8 6,8 6,8 6,8 6,8 6,8 6,8 14,7 14,7 Motor RPM (rpm) 680 680 680 680 680 680 680 680 915 915
Dimensions
Height (mm) 1582 1582 1582 1582 1582 1582 1584 1584 1598 1598 Length (mm) 2061 2061 2061 2921 2921 2921 2225 2225 3090 3090 Width (mm) 995 995 995 995 995 995 1865 1865 1948 1948 Weight uncrated (kg) 514 584 650 810 900 926 1040 1168 1575 1634 Weight crated (kg) 555 625 691 869 959 985 1123 1251 1695 1754
System Data
Refrigerant circuit 111222222 2
Refrigerant Charge (3)
Circuit A & B (kg)
(1) at 7°C SST and 35°C ambiant (2) per motor (3) per circuit (4) 5°C sat suction temp. - 60°C sat discharge temp. (5) In accordance with ISO 3746
Split
system
Split
system
Split
system
Split
system
Split
system
Split
system
Split
system
Split
system
Split
system
Split
system
Page 8
8 RAU-SVX01B-E4
Table 2 - R134a Units Characteristics
RAU 190 RAU 260 RAU 300 RAU 350 RAU 400 RAU 450 RAU 500 RAU 600 RAU 700 RAU 80 0
R134a R134a R134a R134a R134a R134a R134a R134a R134a R134a
Performances (1)
Gross cooling capacity (1) (kW) 43,8 53,2 63,9 75,4 85,1 93,6 106,3 127,9 153,8 172,7 Power input in cooling (1) (kW) 12,1 15,8 18,5 21,3 24,3 27,7 31,5 37,0 47,1 53,9 Main Power supply 400/3/50 400/3/50 400/3/50 400/3/50 400/3/50 40 0/3/50 400/3/50 400/3/50 400/3/50 400/3/50 Sound Power Level (5) (dB(A)) 88 90 91 91 92 93 93 94 98 98
Units Amps
Nominal (4) (A) 25,4 32,4 39,4 45,1 52,1 59,1 64,8 78,8 90,2 104,2 Start-up Amps (A) 137 193 202 210 219 228 236 255 271 289 Max supply cable size (mm2)3535355050959595150 150
Compressor
Number 2 2 2 3 33446 6
Type Scroll Scroll Scroll Scroll Scroll Scroll Scroll Scroll Scroll Scroll Model 10T+10T 10T+15T 2x15T 2x10T+15T 10T+2x15T 3x15T 2x(10T+15T) 4x15T 4x10T+2x15T 2x10T+4x15T Speeds number 1 1 1 1 11111 1 Motors Number 1 1 1 1 11111 1 Rated Amps (2)(4) (A) 30 42 50 55 65 75 84 101 109 130 Locked rotor Amps (2) (A) 120 175 175 175 175 175 175 175 175 175 Motor RPM (rpm) 2900 2900 2900 2900 2900 2900 2900 290 0 2900 2900 Sump Heater (2) (W) 50W - 40 0V 50W - 400V 50W - 400V 50W - 40 0V 50W - 400V 50W - 400V 50W - 400V 50W - 400V 50W - 400V 50W - 400V
Liquid and Suction connection
Suction connection brazed 1"5/8 1"5/8 1"5/8 1"5/8 1"5/8 1"5/8 1"5/8 1"5/8 2"1/8 2"1/8 Liquid connection brazed 7/8" 7/8" 7/8" 7/8" 7/8" 7/8" 7/8" 7/8" 1"1/8 1"1/8
Coil
Type Plate Fin Plate Fin Plate Fin Plate Fin Plate Fin Plate Fin Plate Fin Plate Fin Plate Fin Plate Fin Tube size (mm) 9,52 9,52 9,52 9,52 9,52 9,52 9,52 9,52 9,52 9,52 Tube type Smooth Smooth Smooth Smooth Smooth Smooth Smooth Smooth Smooth Smooth Height (mm) 1219 1219 1219 1219 1219 1219 1219 1219 1219 1219 Length (mm) 2743 2743 2743 3455 4115 4115 5486 5486 5486 5486 Face Area (m2) 3,34 3,34 3,34 4,21 5,02 5,02 6,69 6,69 6,69 6,69 Rows # 2,0 2,0 3,0 3,0 3,0 3,0 2,0 3,0 3,0 3,0 Fins per foot (fpf) # 156,0 156,0 156,0 156,0 156,0 156,0 156,0 156,0 156,0 156,0
Fan
Type Propeller Propeller Propeller Propeller Propeller Propeller Propeller Propeller Propeller Propeller Number 2 2 2 3 33446 6 Diameter (mm) 962 962 962 962 962 962 962 962 962 962 Drive type Direct Direct Direct Direct Direct Direct Direct Direct Direct Direct Speeds number 1 1 1 1 11111 1 Air flow (m3/h) 2700 0 27000 2530 0 3590 0 3790 0 3790 0 5400 0 50700 89100 89100 Motors Number 2 2 2 3 33446 6 Motor HP (2) (kW) 0,85 0,85 0,85 0,85 0,85 0,85 0,85 0,85 1,88 1,88 Rated Amps (2) (A) 2,4 2,4 2,4 2,4 2,4 2,4 2,4 2,4 4,2 4,2 Locked rotor Amps (2) (A) 6,8 6,8 6,8 6,8 6,8 6,8 6,8 6,8 14,7 14,7 Motor RPM (rpm) 680 680 680 680 680 680 680 680 915 915
Dimensions
Height (mm) 1582 1582 1582 1582 1582 1582 1584 1584 1598 1598 Length (mm) 2061 2061 2061 2921 2921 2921 2225 2225 3090 3090 Width (mm) 995 995 995 995 995 995 1865 1865 1948 1948 Weight uncrated (kg) 514 584 650 810 900 926 1040 1168 1575 1634 Weight crated (kg) 555 625 691 869 959 985 1123 1251 1695 1754
System Data
Refrigerant circuit 111222222 2
Refrigerant Charge (3)
Circuit A & B (kg)
(1) at 7°C SST and 35°C ambiant (2) per motor (3) per circuit (4) 5°C sat suction temp. - 60°C sat discharge temp. (5) In accordance with ISO 3746
Split
system
Split
system
Split
system
Split
system
Split
system
Split
system
Split
system
Split
system
Split
system
Split
system
Page 9
9RAU-SVX01B-E4
Table 3 - R407C Units Characteristics
RAU 190 RAU 260 RAU 300 RAU 350 RAU 400 RAU 450 RAU 500 RAU 600 RAU 700 RAU 80 0
R407C R407C R407C R407C R407C R407C R407C R407C R407C R407C
Performances (1)
Gross cooling capacity (1) (kW) 54,8 66,6 81,1 95,3 108,3 118,8 133,0 162,0 194,7 218,8 Power input in cooling (1) (kW) 18,2 25,1 29,8 33,4 38,4 45,6 51,7 61,0 71,3 83,9 Main Power supply 400/3/50 400/3/50 400/3/50 400/3/50 400/3/50 40 0/3/50 400/3/50 400/3/50 400/3/50 400/3/50 Sound Power Level (5) (dB(A)) 88 90 91 91 92 93 93 94 98 98
Units Amps
Nominal (4) (A) 35,4 44,3 53,2 62 70,9 79,8 88,6 106,4 124 141,8 Start-up Amps (A) 137 193 202 210 219 228 236 255 271 289 Max supply cable size (mm2)3535355050959595150 150
Compressor
Number 2 2 2 3 33446 6 Type Scroll Scroll Scroll Scroll Scroll Scroll Scroll Scroll Scroll Scroll Model 10T+10T 10T+15T 2x15T 2x10T+15T 10T+2x15T 3x15T 2x(10T+15T) 4x15T 4x10T+2x15T 2x10T+4x15T Speeds number 1 1 1 1 11111 1 Motors Number 1 1 1 1 11111 1 Rated Amps (2)(4) (A) 30 42 50 55 65 75 84 101 109 130 Locked rotor Amps (2) (A) 120 175 175 175 175 175 175 175 175 175 Motor RPM (rpm) 2900 2900 2900 2900 2900 2900 2900 290 0 2900 2900 Sump Heater (2) (W) 50W - 40 0V 50W - 400V 50W - 400V 50W - 40 0V 50W - 400V 50W - 40 0V 50W - 400V 50W - 400V 50W - 400V 50W - 400V
Liquid and Suction connection
Suction connection brazed 1"5/8 1"5/8 1"5/8 1"5/8 1"5/8 1"5/8 1"5/8 1"5/8 2"1/8 2"1/8 Liquid connection brazed 7/8" 7/8" 7/8" 7/8" 7/8" 7/8" 7/8" 7/8" 1"1/8 1"1/8
Coil
Type Plate Fin Plate Fin Plate Fin Plate Fin Plate Fin Plate Fin Plate Fin Plate Fin Plate Fin Plate Fin Tube size (mm) 9,52 9,52 9,52 9,52 9,52 9,52 9,52 9,52 9,52 9,52 Tube type Smooth Smooth Smooth Smooth Smooth Smooth Smooth Smooth Smooth Smooth Height (mm) 1219 1219 1219 1219 1219 1219 1219 1219 1219 1219 Length (mm) 2743 2743 2743 3455 4115 4115 5486 5486 5486 5486 Face Area (m2) 3,34 3,34 3,34 4,21 5,02 5,02 6,69 6,69 6,69 6,69 Rows # 2,0 2,0 3,0 3,0 3,0 3,0 2,0 3,0 3,0 3,0 Fins per foot (fpf) # 156,0 156,0 156,0 156,0 156,0 156,0 156,0 156,0 156,0 156,0
Fan
Type Propeller Propeller Propeller Propeller Propeller Propeller Propeller Propeller Propeller Propeller Number 2 2 2 3 33446 6 Diameter (mm) 962 962 962 962 962 962 962 962 962 962 Drive type Direct Direct Direct Direct Direct Direct Direct Direct Direct Direct Speeds number 1 1 1 1 11111 1 Air flow (m3/h) 2700 0 27000 2530 0 3590 0 3790 0 3790 0 5400 0 50700 89100 89100 Motors Number 2 2 2 3 33446 6 Motor HP (2) (kW) 0,85 0,85 0,85 0,85 0,85 0,85 0,85 0,85 1,88 1,88 Rated Amps (2) (A) 2,4 2,4 2,4 2,4 2,4 2,4 2,4 2,4 4,2 4,2 Locked rotor Amps (2) (A) 6,8 6,8 6,8 6,8 6,8 6,8 6,8 6,8 14,7 14,7 Motor RPM (rpm) 680 680 680 680 680 680 680 680 915 915
Dimensions
Height (mm) 1582 1582 1582 1582 1582 1582 1584 1584 1598 1598 Length (mm) 2061 2061 2061 2921 2921 2921 2225 2225 3090 3090 Width (mm) 995 995 995 995 995 995 1865 1865 1948 1948 Weight uncrated (kg) 514 584 650 810 900 926 1040 1168 1575 1634 Weight crated (kg) 555 625 691 869 959 985 1123 1251 1695 1754
System Data
Refrigerant circuit 1 1 1 2 22222 2
System Data
Refrigerant circuit 1 1 1 2 22222 2
Refrigerant Charge (3)
Circuit A & B (kg)
(1) at 7°C SST and 35°C ambiant (2) per motor (3) per circuit (4) 5°C sat suction temp. - 60°C sat discharge temp. (5) In accordance with ISO 3746
Split
system
Split
system
Split
system
Split
system
Split
system
Split
system
Split
system
Split
system
Split
system
Split
system
Page 10
10 RAU-SVX01B-E4
Electrical connections
Caution
1. The greatest care should be taken when cutting through passages and installing electric wiring. Under no circumstances should chips of metal or cuttings of copper or isolating material fall into the starter panel or electric components. Relays, contactors, terminals and control wiring should be covered and protected before power supplies are connected.
2. Install power supply cabling as shown in wiring diagram. Adequate cable gland should be chosen, ensuring no foreign bodies enter the electrical housing or components.
Caution
1. Cabling must comply with standards in force. The type and location of fuses must also comply with standards. As a safety measure, fuses should be visibly installed, close to the unit.
2. Only copper wiring should be used. Using aluminium wires can produce galvanic corrosion and possibly lead to superheat and failure of connection points.
As an option, Trane provides the unique power supply which includes the transformer. If the transformer is not ordered, it is necessary to foresee the power supply of the electronic module separately. Warranty reserves will be formulated if a transformer, not supplied by Trane, is installed inside the electric panel
One temperature sensors per circuit is provided as an accessory, in control panel of unit. They have to be fitted in order to measure the air outlet temperature downstream to the DX coil (evaporator). The SMM control module has to be set up according to the above temperature. Refer to supplied wiring diagram for connection of sensors
Note: If the sensor cables are too short, an extension-screened cable type will be connected as close as possible to the sensor (50 cm max.). This extension must be soldered and isolated with thermo-retractable cable sheathing. Do not install or cross the sensor cables with the power cable in order to avoid electrical disturbance and affect the operation of the SMM control module.
Air
Intake
Fan
Evaporating
Coil
Air
Supply
5R51-15R51-2
Single circuit units: 5R51-1 Only Dual circuit units: 5R51-1 + 5R51-2
Thermostatic
Expansion
Valve
Sight Glass
Manual
Shut-Off
Valve
Filter
Dryer
Liquid
Solenoid
Valve
Page 11
11RAU-SVX01B-E4
General start-up
Start-up Preparation
Carry out all operations on check list and that the unit is correctly installed and ready to operate. The installer must check all the following points before calling in the Trane Servicing Department to put the equipment into service:
- Check position of unit.
- Check unit is level.
- Check type and position of rubber
pads.
- Check clearance required for
maintenance access (See submittals).
- Check clearance around condenser
(See Submittals).
- Check Filter(s) dryer are present.
- Insure that thermostatic expansion
valve(s) are well positioned.
- Insure that air discharge sensors are
well positioned.
- Insure that the isolation resistance
of all power supply terminals to ground complies with standards and regulations in force.
- Check that unit voltage and
frequency supplied match rated input voltage and frequency.
- Check that all electrical connections
are clean and sound.
- Check that main power supply
switch is sound.
- On start-up of each motor in the
system, check the direction of rotation and operation of all the components they drive.
- Check that there is sufficient
demand for cooling on the day of start-up (around 50% of nominal load).
Start-up
Follow the instructions below to correctly start-up the unit.
Installation and chiller inspection:
- Ensure that all the operations above (start-up preparation), are followed.
Follow the instruction stuck inside the electrical cabinet:
- Unscrew the screws securing the isolators located under the rails supporting the compressor.
- Put the plexiglass supplied by Trane in front of the power terminal.
- Ensure all refrigerant valves are in service positions.
- Ensure that the unit is not damaged.
- Check fixing of capillary tubes (protection from vibration and from wear) and ensure that they are not damaged.
- Reset all manually set control devices.
- Check refrigerating circuits tightness.
Checking and setting:
Compressors:
- Check oil level at rest. The level should reach at least halfway up indicator located on housing. See fig. 4 for correct level.
Figure 4 - Compressor oil level
- Check fixing of capillary tubes (protection from vibration and from wear) and insure that they are not damaged.
- Reset all manually set control devices.
- Check refrigerating circuits tightness.
- Check oil acidity.
- Check electrical terminals tightening of the motors and in the control panel.
- Check the isolation of the motors using a 500V DC megohmeter which meets manufacturer’s specifications (minimum value 2 meghoms).
- Check the direction of the rotation using phasemeter.
Electrical power wiring:
- Check all the electrical terminals tightening.
- Set-up compressors overload relays.
- Set-up fan-motors overload relays.
Electrical control wiring:
- Check all the electrical terminals tightening.
- Check all the pressostats.
- Check and set-up the SMM module.
- Test and start-up without the electrical power.
Condenser:
- Check setting of the safety pressure valve.
- Check direction of the rotation of fans.
- Check the isolation of the motors using a 500V DC megohmeter which meets manufacturer’s specifications (minimum value 2 meghoms).
Max oil level
Min oil level
Page 12
12 RAU-SVX01B-E4
Operating parameters statement:
- Switch on main power supply switch.
- Start-up the unit pushing button ”I” of control module. The green LED must be lit, the SMM control module must be in”cooling mode”.
- After unit start up, leave in operation for at least 15 minutes, to insure pressures are stabilized.
Then check:
- voltage.
- compressors and fan-motors currents.
- suction temperature and pressure.
- ambient air temperature.
- blowing air temperature.
- discharge pressure and temperature.
- liquid refrigerant temperature and pressure.
- operating parameters:
- superheat: difference between suction temperature and dew point temperature. Normal superheat must be within 5°C and 10°C.
- sub-cooling: difference between liquid temperature and bubble point temperature. Normal sub­cooling on standard unit with R22 or 134a should be 5 to 10°C, and 2 to 5°C with 407c.
- difference between dew point temperature in high pressure and condenser air inlet temperature. Normal value on standard unit with R22 or 134a and all the fans operating should be 15 to 18°C. With 407c, it should be 20 to 23°C.
Final check:
When the unit is operating correctly:
- Check that the unit is clean and clear of any debris, tools, etc…
- All valves are in operating position.
- Close control and starter panel doors and check panels fixation.
Caution
- For the warranty to apply, any start-up carried out directly by the customer must be recorded in a detailed report, which must be sent as soon as possible to the nearest Trane office.
- Do not start-up a motor whose insulation resistance is less than 2 meghoms.
- Phase imbalance should not be greater than 2%.
- The voltage supplied to motors should be within 5% of the rated voltage on the compressor nameplate.
- Excessive emulsion of the oil in the compressor shows that refrigerant is present in the oil and the result will be that compressor is not lubricated enough. Shut down compressor and consult Trane technician.
- Excess oil in compressor can damage the compressor. Before adding oil, consult Trane technician. Use only Trane products recommended.
- The compressors must operate in a single direction of rotation. If refrigerant high pressure remains stable in the 30 seconds after compressor start-up, immediately shut down unit and check the direction of rotation using phasemeter.
Page 13
13RAU-SVX01B-E4
Operation
Control System
The control is through the SMM control module.
Unit operations
- Start up unit pushing button”I” of the SMM control module. The compressors will start up if the discharge air temperature is above the SMM control module setpoint.
Weekly start up
- Push button”I” of the module to allow unit operation.
Week end shutdown
- If the unit needs to be shut down for a short period of time, push button ”O” of the module.
- If the unit is shut down for a longer period, see under ”Seasonal shutdown”, below.
- Insure that all safeties are taken to protect the compressor against refrigerant migration.
- Do not put the general and control disconnect switches to off.
Seasonal shutdown
- Carry out leak test.
- Carry out oil analysis
- Record operating pressures, temperatures, amperages and voltage.
- Check operation of machines/ compare conditions of operation against original commissioning data.
- Push button”O” of the module.
- Insure that all safeties are taken to protect the compressor against refrigerant migration.
- Fill out the visit log sheet and review with the operator.
- Do not put the general and control disconnect switches to off.
Seasonal start-up
- Check operational set points and performance.
- Calibrate controls.
- Check operation of all safety devices.
- Inspect contacts & tighten terminals.
- Megger the motor compressor windings.
- Record operating pressures, temperatures, amperages and voltage.
- Carry out leak test.
- Check configuration of unit control module.
- Change the oil as required based upon results of the oil analysis made during seasonal shutdown
- Check operation of machines/ compare conditions of operation against original commissioning data.
- Fill out the visit log sheet and review with the operator
Page 14
14 RAU-SVX01B-E4
Maintenance
Maintenance Instructions
The following maintenance instructions are part of maintenance operations required for this equipment. A qualified technician is needed for regular maintenance as part of a regular maintenance contract. Carry out all operations as required by schedule. This will insure long unit service life and reduce the possibility of serious and costly breakdown. Keep service records up to date, showing monthly information on unit operations. These records can be of great help to maintenance personnel diagnostics. Similarly, if machine operator keeps a log of changes in unit operating conditions, problems can be identified and solutions found before more serious problems arise.
Inspection visit after the first 500 hours of operation from unit start up
- Carry out oil analysis.
- Carry out leak test.
- Inspect contacts and tighten terminals.
- Record operating pressures, temperatures, amperages and voltage.
- Check operation of machines/compare conditions of operation against original commissioning data.
- Fill out inspection visit log sheet and review with the operator.
Monthly preventive visit
- Carry out leak test.
- Oil test of acidity.
- Inspect contacts and tighten terminals.
- Record operating pressures, temperatures, amperages and voltage.
- Check operation of machines/ compare conditions of operation against original commissioning data.
- Fill out visit log sheet and review with the operator.
Annual preventive visit
- Check operational set points and performance.
- Calibrate controls.
- Check operation of all safety devices.
- Inspect contacts & tighten terminals.
- Megger the motor compressor windings.
- Record operating pressures, temperatures, amperages and voltage.
- Carry out leak test.
- Check configuration of unit control module.
- Carry out oil analysis
- Change the oil as required based upon results of the oil analysis
- Check operation of machines/compare conditions of operation against original commissioning data.
- Fill out the annual start up visit log sheet and review with the operator.
Caution
- Please refer to specific Trane documentation on oil, available from your nearest Trane office. Oils recommended by Trane have been exhaustively tested in Trane laboratories to the specific requirement of Trane chiller and hence the user’s requirements. Any use of oils not meeting specifications recommended by Trane is the responsibility of the user only, who thereby is liable to warranty loss.
- Oil analysis and oil test acidity must be carried out by a qualified technician. Poor interpretation of results may cause unit operating problems. Also, oil analysis must follow the correct procedures, to avoid accidental injury to maintenance personnel.
- If the condensers are dirty, clean them with a brush. If the coils are too dirty, consult a cleaning professional. Never use water to clean condenser coils.
- Contact Trane ServiceFirst for information on maintenance contracts.
Warning
- Switch off unit main power supply before to any intervention. Failure to follow this safety instruction can lead to accident death of the maintenance personnel and may also destroy equipment.
- Never use steam or hot water above 55°C to clean condenser coils. The resulting increasing pressure could cause refrigerant loss through the safety valve.
Page 15
15RAU-SVX01B-E4
INSTALLATION CHECKLIST
RAUL Trane Air Cooled Condensing Unit
This list must be checked off by the installer to ensure correct installation before the unit starts up.
Unit acceptance
Check for damage, if any, on transportationCheck for equipment shipped against delivery slipCheck lifting system
Unit positioning
Remove packagingCheck position of unitCheck unit is levelCheck clearance around condenserCheck clearance required for maintenance accessCheck position of rubber pads
Refrigerant circuit
Check filter dryer and sight glass presenceCheck oil traps presence on discharge line (if there vertical risers>3m)Check pitch for horizontal lines (1cm/m)Check refrigerant presence
Electrical equipment
Check direction of rotation of compressors and fan motorsCheck installation and rating of mains power switch/fuseCheck that electrical connections comply with specificationCheck that electrical connections match information on manufacturer's identification plateCheck electrical connections and connections to mains power switch
General
Check available cooling charge (50% of rated installation load)Check with other trades handling installation works
Comments: ........................................................................................................................................................................................
............................................................................................................................................................................................................
............................................................................................................................................................................................................
............................................................................................................................................................................................................
Signature: ............................................................Name ..................................................................................................................
Order N° ..........................................................................................................................................................................................
Work site: ..........................................................................................................................................................................................
Please return to your local Trane Service Agency
Page 16
16 RAU-SVX01B-E4
A) The compressor does not start up
Compressor terminals are live but motor does not start Contactor motor not operational. No current ahead of motor contactor.
Current ahead of fuse, but not on contactor side. Low voltage reading on voltmeter. Starter coil not excited.
Compressor does not run. Compressor motor ”groans”. High pressure switch tripped to contacts open on high pressure. Discharge pressure too high.
B) Compressor stops High pressure switch tripped.
Over current thermal relay tripped.
Motor temperature thermostat tripped. Anti-freeze security tripped.
C) Compressor stops just after its
start
Suction pressure too low. Filter drier iced up.
Motor burned out.
Coil burned out or broken contacts. a) Power cut. b) Main power supply switched off.
Fuse blown.
Voltage too low. Regulation circuit open.
Compressor sticking (damaged or sticking components). Discharge pressure too high
Discharge pressure too high.
a) Voltage too low. b) Cooling demand too high, or
condensing temperature too high.
Not enough cooling fluid.
Filter drier clogged.
Replace compressor
Repair or replace. Check fuses and connection. See why system tripped. If system is operational, switch on main power supply. Check motor insulation. Replace fuse.
Contact power Supply Utility. Locate regulation device which has tripped out and see why. See instructions concerning this device. Replace compressor. See instructions for “discharge pressure high”.
See instructions for “discharge pressure high”. a) Contact Power Supply Utility. b) See instruction “discharge pressure
too high”.
Repair leak. Add refrigerant.
Replace filter drier.
Troubleshooting guide
These are simple diagnostic hints. If there is a breakdown, the Trane Service office should be contacted for confirmation and assistance.
Problems symptoms Problem cause Action recommended
Page 17
17RAU-SVX01B-E4
D) The compressor keeps running
without stopping
Temperature too high in areas requiring air-conditioning.
E) Loss of oil in compressor
Oil level too low in indicator. Gradual fall in oil level. Suction line too cold. Compressor noisy
F) Compressor noisy
Compressor knocks. Suction line abnormally cold.
G) Insufficient cooling capacity
Thermostatic expansion valve ”whistles”. Excess pressure drops through filter drier. Excessive superheat.
H) Discharge pressure too high
Condenser abnormally hot.
Condenser air output too hot.
Excess load on cooling system.
Not enough oil. Filter drier clogged. Liquid flows back to compressor.
Components broken in compressor. a) Uneven liquid flow. b) Expansion valve locked in open
position.
Not enough refrigerant.
Drier filter clogged.
Superheat not properly adjusted.
Presence of uncondensable liquids in system, or excess refrigerant. Reduced air flow. Air intake temperature higher than specified for unit.
Check thermal insulation and air­tightness of areas requiring air-conditioning.
Contact Trane office before to order oil Replace filter drier. Adjust superheat and check bulb fixing of the expansion valve.
Change compressor. a) Check superheat setting and fixing
of expansion valve bulb.
b) Repair or replace.
Check refrigerant circuit tightness and add refrigerant. Replace.
Check adjustment of superheat and adjust thermostatic expansion valve.
Purge uncondensable fluids and drain off excess refrigerant. Clean battery. Check operation of motor fans.
Problems symptoms Problem cause Action recommended
Page 18
Caution
The above is not a comprehensive analysis of the Scroll compressor refrigeration system. The aim is to give operators simple instructions on basic unit processes so that they have the technical knowledge to identify and bring defective operations to the notice of qualified technicians.
18 RAU-SVX01B-E4
I) Suction pressure too high
Compressor operates continuously.
Suction duct abnormally cold.
Refrigerant flows back to compressor.
J) Suction pressure too low
Excessive pressure drop through filter drier. Refrigerant does not flow through thermostatic expansion valve. Loss of power. Superheat too low.
Excess cooling demand on evaporator. a) Expansion valve too far open.
b) Expansion valve locked in open
position.
Drier filter clogged. Expansion valve bulb has lost its refrigerant. Expansion valve obstructed. Excessive pressure drops through evaporator.
Check system.
a) Check for superheat and check that
expansion valve bulb is secure.
b) Replace.
Replace the deshydrator. Replace the bulb.
Replace. Check adjustment of superheat and adjust thermostatic expansion valve.
Problems symptoms Problem cause Action recommended
Page 19
19RAU-SVX01B-E4
Operating Pressure - R22
Table 1
RAU 190 R22 RAU 260 R22
Outdoor Ambient Temperature (°C)
25°C 30°C 35°C 40°C 45°C 25°C 30°C 35°C 40°C 45°C HP LP HP LP HP LP HP LP HP LP HP LP HP LP HP LP HP LP HP LP bar bar bar bar bar bar bar bar bar bar bar bar bar bar bar bar bar bar bar bar
-14 °C 14.3 3.1 15.9 3.1 17.9 3.1 15.3 3.1 17.2 3.1
-12 °C 13.8 3.3 15.5 3.3 17.5 3.3 15.0 3.3 16.9 3.3
-10 °C 13.9 3.5 15.7 3.5 17.7 3.5 15.3 3.5 17.2 3.5 19.3 3.5
-8 °C 14.2 3.8 16.0 3.8 18.0 3.8 20.1 3.8 15.6 3.8 17.6 3.8 19.7 3.8
-6 °C 14.4 4.1 16.2 4.1 18.2 4.1 20.4 4.1 15.9 4.1 17.9 4.1 20.1 4.1
-4 °C 14.7 4.4 16.5 4.4 18.5 4.4 20.7 4.4 16.3 4.4 18.3 4.4 20.5 4.4 22.9 4.4
-2 °C 14.9 4.7 16.8 4.7 18.8 4.7 21.0 4.7 23.4 4.7 16.6 4.7 18.7 4.7 20.9 4.7 23.3 4.7 0 °C 15.2 5.0 17.1 5.0 19.2 5.0 21.4 5.0 23.8 5.0 17.0 5.0 19.1 5.0 21.3 5.0 23.7 5.0 2 °C 15.5 5.3 17.4 5.3 19.5 5.3 21.8 5.3 24.2 5.3 17.4 5.3 19.5 5.3 21.8 5.3 24.2 5.3 4 °C 15.8 5.7 17.8 5.7 19.9 5.7 22.1 5.7 24.6 5.7 17.9 5.7 20.0 5.7 22.3 5.7 24.7 5.7 27.4 5.7 6 °C 16.2 6.0 18.1 6.0 20.2 6.0 22.5 6.0 25.0 6.0 18.3 6.0 20.5 6.0 22.8 6.0 25.2 6.0 27.9 6.0 8 °C 16.5 6.4 18.5 6.4 20.7 6.4 23.0 6.4 25.4 6.4 18.8 6.4 20.9 6.4 23.3 6.4 25.8 6.4 28.5 6.4
10 °C 16.9 6.8 18.9 6.8 21.1 6.8 23.4 6.8 25.9 6.8 19.3 6.8 21.5 6.8 23.8 6.8 26.3 6.8 29.1 6.8
Saturated suction
temperature.
Table 2
RAU 300 R22 RAU 350 R22
Outdoor Ambient Temperature (°C)
25°C 30°C 35°C 40°C 45°C 25°C 30°C 35°C 40°C 45°C HP LP HP LP HP LP HP LP HP LP HP LP HP LP HP LP HP LP HP LP bar bar bar bar bar bar bar bar bar bar bar bar bar bar bar bar bar bar bar bar
-14 °C 15.0 3.1 16.5 3.1 18.6 3.1 14.6 3.1 16.1 3.1 17.8 3.1
-12 °C 14.9 3.3 16.8 3.3 18.9 3.3 14.2 3.3 15.6 3.3 17.2 3.3
-10 °C 15.2 3.5 17.1 3.5 19.3 3.5 13.8 3.5 15.2 3.5 16.6 3.5
-8 °C 15.5 3.8 17.5 3.8 19.6 3.8 22.0 3.8 13.5 3.8 14.8 3.8 16.2 3.8 17.8 3.8
-6 °C 15.8 4.1 17.8 4.1 20.0 4.1 22.4 4.1 13.2 4.1 14.4 4.1 15.8 4.1 17.3 4.1
-4 °C 16.2 4.4 18.2 4.4 20.4 4.4 22.8 4.4 13.0 4.4 14.1 4.4 15.4 4.4 16.8 4.4
-2 °C 16.6 4.7 18.6 4.7 20.8 4.7 23.2 4.7 12.8 4.7 13.9 4.7 15.1 4.7 16.5 4.7 18.0 4.7 0 °C 17.0 5.0 19.0 5.0 21.2 5.0 23.7 5.0 26.3 5.0 12.6 5.0 13.7 5.0 14.9 5.0 16.2 5.0 17.6 5.0 2 °C 17.4 5.3 19.5 5.3 21.7 5.3 24.1 5.3 26.8 5.3 12.5 5.3 13.5 5.3 14.7 5.3 15.9 5.3 17.3 5.3 4 °C 17.8 5.7 19.9 5.7 22.2 5.7 24.6 5.7 27.3 5.7 12.4 5.7 13.4 5.7 14.5 5.7 15.7 5.7 17.0 5.7 6 °C 18.3 6.0 20.4 6.0 22.7 6.0 25.2 6.0 27.8 6.0 12.4 6.0 13.3 6.0 14.4 6.0 15.5 6.0 16.7 6.0 8 °C 18.8 6.4 20.9 6.4 23.2 6.4 25.7 6.4 28.4 6.4 12.3 6.4 13.3 6.4 14.3 6.4 15.4 6.4 16.6 6.4
10 °C 19.3 6.8 21.4 6.8 23.8 6.8 26.3 6.8 29.0 6.8 12.3 6.8 13.2 6.8 14.2 6.8 15.3 6.8 16.4 6.8
Saturated suction
temperature.
Table 3
RAU 400 R22 RAU 450 R22
Outdoor Ambient Temperature (°C)
25°C 30°C 35°C 40°C 45°C 25°C 30°C 35°C 40°C 45°C HP LP HP LP HP LP HP LP HP LP HP LP HP LP HP LP HP LP HP LP bar bar bar bar bar bar bar bar bar bar bar bar bar bar bar bar bar bar bar bar
-14 °C 15.1 3.1 16.6 3.1 18.3 3.1 15.1 3.1 16.6 3.1 18.3 3.1
-12 °C 14.7 3.3 16.1 3.3 17.8 3.3 14.7 3.3 16.1 3.3 17.7 3.3
-10 °C 14.3 3.5 16.0 3.5 18.0 3.5 14.3 3.5 15.7 3.5 17.2 3.5
-8 °C 14.4 3.8 16.3 3.8 18.3 3.8 14.0 3.8 15.3 3.8 16.8 3.8
-6 °C 14.7 4.1 16.5 4.1 18.6 4.1 20.8 4.1 13.7 4.1 15.0 4.1 16.4 4.1 17.9 4.1
-4 °C 14.9 4.4 16.8 4.4 18.9 4.4 21.2 4.4 13.5 4.4 14.7 4.4 16.0 4.4 17.5 4.4
-2 °C 15.2 4.7 17.2 4.7 19.2 4.7 21.5 4.7 13.3 4.7 14.5 4.7 15.7 4.7 17.2 4.7 0 °C 15.5 5.0 17.5 5.0 19.6 5.0 21.9 5.0 24.4 5.0 13.2 5.0 14.3 5.0 15.5 5.0 16.9 5.0 18.3 5.0 2 °C 15.9 5.3 17.8 5.3 20.0 5.3 22.3 5.3 24.8 5.3 13.0 5.3 14.1 5.3 15.3 5.3 16.6 5.3 18.0 5.3 4 °C 16.2 5.7 18.2 5.7 20.3 5.7 22.7 5.7 25.2 5.7 13.0 5.7 14.0 5.7 15.2 5.7 16.4 5.7 17.7 5.7 6 °C 16.6 6.0 18.6 6.0 20.7 6.0 23.1 6.0 25.6 6.0 12.9 6.0 13.9 6.0 15.0 6.0 16.2 6.0 17.5 6.0 8 °C 17.0 6.4 19.0 6.4 21.2 6.4 23.5 6.4 26.1 6.4 12.9 6.4 13.9 6.4 14.9 6.4 16.1 6.4 17.3 6.4
10 °C 17.3 6.8 19.4 6.8 21.6 6.8 24.0 6.8 26.6 6.8 12.9 6.8 13.8 6.8 14.9 6.8 16.0 6.8 17.2 6.8
Saturated suction
temperature.
Page 20
20 RAU-SVX01B-E4
Table 4
RAU 500 R22 RAU 600 R22
Outdoor Ambient Temperature (°C)
25°C 30°C 35°C 40°C 45°C 25°C 30°C 35°C 40°C 45°C HP LP HP LP HP LP HP LP HP LP HP LP HP LP HP LP HP LP HP LP bar bar bar bar bar bar bar bar bar bar bar bar bar bar bar bar bar bar bar bar
-14 °C 15.3 3.1 17.2 3.1 15.0 3.1 16.5 3.1 18.6 3.1
-12 °C 15.0 3.3 16.9 3.3 14.9 3.3 16.8 3.3 18.9 3.3
-10 °C 15.3 3.5 17.2 3.5 19.3 3.5 15.2 3.5 17.1 3.5 19.3 3.5
-8 °C 15.6 3.8 17.6 3.8 19.7 3.8 15.5 3.8 17.5 3.8 19.6 3.8 22.0 3.8
-6 °C 15.9 4.1 17.9 4.1 20.1 4.1 15.8 4.1 17.8 4.1 20.0 4.1 22.4 4.1
-4 °C 16.3 4.4 18.3 4.4 20.5 4.4 22.9 4.4 16.2 4.4 18.2 4.4 20.4 4.4 22.8 4.4
-2 °C 16.6 4.7 18.7 4.7 20.9 4.7 23.3 4.7 16.6 4.7 18.6 4.7 20.8 4.7 23.2 4.7 0 °C 17.0 5.0 19.1 5.0 21.3 5.0 23.7 5.0 17.0 5.0 19.0 5.0 21.2 5.0 23.7 5.0 26.3 5.0 2 °C 17.4 5.3 19.5 5.3 21.8 5.3 24.2 5.3 17.4 5.3 19.5 5.3 21.7 5.3 24.1 5.3 26.8 5.3 4 °C 17.9 5.7 20.0 5.7 22.3 5.7 24.7 5.7 27.4 5.7 17.8 5.7 19.9 5.7 22.2 5.7 24.6 5.7 27.3 5.7 6 °C 18.3 6.0 20.5 6.0 22.8 6.0 25.2 6.0 27.9 6.0 18.3 6.0 20.4 6.0 22.7 6.0 25.2 6.0 27.8 6.0 8 °C 18.8 6.4 20.9 6.4 23.3 6.4 25.8 6.4 28.5 6.4 18.8 6.4 20.9 6.4 23.2 6.4 25.7 6.4 28.4 6.4
10 °C 19.3 6.8 21.5 6.8 23.8 6.8 26.3 6.8 29.1 6.8 19.3 6.8 21.4 6.8 23.8 6.8 26.3 6.8 29.0 6.8
Saturated suction
temperature.
Table 5
RAU 700 R22 RAU 800 R22
Outdoor Ambient Temperature (°C)
25°C 30°C 35°C 40°C 45°C 25°C 30°C 35°C 40°C 45°C HP LP HP LP HP LP HP LP HP LP HP LP HP LP HP LP HP LP HP LP bar bar bar bar bar bar bar bar bar bar bar bar bar bar bar bar bar bar bar bar
-14 °C 14.4 3.1 15.8 3.1 17.7 3.1 14.8 3.1 16.3 3.1
-12 °C 14.1 3.3 15.9 3.3 17.9 3.3 14.6 3.3 16.5 3.3 18.5 3.3
-10 °C 14.3 3.5 16.1 3.5 18.1 3.5 14.9 3.5 16.7 3.5 18.8 3.5
-8 °C 14.5 3.8 16.4 3.8 18.4 3.8 20.6 3.8 15.1 3.8 17.0 3.8 19.1 3.8
-6 °C 14.8 4.1 16.6 4.1 18.7 4.1 20.9 4.1 15.4 4.1 17.3 4.1 19.5 4.1 21.8 4.1
-4 °C 15.0 4.4 16.9 4.4 19.0 4.4 21.2 4.4 15.7 4.4 17.7 4.4 19.8 4.4 22.1 4.4
-2 °C 15.3 4.7 17.2 4.7 19.3 4.7 21.6 4.7 24.0 4.7 16.0 4.7 18.0 4.7 20.1 4.7 22.5 4.7 0 °C 15.6 5.0 17.5 5.0 19.6 5.0 21.9 5.0 24.4 5.0 16.4 5.0 18.4 5.0 20.5 5.0 22.9 5.0 2 °C 15.9 5.3 17.9 5.3 20.0 5.3 22.3 5.3 24.8 5.3 16.8 5.3 18.8 5.3 20.9 5.3 23.3 5.3 25.8 5.3 4 °C 16.2 5.7 18.2 5.7 20.3 5.7 22.7 5.7 25.2 5.7 17.1 5.7 19.1 5.7 21.3 5.7 23.7 5.7 26.3 5.7 6 °C 16.6 6.0 18.6 6.0 20.7 6.0 23.1 6.0 25.6 6.0 17.5 6.0 19.6 6.0 21.8 6.0 24.2 6.0 26.7 6.0 8 °C 17.0 6.4 19.0 6.4 21.1 6.4 23.5 6.4 26.0 6.4 18.0 6.4 20.0 6.4 22.2 6.4 24.6 6.4 27.2 6.4
10 °C 17.3 6.8 19.4 6.8 21.6 6.8 23.9 6.8 26.5 6.8 18.4 6.8 20.5 6.8 22.7 6.8 25.1 6.8 27.7 6.8
Saturated suction
temperature.
Page 21
21RAU-SVX01B-E4
Operating Pressure - R134a
Table 6
RAU 190 R134a RAU 260 R134a
Outdoor Ambient Temperature (°C)
25°C 30°C 35°C 40°C 45°C 25°C 30°C 35°C 40°C 45°C HP LP HP LP HP LP HP LP HP LP HP LP HP LP HP LP HP LP HP LP bar bar bar bar bar bar bar bar bar bar bar bar bar bar bar bar bar bar bar bar
-14 °C 10.7 1.7 11.7 1.7 12.9 1.7 14.1 1.7 15.5 1.7 11.0 1.7 12.1 1.7 13.3 1.7 14.6 1.7 16.1 1.7
-12 °C 10.3 1.9 11.3 1.9 12.4 1.9 13.6 1.9 14.9 1.9 10.7 1.9 11.7 1.9 12.8 1.9 14.1 1.9 15.5 1.9
-10 °C 10.0 2.0 10.9 2.0 12.0 2.0 13.1 2.0 14.4 2.0 10.4 2.0 11.4 2.0 12.4 2.0 13.6 2.0 15.0 2.0
-8 °C 9.8 2.2 10.6 2.2 11.6 2.2 12.7 2.2 14.2 2.2 10.1 2.2 11.1 2.2 12.1 2.2 13.3 2.2 15.0 2.2
-6 °C 9.6 2.3 10.4 2.3 11.3 2.3 12.7 2.3 14.3 2.3 9.9 2.3 10.8 2.3 11.9 2.3 13.5 2.3 15.2 2.3
-4 °C 9.4 2.5 10.2 2.5 11.3 2.5 12.8 2.5 14.5 2.5 9.8 2.5 10.7 2.5 12.1 2.5 13.7 2.5 15.5 2.5
-2 °C 9.3 2.7 10.1 2.7 11.5 2.7 13.0 2.7 14.7 2.7 9.7 2.7 10.9 2.7 12.3 2.7 13.9 2.7 15.7 2.7 0 °C 9.2 2.9 10.3 2.9 11.7 2.9 13.2 2.9 14.9 2.9 9.7 2.9 11.1 2.9 12.6 2.9 14.2 2.9 16.0 2.9 2 °C 9.2 3.2 10.5 3.2 11.9 3.2 13.4 3.2 15.1 3.2 10.0 3.2 11.3 3.2 12.8 3.2 14.4 3.2 16.2 3.2 4 °C 9.4 3.4 10.7 3.4 12.1 3.4 13.6 3.4 15.3 3.4 10.2 3.4 11.5 3.4 13.0 3.4 14.7 3.4 16.5 3.4 6 °C 9.6 3.6 10.9 3.6 12.3 3.6 13.8 3.6 15.5 3.6 10.4 3.6 11.8 3.6 13.3 3.6 15.0 3.6 16.8 3.6 8 °C 9.8 3.9 11.1 3.9 12.5 3.9 14.0 3.9 15.7 3.9 10.7 3.9 12.1 3.9 13.6 3.9 15.3 3.9 17.1 3.9
10 °C 10.0 4.2 11.3 4.2 12.7 4.2 14.3 4.2 16.0 4.2 10.9 4.2 12.3 4.2 13.9 4.2 15.6 4.2 17.4 4.2
Saturated suction
temperature.
Table 7
RAU 300 R134a RAU 350 R134a
Outdoor Ambient Temperature (°C)
25°C 30°C 35°C 40°C 45°C 25°C 30°C 35°C 40°C 45°C HP LP HP LP HP LP HP LP HP LP HP LP HP LP HP LP HP LP HP LP bar bar bar bar bar bar bar bar bar bar bar bar bar bar bar bar bar bar bar bar
-14 °C 11.2 1.7 12.2 1.7 13.3 1.7 14.5 1.7 15.9 1.7 11.1 1.7 12.1 1.7 13.1 1.7 14.3 1.7 15.6 1.7
-12 °C 10.9 1.9 11.8 1.9 12.9 1.9 14.0 1.9 15.3 1.9 10.7 1.9 11.7 1.9 12.7 1.9 13.8 1.9 15.1 1.9
-10 °C 10.6 2.0 11.5 2.0 12.5 2.0 13.6 2.0 14.8 2.0 10.4 2.0 11.3 2.0 12.3 2.0 13.4 2.0 14.6 2.0
-8 °C 10.3 2.2 11.2 2.2 12.1 2.2 13.2 2.2 14.9 2.2 10.2 2.2 11.0 2.2 11.9 2.2 13.0 2.2 14.1 2.2
-6 °C 10.1 2.3 10.9 2.3 11.9 2.3 13.4 2.3 15.1 2.3 9.9 2.3 10.8 2.3 11.7 2.3 12.6 2.3 13.7 2.3
-4 °C 9.9 2.5 10.7 2.5 12.0 2.5 13.6 2.5 15.3 2.5 9.8 2.5 10.5 2.5 11.4 2.5 12.4 2.5 13.4 2.5
-2 °C 9.8 2.7 10.8 2.7 12.2 2.7 13.8 2.7 15.6 2.7 9.6 2.7 10.4 2.7 11.2 2.7 12.1 2.7 13.1 2.7 0 °C 9.7 2.9 11.0 2.9 12.4 2.9 14.1 2.9 15.8 2.9 9.5 2.9 10.2 2.9 11.0 2.9 11.9 2.9 12.9 2.9 2 °C 9.9 3.2 11.2 3.2 12.7 3.2 14.3 3.2 16.1 3.2 9.4 3.2 10.1 3.2 10.9 3.2 11.8 3.2 12.7 3.2 4 °C 10.1 3.4 11.4 3.4 12.9 3.4 14.6 3.4 16.4 3.4 9.4 3.4 10.1 3.4 10.8 3.4 11.6 3.4 12.5 3.4 6 °C 10.3 3.6 11.7 3.6 13.2 3.6 14.9 3.6 16.7 3.6 9.4 3.6 10.0 3.6 10.7 3.6 11.5 3.6 12.4 3.6 8 °C 10.6 3.9 12.0 3.9 13.5 3.9 15.2 3.9 17.0 3.9 9.4 3.9 10.0 3.9 10.7 3.9 11.5 3.9 12.3 3.9
10 °C 10.9 4.2 12.3 4.2 13.8 4.2 15.5 4.2 17.3 4.2 9.4 4.2 10.0 4.2 10.7 4.2 11.4 4.2 12.2 4.2
Saturated suction
temperature.
Table 8
RAU 400 R 134a RAU 450 R134a
Outdoor Ambient Temperature (°C)
25°C 30°C 35°C 40°C 45°C 25°C 30°C 35°C 40°C 45°C HP LP HP LP HP LP HP LP HP LP HP LP HP LP HP LP HP LP HP LP bar bar bar bar bar bar bar bar bar bar bar bar bar bar bar bar bar bar bar bar
-14 °C 11.3 1.7 12.3 1.7 13.4 1.7 14.6 1.7 15.9 1.7 11.3 1.7 12.3 1.7 13.4 1.7 14.6 1.7 15.9 1.7
-12 °C 10.9 1.9 11.9 1.9 12.9 1.9 14.1 1.9 15.4 1.9 10.9 1.9 11.9 1.9 12.9 1.9 14.1 1.9 15.4 1.9
-10 °C 10.6 2.0 11.5 2.0 12.5 2.0 13.6 2.0 14.9 2.0 10.6 2.0 11.5 2.0 12.5 2.0 13.6 2.0 14.9 2.0
-8 °C 10.4 2.2 11.2 2.2 12.2 2.2 13.3 2.2 14.4 2.2 10.4 2.2 11.2 2.2 12.2 2.2 13.3 2.2 14.4 2.2
-6 °C 10.1 2.3 11.0 2.3 11.9 2.3 12.9 2.3 14.4 2.3 10.1 2.3 11.0 2.3 11.9 2.3 12.9 2.3 14.0 2.3
-4 °C 10.0 2.5 10.8 2.5 11.7 2.5 12.9 2.5 14.6 2.5 10.0 2.5 10.8 2.5 11.7 2.5 12.6 2.5 13.7 2.5
-2 °C 9.8 2.7 10.6 2.7 11.6 2.7 13.1 2.7 14.8 2.7 9.8 2.7 10.6 2.7 11.5 2.7 12.4 2.7 13.4 2.7 0 °C 9.8 2.9 10.5 2.9 11.7 2.9 13.3 2.9 15.0 2.9 9.8 2.9 10.5 2.9 11.3 2.9 12.2 2.9 13.2 2.9 2 °C 9.7 3.2 10.5 3.2 11.9 3.2 13.5 3.2 15.2 3.2 9.7 3.2 10.4 3.2 11.2 3.2 12.1 3.2 13.0 3.2 4 °C 9.6 3.4 10.7 3.4 12.1 3.4 13.7 3.4 15.4 3.4 9.6 3.4 10.3 3.4 11.1 3.4 11.9 3.4 12.8 3.4 6 °C 9.6 3.6 10.9 3.6 12.4 3.6 13.9 3.6 15.7 3.6 9.6 3.6 10.3 3.6 11.0 3.6 11.8 3.6 12.7 3.6 8 °C 9.8 3.9 11.1 3.9 12.6 3.9 14.2 3.9 15.9 3.9 9.6 3.9 10.3 3.9 11.0 3.9 11.8 3.9 12.6 3.9
10 °C 10.0 4.2 11.3 4.2 12.8 4.2 14.4 4.2 16.2 4.2 9.7 4.2 10.3 4.2 11.0 4.2 11.7 4.2 12.5 4.2
Saturated suction
temperature.
Page 22
22 RAU-SVX01B-E4
Table 9
RAU 500 R134a RAU 600 R134a
Outdoor Ambient Temperature (°C)
25°C 30°C 35°C 40°C 45°C 25°C 30°C 35°C 40°C 45°C HP LP HP LP HP LP HP LP HP LP HP LP HP LP HP LP HP LP HP LP bar bar bar bar bar bar bar bar bar bar bar bar bar bar bar bar bar bar bar bar
-14 °C 11.0 1.7 12.1 1.7 13.3 1.7 14.6 1.7 16.1 1.7 11.2 1.7 12.2 1.7 13.3 1.7 14.5 1.7 15.9 1.7
-12 °C 10.7 1.9 11.7 1.9 12.8 1.9 14.1 1.9 15.5 1.9 10.9 1.9 11.8 1.9 12.9 1.9 14.0 1.9 15.3 1.9
-10 °C 10.4 2.0 11.4 2.0 12.4 2.0 13.6 2.0 15.0 2.0 10.6 2.0 11.5 2.0 12.5 2.0 13.6 2.0 14.8 2.0
-8 °C 10.1 2.2 11.1 2.2 12.1 2.2 13.3 2.2 15.0 2.2 10.3 2.2 11.2 2.2 12.1 2.2 13.2 2.2 14.9 2.2
-6 °C 9.9 2.3 10.8 2.3 11.9 2.3 13.5 2.3 15.2 2.3 10.1 2.3 10.9 2.3 11.9 2.3 13.4 2.3 15.1 2.3
-4 °C 9.8 2.5 10.7 2.5 12.1 2.5 13.7 2.5 15.5 2.5 9.9 2.5 10.7 2.5 12.0 2.5 13.6 2.5 15.3 2.5
-2 °C 9.7 2.7 10.9 2.7 12.3 2.7 13.9 2.7 15.7 2.7 9.8 2.7 10.8 2.7 12.2 2.7 13.8 2.7 15.6 2.7 0 °C 9.7 2.9 11.1 2.9 12.6 2.9 14.2 2.9 16.0 2.9 9.7 2.9 11.0 2.9 12.4 2.9 14.1 2.9 15.8 2.9 2 °C 10.0 3.2 11.3 3.2 12.8 3.2 14.4 3.2 16.2 3.2 9.9 3.2 11.2 3.2 12.7 3.2 14.3 3.2 16.1 3.2 4 °C 10.2 3.4 11.5 3.4 13.0 3.4 14.7 3.4 16.5 3.4 10.1 3.4 11.4 3.4 12.9 3.4 14.6 3.4 16.4 3.4 6 °C 10.4 3.6 11.8 3.6 13.3 3.6 15.0 3.6 16.8 3.6 10.3 3.6 11.7 3.6 13.2 3.6 14.9 3.6 16.7 3.6 8 °C 10.7 3.9 12.1 3.9 13.6 3.9 15.3 3.9 17.1 3.9 10.6 3.9 12.0 3.9 13.5 3.9 15.2 3.9 17.0 3.9
10 °C 10.9 4.2 12.3 4.2 13.9 4.2 15.6 4.2 17.4 4.2 10.9 4.2 12.3 4.2 13.8 4.2 15.5 4.2 17.3 4.2
Saturated suction
temperature.
Table 10
RAU 700 R134a RAU 800 R134a
Outdoor Ambient Temperature (°C)
25°C 30°C 35°C 40°C 45°C 25°C 30°C 35°C 40°C 45°C HP LP HP LP HP LP HP LP HP LP HP LP HP LP HP LP HP LP HP LP bar bar bar bar bar bar bar bar bar bar bar bar bar bar bar bar bar bar bar bar
-14 °C 11.1 1.7 12.0 1.7 13.1 1.7 14.3 1.7 15.6 1.7 11.2 1.7 12.2 1.7 13.3 1.7 14.5 1.7 15.8 1.7
-12 °C 10.7 1.9 11.6 1.9 12.6 1.9 13.8 1.9 15.0 1.9 10.9 1.9 11.8 1.9 12.8 1.9 14.0 1.9 15.2 1.9
-10 °C 10.4 2.0 11.2 2.0 12.2 2.0 13.3 2.0 14.5 2.0 10.5 2.0 11.4 2.0 12.4 2.0 13.5 2.0 14.7 2.0
-8 °C 10.1 2.2 10.9 2.2 11.9 2.2 12.9 2.2 14.4 2.2 10.3 2.2 11.1 2.2 12.1 2.2 13.1 2.2 14.8 2.2
-6 °C 9.9 2.3 10.7 2.3 11.6 2.3 12.9 2.3 14.6 2.3 10.0 2.3 10.9 2.3 11.8 2.3 13.2 2.3 15.0 2.3
-4 °C 9.7 2.5 10.5 2.5 11.5 2.5 13.0 2.5 14.7 2.5 9.9 2.5 10.7 2.5 11.9 2.5 13.4 2.5 15.1 2.5
-2 °C 9.5 2.7 10.3 2.7 11.7 2.7 13.2 2.7 14.9 2.7 9.7 2.7 10.6 2.7 12.0 2.7 13.6 2.7 15.4 2.7 0 °C 9.4 2.9 10.5 2.9 11.9 2.9 13.4 2.9 15.1 2.9 9.6 2.9 10.8 2.9 12.3 2.9 13.8 2.9 15.6 2.9 2 °C 9.4 3.2 10.6 3.2 12.1 3.2 13.6 3.2 15.3 3.2 9.7 3.2 11.0 3.2 12.5 3.2 14.1 3.2 15.8 3.2 4 °C 9.5 3.4 10.8 3.4 12.3 3.4 13.8 3.4 15.5 3.4 9.9 3.4 11.2 3.4 12.7 3.4 14.3 3.4 16.0 3.4 6 °C 9.7 3.6 11.0 3.6 12.5 3.6 14.0 3.6 15.8 3.6 10.1 3.6 11.5 3.6 12.9 3.6 14.5 3.6 16.3 3.6 8 °C 9.9 3.9 11.2 3.9 12.7 3.9 14.3 3.9 16.0 3.9 10.4 3.9 11.7 3.9 13.2 3.9 14.8 3.9 16.6 3.9
10 °C 10.1 4.2 11.4 4.2 12.9 4.2 14.5 4.2 16.3 4.2 10.6 4.2 12.0 4.2 13.4 4.2 15.1 4.2 16.8 4.2
Saturated suction
temperature.
Page 23
23RAU-SVX01B-E4
A
B
C
D
E
R407C
0.2 -64.8 -72.4 2.7 -14.3 -20.9 6.0 7.8 1.6 27.0 63.0 58.7
0.3 -58.6 -66.0 2.8 -13.4 -20.0 6.5 10.3 4.2 28.0 64.6 60.4
0.4 -53.9 -61.2 2.9 -12.5 -19.1 7.0 12.6 6.5 29.0 66.1 62.0
0.5 -50.0 -57.3 3.0 -11.6 -18.2 7.5 14.8 8.8 30.0 67.6 63.6
0.6 -46.7 -53.9 3.1 -10.8 -17.3 8.0 16.9 10.9 31.0 69.1 65.2
0.7 -43.9 -51.0 3.2 -9.9 -16.5 8.5 18.9 12.9 32.0 70.6 66.7
0.8 -41.3 -48.4 3.3 -9.1 -15.6 9.0 20.8 14.9 33.0 72.0 68.2
0.9 -39.0 -46.0 3.4 -8.3 -14.8 9.5 22.6 16.8 34.0 73.4 69.7
1.0 -36.9 -43.9 3.5 -7.6 -14.1 10.0 24.3 18.6 35.0 74.7 71.1
1.1 -34.9 -41.9 3.6 -6.8 -13.3 11.0 27.6 22.0 36.0 76.0 72.6
1.2 -33.1 -40.0 3.7 -6.1 -12.5 12.0 30.7 25.1 37.0 77.3 73.9
1.3 -31.4 -38.3 3.8 -5.3 -11.8 13.0 33.6 28.1 38.0 78.6 75.3
1.4 -29.8 -36.6 3.9 -4.6 -11.1 14.0 36.4 31.0 39.0 79.8 76.6
1.5 -28.2 -35.1 4.0 -3.9 -10.3 15.0 39.0 33.6 40.0 81.0 77.9
1.6 -26.8 -33.6 4.1 -3.2 -9.7 16.0 41.4 36.2 41.0 82.2 79.2
1.7 -25.4 -32.2 4.2 -2.6 -9.0 17.0 43.8 38.6 42.0 83.3 80.5
1.8 -24.1 -30.9 4.3 -1.9 -8.3 18.0 46.0 41.0 43.0 84.4 81.7
1.9 -22.9 -29.6 4.4 -1.3 -7.6 19.0 48.2 43.2 44.0 85.5 83.0
2.0 -21.7 -28.4 4.5 -0.6 -7.0 20.0 50.3 45.4 45.0 86.6 84.2
2.1 -20.5 -27.2 4.6 0.0 -6.3 21.0 52.3 47.5 46.0 87.6 85.4
2.2 -19.4 -26.1 4.7 0.6 -5.7 22.0 54.2 49.5 47.0 88.6 86.5
2.3 -18.3 -25.0 4.8 1.2 -5.1 23.0 56.1 51.4 48.0 89.6 87.7
2.4 -17.3 -23.9 4.9 1.8 -4.5 24.0 57.9 53.3 49.0 90.6 88.8
2.5 -16.2 -22.9 5.0 2.4 -3.9 25.0 59.6 55.2 50.0 91.6 90.0
2.6 -15.3 -21.9 5.5 5.2 -1.0 26.0 61.3 57.0
Table 11 - Dew point and Bubble temperature versus pressure for R407C
Absolute Pressure
bar
Dew
Temp.
°C
Bubble
Temp.
°C
Absolute Pressure
bar
Dew
Temp.
°C
Bubble
Temp.
°C
Absolute Pressure
bar
Dew
Temp.
°C
Bubble
Temp.
°C
Absolute Pressure
bar
Dew
Temp.
°C
Bubble
Temp.
°C
Pressure
Condensing
Presure
Subcooling
Liquid
Liquid
+
Vapour
Vapour
Enthalpy
Dew Temperature at Evaporating Pressure
Dew Temperature at Condensing Pressure
Bubble Temperature at Condensing Pressure
Liquid Temperature at Condensing Pressure
Inlet Temperature at Evaporating Pressure
Subcooling = -
D
C
EDC
B
A
Performance Data
Performance in the following tables are given for Ambient air temperature versus Dew temperature at evaporating pressure. Refer to point A on Figure 1.
Figure 1
Evaporating
Presure
Page 24
24 RAU-SVX01B-E4
Table 12
RAU 190 R407C RAU 260 R407C
Outdoor Ambient Temperature (°C)
25°C 30°C 35°C 40°C 45°C 25°C 30°C 35°C 40°C 45°C HP LP HP LP HP LP HP LP HP LP HP LP HP LP HP LP HP LP HP LP bar bar bar bar bar bar bar bar bar bar bar bar bar bar bar bar bar bar bar bar
-14 °C 14.0 2.7 15.9 2.7 18.1 2.7 15.0 2.7 17.0 2.7 19.4 2.7
-12 °C 14.2 3.0 16.1 3.0 18.3 3.0 20.7 3.0 15.3 3.0 17.4 3.0 19.7 3.0
-10 °C 14.4 3.2 16.3 3.2 18.5 3.2 20.9 3.2 15.6 3.2 17.7 3.2 20.0 3.2
-8 °C 14.6 3.4 16.6 3.4 18.8 3.4 21.2 3.4 15.9 3.4 18.0 3.4 20.4 3.4 23.0 3.4
-6 °C 14.9 3.7 16.9 3.7 19.1 3.7 21.5 3.7 24.2 3.7 16.3 3.7 18.4 3.7 20.8 3.7 23.4 3.7
-4 °C 15.1 4.0 17.1 4.0 19.3 4.0 21.8 4.0 24.5 4.0 16.6 4.0 18.8 4.0 21.2 4.0 23.9 4.0
-2 °C 15.4 4.3 17.4 4.3 19.7 4.3 22.1 4.3 24.8 4.3 17.0 4.3 19.2 4.3 21.7 4.3 24.3 4.3 0 °C 15.7 4.6 17.8 4.6 20.0 4.6 22.5 4.6 25.1 4.6 17.4 4.6 19.7 4.6 22.1 4.6 24.8 4.6 27.7 4.6 2 °C 16.0 4.9 18.1 4.9 20.3 4.9 22.8 4.9 25.5 4.9 17.9 4.9 20.1 4.9 22.6 4.9 25.3 4.9 28.3 4.9 4 °C 16.4 5.3 18.4 5.3 20.7 5.3 23.2 5.3 25.9 5.3 18.3 5.3 20.6 5.3 23.1 5.3 25.8 5.3 28.8 5.3 6 °C 16.7 5.7 18.8 5.7 21.1 5.7 23.6 5.7 26.3 5.7 18.8 5.7 21.1 5.7 23.6 5.7 26.4 5.7 29.3 5.7 8 °C 17.1 6.0 19.2 6.0 21.5 6.0 24.0 6.0 26.7 6.0 19.3 6.0 21.6 6.0 24.2 6.0 26.9 6.0 29.9 6.0
10 °C 17.5 6.4 19.6 6.4 21.9 6.4 24.5 6.4 27.2 6.4 19.8 6.4 22.2 6.4 24.7 6.4 27.5 6.4 30.5 6.4
Dew Temperature
At Evaporating
Pressure
Table 13
RAU 300 R407C RAU 350 R407C
Outdoor Ambient Temperature (°C)
25°C 30°C 35°C 40°C 45°C 25°C 30°C 35°C 40°C 45°C HP LP HP LP HP LP HP LP HP LP HP LP HP LP HP LP HP LP HP LP bar bar bar bar bar bar bar bar bar bar bar bar bar bar bar bar bar bar bar bar
-14 °C 14.8 2.7 16.8 2.7 19.1 2.7 14.2 2.7 15.6 2.7 17.2 2.7
-12 °C 15.0 3.0 17.1 3.0 19.4 3.0 13.7 3.0 15.0 3.0 16.6 3.0 18.3 3.0
-10 °C 15.3 3.2 17.4 3.2 19.8 3.2 22.4 3.2 13.2 3.2 14.5 3.2 16.0 3.2 17.6 3.2
-8 °C 15.7 3.4 17.8 3.4 20.2 3.4 22.8 3.4 12.9 3.4 14.1 3.4 15.5 3.4 17.1 3.4
-6 °C 16.0 3.7 18.2 3.7 20.5 3.7 23.2 3.7 12.6 3.7 13.7 3.7 15.1 3.7 16.6 3.7 18.2 3.7
-4 °C 16.4 4.0 18.6 4.0 21.0 4.0 23.6 4.0 26.5 4.0 12.3 4.0 13.4 4.0 14.7 4.0 16.1 4.0 17.7 4.0
-2 °C 16.8 4.3 19.0 4.3 21.4 4.3 24.0 4.3 27.0 4.3 12.1 4.3 13.2 4.3 14.4 4.3 15.8 4.3 17.3 4.3 0 °C 17.2 4.6 19.4 4.6 21.8 4.6 24.5 4.6 27.4 4.6 11.9 4.6 13.0 4.6 14.2 4.6 15.4 4.6 16.9 4.6 2 °C 17.6 4.9 19.9 4.9 22.3 4.9 25.0 4.9 28.0 4.9 11.8 4.9 12.8 4.9 13.9 4.9 15.2 4.9 16.6 4.9 4 °C 18.1 5.3 20.4 5.3 22.8 5.3 25.5 5.3 28.5 5.3 11.7 5.3 12.7 5.3 13.8 5.3 15.0 5.3 16.3 5.3 6 °C 18.6 5.7 20.9 5.7 23.4 5.7 26.1 5.7 29.1 5.7 11.7 5.7 12.6 5.7 13.7 5.7 14.8 5.7 16.0 5.7 8 °C 19.1 6.0 21.4 6.0 23.9 6.0 26.7 6.0 29.6 6.0 11.6 6.0 12.6 6.0 13.6 6.0 14.7 6.0 15.9 6.0
10 °C 19.6 6.4 22.0 6.4 24.5 6.4 27.3 6.4 30.3 6.4 11.6 6.4 12.5 6.4 13.5 6.4 14.6 6.4 15.7 6.4
Dew Temperature
At Evaporating
Pressure
Table 14
RAU 400 R407C RAU 450 R407C
Outdoor Ambient Temperature (°C)
25°C 30°C 35°C 40°C 45°C 25°C 30°C 35°C 40°C 45°C HP LP HP LP HP LP HP LP HP LP HP LP HP LP HP LP HP LP HP LP bar bar bar bar bar bar bar bar bar bar bar bar bar bar bar bar bar bar bar bar
-14 °C 14.5 2.7 16.0 2.7 18.1 2.7 14.5 2.7 16.0 2.7 17.7 2.7
-12 °C 14.2 3.0 16.2 3.0 18.4 3.0 14.0 3.0 15.4 3.0 17.0 3.0
-10 °C 14.4 3.2 16.4 3.2 18.6 3.2 21.1 3.2 13.6 3.2 14.9 3.2 16.5 3.2 18.2 3.2
-8 °C 14.7 3.4 16.7 3.4 18.9 3.4 21.4 3.4 13.2 3.4 14.5 3.4 16.0 3.4 17.6 3.4
-6 °C 15.0 3.7 17.0 3.7 19.2 3.7 21.7 3.7 12.9 3.7 14.2 3.7 15.6 3.7 17.1 3.7
-4 °C 15.2 4.0 17.3 4.0 19.6 4.0 22.0 4.0 12.7 4.0 13.9 4.0 15.2 4.0 16.7 4.0
-2 °C 15.5 4.3 17.6 4.3 19.9 4.3 22.4 4.3 25.1 4.3 12.5 4.3 13.7 4.3 14.9 4.3 16.3 4.3 17.9 4.3 0 °C 15.9 4.6 18.0 4.6 20.3 4.6 22.8 4.6 25.5 4.6 12.4 4.6 13.5 4.6 14.7 4.6 16.0 4.6 17.6 4.6 2 °C 16.2 4.9 18.3 4.9 20.6 4.9 23.2 4.9 25.9 4.9 12.3 4.9 13.3 4.9 14.5 4.9 15.8 4.9 17.2 4.9 4 °C 16.6 5.3 18.7 5.3 21.0 5.3 23.6 5.3 26.4 5.3 12.2 5.3 13.2 5.3 14.3 5.3 15.6 5.3 17.0 5.3 6 °C 16.9 5.7 19.1 5.7 21.4 5.7 24.0 5.7 26.8 5.7 12.1 5.7 13.1 5.7 14.2 5.7 15.4 5.7 16.7 5.7 8 °C 17.3 6.0 19.5 6.0 21.9 6.0 24.5 6.0 27.3 6.0 12.1 6.0 13.1 6.0 14.2 6.0 15.3 6.0 16.6 6.0
10 °C 17.8 6.4 20.0 6.4 22.4 6.4 25.0 6.4 27.8 6.4 12.1 6.4 13.1 6.4 14.1 6.4 15.2 6.4 16.4 6.4
Dew Temperature
At Evaporating
Pressure
Page 25
25RAU-SVX01B-E4
Table 15
RAU 190 R407C RAU 260 R407C
Outdoor Ambient Temperature (°C)
25°C 30°C 35°C 40°C 45°C 25°C 30°C 35°C 40°C 45°C HP LP HP LP HP LP HP LP HP LP HP LP HP LP HP LP HP LP HP LP bar bar bar bar bar bar bar bar bar bar bar bar bar bar bar bar bar bar bar bar
-14 °C 15.0 2.7 17.1 2.7 19.4 2.7 14.8 2.7 16.9 2.7 19.2 2.7
-12 °C 15.3 3.0 17.4 3.0 19.8 3.0 15.1 3.0 17.2 3.0 19.5 3.0
-10 °C 15.6 3.2 17.8 3.2 20.1 3.2 15.4 3.2 17.5 3.2 19.8 3.2 22.5 3.2
-8 °C 16.0 3.4 18.1 3.4 20.5 3.4 23.1 3.4 15.7 3.4 17.8 3.4 20.2 3.4 22.8 3.4
-6 °C 16.3 3.7 18.5 3.7 20.9 3.7 23.5 3.7 16.1 3.7 18.2 3.7 20.6 3.7 23.2 3.7
-4 °C 16.7 4.0 18.9 4.0 21.3 4.0 24.0 4.0 16.4 4.0 18.6 4.0 21.0 4.0 23.7 4.0 26.6 4.0
-2 °C 17.1 4.3 19.3 4.3 21.7 4.3 24.4 4.3 16.8 4.3 19.0 4.3 21.4 4.3 24.1 4.3 27.1 4.3 0 °C 17.5 4.6 19.7 4.6 22.2 4.6 24.9 4.6 27.9 4.6 17.2 4.6 19.5 4.6 21.9 4.6 24.6 4.6 27.5 4.6 2 °C 17.9 4.9 20.2 4.9 22.7 4.9 25.4 4.9 28.4 4.9 17.7 4.9 19.9 4.9 22.4 4.9 25.1 4.9 28.1 4.9 4 °C 18.4 5.3 20.7 5.3 23.2 5.3 25.9 5.3 28.9 5.3 18.1 5.3 20.4 5.3 22.9 5.3 25.6 5.3 28.6 5.3 6 °C 18.9 5.7 21.2 5.7 23.7 5.7 26.5 5.7 29.4 5.7 18.6 5.7 20.9 5.7 23.4 5.7 26.2 5.7 29.2 5.7 8 °C 19.4 6.0 21.7 6.0 24.3 6.0 27.0 6.0 30.0 6.0 19.1 6.0 21.5 6.0 24.0 6.0 26.8 6.0 29.8 6.0
10 °C 19.9 6.4 22.3 6.4 24.8 6.4 27.6 6.4 30.6 6.4 19.7 6.4 22.0 6.4 24.6 6.4 27.4 6.4 30.4 6.4
Dew Temperature
At Evaporating
Pressure
Table 16
RAU 700 R407C RAU 800 R407C
Outdoor Ambient Temperature (°C)
25°C 30°C 35°C 40°C 45°C 25°C 30°C 35°C 40°C 45°C HP LP HP LP HP LP HP LP HP LP HP LP HP LP HP LP HP LP HP LP bar bar bar bar bar bar bar bar bar bar bar bar bar bar bar bar bar bar bar bar
-14 °C 14.3 2.7 16.2 2.7 18.5 2.7 14.7 2.7 16.8 2.7 19.0 2.7
-12 °C 14.5 3.0 16.5 3.0 18.7 3.0 15.0 3.0 17.0 3.0 19.3 3.0
-10 °C 14.7 3.2 16.7 3.2 19.0 3.2 21.4 3.2 15.2 3.2 17.3 3.2 19.6 3.2 22.2 3.2
-8 °C 14.9 3.4 17.0 3.4 19.2 3.4 21.7 3.4 15.5 3.4 17.6 3.4 19.9 3.4 22.5 3.4
-6 °C 15.2 3.7 17.2 3.7 19.5 3.7 22.0 3.7 15.8 3.7 17.9 3.7 20.3 3.7 22.8 3.7
-4 °C 15.5 4.0 17.5 4.0 19.8 4.0 22.3 4.0 25.1 4.0 16.1 4.0 18.3 4.0 20.6 4.0 23.2 4.0
-2 °C 15.8 4.3 17.9 4.3 20.1 4.3 22.7 4.3 25.4 4.3 16.5 4.3 18.6 4.3 21.0 4.3 23.6 4.3 26.4 4.3 0 °C 16.1 4.6 18.2 4.6 20.5 4.6 23.0 4.6 25.8 4.6 16.8 4.6 19.0 4.6 21.4 4.6 24.0 4.6 26.8 4.6 2 °C 16.4 4.9 18.5 4.9 20.9 4.9 23.4 4.9 26.2 4.9 17.2 4.9 19.4 4.9 21.8 4.9 24.4 4.9 27.3 4.9 4 °C 16.8 5.3 18.9 5.3 21.2 5.3 23.8 5.3 26.6 5.3 17.6 5.3 19.8 5.3 22.2 5.3 24.9 5.3 27.7 5.3 6 °C 17.1 5.7 19.3 5.7 21.6 5.7 24.2 5.7 27.0 5.7 18.0 5.7 20.2 5.7 22.7 5.7 25.3 5.7 28.2 5.7 8 °C 17.5 6.0 19.7 6.0 22.1 6.0 24.6 6.0 27.5 6.0 18.5 6.0 20.7 6.0 23.2 6.0 25.8 6.0 28.7 6.0
10 °C 17.9 6.4 20.1 6.4 22.5 6.4 25.1 6.4 27.9 6.4 18.9 6.4 21.2 6.4 23.7 6.4 26.3 6.4 29.2 6.4
Dew Temperature
At Evaporating
Pressure
Page 26
26 RAU-SVX01B-E4
Control parameters of the SMM control module
To cancel a manually reset default press key 1.
A
A01 Active Evap. discharge air set point
A02 Evaporator Evap. discharge air outlet mix
temperature
A03 Circuit 1 evaporator Evap. discharge air
outlet temperature
A04 Circuit 2 evaporator Evap. discharge air
outlet temperature
A05 Air temperature
A06 Number of compressor A1 operating
hours
A07 Number of compressor A1 starts
A08 Number of compressor B1 operating
hours
A09 Number of compressor B1 starts
A10 Number of compressor A2 operating
hours
A11 Number of compressor A2 starts
A12 Number of compressor B2 operating
hours
A13 Number of compressor B2 starts
B
B01 Evaporator outlet temperature set point
B02 Not used
B03 Auxiliary discharge air temperature set
point
B04 Circuit 1 ON validation
B05 Circuit 2 ON validation
B06 Operating mode
B07 Remote control validation
B08 Auxiliary set point validation
B09 Current date display
B091 Day
B092 Month
B093 Year
B10 Current time display
B101 Hours
B102 Minutes
B103 Seconds
B11 Set this parameter to 0.0 °C
B12 Set this parameter to 0.0°C
B13 Set this parameter to 0.0°C
C
C01 Default display
C02 Current default reset
D
D01 Cooling set point reset type
D02 Cooling reset starting value
D03 Cooling reset value range
D04 Cooling reset range
D05 Not used
D06 Not used
D07 Not used
D08 Not used
D09 Generic input type
D10 Not used
D11 Not used
D12 Compressor lead-lag
D13 Default 1 report type
D14 Default 2 report type
D15 Serial link address
E
E01 Circuit 1 evaporator saturated temperature
E02 Circuit 1 evaporator saturated pressure
E03 Circuit 1 condenser saturated temperature
E04 Circuit 1 condenser saturated pressure
E05 Circuit 2 evaporator saturated temperature
E06 Circuit 2 evaporator saturated pressure
E07 Circuit 2 condenser saturated temperature
E08 Circuit 2 condenser saturated pressure
E09 Evaporator air inlet temperature
E10 Not used
E11 Not used
Page 27
27RAU-SVX01B-E4
Notes
Page 28
The manufacturer has a policy of continuous product improvement, and reserves the right to alter any details of the products at any time without notice.
This publication is a general guide to install, use and properly maintain our products. The information given may be different from the specification for a particular country or for a specific order. In this event, please refer to your nearest office.
Safety recommendations
To avoid accidents and damage, the following recommendations should be observed during maintenance and service visits:
1. The maximum allowable pressures for system leak testing on low and high pressure side are given in the chapter “Installation”. Always provide a pressure regulator.
2. Disconnect the main supply before any servicing on the unit.
3. Service work on the refrigeration system and the electrical system should be carried out only by qualified and experienced personnel.
Maintenance contract
It is strongly recommended that you sign a maintenance contract with your local Service Agency. This contract provides regular maintenance of your installation by a specialist in our equipment. Regular maintenance ensures that any malfunction is detected and corrected in good time and minimizes the possibility that serious damage will occur. Finally, regular maintenance ensures the maximum operating life of your equipment. We would remind you that failure to respect these installation and maintenance instructions may result in immediate cancellation of the warranty.
Training
The equipment described in this manual is the result of many years of research and continuous development. To assist you in obtaining the best use of it and maintaining it in perfect operating condition over a long period of time, the manufacturer has at your disposal a refrigeration and air conditioning service school. The principal aim of this is to give operators and technicians a better knowledge of the equipment they are using, or that is under their charge. Emphasis is particularly given to the importance of periodic checks on the unit operating parameters as well as on preventive maintenance, which reduces the cost of owning the unit by avoiding serious and costly breakdown.
Literature Order Number RAU-SVX01B-E4
Date 0304
Supersedes RAU-SVX01A-GB_1100
Stocking Location Europe
American Standard Europe BVBA Registered Office: 1789 Chaussée de Wavre, 1160 Brussels - Belgium
www.trane.com
For more information contactyour local district office or e-mail us at comfort@trane.com
Trane has a policy of continuous product and product data improvement and reserves the right to change design and specifications without notice. Only qualified technicians should perform the installation and servicing of equipment referred to in this publication.
For additional information, contact:
Distributor / Installer stamp
Loading...