Toshiba TCB-IFCB5-PE User Manual

Toshiba TCB-IFCB5-PE User Manual

How many Indoor Units can be connected?

The TCB-IFCB5-PE Interface can be used to control a single Indoor Unit or a group of up to 8 Indoor Units when connected to the master unit of that group.

Up to 8

Which Indoor Unit Models can be connected?

ResidentialEquipment

No connection to residential models available.

VRF,SDI&DI

Available on all Indoor units, excluding the RAV-SM***XT-E and RAV-SM***0KRT-E models.

CN61 connection diagram

Indoor Unit PC Board

TCB-IFCB5-PE

Locally Procured O

 

 

N/OFF Switch/Window Switch

 

 

J1

CN61

J21

 

Toshiba’s Commitment to the environment

Toshiba constantly works to ensure that our air conditioners help protect the environment while delivering comfort, reassurance, reliability and cost savings to our customers around the world.

The new TCB-IFCB-5E is no exception, conceived to offer further efficiency, reliability and cost savings for our already renowned products.

Toshiba EMEA Pre Sales & Controls Department

April 2010 – The manufacturer reserves the right to change the product specifications, data and images without notice.

Window Switch & On/Off

Application Control

Board

TCB-IFCB5-PE

Window Switch & On/Off

Application Control Board

WhatistheTCB-IFCB5-PE?

This is an application control PC Board that is capable of providing two different control functions when connected to a Toshiba Indoor Unit, these are:

Window Switch

Remote On/Off Interface Controller

WhatisaWindowSwitch?

A Window Switch is a device used to ensure that an Indoor unit does not operate when a window in the air conditioned space is open.

Why use a Window Switch?

A window switch increases the efficiency and working life of the system by reducing the amount of energy that would be wasted in conditioning the outside air that flows into the conditioned space whilst the window is open.

Not only does this help to increase environmental friendliness of your Toshiba conditioned buildings but also helps to reduce the cost of running your Toshiba equipment.

How does the Window Switch Interface work?

The Toshiba window switch operates with the use of a locally procured window switch interface (Volt-Free Contact).

This switch is fitted to the window such that the contact is made when the window is closed, and broken when the window is open.

Window switch

TCB-IFCB5-PE

 

OFF

 

 

 

 

 

 

 

 

 

 

Each time the window is opened (contact open) the Indoor

Unit operation is turned Off and will not operate again until the window is closed.

There are two possible operation selections for when the window is closed again.

StandardFunctionMode

The Indoor Unit operation remains Off.

ReturnFunctionMode

The Indoor Unit will revert to the last setting before the window was opened.

This function also allows the Interface to remember any ON commands sent to the Indoor Unit from another controller whilst the window is open, then using this information, it will switchtheIndoorUnitONwhenthewindowisclosedregardless of the previous setting.

What is the Remote On/Off Controller?

TheRemoteOn/Offcontrollerisusedtoallowanexternalvolt-free contact signal to turn the connected Air Conditioner On and Off, and has four possible priorty settings.

Fullpriority

External On/Off control has full On/Off priority over the unit.

OnPriority

External On/Off control has On priority, but Off control is set to last touch priority.

OffPriority

External On/Off control has Off priority, but On control is set to last touch priority.

LastTouchPriority

Priority is given to the most recent On/Off command.

How does the On/Off Controller operate?

The Remote On/Off Controller option operates with the use of a locallysupplied volt-freeSwitch.Whenthe switch contact is made the Indoor Unit will turn On.

When the switch contact is broken the Indoor Unit will switch off.

Loading...