INSTALLATION MANUAL
To Personnel Charged in Installation Work and Service
Wireless Remote Controller Kit
Model: RBC-AX31U(W)-E, RBC-AX31U(WS)-E
Observe the safety precautions described in the Owner’s Manual of the wireless remote controller kit,
Installation Manual and Owner’s Manual of the 4-way air discharge cassette type air conditioner
(indoor unit), or the installation manual supplied with the ceiling panel.
Accessories
Signal receiving part
Remote controller
Remote controller holder
Battery
Part Name Q’ty
Owner’s Manual
1
Installation Manual (this
manual)
Tapping screw
1
Ø4×16 mm
Clamper
1
Clamper screw
Ø4×12 mm
2
Settings for the signal receiving part before installation
Before installing the signal receiving part, make the following settings referring to each description.
• When installing wireless remote controller together with wired remote controller → Perform
“Settings when installing the wireless remote controller kit together with wired remote controller”
• When ceiling height exceeds the standard height (factory setting) → Perform “Settings for high
ceiling”
• When installing multiple signal receiving parts in a room → Perform “Remote controller address
setting”
How to attach the signal receiving part
Since the signal receiving part can
be attached at only one corner
shown in (Fig. 1), be careful of the
orientation of the signal receiving
part after the ceiling panel is
attached to the indoor unit.
1. Detach the air inlet grille.
2. Detach the adjust corner cap at
the corner where the signal
receiving part is to be installed.
(Fig. 2)
Pull the knob of the adjust
corner cap in the arrow 1
direction, and detach the adjust corner cap.
*The knob is provided only on one side of the cap. Be sure to detach the cap from the knob side.
(Fig. 2)
3. A pad is packed in the two rectangular holes (indoor unit side and signal receiving part side) for
ceiling panel wires. Remove the pads temporarily, and pass the wires from the wireless signal
receiving part through the rectangular holes. (Fig. 3)
4. After the wiring is completed following “How to wire the signal receiving part” below without slack
of the wires, pull the black pad that covers the wire by approx. 20 mm out of the rectangular hole
on the indoor unit side, and then clamp the wires with the supplied clamper tightened with the
screw. Then return the packing removed from the rectangular hole on the signal receiving part to
the original position. (Fig. 3)
* Securely position the black pad and fix the packing. Failure to do so may cause water leakage or dew
(Fig. 3)
5.
Attach the signal receiving part to the ceiling panel, while taking care not to catch the wires.
(Fig. 4)
• Push the three claws of the adjust corner cap firmly as far as they will go. Failure to do so may
result in water leakage.
* For details of the wiring and test run, refer to “How to wire the signal receiving part” and “Test run” below.
Note: Do not bundle these control signal wires with the power wire to avoid malfunction.
Adjust corner cap
Knob
drop on the unit and wires.
Clamper
Remove the pad from the
rectangular hole on the indoor
unit side.
Pull the black pad that covers the wire by
approx. 20 mm out of the hole.
Insert the two claws on the adjust corner cap
(with signal receiving part) into the rectangular
holes of the ceiling panel in the a rrow direction.
Indoor unit drain
pipe side
Indoor unit electric
parts box
(Fig. 1)
1
Claws
Ceiling panel
Adjust corner cap
Rectangular
holes
Part Name Q’ty
Indoor unit
refrigerant pipe
side
Signal receiving
part attaching
position
Remove the pad from the rectangular
hole on the signal receiving part side,
clamp the wires with the clamper,
secure the clamper with the Ø4×12
screw, and then return the pad to the
original position.
Push the adjust corner cap in the arrow
directions so that the three claws are fitted.
1
1
2
1
1
(Fig. 4)
• Thank you for purchasing Wireless Remote Controller Kit Toshiba packaged air conditioner.
• Read this manual carefully for correct installation of the wireless remote controller kit before
starting work.
• After the installation is completed, execute a test run to check for normal operation and explain
how to use and maintain the wireless remote controller kit to the customer according to the
Owner’s Manual.
Ask the customer to keep this manual with the Owner’s Manual.
How to wire the signal receiving part
<Connection diagram>
<Connection>
Connect the wires from the signal receiving part to the remote controller connection terminal block of
the indoor unit. (The terminals are nonpolar.)
• Clamp the redundant portion of the wires with the clampers in the electric parts box.
Electric parts box
Indoor unit remote
controller connection
terminal block
Indoor unit Signal receiving part
Remote controller
connection
terminal block
White
Black
Clampers Clamping claw
white
Signal receiving part
Test run
Perform usual operations using the remote controller to check for normal operation. A test run can be
executed forcibly by using the following procedure if the room temperature is too high to turn off the
thermostat.
1. Turn off the power of the air conditioner, and remove the screws to detach the signal receiving
part cover.
2. Set bit 1 of DIP switch S003 on the signal receiving part P.C. board to ON.
3. Attach the signal receiving part to the ceiling panel by reversing the procedure of removal, and
then turn on the power of the air conditioner.
4. Push [START/STOP] on the wireless remote controller, and select COOL or HEAT with [Mode
select]. (Temperature cannot be controlled during a test run.)
5. All LEDs on the signal receiving part flash during a test run.
6. After the test run has been completed, be sure to set bit 1 of DIP switch S003 to OFF and confirm
that the LEDs do not flash.
7. Clamp the wires properly with the clamper secured together with the signal receiving part cover.
Note 1: Use the forced test run only for test run because it overloads the air conditioner.
Note 2: The remote controller is disabled for approx. 1 minute after power-on, but this is normal. The signal
from the remote controller is received, but the receive data is discarded.
Signal receiving
part cover
Clamper
Screw
Adjust corner cap with
signal receiving part
S003
Bit1 : OFF ON
123
4
ON
Signal receiving part P.C. board
Settings when installing the wireless remote controller kit together
with wired remote controller
A dual remote controller system is available by installing the wireless remote controller kit together
with the wired remote controller. (Up to two wireless and wired remote controllers can be installed.)
The dual remote controller system controls one or more indoor units with two remote controllers.
Note: Connect wires correctly to the signal receiving part, checking terminal numbers on the indoor unit. If
220/240 VAC is applied, the circuit will be broken.
Note: Multiple wireless remote controller kits cannot be attached to one indoor unit.
Note: To use the wireless remote controller kit together with the wired remote controller, set either
remote controller to a follower remote controller.
• To use the wired remote controller as a follower, change the setting of the DIP switch on the back of
the wired remote controller P.C. board from Header to Follower. For changing DIP switch setting,
refer to the installation manual of the wired remote controller.
• To use the wireless remote controller as a follower, set bit 3 of DIP switch S003 on the signal
receiving part P.C. board to ON.
Controlling one indoor unit by two remote controllers
• The indoor unit is operable regardless of the settings (Header or Follower) of the remote
controllers.
Wireless remote
controller kit * (Header)
Signal
receiving part
Remote controller
connection
terminal block
* Use 0.5 to 2 mm2 wires for on-site wiring.
* The total length of wires should be 400m or less.
Earth
(Separately sold)
Indoor unit
Wired remote
controller * (Follower)
Remote controller wires
(procured on site)
Performing group control of multiple indoor units by two remote controllers
• Header and follower indoor units are operable even if they are attached to any indoor unit.
Wireless remote
controller kit * (Header)
Signal
receiving part
Remote controller
connection
terminal block
Earth
* Use 0.5 to 2 mm2 wires for on-site wiring.
* The total length of inter-unit wires should be 200m or less.
(Separately sold)
Indoor unit No.1 Indoor unit No.2 Indoor unit No.3 Indoor unit No.4
Remote controller inter-unit
wires for group control
(procured on site)
Earth Earth Earth
Wired remote
controller * (Follower)
(Separately sold)
Settings for high ceiling
• When an indoor unit is installed on a ceiling higher than the standard height (factory setting shown
in the table below) or when changing the number of air discharge ports by using the windshield kit
(separately sold), the DC fan tap is required. Bit 2 (tap 1) and bit 4 (tap 2) of DIP switch S003 on the
signal receiving part P.C. board are used for the DC fan tap setting.
Change the setting with DIP switch S003 on the signal receiving part P.C. board of this product
(RBC-AX31U).
The setting change is shown below.
Clamper
Screw
DIP switch
Signal receiving part cover
Adjust corner cap with signal receiving part
Signal receiving part P.C. board
DIP switch [S003]
1 For test run
2 Tap 1
3 For switching header/follower
4 Tap 2
S003
The following table shows tap settings.
Ceiling Height
Tap 1 Tap 2
OFF OFF
Factory setting
OFFON3.23.53.83.33.53.84.24.44.6
ON OFF 3.5 3.8 - 3.6 3.8 - 4.5 4.6 -
Note: The windshield kit is necessary to set the air discharge direction to 3 or 2 directions. In addition to the
setting change mentioned above, change the setting using the wired remote controller according to
the installation manual of the windshield kit. Failure to change the setting may cause condensation.
After the setting change has been completed, reassemble the parts as they were. Clamp the wires
properly with the clamper secured together with the signal receiving part cover.
SM56 types SM80 types SM110, 140 types
4
directions3 directions2 directions4 directions3 directions2 directions4 directions3 directions2 directions
2.8 3.2 3.5 3.0 3.3 3.6 3.9 4.2 4.5
Unit installable ceiling height (unit: m)
Remote controller address setting
• When two or more signal receiving parts are installed in a room, a unique address can be set for
each signal receiving part to prevent interference.
• When you push the reset button after replacing batteries, the address displayed on the remote
controller shows “ALL” While “ALL” is displayed, signals from the remote controller can be received
regardless of the setting of the address switches in the signal receiving part.
• For how to change remote controller addresses, refer to the Owner’s Manual.
• Detach the signal receiving part cover of the signal receiving part when changing the signal
receiving part address. After the setting change has been completed, clamp the wires properly with
the clamper secured together with the signal receiving part cover.
Address
displayed on
the remote
controller
Address
switch
setting in the
signal
receiving
part
Address Address Address Address
*
Any address
setting is OK.
How to handle the remote controller
• To set the remote controller on the wall
Push [START/STOP] at the installation position on the wall to check that the signal from the remote
controller is received correctly.
Remote controller holder
Screw
Tapping screw Ø4×16
Put on.
1
Push
2
To take the r emote
controller out of the
holder, pull it toward you.
Remote controller
Remote controller
holder
• Replacing batteries
1. Slide and remove the cover downward while
holding both sides of the cover.
2. Insert two AAA alkaline batteries correctly
matching the (+) and (-) polarities with the
indication.
3. Push the reset button with a fine-tipped tool
and attach the cover.
Cover Reset button
Batteries
Setting the room temperature sensor
• The room temperature sensor is provided in the indoor
unit and the remote controller. The room temperature
sensor functions in either indoor unit or remote controller.
• The sensor setting was made to the indoor unit side when
the product was shipped. To change the setting to the
remote controller side, push the sensor button (right
figure) inside the remote controller cover and check that
“Main sensor”
Note: Even if the sensor is set to the remote controller side,
disappears from the LCD display.
when the room temperature data from the remote
controller does not arrive at the indoor unit for 10
minutes, the sensor setting automatically changes to the
indoor unit side. Install the remote controller pointing it
at the indoor unit as much as possible.
ACL
ADR
SENSOR
Sensor button
How to set slide switches
• Set the slide switches in the battery compartment of
the remote controller depending on indoor unit
types that use the signal receiving part.
Note: The slide switches are set to “S” and “A” by
default.
Note: After the switch setting has been changed, push
the reset button.
* For details, refer to the Owner’s Manual.
Heat pump (With automatic
cooling/heating)
* Do not change the flap display setting.
Heat pump (Without
automatic cooling/heating)
Cool-only Flap display switching
Operation
mode
switch
Flap display
switch
Self-diagnosis function and measures
• The following table shows a few examples. For details of indoor unit errors, refer to the Installation
Manual of the indoor unit.
LED Possible cause Measures
- Power is not turned on.
- Incorrect connection between signal
T
hese LEDs do not light or flash even if
the remote controller is operated.
Flashing
Flashing
Flashing alternately
Flashing alternately
LEDs on the signal receiving part : OFF : Flashing (at intervals of 0.5 seconds)
LED color : Green : Green : Orange
receiving part and indoor unit
Loose connection between signal
receiving part and indoor unit
Incorrect or loose connection between
indoor unit and outdoor unit
The protective device of the outdoor
unit is activated.
The protective device of the indoor
unit is activated.
Check connections and reconnect
wires correctly, if necessary.
Check the outdoor unit.
Check the indoor unit.
Notes on installing remote controller
• When using a wireless remote controller in the remote controller holder on a wall, turn on a
fluorescent light and operate the remote controller at the installation position. Make sure that the air
conditioner operates normally and then secure the remote controller holder on the wall.
• When installing a remote controller that senses room temperature with the sensor, avoid the
following places.
• A place exposed to direct cool air , warm air or direct sunlight
• A place subject to thermal effects
Explanation to the customer
• After the installation work has been completed, execute a test run to check for normal operation
and then hand the customer the Owner’s Manual and Installation Manual of the wireless remote
controller kit.
• Explain how to use and maintain the wireless remote controller kit to the customer according to the
Owner’s Manual of the wireless remote controller kit.