TeeJet 854 User Manual

4 (2)
TeeJet 854 User Manual

854 Sprayer Control

854SprayerControl

COPYRIGHTS

© 2010 TeeJet Technologies. All rights reserved. No part of this document or the computer programs described in it may be reproduced, copied, photocopied, translated, or reduced in any form or by any means, electronic or machine readable,

recording or otherwise, without prior written consent from TeeJet Technologies.

TRADEMARKS

Unless otherwise noted, all other brand or product names are trademarks or registered trademarks of their respective companies or organizations.

LIMITATION OF LIABILITY

TEEJET TECHNOLOGIES PROVIDES THIS MATERIAL “AS IS” WITHOUT WARRANTY OF ANY KIND, EITHER EXPRESSED OR IMPLIED. NO COPYRIGHT LIABILITY OR PATENT IS ASSUMED. IN NO EVENT SHALL TEEJET TECHNOLOGIES BE LIABLE FOR ANY LOSS OF BUSINESS, LOSS OF PROFIT, LOSS OF USE OR DATA, INTERRUPTION OF BUSINESS, OR FOR INDIRECT, SPECIAL, INCIDENTAL, OR CONSEQUENTIAL DAMAGES OF ANY KIND, EVEN IF TEEJET TECHNOLOGIES HAS BEEN ADVISED OF SUCH DAMAGES ARISING FROM TEEJET TECHNOLOGIES SOFTWARE

TableofContents

 

COPYRIGHTS..........................................................................................................................................................

I

TRADEMARKS........................................................................................................................................................

I

LIMITATION OF LIABILITY..................................................................................................................................

I

CHAPTER 1 - INTRODUCTION.....................................................................

1

Power On the Console_ _______________________________________________ 2

 

Power Off the Console_ _______________________________________________ 2

 

CHAPTER 2 - OEM PROGRAM MODE.........................................................

3

Number of Boom Section Switches On the Console_________________________ 3

 

Lane Width (GLM Working Units)________________________________________ 3

 

Regulation Parameters________________________________________________ 4

 

Minimum Regulating Valve Voltage________________________________________ 4

 

Regulation Stop Band_________________________________________________ 4

 

Rotation Time of Regulating Valve_______________________________________ 5

 

Display Stabilization__________________________________________________ 6

 

Data Display Screen Options_ __________________________________________ 6

 

Calibrate Tip Level Percent_____________________________________________ 6

 

Digital Output #2____________________________________________________ 7

 

Dual Boom Regulation Mode___________________________________________ 8

 

Fill Valve Default_ ____________________________________________________ 8

 

Auto Power Down____________________________________________________ 9

 

www.teejet.com i

854SprayerControl

 

TEEJET COMMUNICATION SYSTEM (TCS) CONFIGURATION.............................................................

9

Job Operating System________________________________________________ 9

 

Console Identification Number_ _______________________________________ 10

 

Maximum Speed Achieved___________________________________________ 10

 

Hidden Area Counter_ _______________________________________________ 10

 

Hidden Volume Counter______________________________________________ 10

 

PRESSURE TRANSDUCER CALIBRATION (P HI).....................................................................................

11

Memory Save Function_______________________________________________ 12

 

CHAPTER 3 - SYSTEM SETUP MODE.......................................................

13

Selection of Working Units____________________________________________ 13

 

Reset to Defaults____________________________________________________ 13

 

Speed Sensor Calibration_____________________________________________ 14

 

Proximity/Magnetic Pulses______________________________________________ 14

 

Automatic Calibration__________________________________________________ 14

 

Distance Counter___________________________________________________ 15

 

Pressure Hold______________________________________________________ 15

 

Pressure Sensor Installed_ ____________________________________________ 16

 

Pressure Transducer Low Pressure Calibration (P Ref)______________________ 16

 

Automatic Calibration__________________________________________________ 16

 

Pressure Transducer Maximum Rating (P HI)______________________________ 17

 

Flow Meter Installed_________________________________________________ 17

 

Flow Meter Pulses___________________________________________________ 18

 

Manual Entry_________________________________________________________ 18

 

Automatic Calibration__________________________________________________ 18

 

Flow Sensor Minimum Flow Capacity_ __________________________________ 19

 

Sensor Selection____________________________________________________ 20

 

Section Valve Type__________________________________________________ 20

 

Pressure Regulating Mode____________________________________________ 21

 

Regulating Valve Capacity_ ___________________________________________ 22

 

Regulating Valve Speed - Coarse Adjustment_____________________________ 22

 

Regulating Valve Speed - Fine Adjustment_______________________________ 23

 

Tank Volume_ ______________________________________________________ 23

 

Low Tank Volume Alarm______________________________________________ 24

 

Fill Flow Meter Calibration_ ___________________________________________ 24

 

Manual Entry_________________________________________________________ 24

 

Automatic Calibration__________________________________________________ 24

 

Communications____________________________________________________ 26

 

Printing Memory Contents______________________________________________ 26

 

Using GPS___________________________________________________________ 27

 

ii www.teejet.com

854SprayerControl

Communicating With a Laptop Running Fieldware Software__________________ 27 Logging Information to a Laptop running Logging Software__________________ 28

GPS Speed_________________________________________________________ 28 Use External Rate_ __________________________________________________ 28

Simulated Ground Speed_____________________________________________ 29

Low Speed___________________________________________________________ 29 High Speed___________________________________________________________ 29

Auto Master Off - Speed______________________________________________ 30 Minimum Pressure Setting____________________________________________ 30 Maximum Pressure Setting___________________________________________ 30 Audible Alarm______________________________________________________ 31 Dual Boom On Setting_ ______________________________________________ 31 Memory Reload Function_____________________________________________ 32

CHAPTER 4 - APPLICATION PRESET SETUP MODE................................

33

Tip Spacing_ _______________________________________________________ 33 Number of Tips Per Boom Section______________________________________ 34

Density___________________________________________________________ 34

Alternate Density Used_________________________________________________ 34 Density Value_________________________________________________________ 34

Tip Selection_______________________________________________________ 35 Target Application Rate_ _____________________________________________ 35

Calculation Steps___________________________________________________ 36

Known Pressure Calculation____________________________________________ 36 Known Speed Calculation______________________________________________ 36

CHAPTER 5

- OPERATIONS.......................................................................

37

Sprayer Evaluation_ _________________________________________________ 37

 

Spraying__________________________________________________________ 38

 

CHAPTER 6

- FEATURES............................................................................

39

Area/Volume Display________________________________________________ 39

Memory Feature_ ___________________________________________________ 40

Viewing Memory Information____________________________________________ 40 Clearing Memory Locations_____________________________________________ 40 Saving Information to Memory___________________________________________ 40

Tank Feature_ ______________________________________________________ 41

Auto Tank Filling______________________________________________________ 41 Tank Volume Feature___________________________________________________ 42

Viewing Remaining Tank Volume______________________________________ 42 Resetting Tank Volume______________________________________________ 42

www.teejet.com iii

854SprayerControl

Application Alarm___________________________________________________ 42

Sensor LED Alarms_ _________________________________________________ 43

No Speed Alarm_______________________________________________________ 43 No Flow Alarm________________________________________________________ 43 No Pressure Alarm____________________________________________________ 44 Flow/Pressure Discrepancy Alarm_______________________________________ 44

Boost Mode________________________________________________________ 44

Boost Up____________________________________________________________ 44 Boost Down__________________________________________________________ 45

Auto Power Down___________________________________________________ 45 Smart Sensing______________________________________________________ 45

iv www.teejet.com

854SprayerControl

CHAPTER 1 - INTRODUCTION

This User Guide provides information for software version 1.20.

Make sure that all hardware components are properly installed and tested. Before starting the programming process, confirm that the console and all sensors are working properly.

IMPORTANT! Before beginning, review the following Program Guidelines that control the programming process.

To exit any Setup Mode, press and hold the PROGRAMkey for 3 seconds. The inputs are stored and the computer will exit Program Mode.

To increase the value of a programmable digit, press the PLUSkey. To decrease the value, press the MINUSkey. These keys are located directly to the right of the display. For some program steps, press and hold the PLUSand MINUSkeys to quickly change the values. Press the PLUSand MINUSkeys once to increment/decrement the values by one unit.

Figure 2-1: 854 Console

Press and hold the AUTO/MANkey to reset the value to “0” or restore factory default settings during some steps.

Press the PROGRAMkey to advance the system to the next program step. After the final program step is complete, the console will finish the programming loop and return to the initial programming step.

System Setup mode contains the options that customize the controller to the sprayer or sprayer components. These include calibration steps and parameters that seldom change once programmed.

Application Setup mode contains settings that are frequently changed (tip spacing, number of tips per boom section, density, nozzles used, and target application rate).

Sensor LED Alarms

 

Plus and Minus keys

On/Program button

 

 

 

 

Preset key

 

 

 

 

 

 

 

 

Auto/Manual mode indicator

 

 

 

Tank key

Auto/Man key

 

 

 

Memory key

Master Switch

 

 

 

 

 

 

 

Display

 

Boom Section Controls

 

 

www.teejet.com 1

854SprayerControl

Power On the Console

The 854 console can be powered on by pressing the PROGRAMkey one time. The console will initially display the software version at the top of the screen and the serial number of the console at the bottom of the screen. After approximately 5 seconds, the console will enter into swath width view.

Press the PROGRAMkey to advance to normal Operations mode.

Figure 2-2: Power On the Console

SFt 1.20

H28 0008

Power Off the Console

To power off the 854 console, press and release the MINUSand PROGRAMkeys simultaneously. The console will save new information (area and volume counters) to memory before it powers down. The console also has an automatic power down feature. This is described in further detail in the Features section of this User Guide.

Figure 2-3: Power Off the Console

2 www.teejet.com

854SprayerControl

CHAPTER 2 - OEM PROGRAM MODE

The OEM Program Mode contains configuration steps for the console. The console is typically pre-configured before being shipped. Changing the configurations is not recommended unless instructed to do so as it may adversely affect the performance of the controller.

To enter the OEM Program Mode:

Begin with the console powered “Off”.

Press the MINUSkey and the PROGRAM

key simultaneously to turn the console “Off” if required.

• Press and hold the PLUSand MINUS

keys. While still holding them, press the PROGRAMkey 4 times.

• Release all keys.

Figure 3-1: Entering OEM Program Mode

nr 5

SEC

Number of Boom Section Switches On the Console

The number of individual boom section switches actually present on the control console (regardless of the number of boom sections that are on the sprayer) can be programmed.

Press and hold the AUTO/MANkey for 3 seconds to set the value to “1”.

Press the AUTO/MANkey once to reset the value to the default value of “5”.

Press the PROGRAMkey to accept the value and advance to the next program step.

Lane Width (GLM Working Units)

When Gallons per Lane Mile “GLM” is selected as the working units, this screen will allow the operator to enter the lane width in inches.

Use the PLUSor MINUSkeys to modify the value.

Press the Programkey to accept the value and advance to the next program step.

Figure 3-2:

Lane Width (GLM Working Units) Window

144

Use the PLUSor MINUSkeys to modify the value.

1 to 11 switches can be programmed.

This number will determine the number of spray tips per boom section during the System Setup Mode.

www.teejet.com 3

854SprayerControl

Regulation Parameters

The regulation algorithm is configured with the next three parameters:

1.Minimum Regulating Valve Voltage: the minimum voltage that can drive the regulating valve.

2.Regulation Stop Band: the maximum allowed application error rate.

3.Rotation Time of Regulating Valve: the total time required to close the regulating valve at maximum speed.

These three OEM parameters depend on the regulating valve used.

Minimum Regulating Valve Voltage

The console uses variable voltages to drive the regulating valve. Select the minimum voltage that the regulating valve needs to make it turn at its slowest rotation speed (i.e., if the motor of the regulating valve turns with a minimum of 3.5v, the number should be used in this location).

The affect of this parameter on the regulation behavior is illustrated in Figure 2-4. This value must match the actual operation of the regulating valve used. Check with the valve manufacturer for the value.

Use the Plusor MINUSkeys to change the voltage.

Press and hold the AUTO/MANkey for 3 seconds to set the value to “0.0”.

Press the AUTO/MANkey once to set to the default value of 3.5v.

Press the PROGRAMkey to accept the value and advance to the next program step.

NOTE: Standard TeeJet Technologies regulating valve minimum voltage is 3.5v.

If 12v is selected as a minimum voltage, no variable voltage regulation occurs. Instead, a pulse regulation occurs. This is necessary when using solenoid operated regulating valves (i.e., a Ramsay valve).

Figure 3-3: Minimum Regulating Valve Voltage

rE6 3.5

Figure 3-4: Voltage Comparison

Regulation Stop Band

The Regulation Stop Band is the maximum error percentage allowed on the application rate before the regulating valve reacts (i.e., if a stop band of 1.5% is selected, there is no action on the regulating valve if the actual application rate is within 1.5% of the target rate). This minimum percentage prevents the regulating valve from oscillating in a narrow band around the target point.

Use the PLUSor MINUSkeys to change the regulation stop band (value is expressed

4 www.teejet.com

854SprayerControl

in error percentage). The maximum value is 10.0%.

Press and hold the AUTO/MANkey for 3 seconds to set the value to “0.0”.

Press the AUTO/MANkey once to set the value to the default setting of “1.5%”.

Press the PROGRAMkey to accept the value and advance to the next program step.

Figure 3-5: Regulation Stop Band

rE6 1.5

STP BAnd

Rotation Time of Regulating Valve

The Rotation Time of Regulating Valve is the number of seconds the regulating valve needs to turn from the complete closed position to the complete open position at the nominal voltage (i.e., 14v).

Use the PLUSor MINUSkeys to change the rotating time of the regulating valve in seconds (minimum “0’s”, maximum “50’s”).

Press and hold the AUTO/MANkey for 3 seconds to set the value to “0.0”.

Press the AUTO/MANkey once to set the value to the default setting of “6 seconds”.

Press the PROGRAMkey to accept the value and advance to the next program step.

NOTE: Standard TeeJet regulating valve rotation time is 6 seconds.

Figure 3-6: Effects of Parameters

 

 

The console uses this parameter to control the

 

 

regulation speed. The value must match the actual

 

 

 

 

 

 

Voltage on REGULATING VALVE

 

 

 

 

operation of the regulating valve used. Check with

14

 

 

 

 

 

the valve manufacturer for this value.

 

 

 

 

 

Figure 3-7: Rotation Time of Regulating Valve

 

 

 

 

 

 

 

 

 

 

 

 

rE6

6

0

Regulation Stop Band

 

SPd

SEC

 

 

 

 

 

 

 

0

10

20

30

40

50

60 %

 

Percentage of DEVIATION between TARGET and DOSE RATE

 

 

www.teejet.com 5

854SprayerControl

Display Stabilization

Display Stabilization establishes the stabilization rate that steadies the Application Rate displayed during minor adjustments of the control system. The controller will continue to make the required adjustments at all times. Enter the percentage of allowable change from the target rate in this step.

For example, the system has a target rate of 20 GPA with 5% programmed for Display Stabilization. The display will indicate 20 GPA at any time the actual rate is +/- 5%, or:

Use the PLUSor MINUSkeys to change the value.

Press and hold the AUTO/MANkey for 3 seconds to set the value to “0.0”.

Press the AUTO/MANkey once to set the value to the default setting of “5%”.

Press the PROGRAMkey to accept the value and advance to the next program step.

NOTE: The Display Stabilization value is limited to 20%. A value of 0% will disable the setting.

Figure 3-8: Display Stabilization

s O

5

diS

rAtE

Data Display Screen Options

The lower right hand display used during normal operations mode can be customized to display:

volume sprayed

area covered

both volume sprayed and area covered (alternating every 3 seconds)

To customize the data display options:

Use the PLUSor MINUSkeys to change the data to be displayed.

Press the PROGRAMkey to accept the value and advance to the next program step.

Figure 3-9: Data Display Screen

dAt bOth

Calibrate Tip Level Percent

If both a pressure sensor and a flow meter are installed and being used, the 854 uses one sensor to cross check the other for system errors.

Select the primary sensor (used for regulation) in the Sensor Select step of System Setup Mode. The opposite sensor will automatically perform the crosschecking function.

The Calibrate Tip Level % will establish the % of allowable error between the sensors before an alarm is activated. All sprayer systems have some discrepancy between pressure and flow due to pressure drops and positioning of sensors.

Use the PLUSor MINUSkeys to change the % of allowable error.

Press the PROGRAMkey to accept the value and advance to the next program step.

NOTE: It is recommended that this value remain at 50% unless instructed otherwise.

6 www.teejet.com

 

 

854SprayerControl

Figure 3-10: Calibrate Tip Level %

Figure 3-11: Digital Output # 2a

CAL

50

Out

2

tIP

LEv

nOT

USEd

Digital Output #2

The primary output from the console computer drives the pressure regulating valve. A second output is available and can be configured for the following uses:

Not Used - the second digital output is not used

Dual Boom - used to control a shutoff valve on a second boom line that is automatically activated based on speed and pressure

Fill Valve - used to automatically shut off a valve or switch during a tank filling operation when used with a tank fill flow meter

To establish the Digital Output settings:

Use the PLUSor MINUSkeys to change the value.

Press the PROGRAMkey to accept the value and advance to the next program step.

Out

2

dUA

bOOn

Out

2

FiL

vALV

www.teejet.com 7

854SprayerControl

Dual Boom Regulation Mode

NOTE: This step will only be displayed if “Dual Boom” was selected during the DIGITAL OUTPUT #2 step.

Dual Boom Regulation Mode is used to regulate the dual boom feature by either speed (SPD) or pressure (PRS).

If speed is used to regulate the mode, when the vehicle reaches the designated speed, the second boom line will turn On/Off.

If pressure is used to regulate the mode, when the pressure reaches the designated amount, the second boom line will turn On/Off.

Use the PLUSor MINUSkeys to change the value.

Press the PROGRAMkey to accept the value and advance to the next program step.

The value selected will determine how programming steps appear during System Setup Mode. Specific speed or pressure values to be used during operation are selected during the System Setup Mode.

Figure 3-12: Dual Boom Regulation Mode - Speed

db SPd

re6

Figure 3-13: Dual Boom Regulation Mode - Pressure

db PrS

re6

Fill Valve Default

NOTE: This step will only be displayed if “Dual Boom” was selected during the DIGITAL OUTPUT #2 step.

The Fill Valve Default establishes the normal operating state of the fill valve being used. If the fill valve requires a +12v signal during the spraying operation, the valve default is “On”. If the fill valve requires a +12v signal during the filling operation, the valve default is “Off”.

Use the PLUSor MINUSkeys to change the value.

Press the PROGRAMkey to accept the value and advance to the next program step.

Figure 3-14: Fill Valve Default

FiL OUt

OFF dFLt

8 www.teejet.com

854SprayerControl

Auto Power Down

The 854 console is designed to automatically power down after 10 minutes of inactivity from the sensor or operator. To adjust the length of time:

Use the PLUSor MINUSkeys to change the value of the power down time.

Press the PROGRAMkey to accept the value and advance to the next program step.

NOTE: If the Power Down Time is set to “0”, the Auto Power Down feature will be disabled.

Figure 3-15: Auto Power Down

Pur 10

Off

TEEJET COMMUNICATION SYSTEM (TCS) CONFIGURATION

NOTE: If the TeeJet Communication System (TCS) package was not purchased for this console, the next 2 programming steps DO NOT pertain to your spraying operation. IF THIS IS THE CASE, THESE VALUES SHOULD BE LEFTAT THE DEFAULT SETTINGS.

Job Operating System

Job No (Default) - the console uses application parameters entered by the operator only

Job Only - the console uses application parameters entered from the TeeJet Communication System only

Job Both - the console accepts application parameters for both the operator and the TeeJet Communication System

To establish the Job Operating System settings:

Use the PLUSor MINUSkeys to change the value.

Press the PROGRAMkey to accept the value and advance to the next program step.

Figure 3-16: Job Operating System

JOb

www.teejet.com 9

854SprayerControl

Console Identification Number

The TeeJet Communications System (TCS) is capable of monitoring and communicating with several consoles at one time. Therefore each console communicating with a single TCS must be assigned a unique identification number. THE DEFAULT NUMBER IS “1”.

Use the PLUSor MINUSkeys to change the value.

Press the PROGRAMkey to accept the value and advance to the next step.

Figure 3-17: Console Identification Number

1

Id

Maximum Speed Achieved

The Maximum Speed Achieved feature records the maximum speed achieved by the sprayer. This value can only be cleared by an authorized TeeJet Dealer, Distributor, or Representative.

Press the PROGRAMkey to advance to the next step.

Figure 3-18: Maximum Speed Achieved

SPd

MPH

5.3 High

Hidden Area Counter

The Hidden Area Counter can only be viewed and cleared during this step. This value can only be cleared by an authorized TeeJet Dealer, Distributor, or Representative.

Press the PROGRAMkey to advance to the next step.

Figure 3-19: Hidden Area Counter

Ar

1480Ac

Hidden Volume Counter

The Hidden Volume Counter can only be viewed and cleared during this step. This value can only be cleared by an authorized TeeJet Dealer, Distributor, or Representative.

Press the PROGRAMkey to advance to the next step.

Figure 3-20: Hidden Volume Counter

uOL

4630Vol

10 www.teejet.com

854SprayerControl

PRESSURE TRANSDUCER CALIBRATION (P HI)

NOTE: This step may not appear if the console has not been programmed during System Setup Mode for use with a pressure sensor.

WARNING! It is not recommended that this calibration procedure be initially performed. It should ONLY be performed if a known pressure drop exists between the Pressure Transducer and the spray tips and if a TeeJet representative recommends performing it.

The pressure sensor can be automatically calibrated to compensate for pressure loss between the pressure transducer and the spray tips.

Press and hold the PLUSand MINUS keys to start the Auto Calibration process. The lower left hand screen will go blank.

Place an accurate manual pressure gauge in the spray line, as close to the spray tips as possible.

Activate the pump and boom sections to be used for calibration.

Turn the Master Switch to the “On” position.

Press the PLUSor MINUSkeys to adjust the pressure on the manual pressure gauge near the tips to the desired pressure to be used for the calibration. The higher the pressure the better.

Turn the Master Switch to the “Off” position.

Use the PLUSor MINUSkeys to adjust the displayed pressure to match the actual calibration pressure.

Activate the pump and boom sections to be used for calibration.

Confirm that the actual pressure matches the displayed pressure.

Press the PROGRAMkey to begin calibration.

The console will display “0-10” during the calibration process.

The new Pressure Transducer Maximum Rating will be displayed. The value is automatically carried over to the System Setup Mode.

Press the PROGRAMkey to advance to the next step.

Figure 3-21: Pressure Transducer Calibration

145PSI PHi

PrS SenS

PSI75 16.2

206

www.teejet.com 11

Loading...
+ 36 hidden pages