Taylor-Wharton MicroBulk MB-450 Installation And Operation Manual

Page 1
MB - 450
Installation and Operation Manual
Do not attempt to use or maintain these units until you read and understand these instructions. Refer to the Taylor Wharton’s “Safety First” booklet (TW - 202) for handling cryogenic material. Do not permit untrained persons to use or maintain this equipment. If you do not understand these instructions, contact your supplier for additional information. www.taylorwharton.com
BT- 434 REV.A
Page 2
BT- 434 Rev.A
2
WARNING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3
Safety Precautions for Liquid Oxygen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3
Safety Precautions for Liquid Nitrogen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4
INTRODUCTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6
System Description. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6
Specication. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7
PIPING CIRCUITS. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .8
P&ID: MB-450 Standard Conguration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .8
Fill and Vent Circuits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .9
Express Fill Circuit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Pressure Building Circuit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Gas Withdrawal Circuit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Economizer Circuit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Safety Devices. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Instrumentation Circuits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
OPERATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Receiving Inspection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Handling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .16
Customer Installed Equipment/Piping . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Filling by Pressure Transfer. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Filling by Pump Transfer. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Filling for Road Transport. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Withdrawing Gas . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Withdrawing Liquid . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Changing Gas Service . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
MAINTENANCE. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Leak Test . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .19
Globe Valves . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Regulator . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Instruments . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Checking Vacuum. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Trouble-Remedy Guide . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Replacement Parts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .24
APPENDIXES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
Appendix 1 – MB - 450 General Arrangement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
TABLE OF CONTENTS
Page 3
BT- 434 Rev.A
3
WARNING
The following safety precautions are for your protection. Before installing, operating, or maintain­ing this unit read and follow all safety precautions in this section and in the reference publications. Failure to observe all safety precautions can result in property damage, personal injury, or possibly death. It is the responsibility of the purchaser of this equipment to adequately warn the user of
the precautions and safe practices for the use of this equipment and the cryogenic uid stored in it.
CAUTION: When installing eld-fabricated piping, it is recommended to make certain a suitable safe-
ty valve is installed in each section of piping between shut-o valves.
For more detailed information concerning safety precautions and safe practices to be observed when handling cryogenic liquids consult CGA pamphlet P-12 “Handling Cryogenic Liquids” avail-
able from the Compressed Gas Association, 1235 Jeerson Davis Highway, Arlington, VA 22202.
Safety Precautions for Liquid Oxygen
Oxygen is a colorless, odorless, and tasteless gas that can be condensed into a liquid at the low
temperature of 297 degrees below zero Fahrenheit (-183�C) under normal atmospheric pres­sure. Approximately one-fth of normal air is oxygen. As a liquid, oxygen is pale blue in color. Ox­ygen is non-ammable; however it vigorously accelerates the burning of combustible materials.
Keep Combustibles Away from oxygen and eliminate ignition sourc­es. Many substances that do not normally burn in air require only a slight spark or
moderate heat to set them aame in the presence of concentrated oxygen. Oth­er sub stances, which are only moderately combustible in air, can burn violently when a high percentage of oxygen is present.
Do not permit smoking or open ame in any area where liquid oxygen is stored, handled, or used. Keep all organic materials and other ammable substances
away from possible contact with liquid oxygen. Some of the materials that can react violently with oxygen are oil, grease, kerosene, cloth, wood, paint, tar, and
dirt that contains oil or grease. Under certain conditions ammable materials that
have become permeated with liquid oxygen are impact sensitive and can detonate if subjected to shock.
Keep Area and Exterior Surfaces Clean to Prevent Ignition
As normal industrial soot and dirt can constitute a combustion hazard, all equip­ment surfaces must be kept very clean. Do not place oxygen equipment on as­phalt surfaces, or allow grease or oil deposits to remain on benches or concrete surfaces in the vicinity of the oxygen equipment. Use cleaning agents, which will not leave organic deposits, on the cleaned surfaces. Equipment to be used in con­tact with liquid oxygen should be handled only with clean gloves or hands washed clean of oil.
Maintain Adequate Ventilation
Enclosed areas containing oxygen equipment should be ventilated to prevent ac­cumulations of oxygen and thereby minimize combustion hazards.
Page 4
BT- 434 Rev.A
4
WARNING
Extreme Cold - Cover Eyes and Exposed Skin
Accidental contact of liquid oxygen or cold issuing gas with the skin or eyes may cause a freezing injury similar to frostbite. Handle the liquid so that it won’t splash or spill. Protect your eyes and cover the skin where the possibility of contact with the liquid, cold pipes and equipment, or the cold gas exists. Safe- ty goggles or a face shield should be worn if liquid ejection or splashing may occur or cold gas may issue forcefully from equipment. Clean, insulated gloves that can be easily removed and long sleeves are recommended for arm protec-
tion. Cuess trousers should be worn outside boots or over the shoes to shed
spilled liquid. If clothing should be splashed with liquid oxygen or otherwise saturated with the gas, air out the clothing immediately, removing it if possible.
Such clothing will be highly ammable and easily ignited while the concentrat­ed oxygen remains, and should not be considered safe for at least 30 minutes.
Replacement Parts Must be Suitable for Oxygen Service
Many materials, especially some non-metallic gaskets and seals, constitute a combustion hazard when in oxygen service, although they may be acceptable for use with other cryogenic liquids. Make no substitutions for recommended spare parts. Also, be sure all replacement parts are thoroughly “Cleaned For Oxygen
Service” in accordance with Compressed Gas Association (CGA) Pamphlet G-4.1 “Cleaning for Oxygen Service” or equivalent industrial cleaning specications.
Observe Safety Codes When Locating Oxygen Equipment
Before locating oxygen equipment, become thoroughly familiar with National
Fire Protection Association (NFPA) Standard No. 50, “Bulk Oxygen Systems”,
and with all federal, state and local safety codes. The NFPA Standard covers the general principles recommended for the installation of bulk oxygen sys­tems on industrial and institutional consumer premises.
Safety Precautions for Liquid Nitrogen
Extreme Cold - Cover Eyes and Exposed Skin
Accidental contact of liquid nitrogen or cold issuing gas with the skin or eyes may cause a freezing injury similar to frostbite. Handle the liquid so that it won’t splash or spill. Protect your eyes and cover the skin where the possibility of con­tact with the liquid, cold pipes and equipment, or the cold gas exists. Safety gog­gles or a face shield should be worn if liquid ejection or splashing can occur or cold gas can issue forcefully from equipment. Insulated gloves that can be easily removed and long sleeves are recommended for arm protection. Trousers with-
out cus should be worn outside boots or over the shoes to shed spilled liquid.
Nitrogen is an inert, colorless, odorless, and tasteless gas making up four-fths of the air you
breathe. Liquid nitrogen is obtained by cooling air until it becomes a liquid and then removing
the oxygen. Air is roughly one-fth oxygen. Liquid nitrogen is at a temperature of -320�F (-196�C)
under normal atmospheric pressure.
Page 5
BT- 434 Rev.A
5
WARNING
Keep Equipment Area Well Ventilated
Although nitrogen is non-toxic and non-ammable, it can cause asphyxiation in a conned area without adequate ventilation. Any atmosphere not containing
enough oxygen for breathing can cause dizziness, unconsciousness, or even death. Nitrogen, a colorless, odorless, and tasteless gas, cannot be detected by the human senses and will be inhaled normally. Without adequate ventilation, the expanding nitrogen will displace the normal air resulting in a non-life-supporting atmosphere.
Dispose of Waste Liquid Nitrogen Safely
Dispose of waste liquid nitrogen out-of-doors where its cold temperature cannot damage oors or driveways and where it will evaporate rapidly. An outdoor pit lled with clean sand or gravel will evaporate liquid nitrogen safely and quickly.
NOTE: Argon is an inert gas whose physical properties are very similar to those of
nitrogen. For handling of liquid argon, follow the safe practices described for the
handling and use of liquid nitrogen.
Page 6
BT- 434 Rev.A
6
INTRODUCTION
This manual provides information for the operation and maintenance of Taylor-Wharton’s line of MB-
450 cryogenic gas supply systems. These products store cryogenic liquid and dispense it as a warm pressurized gas. The MB-450 is designed for applications requiring nitrogen, argon, or oxygen gas. These products are ideal for on-site lling with Taylor-Wharton’s Express cryogenic liquid delivery ve-
hicle.
Additional product specications, ow diagram, views, and important dimensions are shown on the
general arrangement drawing provided in the appendix of this manual.
System Description
The MB-450 consists of a cryogenic liquid vessel, piping, internal vaporizer, and an internal pressure
builder.
The system vessel has an approximate gross capacity of 450 liters. The vessel consists of a pressure
vessel suspended inside a jacket. The space between the pressure vessel and the jacket is evacuated
and insulated with a micro-berglass / aluminum foil radiation shield. Both the inner pressure vessel and vacuum jacket are constructed of type 304 stainless steel. Models are available designed and con­structed in accordance with DOT-4L or ASME Section VIII. The DOT-4L vessels may be legally transport-
ed by truck in the United States while containing product.
Piping circuits allow the vessel to vent, ll, pressurize, and provide pressurized gas. Piping is type-304 stainless steel. Valves are brass. Fittings are machined from forged brass.
Instrumentation consists of a pressure gauge and a dierential pressure gauge. The pressure gauge
allows the vessel pressure to be monitored. Accurate measurement of the vessel contents is provided
by the dierential pressure gauge. The dierential pressure gauge instrument lines are constructed of
copper tube.
The MB-450 automatically maintains pressure by vaporizing cryogenic liquid in a controlled fashion. All
energy for building pressure and vaporizing liquid is provided by heat from ambient air. The vaporizer and pressure builder coils are attached to the inside surface of the outer jacket.
Page 7
BT- 434 Rev.A
7
Specication
Model EF-450-DOT EF-450HP DOT EF-450VHP DOT Part Number M4500C12-EZ H4500C12-EZ V4500C12-EZ
Dimensions
Footprint inch 31 x 31 31 x 31 31 x 31
(mm) 787 x 787 787 x 787 787 x 787
Cylinder Diameter inch 30 30 30
(mm) 762 762 762
Height inch 74 74 74
(mm) 1,880 1,880 1,880
Empty Weight Ibs 640 730 885
(Kg) 290 331 401
Capacity, Gross gallons 118 117 115
(liters) 448 443 437
MAWP psig 250 350 500
(kPa) 1,724 2,413 3,448 Design Specication DOT 4L Safety Devices Pressure Relief Valve psig 250 250 250
(kPa) 1,724 1,724 1,724 Inner Container Bursting Disc psig 356 525 750
(kPa) 2,455 3,620 5,171 Road Relief Valve psig 22 22 22
(kPa) 152 152 152 Pressure Control Devices Economizer Setting psig 200 325 420
(kPa) 1,379 2,241 2,896 Pressure Building Setting psig 175 300 400
(kPa) 1,207 2,069 2,758
Gaseous Capacity NPT
1
Nitrogen cu. ft. 9,250 8,750 7,687
(cu. M) 262 248 218
Oxygen cu. ft. 11,400 11,000 10,208
(cu. M) 323 312 289
Argon cu. ft. 11,000 10,700 9,947
(cu. M) 312 303 282
Weight of Contents
1
Nitrogen lbs 670 634 557
(kg) 304 288 253
Oxygen lbs 946 907 845
(kg) 429 411 383
Argon lbs 1,134 1,102 1,028
(kg) 514 500 466
Gas Delivery Rate c 450 450 450
(cu. M/h) 12.7 12.7 12.7
NER (Percent of capacity per day O2) 1.0%
1
Based on liquid at full trycock for ASME designs and maximum liquid weight for DOT designs.
Page 8
BT- 434 Rev.A
8
PIPING CIRCUITS
The following paragraphs describe the operation of the piping circuits of the system. The descriptions refer to the main components of each circuit and are grouped by function. Reference the piping sche­matic below and in the general arrangement drawing for the component designations. These compo­nent and circuit descriptions should be understood before attempting operation.
P&ID: MB-450 Standard Conguration
Figure 1-System Piping Schematic
VC-1
C
V-1
F
V-1
V-5
-
V-3
-
LI-1
PI-1
-
R-2
V-2
SV-1
SV-2
PBC-1
PCV-1
CN-2
CN-1
-
-
Legend
CN-1 Connection, Liquid Fill / Withdrawal LI-1 Liquid Level Gauge CN-2 Connection, Full Trycock & Vent PI-1 Pressure Gauge CN-3 Connection, Pump / Top Fill PBC-1 Pressure Building Coil CN-4 Connection, Gas Withdrawal VC-1 Vaporizer Coil V-1 Valve, Liquid Fill / Withdrawal PCV-1 Pressure Building Regulator V-2 Valve, Full Trycock / Vent SV-1 Safety Valve V-3 Valve, Gas Withdrawal SV-2 * Safety Valve, 22 psig V-4 Valve, Pressure Building R-1 Safety Disc V-5 * Valve, Isolation R-2 Outer Casing Safety Disc CV-1 Pump / Top Fill Check Valve FSV-1 Fill Stop Valve
Notes:
* Featured on DOT models only.
Page 9
BT- 434 Rev.A
9
Fill and Vent Circuits
The liquid valve (V-1) communicates with the bottom of the vessel. A stainless steel tag labeled “LIQ­UID” identies the valve and the liquid connection (CN-1). Liquid is added or removed from the vessel
through this connection and valve.
The vent / trycock valve (V-2) is attached to a vertical tube in the upper portion of the vessel. The open end of the tube is positioned at 90% liquid level based on the vessel volume. Opening the vent valve reduces pressure in the vessel during lling. It also severs as a “full trycock”, venting liquid from the vessel when the liquid level exceeds 90%. A tag labeled “VENT” is attached to this valve.
Fill and Vent Circuits
Figure 2-Fill and vent circuits highlighted in blue.
V-1
V-2
CN-2
CN-1
Page 10
BT- 434 Rev.A
10
Fill Circuit
The Fill circuit may be used for lling from the Microbulk Truck or for top lling by a cryogenic pump. The check valve (CV-1) prevents product from escaping the vessel.
A ll stop valve (FSV-1) within the vessel prevents over lling. This device functions when lled by the Microbulk Truck in automatic ll mode. The ll stop valve will not function when the vessel is lled by
a typical cryogenic pump.
Fill Circuit
Figure 3-Fill circuit highlighted in blue.
CV-1
CN-3
Page 11
BT- 434 Rev.A
11
Pressure Building Circuit
The pressure building circuit serves to build pressure after lling the vessel. The circuit is also used to ensure sucient driving pressure during high product withdrawal periods. Opening the pressure build­ing circuit valve (V-4) permits the circuit to function. A stainless steel tag labeled “P.B.” is attached to
the valve. When the pressure inside the vessel drops below the pressure builder setting, the pressure
building stage of the pressure building/economizer regulator (PCV-1) opens. This creates a path from
the liquid in the bottom of the container to the gas space in the top. This path contains an internal
pressure building coil (PBC-1) to vaporize product as it ows from the bottom to the top of the vessel.
Liquid is expanded to a vapor and pressure is increased in the vessel. The pressure building coil is at­tached to the inside surface of the vacuum jacket.
Pressure Building Circuit
Figure 4-Pressure building circuit highlighted in blue.
V-4
PCV-1
Page 12
BT- 434 Rev.A
12
Gas Withdrawal Circuit
The gas withdrawal circuit vaporizes cryogenic liquid and warms it to ambient temperature for use
in the nal application. Opening the gas withdrawal valve (V-3) allows liquid, driven by the pressure within the vessel, to ow through the vaporizer (VC-1). The vaporizer uses heat from the ambient air
to convert the liquid into a gas and warm it. The vaporizer, like the pressure building coil, is attached to the inside surface of the vacuum jacket. The vaporizer is located in the upper ¾ of the jacket, the pressure builder in the lower ¼.
Gas Withdrawal Circuit
Figure 5-Gas withdrawal circuit highlighted in blue.
V-3
CN-4
Page 13
BT- 434 Rev.A
13
Economizer Circuit
The economizer circuit reduces product loss due to normal evaporation of the liquid within the vessel.
The economizer stage of the pressure building/economizer regulator (PCV-1) opens when the pressure
within the vessel exceeds the economizer setpoint. The economizer setpoint varies depending on the
model. This allows gas from the top of the vessel to ow into the vaporizer circuit. Provided that gas
from the vaporizer is being withdrawn for use, the vessel pressure will be reduced. The primary safety
valve (SV-1) will be prevented from opening, avoiding product loss.
Economizer Circuit
Figure 6-Economizer circuit highlighted in blue.
PCV-1
Page 14
BT- 434 Rev.A
14
Safety Devices
The MB-450 features a safety valve to prevent over pressurization of the vessel. The safety valve (SV-
1) relieves pressure when it exceeds the maximum operating pressure of the vessel. The valve reseats
when pressure drops below this point. In addition, the primary safety valve is supported by a second-
ary relief device consisting of a rupture disc (R-1). The rupture disc requires replacement in the event a
safety valve malfunctions and allows vessel pressure to reach the burst pressure rating.
A relief valve (SV-2), set to open at 22 psig, is provided on the DOT models. Closing the isolation valve (V-5) prevents ow through the relief valve. This feature is useful if it is necessary to transport the MB­450 at a reduced pressure. It also allows liquid to be stored at a low pressure. This is reduces product loses when using the MB-450 to dispense cryogenic liquid.
Safety Devices
Figure 7-Safety circuit highlighted in blue.
SV-1
PI-1
R-1
Page 15
BT- 434 Rev.A
15
Instrumentation Circuits
The instrumentation consists of a pressure gauge and dierential pressure gauge. The pressure gauge (PI-1) displays the inner vessel pressure in pounds-per-square-inch and kilopascals. The liquid level gauge (LI-1) measures the dierence in pressure between the top and bottom of the vessel. Product
within the vessel creates a higher pressure at the bottom of the vessel than at the top. Readings on the liquid level gauge are in inches of water. This reading, when compared to the contents chart attached to the front of the vessel, allows accurate monitoring of the amount of product within the vessel.
Instrumentation Circuits
Figure 8-Instrumentation circuits highlighted in blue.
LI-1
PI-1
Page 16
BT- 434 Rev.A
16
OPERATION
These instructions are for operators experienced with cryogenic equipment. Before operating the system, become familiar with the safety precautions in this manual and in reference publications. Study this manual and the general arrangement drawing located in the back of this manual thor­oughly. Know the location and function of all system components.
Receiving Inspection
Handling
Customer Installed Equipment/Piping
Filling by Pressure Transfer
Freight and damage claims are the customer’s responsibility. Take time to visually inspect each ship-
ment in the presence of the carrier’s agent before accepting delivery. If any damage is observed, make an appropriate notation on the freight bill. Ask the driver to sign the notation before receiving the
equipment. Do not accept equipment with damage that may aect serviceability.
The MB-450 should be handled only by a forklift or crane. Ensure that handling equipment has ade-
quate rated capacity for the system weight listed on the general arrangement drawing in the appendix.
The MB-450 is a rugged product intended for years of industrial use. However, take care when mov­ing the unit. Abuse (dropping or careless handling by forklift) may aect the integrity of the insula-
tion system or damage piping. Always transport, operate, and store the unit in the vertical position. Never place the unit on its side.
Important: When lifting by crane, use the lift-eyes provided on the top of the jacket. Never lift the unit over­head.
When installing the MB-450 for remote lling, be sure to follow accepted design practices for cryogenic
equipment. All equipment must be cleaned for oxygen service. Be sure to include pressure relief valves in all piping where liquid product could be trapped between closed valves, regulators, etc.
Designing safe and eective cryogenic systems requires extensive knowledge and experience. Persons
lacking the necessary skills are urged to seek competent advice before attempting to design cryogenic systems.
Design and consultation services are available from the factory at the location shown at the front of the
manual.
Filling by pressure transfer is accomplished by lowering the pressure in the MB-450 below that of the
source vessel. Typically the source vessel is a cryogenic bulk tank or truck mounted vessel. The pres-
sure is reduced in the MB-450 by venting gas through the vent valve (V-2). Liquid is pushed by pressure from the bulk tank and into the MB-450.
CAUTION: Follow the safety precautions at the beginning of this manual. Accidental contact with liquid or
cold gas can occur during lling.
A cryogenic transfer hose equipped with a relief valve and dump valve should be used to connect the
MB-450 to the liquid source. Follow the instructions below to ll by pressure transfer:
Page 17
BT- 434 Rev.A
17
OPERATION
Withdrawing Gas
Filling by Pump Transfer
Filling for Road Transport
1. Visually inspect the MB-450, transfer hose, and bulk tank piping. Do not attempt to fill the unit if
any components are broken or missing.
2. Connect a transfer hose from the bulk tank to the liquid connection (CN-1).
3. Open the liquid valve (V-1) and vent valve (V-2) to begin the fill.
4. When liquid issues from the vent valve, the vessel is full. A 10% gas head space will remain above
the liquid. Close the liquid valve (V-1).
5. Once liquid stops issuing from the vent valve (V-2), close the vent valve.
6. Close the liquid source supply valve and open the transfer hose dump valve.
7. Disconnect the transfer hose from the liquid connection (CN-1).
When a pump is used to ll the container, the pump / top ll connection (CN-3) should be used. Closely monitor the vessel pressure during the ll. If the vessel pressure approaches the relief valve setting or the pump pressure rating, shut down the pump. Open the vent valve (V-2) to reduce pressure as
needed.
When lling using the Taylor-Wharton Express truck in automatic mode, the ll is stopped at a level
providing an adequate gas head space.
When using a traditional pumping system, the vent valve (V-2) should remain open during the ll. Moni­tor the product exiting the vent valve closely. When liquid issues from the vent valve (V-2) immediately
stop the pump. Once liquid stops issuing from the vent valve, close the vent valve.
The DOT-4L design vessels may be transported over the road while containing product. When filling
these vessels for transport, it is recommended that they be placed on a scale during the fill. The
weight of the contents should not exceed the maximum weight allowed by the DOT (Department of Transportation).The weight of contents can be found on the Specifications page.
The vessel tare weight, labeled TW, can be found on the nameplate located on the upper head of the vessel jacket. Add the weight of contents for the appropriate vessel design and gas service to the tare weight of the vessel. The weight of the full vessel must not exceed the sum of the tare weight and weight of contents.
To withdraw gas from the MB-450 connect a suitable line regulator to the gas withdrawal connection (CN-4). Connect the outlet of the regulator to the application. Follow these steps:
1. Close the isolation valve (V-5) for the 22 psig relief valve (SV-2) if so equipped.
2. Open the pressure building valve (V-4). Monitor the pressure gauge (PI-1). When the pressure
exceeds the desired delivery pressure, continue.
3. Open the gas withdrawal valve (V-3).
4. Adjust the line regulator to desired delivery pressure.
Page 18
BT- 434 Rev.A
18
OPERATION
Withdrawing Liquid
Changing Gas Service
Attach a transfer hose from the receiver vessel to the MB-450 liquid connection (CN-1) and open the adjacent liquid valve (V-1). The pressure in the container will drive liquid product out through the valve
as long as the container pressure exceeds that of the receiver.
The MB - 450 may be used for argon, oxygen, or nitrogen service. Follow these steps to properly change gas service:
1. Safely empty all liquid from the container.
2. Open the pressure building valve (V-4) and the vent valve (V-2) to vaporize any residual liquid
that may remain in the bottom of the vessel. It may require an hour or longer to vaporize all the residual liquid.
3. To ensure purity, it is recommended that the MB-450 be evacuated with a suitable vacuum pump.
The ultimate vacuum reading should be at least 20 inches of mercury.
4. Replace the fittings for the vent, liquid, and use connections with the appropriate fittings shown in the chart below. Use Teflon tape or another suitable thread sealant when threading the fittings into the connections.
5. Remove any decals identifying the previous gas service. Attach new gas service identification decals.
Gas Service Valve Description TW Part Number
Oxygen
Use Fitting CGA 540 x 3/8” NPT 7114-0163
Liquid & Vent Fitting CGA 440 x 3/8” NPT 6514-8992 (2 required)
Top Fill CGA 440 x 1/2” NPT 6514-8990 NA Oxygen Service Decal GL55-9C52
Nitrogen
Use Fitting
CGA 580 x 3/8” NPT 7114-0164
Liquid & Vent Fitting
CGA 295 x 3/8” NPT 7355-4712 (2 required)
Top Fill
CGA 295 x 1/2” NPT 7355-4698
NA
Nitrogen Service Decal GL55-9C51
Argon
Use Fitting
CGA 580 x 3/8” NPT 7114-0164
Liquid & Vent Fitting
CGA 295 x 3/8” NPT 7355-4712 (2 required)
Top Fill
CGA 295 x 1/2” NPT 7355-4698
NA
Argon Service Decal GL55-9C53
Page 19
BT- 434 Rev.A
19
MAINTENANCE
Routine inspections of the system are recommended. The need for maintenance usually becomes appar­ent from inspection and indications of improper operation. Typical trouble indications include leakage from valves or piping connections and excessive venting through relief valves. Keep a permanent log of all inspections and repairs performed. Such a log can be valuable in evaluating performance and schedul­ing maintenance.
Date Nature of Work (Describe in Full) Remarks Service men’s Signature
Always observe the safety precautions at the front of this manual and follow the instructions given in this section. Before working on the system, properly empty the vessel of liquid and relieve pressure on the
vessel and piping. Do not allow unqualied persons to attempt repairs on this equipment. Refer to the
Trouble - Remedy Guide in this manual for assistance in troubleshooting.
Figure 9: Inspection and Repair Log (Sample Form)
Leak Test
Globe Valves
Regulator
After making repairs requiring disassembly or replacement of components, leak test all valves or piping
joints that were taken apart and reconnected. Apply leak detector uid to the test surface. Large leaks instantly form large bubble clusters, while ne leaks produce white foam that builds up more slowly. All
leaks must be repaired and retested before the system is returned to service.
All of the globe valves (V-1, V-2, V-3, & V-4) are an integral part of the system and are not easily removable.
However, the valves may be rebuilt without removal from the system. All of the globe valves use the same
rebuild kit. The Taylor-Wharton part number for the rebuild kit is 1750-9C35. All valve components, except
the body, are provided in the kit.
A dual stage, spring-loaded regulator (PCV-1) is employed for the pressure building/economizer circuit.
The regulator may be adjusted without removal from the system. The following procedure describes the
process:
Page 20
BT- 434 Rev.A
20
MAINTENANCE
1. Fill the container with liquid product.
2. Open the pressure building valve and allow the container pressure to stabilize for about an hour. Note the pressure.
3. Loosen the adjustment screw on the top of the regulator to raise or lower the pressure to the desired point. When decreasing the setting, the pressure building valve must be closed and the container vented to a lower pressure. Repeat step two and observe the change.
For more accurate adjustment it is recommended that the regulator be removed from the system. A reg-
ulator bench adjustment xture should be used. The gure below shows a typical setup.
Port Stamped “P.B. IN”
Regulator to be
Adjusted Top View
On/O Valve
Dum
p
Valve
Regulator to be Adjusted
Pressure Gauge
Regulator
High Pressure
Cylinder
Figure 10: Regulator bench adjustment xture.
1. Leak test joints between the high pressure cylinder regulator and the dump valve. Joints must be leak free before proceeding.
2. Close the on/o valve and the dump valve.
3. Open the high pressure cylinder valve.
4. Set the high pressure regulator above the desired set point for the pressure builder.
5. Slowly open the on/o valve and observe the downstream pressure gauge.
6. When the regulator under adjustment closes, the pressure-building. Set point is indicated on the downstream pressure gauge.
7. Close the on/o valve and open the dump valve.
8. To reset the regulator, loosen the lock nut on the adjusting screw. Raise the set point by turning the
adjusting screw clockwise; lower the set point by turning the screw counterclockwise. After adjust­ment, repeat steps 5 and 6 to check the setting before reinstalling the regulator on the liquid contain-
er.
Page 21
BT- 434 Rev.A
21
Instruments
User adjustment of the pressure gauge or liquid level gauge is not possible. If the gauges are malfunction­ing, they must be replaced. Empty the container of liquid and completely depressurize it before replacing either gauge.
Note that the liquid level gauge may read erratically while the safety valve is venting. This is normal and will stop when the safety valve reseats.
Checking Vacuum
MAINTENANCE
Cryogenic containers are two containers, one within the other. The space between the containers acts as a highly ecient thermal barrier including high technology insulation, a vacuum, and a vacuum mainte­nance system. Each serves a very important part in the useful life of the container. The high technology
insulation is very eective in preventing radiated heat from entering the inner container. Unfortunately,
the perfect vacuum cannot be achieved since trace gas molecules begin to enter the vacuum space from the moment of manufacture. The vacuum maintenance system consists of materials that gather trace gas molecules from the vacuum space. The maintenance system can perform its function for years, how­ever it has a limited capacity. When the vacuum maintenance system becomes saturated it can no longer maintain the vacuum integrity of the container. The change will be very gradual and may go unnoticed
for several years. When the vacuum in the insulation space is no longer eective, the following symptoms may appear:
1. With liquid in the container, the outer casing will be much colder than comparative containers.
2. Frost, indicating the liquid level, may be visible on the outer casing of the container.
3. Condensation may form on the container. Note that some icing or condensation is normal around the piping connections of the vessel. Condensation may also occur on the vessel outer surface as a result of high humidity.
4. The relief valve will open continuously until the container is empty.
If a loss of vacuum integrity is suspected, the container’s normal evaporation rate (NER) should be
checked. The test procedure explained below measures the actual product lost over time.
1. Fill the container with approximately 200 pounds of liquid nitrogen.
2. Close the liquid valve and the pressure building valve. Leave the vent valve open for the duration of the test.
3. Allow the container to stabilize for 24 hours after lling. Weigh the container. Record the weight, date, and time.
4. Move the container as little as possible during the test. After 48 hours, weigh the container a second time. Record the weight, date, and time.
Page 22
BT- 434 Rev.A
22
The following formula will provide the actual normal evaporation rate in pounds per day. An actual NER
that exceeds 20 pounds per day indicates a vacuum problem.
Daily N.E.R. =
Weight (Step 4) – Weight (Step 5)
Time between Step 3 and 4 in hours
X 24
If it has been determined that the vessel has a vacuum problem it will be necessary to repair and re-evacu­ate the vessel. A skilled service technician should perform vessel repair. Contact Taylor-Wharton custom-
er service at 1-800-898-2657 for assistance in locating the closest service center.
MAINTENANCE
Page 23
BT- 434 Rev.A
23
Trouble-Remedy Guide
MAINTENANCE
Trouble Possible Cause Remedy
1. Low operating pressure.
a. Safety valve leaking or frozen open.
a. Thaw out valve or replace if
necessary. b. Safety disc ruptured. b. Replace disc. c. Piping leaks to atmosphere. c. Leak test and repair piping. d. Pressure building / economizer
regulator malfunction.
d. Adjust regulators. Replace if
necessary. e. Excessive product withdrawal. e. Check for leaks downstream.
Reduce product use. f. Pressure building valve closed. f. Open pressure building valve. g. Malfunctioning pressure
gauge.
g. Replace pressure gauge.
h. Excessive frost on pressure-
building coils.
h. Thaw pressure building coils.
2. Excessive system pressure.
a. Extensive shutdown time. a. No remedy. b. Low withdrawal rate. b. No remedy. c. Malfunction of pressure build-
ing circuit.
c. Adjust pressure building regu-
lators. Replace if necessary. d. Malfunction of pressure gauge. d. Replace gauge. e. Bad vessel vacuum. e. Perform NER test. Have vessel
repaired and re-evacuated if
necessary.
3. Leaking relief valve.
a. Dirt or ice in valve. a. Thaw out valve. Replace if nec-
essary. b. Damaged valve seat. b. Replace valve.
4. Ruptured pressure vessel rup­ture disc.
a. Excessive vessel pressure. a. Refer to Step 2, this section.
Replace rupture disc. b. Defective rupture disc. b. Replace rupture disc. c. Atmosphere corrosion and/or
disc fatigue.
c. Replace rupture disc.
d. Interior disc corrosion. d. Blow out safety device line. Re-
place rupture disc. e. Relief device failed. e. Replace relief device and rup-
ture disc.
Page 24
BT- 434 Rev.A
24
Replacement Parts
Order replacement parts from Taylor-Wharton Customer Service at 1-800-898-2657. Refer to the piping
circuits section to identify the components.
MAINTENANCE
ITEM PART NUMBER DESCRIPTION
V-1 VP50-9C44 Globe Valve, Liquid, 3/8” Pipe Stub
V-2 VP50-9C41 Globe Valve, Vent, 3/8” Pipe Stub V-3 VP50-9C43 Globe Valve, Use, 3/8” Pipe Stub V-4 VP50-9C42 Globe Valve, PB, 3/8” Pipe Stub
V-5 * 6916-7116 Ball Valve, ¼” NPT
CV-1 6913-9365 Check Valve, Swing, ½” FNPT
LI-1 57143698 Dierential Pressure Gauge, 0-80 inches H2O
PI-1, 250 psi Vessel 7702-6196 Pressure Gauge, 400 psig
PI-1, 350 & 500 psi Vessel 1706-9C14 Pressure Gauge, 600 psig
PCV-1, 250 psi Vessel 85368135 Regulator, P.B. / Economizer, 175 psig PCV-1, 350 psi Vessel 6999-9018 Regulator, P.B. / Economizer, 300 psig PCV-1, 500 psi Vessel 8816-1060 Regulator, P.B. / Economizer, 400 psig
SV-1, 250 psi Vessel 85440299 Relief Valve, ½” MNPT, 250 psig SV-1, 350 psi Vessel 85450309 Relief Valve, ½” MNPT, 350 psig
SV-1, 500 psi Vessel 85450312 Relief Valve, ½” MNPT, 500 psig
SV-2 * 6913-9069 Relief Valve, ¼” MNPT, 22 psig R-1, 250 psi Vessel M6009C33 Safety Disc, ½” MNPT, 356 psig R-1, 350 psi Vessel H6009C33 Safety Disc, ½” MNPT, 525 psig R-1, 500 psi Vessel V6009C33 Safety Disc, ½” MNPT, 750 psig
R-2 BC04-6C66 Casing Safety Disc
Notes: * Featured on DOT vessels only.
Page 25
BT- 434 Rev.A
25
APPENDIXES
Appendix 1 – MB - 450 General Arrangement
Page 26
BT- 434 Rev.A
26
APPENDIXES
Page 27
BT- 434 Rev.A
27
P/N : BT-434 Rev.A
Publication - #####
Taylor-Wharton Cryogenics LLC
4075 Hamilton Boulevard
Theodore, AL 36582
Phone : +251 - 443 - 8680
Phone : +800 - 898 - 2657
www.taylorwharton.com
Loading...