Taylor RC25, RD30 User Manual

Models RD30 & RC25
Remote Slim-Line
Slush Freezer
Original Operating Instructions
051060--M
11/99 (Original Publication)
(Updated 6/11/12)
Complete this page for quick reference when service is required:
Address:
Phone:
Service:
Parts:
Date of Installation:
Information found on the data label:
Model Number:
Serial Number:
Electrical Specs: Voltage Cycle
Phase
Maximum F use Size: A
Minimum Wire Ampacity: A
E November, 1999 Taylor
All rights reserved. 051060--M
The word Taylor and the Crown design are registered trademarks in the United States of America and certain other countries.
Taylor Company 750 N. Blackhawk Blvd. Rockton, IL 61072
Table of Contents
Section 1 To th e Installer 1............................................
Installer Safety 1........................................................
Site Preparation 1.......................................................
Electrical Connections 2.................................................
Beater Rotation 2.......................................................
Refrigerant 3...........................................................
Section 2 To the Operator 7...........................................
Compressor Warranty Disclaimer 7.......................................
Section 3 Safety 8....................................................
Section 4 Operator Parts Identification 10...............................
Section 5 Important: To the Operator 12.................................
Control Switch 12........................................................
Fill Switch 12............................................................
Mix Out Light 12.........................................................
Viscosity Control 12......................................................
Section 6 Operating Procedures 13.....................................
Assembly 13............................................................
Sanitizing 17............................................................
Priming 20..............................................................
Closing Procedure 20....................................................
Draining Product From The Freezing Cylinder 20............................
Rinsing 21..............................................................
Table of Contents Models RD30/RC25
Table of Contents -- Page 2
Cleaning 21.............................................................
Disassembly 21..........................................................
Brush Cleaning 22.......................................................
Section 7 Important: Operator Checklist 23..............................
During Cleaning and Sanitizing 23.........................................
Troubleshooting Bacterial Count 23........................................
Regular Maintenance Checks 23...........................................
Winter Storage 23........................................................
Section 8 Troubleshooting Guide 24....................................
Section 9 Parts Replacement Schedule 27...............................
Section 10 Parts List 28.................................................
Wiring Diagrams 37......................................................
Note: Continuing research results in steady improvements; therefore, information in this manual is subject to change without notice.
Note: Only instructions originating from the factory or its authorized translation representative(s) are considered to be the original set of instructions.
E November, 1999 Taylor (Original Publication)
(Updated June, 2012) All rights reserved. 051060--M
The word Taylor and the Crown design are registered trademarks in the United States of America and certain other countries.
Models RD30/RC25 Table of Contents
Taylor Company 750 N. Blackhawk Blvd. Rockton, IL 61072
Section 1 To the Installer
The following are general installation instructions. For complete installation details, please see the check out card.
cause severe injuries.
Installer Safety
This unit has many sharp edges that can
In all areas of the world, equipment should be installed in accordance with existing local codes. Please contact your local authorities if you have any questions.
Care should be taken to ensure that all basic safety practices are followed during the installation and servicing activities related to the installation and service of Taylor equipment.
S Only authorized Taylor service personnel
should perform installation and repairs on the equipment.
S Authorized service personnel should consult
OSHA Standard 29CFRI910.147 or the applicable code of the local area for the industry standards on lockout/tagout procedures before beginning any installation or repairs.
S Authorized service personnel must ensure
that the proper PPE is available and worn when required during installation and service.
S Authorized service personnel must remove
all metal jewelry, rings, and watches before working on electrical equipment.
The main power supply(s) to the freezer must be disconnected prior to performing any repairs. Failure to follow this instruction may result in personal injury or death from electrical shock or hazardous moving parts as well as poor performance or damage to the equipment.
Note:Allrepairsmustbeperformedbyan authorized Taylor Service Technician.
Site Preparation
Review the area the unit is to be installed in before uncrating the unit, making sure that all possible hazards the user or equipment may come into have been addressed.
For Indoor Use Only: This unit is designed to operate indoors, under normal ambient temperatures of 70_-75_F(21_-24_C). The freezer has successfully performed in high ambient temperatures of 104_(40_C) at reduced capacities.
This unit must NOT be installed in an area where a water jet or hose can be used. NEVER use a water jet or hose to rinse or clean the unit. Failure to follow this instruction may result in electrocution.
This unit must be installed on a level surface to avoid the hazard of tipping. Extreme care should be taken in moving this equipment for any reason. Two or more persons are required to safely move this unit. Failure to comply may result in personal injury or equipment damage.
Uncrate the unit and inspect it for damage. Report any damage to your Taylor Distributor.
This piece of equipment is made in the USA and has USA sizes of hardware. All metric conversions are approximate and vary in size.
081208
Models RD30/RC25 To the Installer
1
Electrical Connections
In the United States, this equipment is intended to be installed in accordance with the National Electrical Code (NEC), ANSI/NFPA 70-1987. The purpose of the NEC code is the practical safeguarding of persons and property from hazards arising from the use of electricity. This code contains provisions considered necessary for safety. In all other areas of the world, equipment should be installed in accordance with the existing local codes. Please contact your local authorities.
FOLLOW YOUR LOCAL ELECTRICAL CODES!
Each unit requires one power supply for each data label on the unit. Check the data label(s) on the freezer for branch circuit overcurrent protection or fuse, circuit ampacity, and other electrical specifications. Refer to the wiring diagram provided inside of the electrical box for proper power connections.
S Appliances that are permanently connected
to fixed wiring and for which leakage currents may exceed 10 mA, particularly when disconnected or not used for long periods, or during initial installation, shall have protective devices such as a GFI, to protect against the leakage of current, installed by the authorized personnel to the local codes.
S Supply cords used with this unit shall be
oil-resistant, sheathed flexible cable not lighter than ordinary polychloroprene or other equivalent synthetic elastomer-sheathed cord (Code designation 60245 IEC 57) installed with the proper cord anchorage to relieve conductors from strain, including twisting, at the terminals and protect the insulation of the conductors from abrasion.
Beater Rotation
CAUTION: THIS EQUIPMENT MUST BE PROPERLY GROUNDED! FAILURE TO DO SO CAN RESULT IN SEVERE PERSONAL INJURY FROM ELECTRICAL SHOCK!
This unit is provided with an equipotential grounding lug that is to be properly attached to the rear of the frame by the authorized installer. The installation location is marked by the equipotential bonding symbol (5021 of IEC 60417-1) on both the removable panel and the equipment’s frame.
S Stationary appliances which are not
equipped with a power cord and a plug or another device to disconnect the appliance from the power source must have an all-pole disconnecting device with a contact gap of at least 3 mm installed in the external installation.
Beater rotation must be clockwise as viewed
looking into the freezing cylinder.
Note: The following procedures must be performed by an authorized Taylor service technician.
To correct the rotation on a three--phase unit, interchange any two incoming power supply lines at freezer main terminal block only.
To correct rotation on a single--phase unit, change the leads inside the beater motor. (Follow the diagram printedonthemotor.)
Electrical connections are made directly to the splice box. The splice box is located behind the right side panel.
120611
2
Models RD30/RC25To the Installer
Refrigerant
In consideration of our environment, Taylor proudly uses only earth friendly HFC refrigerants. The HFC refrigerant used in this unit is R404A. This refrigerant is generally considered non-toxic and non-flammable, with an Ozone Depleting Potential (ODP) of zero (0).
However, any gas under pressure is potentially hazardous and must be handled with caution.
Refrigeration Charging and Line Construction
The dispensing unit is shipped with a refrigerant holding charge that is sufficient enough to prevent moisture contamination (8 oz./227 g. R404A). This holding charge will become part of the total system charge.
The condensing unit is shipped with the total amount of refrigerant required for a typical installation of 75 ft. or less with a single dispenser. For other installation configurations, use the following chart for line sizing and for adding required refrigerant.
NEVER fill any refrigerant cylinder completely with liquid. Filling the cylinder to approximately 80% will allow for normal expansion.
Use only R134a refrigerant that conforms to the AHI standard 700 specification. The use of any other refrigerant may expose users and operators to unexpected safety hazards.
Refrigerant liquid sprayed onto the skin may cause serious damage to tissue. Keep eyes and skin protected. If refrigerant burns should occur, flush immediately with cold water. If burns are severe, apply ice packs and contact a physician immediately.
Taylor reminds technicians to be cautious of government laws regarding refrigerant recovery, recycling, and reclaiming systems. If you have any questions regarding these laws, please contact the factory Service Department.
Recommended System Refrigerant Charge
Domestic
Suction Line
Length
Less than 75 ft. Single 10 lb.
More than 75 ft. Single 12 lb. (add 2 lb.)
Less than 75 ft. Dual 13 lb. (add 3 lb.)
More than 75 ft. Dual 15 lb. (add 5 lb.)
International
Suction Line
Length
Less than 22.8 m Single 4.5 kg
More than 22.8 m Single 5.4 kg (add 0.91 kg)
Less than 22.8 m Dual 5.9 kg (add 1.4 kg)
More than 22.8 m Dual 6.8 kg (add 2.3 kg)
Note: Maximum line length is 150 ft. (45.7 m). To meet individual installation requirements, lines must be purchased and constructed locally.
Dispenser Required Charge
Dispenser Required Charge
Line Size
WARNING: R404A refrigerant used in conjunction with polyolester oils is extremely moisture absorbent. When opening a refrigeration system, the maximum time the system is open must not exceed 15 minutes. Cap all open tubing to prevent humid air or water from being absorbed by the oil.
Models RD30/RC25 To the Installer
Liquid Line -- Single or dual dispensers require 3/8”
refrigerant grade copper tubing (hard or soft).
Note: Insulating the liquid line is recommended if it is exposed to high ambient conditions. This will reduce heat accumulation and prevent the formation of flash gas in the liquid line.
120611
3
Single Dispensing Installations
f
Suction Line -- Less than 75 ft. (22.8 m) total line length requires 5/8” refrigerant grade copper tubing (hard or soft). Maximum 5/8” tubing length is 75 ft. (22.8 m).
Dual Dispensing Installations (One Condenser, Two Dispensers)
Individual Suction Line -- Requires 5/8” refrigeration
grade copper tubing (hard or soft) from each dispenser to the common suction tube.
Note: Suction lines must be insulated.
Suction Line -- More than 75 ft. (22.8 m) total line
length requires 3/4” refrigerant grade copper tubing (hard or soft). Maximum tubing length is 150 ft. (45.7 m).
Note: Use 5/8” tubing to attach the quick disconnects to the other fittings.
Common Suction Line -- Requires 3/4” refrigeration
grade copper tubing.
Note: Lines must be insulated and requires a 5/8” x 3/4” reducer fitting at the quick disconnect connections. See the diagram below.
Note: 5/8” individual line lengths are not to exceed 75 ft. (22.8 m) maximum length each. Total line length is not to exceed 150
t. (45.7 m). 5/8” line + 5/8” line + 3/4” line = 150 ft. or less.
4
Models RD30/RC25To the Installer
Installation
Step 1
Install refrigeration lines from the dispenser to the condensing unit. Do not create oil traps.
Note: For proper oil return, installation of horizontal suction lines are to be sloped downward in the direction of the condensing unit. The slope must be a minimum 1/4” (.64 cm.) angle per 10 ft. (3.048 m.) of line length.
Step 5
Evacuate the field constructed refrigerant lines using the access fittings brazed on the condensing end of the refrigeration lines.
Step 6
When the evacuation process is complete, relieve the vacuum with 4 oz. (113 g.) of HP62 refrigerant per line, for a total of 8 oz. (227 g.) This procedure will prevent moisture contamination during dispenser and condensing unit connection and complete the total charge.
Refrigeration Connections
Connect the refrigerant line quick connect/disconnect couplings to the mating quick connect/disconnect couplings on the dispensing and condensing unit.
Step 1
Remove the shipping caps from the quick connect/disconnect coupling on the dispensing unit.
Step 2
Thoroughly clean and lubricate the mating surfaces of the quick connect/disconnects.
Note: Use polyolester oil to lubricate the surfaces.
Figure 1
Normally, any straight run of tubing must be supported near each end of the run. Long runs require additional supports. As a guide, 3/8” to 3/4” copper should be supported every 5 ft. When changing directions, no corner should be left unsupported. Supports should be placed a maximum of 2 ft. in each direction from the corner. If soft copper tube is used, make sure it is not kinked or flattened. If hard drawn copper tubing is used, use only long radius elbows.
Step 2
Braze the supplied quick connect/disconnect couplings on the dispenser end of the refrigeration lines. Couplings are supplied with the dispenser.
Step 3
Braze the quick connect/disconnect couplings and access tees on the condensing unit end of the refrigeration lines. Couplings and access tees are supplied with the unit.
Note: Wrap a wet cloth aroundthe brasscoupling bodies to prevent heat damage to the seal.
Step 3
Manually thread the coupling halves together to insure proper mating of the threads.
Step 4
Using proper sized wrenches, tighten the coupling halves until the round, flat surfaces of inner coupling bodies completely depress one another.
Step 5
Once the flat surfaces are completely depressed, tighten the couplings an additional 1/4 turn. This step is necessary to insure that the knife edge of the seal seats into the brass seat of the coupling halves, forming a leak--proof joint (metal seal).
Step 4
Test the field constructed lines for leaks.
Models RD30/RC25 To the Installer
5
Figure 2
Step 6
Check all connections for leaks.
Step 7
Insulate all exposed suction line tubing and fittings.
Step 8
Set the pump down switch located in the condensing unit. For indoor condensing unit application:
Set cut in at 30 PSIG (207 kPa). Set cut out at 5 PSIG (34 kPa).
For outdoor condensing unit application:
Set cut in at 20 PSIG (138 kPa). Set cut out at 0 PSIG (0 kPa).
Pump down pressure readings are to be taken at the refrigeration line access fittings at the condensing unit.
Step 6
Allow the dispenser to run until the condensing unit cycles off. Verify the proper pump down pressure switch setting. See Step 8 of “Refrigeration Connections” (page 6).
Note: Pump down pressure readings are to be taken at the refrigeration line access fittings near the condensing unit.
Step 7
If necessary, adjust viscosity to produce satisfactory product. Adjustments are made by turning the viscosity adjustment screw (located on the front panel) clockwise for a thicker product or counterclockwise for a thinner product.
Set Up Procedures
Standard Fill Module
Step 1
Connect the product supply line to the 1/4” barbed fitting on the fill module. Adjust the fill system pressure to deliver product to the hopper at 1.5 to 2.5 oz. (42.5 to 70.9 g) per second. (Approximately 15 to 20 PSIG [103--138 kPa] for most products.)
Step 2
Lubricate, assemble, sanitize and prime the dispenser as outlined in the Assembly section of this manual.
Step 3
Place the fill switch in the “ON” position. Allow the product to fill the cylinder and the hopper until the mix level float is satisfied.
Step 4
Place the power switch in the “AUTO” position.
Step 5
To observe the suction pressure, attach refrigeration gauges to the suction access fitting in the dispenser. Pressures should read approximately 32 psi. (221 kPa) for non--alcoholic application and 28 psi. (193 kPa) for alcoholic application.
Note: Connection to the condensing unit suction access can give an improper reading.
Units Equipped With Post Mix Valve
Step 1
Connect syrup and water lines.
Note: Adjust the syrup supply pressure to maintain 60 PSIG. Water pressure minimum 40 PSIG, maximum 100 PSIG, may require regulated water supply.
Step 2
Turn the “FILL” switch in the front of the RD30 to the “ON” position.
Step 3
Press and hold the area on the front of the post mix valve marked “PUSH” to prime the fill system. Priming is required until the B.I.B. switch and the float switch are both satisfied. Priming is complete when product will flow without pressing the “PUSH” button.
Step 4
To adjust either the syrup or water flow rate, turn the flow adjustment screw clockwise to increase flow, or counterclockwise to decrease flow. Adjust the screws until the desired brix is obtained. The flow rate should be 1.5 to 2.5 oz. (43 fl. ml.) per second.
Note: Both syrup and water flow adjustment screws are located inside the post mix valve cover. Viewed from the front, the syrup adjustment screw is on the right and water adjustment is on the left.
6
Models RD30/RC25To the Installer
Section 2 To the Operator
The freezer you have purchased has been carefully engineered and manufactured to give you dependable operation. The T aylor Model RD30/RC25, when properly operated and cared for, will produce a consistent quality product. Like all mechanical products, this machine will require cleaning and maintenance. A minimum amount of care and attention is necessary if the operating procedures outlined in this manual are followed closely.
This Operator’s Manual should be read before operating or performing any maintenance on your equipment.
Your Model RD30/RC25 will NOT eventually compensate and correct for any errors during the set--up or filling operations. Thus, the initial assembly and priming procedures are of extreme importance. It is strongly recommended that all personnel responsible for the equipment’s operation thoroughly read this manual.
If you require technical assistance, please contact your local authorized Taylor Distributor.
Note: Warranty is valid only if the parts are authorized Taylor parts, purchased from an authorized Taylor Distributor, and the required service work is provided by an authorized Taylor service technician. Taylor reserves the right to deny warranty claims on equipment or parts if non--approved parts or refrigerant were installed in the machine, system modifications were performed beyond factory recommendations, or it is determined that the failure was caused by neglect or abuse.
Note: Constant research results in steady improvements; therefore, information in this manual is subject to change without notice.
If the crossed out wheeled bin symbol is affixed to this product, it signifies that this product is compliant with the EU Directive as well as other similar legislation in effect after August 13, 2005. Therefore, it must be collected separately after its use is completed, and cannot be disposed as unsorted municipal waste.
The user is responsible for returning the product to the appropriate collection facility, as specified by your local code.
For additional information regarding applicable local laws, please contact the municipal facility and/or local distributor.
Compressor Warranty Disclaimer
The refrigeration compressor(s) on this machine are warranted for the term indicated on the warranty card accompanying this machine. However, due to the Montreal Protocol and the U.S. Clean Air Act Amendments of 1990, many new refrigerants are being tested and developed, thus seeking their way into the service industry. Some of these new refrigerants are being advertised as drop--in replacements for numerous applications. It should be noted that, in the event of ordinary service to this machine’s refrigeration system, only the refrigerant specified on the affixed data label should be used. The unauthorized use of alternate refrigerants will void your compressor warranty . It will be the owner’s responsibility to make this fact known to any technician he employs.
It should also be noted that Taylor does not warrant the refrigerant used in its equipment. For example, if the refrigerant is lost during the course of ordinary service to this machine, Taylor has no obligation to either supply or provide its replacement either at billable or unbillable terms. Taylor does have the obligation to recommend a suitable replacement if the original refrigerant is banned, obsoleted, or no longer available during the five year warranty of the compressor.
Taylor will continue to monitor the industry and test new alternates as they are being developed. Should a new alternate prove, through our testing, that it would be accepted as a drop--in replacement, then the above disclaimer would become null and void. To find out the current status of an alternate refrigerant as it relates to your compressor warranty, call the local Taylor Distributor or the T aylor Factory. Be prepared to provide the Model/Serial Number of the unit in question.
081029
Models RD30/RC25 To the Operator
7
Section 3 Safety
We at Taylor Company are concerned about the safety of the operator when he or she comes in contact with the freezer and its parts. Taylor has gone to extreme efforts to design and manufacture built--in safety features to protect both you and the service technician. As an example, warning labels have been attached to the freezer to further point out safety precautions to the operator.
IMPORTANT -- Failure to adhere to the following safety precautions may result in severe personal injury or death. Failure to comply with these warnings may damage the machine and its components. Component damage will result in part replacement expense and service repair expense.
DO NOT operate the freezer without reading
this Operator Manual. Failure to follow this instruction may result in equipment damage, poor freezer performance, health hazards, or personal injury.
Per IEC 60335--1 and its part 2 standards, “This appliance is to be used only by trained personnel. It is not intended for use by children or people with reduced physical, sensory, or mental capabilities, or lack of experience and knowledge, unless given supervision or instruction concerning the use of the appliance by a person responsible for their safety.”
This unit is provided with an equipotential grounding lug that is to be properly attached to the rear of the frame by the authorized installer. The installation location is marked by the equipotential bonding symbol (5021 of IEC 60417-1) on both the removable panel and the equipment’s frame.
S DO NOT operate the freezer unless it is
properly grounded.
S DO NOT operate the freezer with larger
fuses than specified on the freezer data label.
S All repairs must be performed by an
authorized Taylor service technician. The main power supplies to the machine must be disconnected prior to performing any repairs.
S Cord Connected Units: Only Taylor
authorized service technicians may install a plug on this unit.
S Stationary appliances which are not
equipped with a power cord and a plug or another device to disconnect the appliance from the power source must have an all-pole disconnecting device with a contact gap of at least 3 mm installed in the external installation.
S Appliances that are permanently connected
to fixed wiring and for which leakage currents may exceed 10 mA, particularly when disconnected or not used for long periods, or during initial installation, shall have protective devices such as a GFI, to protect against the leakage of current, installed by the authorized personnel to the local codes.
S Supply cords used with this unit shall be
oil-resistant, sheathed flexible cable not lighter than ordinary polychloroprene or other equivalent synthetic elastomer-sheathed cord (Code designation 60245 IEC 57) installed with the proper cord anchorage to relieve conductors from strain, including twisting, at the terminals and protect the insulation of the conductors from abrasion.
DO NOT use a water jet to clean or rinse the freezer. Failure to follow these instructions may result in serious electrical shock.
110824
Failure to follow these instructions may result in electrocution. Contact your local authorized Taylor Distributor for service.
8
Models RD30/RC25Safety
S DO NOT allow untrained personnel to
operate this machine.
S DO NOT operate the freezer unless all
service panels and access doors are
restrained with screws.
S DO NOT remove any internal operating
parts (examples: freezer door, beater,
scraper blades, etc.) unless all control
switches are in the OFF position.
Failure to follow these instructions may result in severe personal injury to fingers or hands from hazardous moving parts.
This unit has many sharp edges that can
cause severe injuries.
S DO NOT put objects or fingers in the door
spout. This may contaminate the product
and cause severe personal injury from blade
contact.
S USE EXTREME CAUTION when removing
the beater asssembly. The scraper blades
are very sharp.
This freezer must be placed on a level surface. Failure to comply may result in personal injury.
Cleaning and sanitizing schedules are governed by your state or local regulatory agencies and must be followed accordingly. Please refer to the cleaning section of this manual for the proper procedure to clean this unit.
For Indoor Use Only: This unit is designed to operate indoors, under normal ambient temperatures of 70_ - 75_F(21_ -24_C). The freezer has successfully performed in high ambient temperatures of 104_(40_C) at reduced capacities.
NOISE LEVEL: Airborne noise emission does not exceed 78 dB(A) when measured at a distance of 1.0 meter from the surface of the machine and at a height of 1.6 meters from the floor.
081029
Models RD30/RC25 Safety
9
Loading...
+ 30 hidden pages