Note: Continuing research results in steady improvements; therefore, information
in this manual is subject to change without notice.
Note: Only instructions originating from the factory or its authorized translation
representative(s) are considered to be the original set of instructions.
E November, 1999 Taylor (Original Publication)
(Updated June, 2012)
All rights reserved.
051060--M
The word Taylor and the Crown design
are registered trademarks in the United States
of America and certain other countries.
Models RD30/RC25Table of Contents
Taylor Company
750 N. Blackhawk Blvd.
Rockton, IL 61072
Section 1To the Installer
The following are general installation instructions. For
complete installation details, please see the check out
card.
cause severe injuries.
Installer Safety
This unit has many sharp edges that can
In all areas of the world, equipment should be
installed in accordance with existing local codes.
Please contact your local authorities if you have any
questions.
Care should be taken to ensure that all basic safety
practices are followed during the installation and
servicing activities related to the installation and
service of Taylor equipment.
SOnly authorized Taylor service personnel
should perform installation and repairs on
the equipment.
SAuthorized service personnel should consult
OSHA Standard 29CFRI910.147 or the
applicable code of the local area for the
industry standards on lockout/tagout
procedures before beginning any installation
or repairs.
SAuthorized service personnel must ensure
that the proper PPE is available and worn
when required during installation and
service.
SAuthorized service personnel must remove
all metal jewelry, rings, and watches before
working on electrical equipment.
The main power supply(s) to the freezer must
be disconnected prior to performing any repairs.
Failure to follow this instruction may result in personal
injury or death from electrical shock or hazardous
moving parts as well as poor performance or damage
to the equipment.
Note:Allrepairsmustbeperformedbyan
authorized Taylor Service Technician.
Site Preparation
Review the area the unit is to be installed in before
uncrating the unit, making sure that all possible
hazards the user or equipment may come into have
been addressed.
For Indoor Use Only: This unit is designed to operate
indoors, under normal ambient temperatures of
70_-75_F(21_-24_C). The freezer has successfully
performedinhighambienttemperaturesof
104_(40_C) at reduced capacities.
This unit must NOT be installed in an area
where a water jet or hose can be used. NEVER use a
water jet or hose to rinse or clean the unit. Failure to
follow this instruction may result in electrocution.
This unit must be installed on a level surface
to avoid the hazard of tipping. Extreme care should be
taken in moving this equipment for any reason. Two or
more persons are required to safely move this unit.
Failure to comply may result in personal injury or
equipment damage.
Uncrate the unit and inspect it for damage. Report any
damage to your Taylor Distributor.
This piece of equipment is made in the USA and has
USA sizes of hardware. All metric conversions are
approximate and vary in size.
081208
Models RD30/RC25To the Installer
1
Electrical Connections
In the United States, this equipment is intended to be
installed in accordance with the National Electrical
Code (NEC), ANSI/NFPA 70-1987. The purpose of the
NEC code is the practical safeguarding of persons and
property from hazards arising from the use of
electricity. This code contains provisions considered
necessary for safety. In all other areas of the world,
equipment should be installed in accordance with the
existing local codes. Please contact your local
authorities.
FOLLOW YOUR LOCAL ELECTRICAL CODES!
Each unit requires one power supply for each data
label on the unit. Check the data label(s) on the freezer
for branch circuit overcurrent protection or fuse, circuit
ampacity, and other electrical specifications. Refer to
the wiring diagram provided inside of the electrical box
for proper power connections.
SAppliances that are permanently connected
to fixed wiring and for which leakage
currents may exceed 10 mA, particularly
when disconnected or not used for long
periods, or during initial installation, shall
have protective devices such as a GFI, to
protect against the leakage of current,
installed by the authorized personnel to the
local codes.
SSupply cords used with this unit shall be
oil-resistant, sheathed flexible cable not
lighter than ordinary polychloroprene or
other equivalent synthetic
elastomer-sheathed cord (Code designation
60245 IEC 57) installed with the proper cord
anchorage to relieve conductors from strain,
including twisting, at the terminals and
protect the insulation of the conductors from
abrasion.
Beater Rotation
CAUTION: THIS EQUIPMENT MUST BE
PROPERLY GROUNDED! FAILURE TO DO SO
CAN RESULT IN SEVERE PERSONAL INJURY
FROM ELECTRICAL SHOCK!
This unit is provided with an equipotential
grounding lug that is to be properly attached to the rear
of the frame by the authorized installer. The installation
location is marked by the equipotential bonding
symbol (5021 of IEC 60417-1) on both the removable
panel and the equipment’s frame.
SStationary appliances which are not
equipped with a power cord and a plug or
another device to disconnect the appliance
from the power source must have an all-pole
disconnecting device with a contact gap of
at least 3 mm installed in the external
installation.
Beater rotation must be clockwise as viewed
looking into the freezing cylinder.
Note: Thefollowingproceduresmustbe
performed by an authorized Taylor service
technician.
To correct the rotation on a three--phase unit,
interchange any two incoming power supply lines at
freezer main terminal block only.
To correct rotation on a single--phase unit, change the
leads inside the beater motor. (Follow the diagram
printedonthemotor.)
Electrical connections are made directly to the splice
box. The splice box is located behind the right side
panel.
120611
2
Models RD30/RC25To the Installer
Refrigerant
In consideration of our environment, Taylor
proudly uses only earth friendly HFC refrigerants. The
HFC refrigerant used in this unit is R404A. This
refrigerant is generally considered non-toxic and
non-flammable, with an Ozone Depleting Potential
(ODP) of zero (0).
However, any gas under pressure is potentially
hazardous and must be handled with caution.
Refrigeration Charging and Line
Construction
The dispensing unit is shipped with a refrigerant
holding charge that is sufficient enough to prevent
moisture contamination (8 oz./227 g. R404A). This
holding charge will become part of the total system
charge.
The condensing unit is shipped with the total amount
of refrigerant required for a typical installation of 75 ft.
or less with a single dispenser. For other installation
configurations, use the following chart for line sizing
and for adding required refrigerant.
NEVER fill any refrigerant cylinder completely with
liquid. Filling the cylinder to approximately 80% will
allow for normal expansion.
Use only R134a refrigerant that conforms to
the AHI standard 700 specification. The use of any
other refrigerant may expose users and operators to
unexpected safety hazards.
Refrigerant liquid sprayed onto the skin may
cause serious damage to tissue. Keep eyes and skin
protected. If refrigerant burns should occur, flush
immediately with cold water. If burns are severe, apply
ice packs and contact a physician immediately.
Taylor reminds technicians to be cautious of
government laws regarding refrigerant recovery,
recycling, and reclaiming systems. If you have any
questions regarding these laws, please contact the
factory Service Department.
Recommended System Refrigerant Charge
Domestic
Suction Line
Length
Less than 75 ft.Single10 lb.
More than 75 ft.Single12 lb. (add 2 lb.)
Less than 75 ft.Dual13 lb. (add 3 lb.)
More than 75 ft.Dual15 lb. (add 5 lb.)
International
Suction Line
Length
Less than 22.8 mSingle4.5 kg
More than 22.8 mSingle5.4 kg (add 0.91 kg)
Less than 22.8 mDual5.9 kg (add 1.4 kg)
More than 22.8 mDual6.8 kg (add 2.3 kg)
Note: Maximum line length is 150 ft. (45.7 m).
To meet individual installation requirements, lines
must be purchased and constructed locally.
DispenserRequired Charge
DispenserRequired Charge
Line Size
WARNING:R404A refrigerant used in
conjunction with polyolester oils is extremely moisture
absorbent. When opening a refrigeration system, the
maximum time the system is open must not exceed 15
minutes. Cap all open tubing to prevent humid air or
water from being absorbed by the oil.
Models RD30/RC25To the Installer
Liquid Line -- Single or dual dispensers require 3/8”
refrigerant grade copper tubing (hard or soft).
Note: Insulating the liquid line is recommended if it is
exposed to high ambient conditions. This will reduce
heat accumulation and prevent the formation of flash
gas in the liquid line.
120611
3
Single Dispensing Installations
f
Suction Line -- Less than 75 ft. (22.8 m) total line
length requires 5/8” refrigerant grade copper tubing
(hard or soft). Maximum 5/8” tubing length is 75 ft.
(22.8 m).
Dual Dispensing Installations
(One Condenser, Two Dispensers)
Individual Suction Line -- Requires 5/8” refrigeration
grade copper tubing (hard or soft) from each dispenser
to the common suction tube.
Note: Suction lines must be insulated.
Suction Line -- More than 75 ft. (22.8 m) total line
length requires 3/4” refrigerant grade copper tubing
(hard or soft). Maximum tubing length is 150 ft.
(45.7 m).
Note: Use 5/8” tubing to attach the quick disconnects to the other fittings.
Common Suction Line -- Requires 3/4” refrigeration
grade copper tubing.
Note: Lines must be insulated and requires a 5/8” x
3/4”reducerfittingatthequick disconnect
connections. See the diagram below.
Note: 5/8” individual line lengths are not to exceed 75 ft. (22.8 m) maximum length each.
Total line length is not to exceed 150
t. (45.7 m). 5/8” line + 5/8” line + 3/4” line = 150 ft. or less.
4
Models RD30/RC25To the Installer
Installation
Step 1
Install refrigeration lines from the dispenser to the
condensing unit. Do not create oil traps.
Note: For proper oil return, installation of horizontal
suction lines are to be sloped downward in the
direction of the condensing unit. The slope must be a
minimum 1/4” (.64 cm.) angle per 10 ft. (3.048 m.) of
line length.
Step 5
Evacuate the field constructed refrigerant lines using
the access fittings brazed on the condensing end of the
refrigeration lines.
Step 6
When the evacuation process is complete, relieve the
vacuum with 4 oz. (113 g.) of HP62 refrigerant per line,
for a total of 8 oz. (227 g.) This procedure will prevent
moisturecontaminationduringdispenserand
condensing unit connection and complete the total
charge.
Refrigeration Connections
Connect the refrigerant line quick connect/disconnect
couplings to the mating quick connect/disconnect
couplings on the dispensing and condensing unit.
Step 1
Removetheshippingcapsfromthequick
connect/disconnect coupling on the dispensing unit.
Step 2
Thoroughly clean and lubricate the mating surfaces of
the quick connect/disconnects.
Note: Use polyolester oil to lubricate the surfaces.
Figure 1
Normally, any straight run of tubing must be supported
near each end of the run. Long runs require additional
supports. As a guide, 3/8” to 3/4” copper should be
supported every 5 ft. When changing directions, no
corner should be left unsupported. Supports should be
placed a maximum of 2 ft. in each direction from the
corner. If soft copper tube is used, make sure it is not
kinked or flattened. If hard drawn copper tubing is
used, use only long radius elbows.
Step 2
Brazethesuppliedquickconnect/disconnect
couplings on the dispenser end of the refrigeration
lines. Couplings are supplied with the dispenser.
Step 3
Braze the quick connect/disconnect couplings and
access tees on the condensing unit end of the
refrigeration lines. Couplings and access tees are
supplied with the unit.
Note: Wrap a wet cloth aroundthe brasscoupling
bodies to prevent heat damage to the seal.
Step 3
Manually thread the coupling halves together to insure
proper mating of the threads.
Step 4
Using proper sized wrenches, tighten the coupling
halves until the round, flat surfaces of inner coupling
bodies completely depress one another.
Step 5
Once the flat surfaces are completely depressed,
tighten the couplings an additional 1/4 turn. This step
is necessary to insure that the knife edge of the seal
seats into the brass seat of the coupling halves,
forming a leak--proof joint (metal seal).
Step 4
Test the field constructed lines for leaks.
Models RD30/RC25To the Installer
5
Figure 2
Step 6
Check all connections for leaks.
Step 7
Insulate all exposed suction line tubing and fittings.
Step 8
Set the pump down switch located in the condensing
unit. For indoor condensing unit application:
Set cut in at 30 PSIG (207 kPa).
Set cut out at 5 PSIG (34 kPa).
For outdoor condensing unit application:
Set cut in at 20 PSIG (138 kPa).
Set cut out at 0 PSIG (0 kPa).
Pump down pressure readings are to be taken at the
refrigeration line access fittings at the condensing unit.
Step 6
Allow the dispenser to run until the condensing unit
cycles off. Verify the proper pump down pressure
switch setting. SeeStep 8of “Refrigeration
Connections” (page 6).
Note: Pump down pressure readings are to be taken
at the refrigeration line access fittings near the
condensing unit.
Step 7
If necessary, adjust viscosity to produce satisfactory
product. Adjustments are made by turning the
viscosity adjustment screw (located on the front panel)
clockwise for a thicker product or counterclockwise for
a thinner product.
Set Up Procedures
Standard Fill Module
Step 1
Connect the product supply line to the 1/4” barbed
fitting on the fill module. Adjust the fill system pressure
to deliver product to the hopper at 1.5 to 2.5 oz. (42.5
to 70.9 g) per second. (Approximately 15 to 20 PSIG
[103--138 kPa] for most products.)
Step 2
Lubricate, assemble, sanitize and prime the dispenser
as outlined in the Assembly section of this manual.
Step 3
Place the fill switch in the “ON” position. Allow the
product to fill the cylinder and the hopper until the mix
level float is satisfied.
Step 4
Place the power switch in the “AUTO” position.
Step 5
To observe the suction pressure, attach refrigeration
gauges to the suction access fitting in the dispenser.
Pressures should read approximately 32 psi. (221
kPa) for non--alcoholic application and 28 psi. (193
kPa) for alcoholic application.
Note: Connection to the condensing unit suction
access can give an improper reading.
Units Equipped With Post Mix Valve
Step 1
Connect syrup and water lines.
Note: Adjust the syrup supply pressure to maintain 60
PSIG. Water pressure minimum 40 PSIG, maximum
100 PSIG, may require regulated water supply.
Step 2
Turn the “FILL” switch in the front of the RD30 to the
“ON” position.
Step 3
Press and hold the area on the front of the post mix
valve marked “PUSH” to prime the fill system. Priming
is required until the B.I.B. switch and the float switch
are both satisfied. Priming is complete when product
will flow without pressing the “PUSH” button.
Step 4
To adjust either the syrup or water flow rate, turn the
flow adjustment screw clockwise to increase flow, or
counterclockwise to decrease flow. Adjust the screws
until the desired brix is obtained. The flow rate should
be 1.5 to 2.5 oz. (43 fl. ml.) per second.
Note: Both syrup and water flow adjustment screws
are located inside the post mix valve cover. Viewed
from the front, the syrup adjustment screw is on the
right and water adjustment is on the left.
6
Models RD30/RC25To the Installer
Section 2To the Operator
The freezer you have purchased has been carefully
engineered and manufactured to give you dependable
operation. The T aylor ModelRD30/RC25, when
properly operated and cared for, will produce a
consistent quality product. Like all mechanical
products, this machine will require cleaning and
maintenance. A minimum amount of care and
attention is necessary if the operating procedures
outlined in this manual are followed closely.
This Operator’s Manual should be read before
operating or performing any maintenance on your
equipment.
Your Model RD30/RC25willNOTeventually
compensate and correct for any errors during the
set--up or filling operations. Thus, the initial assembly
and priming procedures are of extreme importance. It
isstronglyrecommendedthatallpersonnel
responsible for the equipment’s operation thoroughly
read this manual.
If you require technical assistance, please contact
your local authorized Taylor Distributor.
Note: Warranty is valid only if the parts are authorized
Taylor parts, purchased from an authorized Taylor
Distributor, and the required service work is provided
by an authorized Taylor service technician. Taylor
reserves the right to deny warranty claims on
equipment or parts if non--approved parts or
refrigerant were installed in the machine, system
modificationswereperformedbeyondfactory
recommendations, or it is determined that the failure
was caused by neglect or abuse.
Note: Constantresearchresultsinsteady
improvements; therefore, information in this
manual is subject to change without notice.
If the crossed out wheeled bin symbol is
affixed to this product, it signifies that this product is
compliant with the EU Directive as well as other similar
legislation in effect after August 13, 2005. Therefore,
it must be collected separately after its use is
completed, and cannot be disposed as unsorted
municipal waste.
The user is responsible for returning the product to the
appropriate collection facility, as specified by your local
code.
For additional information regarding applicable local
laws, please contact the municipal facility and/or local
distributor.
Compressor Warranty Disclaimer
The refrigeration compressor(s) on this machine are
warranted for the term indicated on the warranty card
accompanying this machine. However, due to the
Montreal Protocol and the U.S. Clean Air Act
Amendments of 1990, many new refrigerants are
being tested and developed, thus seeking their way
into the service industry. Some of these new
refrigerantsarebeingadvertisedasdrop--in
replacements for numerous applications. It should be
noted that, in the event of ordinary service to this
machine’s refrigeration system, only the refrigerantspecified on the affixed data label should be used.
The unauthorized use of alternate refrigerants will void
your compressor warranty . It will be the owner’s
responsibility to make this fact known to any technician
he employs.
It should also be noted that Taylor does not warrant the
refrigerant used in its equipment. For example, if the
refrigerant is lost during the course of ordinary service
to this machine, Taylor has no obligation to either
supply or provide its replacement either at billable or
unbillable terms. Taylor does have the obligation to
recommend a suitable replacement if the original
refrigerant is banned, obsoleted, or no longer available
during the five year warranty of the compressor.
Taylor will continue to monitor the industry and test
new alternates as they are being developed. Should a
new alternate prove, through our testing, that it would
be accepted as a drop--in replacement, then the above
disclaimer would become null and void. To find out the
current status of an alternate refrigerant as it relates to
your compressor warranty, call the local Taylor
Distributor or the T aylor Factory. Be prepared to
provide the Model/Serial Number of the unit in
question.
081029
Models RD30/RC25To the Operator
7
Section 3Safety
We at Taylor Company are concerned about the safety
of the operator when he or she comes in contact with
the freezer and its parts. Taylor has gone to extreme
efforts to design and manufacture built--in safety
features to protect both you and the service technician.
As an example, warning labels have been attached to
the freezer to further point out safety precautions to the
operator.
IMPORTANT -- Failure to adhere to the
following safety precautions may result in severe
personal injury or death. Failure to comply with
these warnings may damage the machine and its
components. Component damage will result in
part replacement expense and service repair
expense.
DO NOT operate the freezer without reading
this Operator Manual. Failure to follow this instruction
may result in equipment damage, poor freezer
performance, health hazards, or personal injury.
Per IEC 60335--1 and its part 2 standards,
“This appliance is to be used only by trained personnel.
It is not intended for use by children or people with
reduced physical, sensory, or mental capabilities, or
lack of experience and knowledge, unless given
supervision or instruction concerning the use of the
appliance by a person responsible for their safety.”
This unit is provided with an equipotential
grounding lug that is to be properly attached to the rear
of the frame by the authorized installer. The installation
location is marked by the equipotential bonding
symbol (5021 of IEC 60417-1) on both the removable
panel and the equipment’s frame.
SDO NOT operate the freezer unless it is
properly grounded.
SDO NOT operate the freezer with larger
fuses than specified on the freezer data
label.
SAll repairs must be performed by an
authorized Taylor service technician. The
main power supplies to the machine must
be disconnected prior to performing any
repairs.
SCord Connected Units: Only Taylor
authorized service technicians may install a
plug on this unit.
SStationary appliances which are not
equipped with a power cord and a plug or
another device to disconnect the appliance
from the power source must have an all-pole
disconnecting device with a contact gap of
at least 3 mm installed in the external
installation.
SAppliances that are permanently connected
to fixed wiring and for which leakage
currents may exceed 10 mA, particularly
when disconnected or not used for long
periods, or during initial installation, shall
have protective devices such as a GFI, to
protect against the leakage of current,
installed by the authorized personnel to the
local codes.
SSupply cords used with this unit shall be
oil-resistant, sheathed flexible cable not
lighter than ordinary polychloroprene or
other equivalent synthetic
elastomer-sheathed cord (Code designation
60245 IEC 57) installed with the proper cord
anchorage to relieve conductors from strain,
including twisting, at the terminals and
protect the insulation of the conductors from
abrasion.
DO NOT use a water jet to clean or rinse the
freezer. Failure to follow these instructions may result
in serious electrical shock.
110824
Failure to follow these instructions may result in
electrocution. Contact your local authorized Taylor
Distributor for service.
8
Models RD30/RC25Safety
SDO NOT allow untrained personnel to
operate this machine.
SDO NOT operate the freezer unless all
service panels and access doors are
restrained with screws.
SDO NOT remove any internal operating
parts (examples: freezer door, beater,
scraper blades, etc.) unless all control
switches are in the OFF position.
Failure to follow these instructions may result in severe
personal injury to fingers or hands from hazardous
moving parts.
This unit has many sharp edges that can
cause severe injuries.
SDO NOT put objects or fingers in the door
spout. This may contaminate the product
and cause severe personal injury from blade
contact.
SUSE EXTREME CAUTION when removing
the beater asssembly. The scraper blades
are very sharp.
This freezer must be placed on a level
surface. Failure to comply may result in personal
injury.
Cleaning and sanitizing schedules are
governed by your state or local regulatory agencies
and must be followed accordingly. Please refer to the
cleaning section of this manual for the proper
procedure to clean this unit.
For Indoor Use Only: This unit is designed to operate
indoors, under normal ambient temperatures of 70_ -
75_F(21_ -24_C). The freezer has successfully
performedinhighambienttemperaturesof
104_(40_C) at reduced capacities.
NOISE LEVEL: Airborne noise emission does not
exceed 78 dB(A) when measured at a distance of 1.0
meter from the surface of the machine and at a height
of 1.6 meters from the floor.
081029
Models RD30/RC25Safety
9
Loading...
+ 30 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.