Note: Continuin g research results in steady improvements; therefore, information
in this manual is subject to change without notice.
Table of ContentsModel PH85
Section 1To the Installer
This machine is designed for indoor use only.
DO NOT install the machine in an area where
a water jet could be used. Failure to follow this
instruction may result in serious electrical shock.
Water Connections
(Water Cooled Units Only)
An adequate cold water supply must be provided with
a hand shut-off valve. On the rear of the unit, two 1/2”
I.P.S. water connectionsfor inlet andoutlet have been
provided for easy hook-up. 1/2” inside diameter water
lines should be connected to the machine. (Flexible
lines are recommended, if local codes permit.)
Depending on local water conditions, it may be
advisable to install a water strainer to prevent foreign
substances from clogging the automatic water valve.
There will be only one water “in” and one water “out”
connection. DO NOT install a hand shut-off valve on
the water “out” line! Water should always flow in this
order:first,throughtheautomaticwatervalve;second,
through the condenser; and third, through the outlet
fitting to an opentrapdrain.
and property from hazards arising from the use of
electricity. This code contains provisions considered
necessary for safety . Compliance therewith and
proper maintenance will result in an installation
essentially free from hazard!
In all other areas of the world, equipment should be
installed in accordance with the existing local codes.
Please contact your local authorities.
Stationary appliances which are not equipped with a
power cord and a plug or other device to disconnect
the appliance from the power source must have an
all--pole disconnecting device with a contact gap of at
least 3 mm installed in the external installation.
CAUTION: THIS EQUIPMENT MUST BE
PROPERLY GROUNDED! FAILURE TO DO SO
CAN RESULT IN SEVERE PERSONAL INJURY
FROM ELECTRICAL SHOCK!
Beater rotation must be clockwise as viewed looking
into the freezing cylinder.
Air Cooled Units
Air cooled units require a minimum of 3” (76 mm) of
clearance around all sides of the freezer to allow for
adequate air flow across the condensers. A deflector
has been added to the underside, preventing
recirculation of warm air. Failure to allow adequate
clearance can reduce the refrigeration capacity of the
freezer and possibly cause permanent damage to the
compressors.
Electrical Connections
Each freezer requires one power supply. Check the
data label on the freezer for fuse, circuit ampacity and
electrical specifications. Refer to the wiring diagram
provided inside of the electrical box, for proper power
connections.
In the United States, this equipment is intended to be
installed in accordance with the National Electrical
Code (NEC), ANSI/NFPA 70--1987. The purpose of
the NECcode isthe practical safeguarding of persons
Figure 1
Note: The following procedures should be
performed by a trained service technician.
To correct rotation on a three-phase unit, interchange
any two incoming power supply lines at the freezer
main terminal block only .
To correct rotation on a single-phase unit, exchange
the leads inside thebeater motor. (Follow thediagram
printedonthemotor.)
Electrical connections are made directly to the
terminal block. The terminal block is provided in the
main control box located behind the service panel.
040419
Model PH85To the Installer
1
Section 2To the Operator
The freezer you have purchased has been carefully
engineered and manufactured to give you dependable
operation. The Taylor Model PH85, when properly
operated and cared for, will produce a consistent
quality product. Like all mechanical products, this
machine will require cleaning and maintenance. A
minimum amount of care and attention is necessary if
the operating procedures outlined in this manual are
followed closely.
This Operator’s Manual should be read before
operating or performing any maintenance on your
equipment.
Your Model PH85 will NOT eventually compensate for
and correct any errors during the set-up or filling
operations. Thus, the initial assembly and priming
procedures are of extreme importance. It is strongly
recommended that personnel responsible for the
equipment’soperation,bothassemblyand
disassembly, study these procedures in order to be
properlytrainedandtomakesurethatno
misunderstandings exist.
In the event you should require technical assistance,
please contact your local authorized Taylor Distributor.
If the crossed out wheeled bin symbol is
affixed to this product, it signifies that this product is
compliant with the EU Directive as well as other similar
legislation in effect after August 13, 2005. Therefore,
it must be collected separately after its use is
completed, and cannot be disposed as unsorted
municipal waste.
The user is responsible for returning the product to the
appropriate collection facility, as specified by your local
code.
For additional information regarding applicable local
laws, please contact the municipal facility and/or local
distributor.
Compressor Warranty Disclaimer
The refrigeration compressor(s) on this machine are
warranted for the term indicated on the warranty card
accompanying this machine. However , due to the
Montreal Protocol and the U.S. Clean Air Act
Amendments of 1990, many new refrigerants are
being tested and developed, thus seeking their way
into the service industry. Some of these new
refrigerantsarebeingadvertisedasdrop-in
replacements for numerous applications. It should be
noted that, in the event of ordinary service to this
machine’s refrigeration system, only the refrigerantspecified on the affixed data label should be used.
The unauthorized use of alternate refrigerants will void
your compressor warranty . It will be the owner’s
responsibility to make this fact known to any technician
he employs.
It should also be noted that Taylor does not warrant the
refrigerant used in its equipment. For example, if the
refrigerant is lost during the course of ordinary service
to this machine, Taylor has no obligation to either
supply or provide its replacement either at billable or
unbillable terms. Taylor does have the obligation to
recommend a suitable replacement if the original
refrigerant is banned, obsoleted, or no longer available
during the five year warranty of the compressor.
The Taylor Company will continue to monitor the
industry and test new alternates as they are being
developed. Should a new alternate prove, through our
testing, that it would be accepted as a drop-in
replacement, thenthe above disclaimer would
become null and void. To find out the current status of
an alternate refrigerantas it relates toyour
compressor warranty, call the local Taylor Distributor
or the Taylor Factory. Be prepared to provide the
Model/Serial Number of the unit in question.
050816
2
Model PH85To th e Operator
Section 3Safety
Weat TaylorCompanyare concernedabout thesafety
of the operator when he or she comes in contact with
the freezer and its parts. Taylor has gone to extreme
efforts to design and manufacture built-in safety
features to protectbothyouandtheservicetechnician.
As anexample, warning labels havebeen attached to
thefreezer to furtherpointoutsafetyprecautionstothe
operator.
IMPORTANT -- Failure to adhere to the
following safety precautions may result in severe
personal injury or death. Failure to comply with
these warnings may damage the machine and its
components. Component damage will result in
part replacement expense and service repair
expense.
SDO NOT allow untrained personnel to
operate this machine.
SDO NOT operate the freezer unless all
service panels and access doors are
restrained with screws.
SDO NOT remove the door, beater, scraper
blades, drive shaft or air/mix pump unless
the power switch is in the OFF position.
Failuretofollow theseinstructionsmayresult in severe
personal injury from hazardous moving parts.
To Operate Safely:
DO NOT operate the freezer without reading
this operator’smanual. Failuretofollow thisinstruction
may result in equipment damage, poor freezer
performance, health hazards, or personal injury.
SDO NOT operate the freezer unless it is
properly grounded.
SDO NOT operate the freezer with larger
fuses than specified on the freezer data
label.
SDO NOT attempt any repairs unless the
main power supply to the freezer has been
disconnected.
Failure to follow these instructions may result in
electrocution. Contact your local authorized T aylor
Distributor for service.
DO NOT use a water jet to clean or rinse the
freezer. Failure to follow this instruction may result in
serious electrical shock.
SDO NOT put objects or fingers in door
spout.
SUSE EXTREME CAUTION when removing
the beater assembly.
Failure to follow these instructions may result in
contaminated product or personal injury from blade
contact.
DO NOT draw product duringthe HEATcycle
because of high product temperatures.
This freezer must be placed on a level
surface. Failureto comply mayresultin personal injury
or equipment damage.
DO NOT obstruct air intake and discharge openings:
3” (76 mm) minimum air space around all sides. A
deflector hasbeen added tothe underside,preventing
recirculation of warm air. Failure to follow this
instruction may cause poor freezer performance and
damage to the machine.
NOISE LEVEL: Airborne noise emission does not
exceed 78 dB(A) when measured at a distance of 1.0
meter from the surface of themachine and at a height
of 1.6 meters from the floor.
1POWER SWITCH
2KEYS -- LEFT SIDE
3KEYS -- RIGHT SIDE
4INDICA T OR LIGHTS
5LIQUID CRYSTAL DISPLAY
6KEYS -- SYRUP HEATERS
Symbol Definitions
To better communicate in the International arena, the
words on many of our operator switches and buttons
have symbols to indicate their functions. Your Taylor
equipment is designed with these International
symbols.
The following chart identifies the symbol definitions.
=OFF
=ON
= WASH
=PUMP
=AUTO
=MENU
=MIXLOW
= MIX OUT
= HEAT MODE, SYRUP HEATERS
= CLEAN MANUALLY/BRUSH CLEAN
10
Model PH85Important: To the Operator
Power Switch
Thepower switchis locatedunder the control panel on
the left hand side of the unit. When placed in the ON
position, the power switch allows Softech panel
operation.
Indicator Lights
Mix Low - When the MIX LOW light begins to flash, it
indicates the mix hopper has a low supply of mix and
should be refilled as soon as possible. The word
“LOW” will also display on theLCD indicatornextto the
word “MIX”.
Liquid Crystal Display
TheLiquidCrystal Display (LCD) islocated on thefront
control panel. The LCD is usedto show in what mode
the freezer is operating and whether or not there is
sufficient mix.
Reset Mechanism
Mix Out - When the MIX OUT light begins to flash, it
indicates the mix hopper has been almost completely
exhausted and has an insufficient supply of mix to
operate the freezer. The word “OUT” will also display
on the LCD indicator next to the word “MIX”. At this
time the AUTO mode is lockedout andthe freezer will
be placed in the STANDBY mode. To initiate the
refrigeration system, add mix to the mix hopper and
press the AUTO key. The freezer will automatically
begin operation.
Heat Mode - When the HEAT MODE light isflashing,
it indicates that the freezer is in the process of a heat
cycle.
Clean Manually -When theCLEAN MANUALLYlight
is flashing, it indicates that the machine must be
disassembled and brush cleaned within 24 hours.
When all four indicatorlights areflashing, thissignifies
a locked condition. When MIX LOW and MIX OUT
lights are flashing only, this signifies an unlocked
condition.
Syrup Heaters -- Indicatorlightsare located abovethe
LEFTandRIGHTkeys.Pressthe LEFTkeytoactivate
the heater for the left side of the syrup rail. Press the
RIGHT key to activate the heater for the right side of
the syrup rail.
The reset buttons are located in the center of the
servicepanel. Thereisone foreach sideof thefreezer.
The reset mechanism protects the beater motor from
an overload condition. Ifan overload occurs, thereset
mechanism will trip. To properly reset the freezer,
place the powerswitch inthe OFF position. Press the
reset button firmly. Turn the power switch to the ON
position. Clear the fault. Press the WASH key and
observe the freezer’s performance. Open the side
access panel tocheck if thebeater motoris turningthe
drive shaft in a clockwise direction (from the operator
end) without binding.
Donot usemetal objectsto press thereset
button. Failure to follow this instruction may
result in electrocution.
If the beater is turning properly, press the WASH key
to cancelthe cycle. PresstheAUTOkey on bothsides
of the machine to resume normal operation. If the
freezer shuts downagain, contacta service
technician.
Model PH85Important: To the Operator
11
Adjustable Draw Handle
Thisunitfeaturesan adjustabledrawhandletoprovide
the best portion control, giving a better, consistent
quality toyour product and controllingcosts.The draw
handle should be adjusted to provide a flow rate of 5
to 7-1/2 oz. of product by weight per 10 seconds. To
INCREASEtheflowrate,turnthescrew
COUNTERCLOCKWISE,andCLOCKWISEto
DECREASE theflow rate. In addition, for purposes of
SANITIZING and RINSING, the flow rate can be
increased by removing the pivot pin and placing the
restrictive bar on the TOP. When drawing product,
always have the restrictive bar on the BOTTOM.
IMPORTANT: Once the draw rate is set,
tighten the lock nut with a wrench.
Operating Screen Descriptions
Whenthemachineispoweredthesystem willinitialize.
The screen will display “INITIALIZING”. There will be
four typesof data the system will check: LANGUAGE,
SYSTEM DATA, CONFIG DATA, and LOCKOUT
DATA. During the INITIALIZING... LANGUAGE
screen, the alarm will be on. If the system data,
configuration data,orlockout history data hasbecome
corrupt, thefollowing screenwill alertthe operatorthat
the system settings may have been changed.
NVRAM FAULT
RESET TODEFAULTS
PRESS SEL KEY
Once the system has initialized the SAFETY
TIMEOUT screen is displayedand thealarm is turned
on.
After the safety timeout has been completed, and the
power switch is OFF, one of the following screens is
displayed.
The first screen is displayed if the machine is not in a
brush clean state. If any of the requirements for a
brush cleanhave notbeen met, the time displayedwill
remain at 5:00 minutes. When all the requirements for
a brush cleaning are met, andthe five minutes expire,
the screen will change to the second screen, which is
the standard power switch OFF screen.
POWER SWITCH OFF
OUTTIME: 4:40OUT
68.5HOPPER62.1
69.5BARREL67.7
POWER SWITCH OFF
-- = -- = -- = -- = -- = -UNIT CLEANED
When the power switch is set in the ON position, the
system mode of operation screen is displayed. In this
example, themachineis ON,but no mode ofoperation
has been selected. The second line of the display
indicates whether there is a sufficient supply of mix in
the hopper or if there is a LOW or OUT mix condition.
The third line of the display shows the temperature of
the mix hopper. After pressing the AUTO key, the last
line of the display shows the month and date (MM =
month, DD = day) that the machine needs to be
disassembled and brush cleaned.
SAFETY TIMEOUT
ANY KEY ABORTS
This screenwill bedisplayed, withthe alarm on, for 60
seconds or until any key is pressed.
12
OFF:MODE:OFF
OK:MIX:OK
40.0FHOPPER40.0F
BRUSH CLEAN ON: MM/DD
Model PH85Important: To the Operator
This display indicates the freezer is operating in 3
different modes. The following information is given:
The left side of the freezer is operating in the
STANDBY mode, and the mix level in the hopper is
OUT. The right side is operating in the WASH and
PUMP modes,and themix level inthe hopper isLOW.
The temperature of the mix in both hoppers is 40_F.
(4.4_C.), and the machine needs to be brushcleaned
on October 31st.
STANDBY:MODE:WSH--PMP
OUT:MIX:LOW
40.0FHOPPER40.0F
BRUSH CLEAN ON: 10/31
The following displays pertain to the HEAT cycle:
While inthe heating phase, you will see this display.It
shows the present temperature of the hopper.
HEAT:MODE:HEAT
HEAT:PHASE:HEAT
140.0FHOPPER140.0F
BRUSH CLEAN ON: MM/DD
The final phase of the heat treatment cycle is the
cooling phase. Now the freezer must cool the mix
below 41_F. (5_C.). If the product fails to cool in 2
hours, the freezer will lock out.
This example illustrates that the temperature is being
lowered, but has not yet reached the set point.
HEAT:MODE:HEAT
COOL:PHASE:COOL
55.0FHOPPER55.0F
BRUSH CLEAN ON: MM/DD
When the entire heat cycle has been completed, the
normaldisplay willappear, showing themachine inthe
STANDBY mode. The machine may now be placed in
AUTO or left in STANDBY.
STANDBY:MODE:STANDBY
OK:MIX:OK
41.0FHOPPER41.0F
BRUSH CLEAN ON: MM/DD
Hard Lock: There are two causes for a hard lock:
The mix temperature must be raised above 151_F.
(66.1_C.) within 90 minutes or the freezer will be
locked in STANDBY, and the cycle failure display will
appear.
In the example, the hopper temperature is 140_F.
(60_C.). The phase shows that the machine is in the
HEAT phase of the treatment cycle.
When theheating phaseis complete,the freezer goes
into the holding phase of the cycle.The holding phase
will hold the temperature above151_F.(66.1_C.) for a
minimum of 30 minutes.
In this example, the hopper temperature is 151_F.
(66.1_C.).
HEAT:MODE:HEAT
HOLD:PHASE:HOLD
151.0FHOPPER151.0F
BRUSH CLEAN ON: MM/DD
1.Fourteen days have elapsed since the last
brush cleaning. The following screen will be
displayed.
14 DAY TIMEOUT
CLEANING REQ’D
FREEZER LOCKED
PRESS SEL KEY
2.There has been a thermistor failure (freezing
cylinder, hopper, or glycol) during the heat
treatment process.
SYSTEM FAULT
SERVICE REQ’D
FREEZER LOCKED
PRESS SEL KEY
All four LED’s on the front of the freezer will flash.
Press the SEL key.
Model PH85Important: To the Operator
13
The next display is the screen which will appear after
thefailuremessage. Tocomply withhealth codes,heat
treatment system freezers must complete a heat
treatment cycle daily, and must also be brushed
cleaned every 14 days. Brush cleaning is the normal
disassembly andcleaning procedure. Failure tofollow
these guidelines will cause the control to lock the
freezer out of the AUTO mode. Press the WASH key.
NO AUTO OPERATION
ALLOWED UNTIL
BRUSH CLEANING
PRESS WASH KEY
The next display is the screen which will appear after
the brush cleaning message and illustrates that the
control is in the OFF mode and the machine needs to
be disassembled and brush cleaned.
Once the unitisunlocked, onlythe mix outand mix low
LED’s will flash.
OFF:MODE:OFF
OK:MIX:OK
41.0FHOPPER41.0F
FREEZER LOCKED
NO HEAT TREAT START
BECAUSE
VARIABLE MESSAGE
PRESS SEL KEY
If the following screen appears, a soft lock has
occurred during the heat treatment cycle.
HEAT TREAT CYCLE
FAILURE
FREEZER LOCKED
PRESS SEL KEY
If the temperature of the product has not fallen below
41_F(5_C)bytheendoftheCOOLcycle,thefollowing
screen will appear.
PRODUCT OVER TEMP
FREEZER LOCKED
PRESS SEL KEY
Soft Lock: If a heat treatment cycle has not been
initiatedwithin the last 24 hours, all four LED’son the
front of the machine will flash and a message will
appear onthe LCD. Line 3 of the LCDwill indicate the
reason the message appears. Following are the
variable messages which will appear on line 3:
1.POWER SWITCH OFF: Power switch was in
the OFF position.
2.MIX OUT PRESENT: There was mix out
condition present.
3.AUTO OR STANDBY OFF: The unit was not in
the AUTO or STANDBY mode.
4.NO HEAT CYCLE TRIED: A heat treatment
cycle was not attempted in the last 24 hours.
(AUTO HEAT TIME was advanced, or a power
loss was experienced at the time the cycle was
to occur, or a heat cycle failure not due to a
thermistor failure.)
Press the SEL key to advance to the next display.
When one of these messages appears, automatic
freezer operation cannot take place untilthe freezer is
disassembled and brush cleaned or has completed a
heat treatment cycle. Thenext display willinstruct the
operator to start a heat treatment cycle manually (by
pressing the AUTOkey),or to disassemble and brush
clean the freezer. If the AUTO key is pressed, the
freezerwill automaticallystarttheheat treatmentcycle
and only the heat cycle LED will flash.
NO AUTO OPERATION
ALLOWED. PRESS
AUTO FOR HEAT CYCLE
WASH TO BRUSH CLEAN
14
Model PH85Important: To the Operator
If the WASH key is pressed, the next display will
appear and the freezer will have to be disassembled
and brush cleaned.
3.HPCO COMPRESSOR: Place the power
switch in the OFF position. Wait 5 minutes for
the machine to cool. Place the power switch in
the ON position. Clear the tone.
OFF:MODE:OFF
OK:MIX:OK
41.0FHOPPER41.0F
FREEZER LOCKED
Once the freezer is unlocked by starting a heat
treatment cycle, only the heat cycle LED will flash. If
the freezer is unlocked by brush cleaning, the mix low
and mix out LED’s will flash.
Operator Menu
The OPERATOR MENU isused to enter the operator
function displays. To access the OPERATOR MENU,
simply press theMENU key.The cursor will flash over
theletter“A” indicatingthat this isscreen “A”. Toselect
a different screen, use the arrow keys and move the
cursor to the desired screen selection and press the
SEL key.
OPERATOR MENU
BCDEFGHIJ
A
EXIT FROM MENU
<--- --->SEL
4.COMP ON TOO LONG: Place the power
switch in the OFF position. Call a service
technician. Clear the tone.
5.HOPPER THERM BAD: Place the power
switch in the OFF position. Call a service
technician.
6.BARREL THERM BAD: Place the power switch
in the OFF position. Call a service technician.
7.GLYCOL THERM BAD: Place the power switch
in the OFF position. Call a service technician.
8.HOPPER OVER TEMP: The hopper
temperature has risen too high as follows. Clear
the tone.
a.The hopper temperature reaches 41_F.
(5_C.) or higher after a power failure.
b.Thehoppertemperaturehasnot fallenbelow
41_F. (5_C.) by the end of the COOL phase
in the heat cycle.
9.BARREL OVER TEMP: The barrel (freezing
cylinder) temperature has risen too high as
follows. Clear the tone.
a.The barrel (freezing cylinder) temperature
Screen “B” is FAULT DESCRIPTION. The fault
description will indicate if there is a fault with the
reaches 41_F. (5_C.) or higherafter a power
failure.
freezer and the side of the freezer where the fault
occurred. To clear the tone for any faults which have
beencorrected,press theleft arrowkey.Tosee if there
is morethan one fault per cylinder,press the SELkey.
b.The barrel (freezing cylinder) temperature
has not fallen below 41_F. (5_C.) by the end
of the COOL phase in the heat cycle.
When the last fault is displayed, the control will return
to the OPERATOR MENU. To return to the main
screen, move the cursor to “A” and press the SELkey
again. Listed below are the variable messages which
10.POWER FAILURE: This message will appear in
the FAULT DESCRIPTION if a power failure
has occurred. Clear the tone.
will appear, along with the corrective action:
1.NO FAULT FOUND: There was no fault found
in the freezer. Nothing will appear on the screen
after this variable message appears.
Screen “C” isSET CLOCK.Thisscreen will displaythe
current date and time. The date and time may be
changed only after the freezer has been manually
brush cleaned, but before it has been placed in the
AUTO mode. Move the cursor under the number you
wish to change. Press the plus key to increase the
number; pressthe minus key to decreasethe number .
When the desired time and date appears, press the
SEL key once to return to the OPERAT OR MENU.
SET CLOCK
10:21 AM11/07/1999
-- -<--- --->+++------SEL
If an illegal date is entered, the following screen will
appear. The correct date must be entered before
leaving this display.
SET CLOCK
10:34 AM02/30/1999
INVALID DATE
SEL
Screen “D” is SYSTEM INFORMATION. The first
screen will indicate the software version used in the
unit.
SOFTWARE VERSION
PH85 Control UVC2
Version 2.00
SEL
Press the SEL key to view the second screen of the
SYSTEM INFORMATION display. This screen will
indicate theBill ofMaterial number and Serial Number
for the unit. Press the SEL key once to return to the
Operator Menu.
B.O.M.PH8533B000
S/NJ0000000
Screen “E” is AUTO HEAT TIME. This screen is used
to set the timeof dayinwhich theheat treatment cycle
will start. Move the cursor under the number you wish
to change.Press the plus key toincrease the number;
press the minus key to decrease the number. When
the desired time appears, press the SEL key once to
return to the OPERATOR MENU.
AUTO HEAT TIME
TIME: 12:00 AM
-- --
<--- --->+++------SEL
Screen “F” is CURRENT CONDITIONS. This screen
gives the viscosity of the product and the hopper and
barrel temperatures. The last line of the display is the
compressor countdown safety timer. The safety timer
prevents the compressor from running more than 11
minutes (other than during the cooling phase of the
heat treatment cycle).
VISCHOPPERBARREL
038.528.5
0.038.518.0
TIME C11:0011:00
Press the SEL key once to view the SERVINGS
COUNTER screen.
The SERVINGS COUNTER screen indicates the
number of times the draw switch has closed (number
ofdraws) sincethe last brushcleaning or sincethelast
serving counter reset. A maximum of 32,767 draws
can be recorded; an additional draw will cause the
counter to restart at zero. Pressing the SEL key will
return the display to the Operator Menu.
SERVINGS COUNTER
LEFTRIGHT
1215
SEL
SEL
Draws are counted during the AUTO mode of
operation only.
16
Model PH85Important: To the Operator
Loading...
+ 46 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.