C OM M E R CIA L
ULTRA FORCE™
UP TO 96% EFFICIENT COMMERCIAL GAS WATER HEATERS
The UItra Force™ SUF product line is the most efficient State commercial water heater line ever built. With a storage tank of up to 130 gallons, high BTU input and up to 96% thermal efficiency,these models deliver more hot water for every energy dollar. A single Ultra Force unit is an ideal energysaving choice for restaurants and other mid-sized commercial applications. Multiple Ultra Force water heaters can be manifolded together to meet the demands of large commercial and industrial applications.
Down-Fired Low-NOx
Powered-Burner Design
•Top-mounted radial burner design ensures optimum combustion efficiency.
Fully Submerged, Spiral-Shaped
Condensing Heat Exchanger
•Spiral shaped heat exchanger coils keeps hot flue gases swirling through the heat exchanger maximizing heat transfer and efficiency.
•Spiral shaped heat exchanger reduces the accumulation of lime scale; maintains higher efficiency performance over time.
Standard Power-Vent or Power-Direct Vent Flexibility
•Vertical or sidewall power-venting
•Vertical or sidewall powered-direct vent draws all combustion air from outside the building.
•Vents using inexpensive PVC, ABS or CPVC pipe. Canadian installations require ULC S636 listed PVC or CPVC pipe for intake and exhaust.
•Air intake and vent runs can be up to 120 equivalent feet.
Space-Saving Design, with Zero Clearance to Combustibles
All Controls Including Gas Valve and Combustion Air Blower Located on Top
•Provides easy access during installation and service.
•Protects against high water damage.
•Protected from dirt and incidental damage.
Advanced Electronic
Control System
•Microprocessor controls all water heater functions including ignition and temperature regulation.
•Precise temperature control adjustable from 90° F to 180° F.
•Large LCD display provides detailed operational and diagnostic information in plain English for ease of operation and service.
•Ultra Force water heaters are iCOMM™ compatible and can be monitored from remote locations. Call 1.888.WATER02 for more information.
Powered Anodes (Standard on All Models)
•Provide long-lasting tank protection
•Non sacrificial anodes never need replacing unless damaged.
ASME Construction
•Optional on 120, 150, 199 and 250 models.
•Standard on 300, 400 and 500 models.
Maximum Hydrostatic Working Pressure: 160 psi
CSA Certified and ASME Rated
T&P Relief Valve
• Approved for installation on combustible flooring.
For more information on Ultra Force™ contact:
State Water Heaters, |
|
500 Tennessee Waltz Parkway |
|
Ashland City, TN 37015 |
|
800-365-0024 Toll-free USA |
|
www.statewaterheaters.com |
December 2009R |
COM M ER CI AL
ULTRA FORCE™
UP TO 96% EFFICIENT COMMERCIAL GAS WATERHEATERS
Other Ultra Force™ Features:
Comme rcial Grade GlassLined Tank and Heat Exchang er for Long -Term Protectio n Against Corrosion
•Heat exchanger glass-lined on both water and vent sides to protect against corrosive flue gases and condensate inside the coil
Handhole Cleanou t
• For easy inspection and cleaning
Comp liance
•Meets or Exceeds theThermal Efficiency and Standby Loss Requirements of the U. S. Department of Energy and Current Edition of ASHRAE/IESNA 90.1
•Complies with SCAQMD Rule 1146.2 and other air quality management districts with similar requirements for NOx emissions
•The 120-250K BTU models are design-certified by CSA International, according to ANSI Z21.10.3 - CSA 4.3 Standards governing storage-type water heaters
•The 300-500K BTU models are design-certified by Underwriter's Laboratories (UL), Inc., according to ANSI Z21.10.3-4.3 CSA Standards governing storage-type
water heaters
•Design-certified by Underwriter's Laboratories (UL), Inc., to NSF Standard 5
Three-Year Limit ed Tank Warra nty
•For complete warranty information, consult written warranty shipped with water heater or contact State Water Heaters
SUF 60 120NE - SUF 100 250NE Models
SUF 130 300NEA - SUF 130 500NEA Models
RECOVERYCAPACITY
|
TYPEOF |
INPUT |
|
Thermal |
|
|
|
U.S.Gallons/Hrand Litres/Hrat TEMPERATURERISEINDICATED |
|
|
|
|
||||||||
MODEL |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||||
|
Approx. |
Fº |
30 Fº |
40 Fº |
50 Fº |
60 Fº |
70 Fº |
80 Fº |
90 Fº |
100 Fº |
|
110 Fº |
120Fº |
130Fº |
140 Fº |
|||||
GAS |
|
|
|
Efficiency |
|
|||||||||||||||
|
|
BTUH |
|
KW |
|
Capacity |
Cº |
17 Cº |
22Cº |
28 Cº |
33 Cº |
39Cº |
44 Cº |
50 Cº |
56 Cº |
|
61 Cº |
67Cº |
72 Cº |
78 Cº |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
SUF 60 |
NATURAL/ |
120,000 |
|
35 |
95% |
60 U.S. Gals. |
GPH |
461 |
345 |
276 |
230 |
197 |
173 |
154 |
138 |
|
126 |
115 |
106 |
99 |
120NE |
PROPANE |
|
227 Litres |
LPH |
1744 |
1308 |
1046 |
872 |
747 |
654 |
581 |
523 |
|
476 |
436 |
402 |
374 |
|||
|
|
|
|
|
||||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
SUF 100 |
NATURAL/ |
150,000 |
|
44 |
95% |
100 U.S. Gals. |
GPH |
576 |
432 |
345 |
288 |
247 |
216 |
192 |
173 |
|
157 |
144 |
133 |
123 |
150 NE |
PROPANE |
|
379 Litres |
LPH |
2179 |
1635 |
1308 |
1090 |
934 |
817 |
726 |
654 |
|
594 |
545 |
503 |
467 |
|||
|
|
|
|
|
||||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
SUF 100 |
NATURAL/ |
199,900 |
|
58 |
95% |
100 U.S. Gals. |
GPH |
767 |
575 |
460 |
384 |
329 |
288 |
256 |
230 |
|
209 |
192 |
177 |
164 |
199 NE |
PROPANE |
|
379 Litres |
LPH |
2904 |
2178 |
1743 |
1452 |
1245 |
1089 |
968 |
871 |
|
792 |
726 |
670 |
622 |
|||
|
|
|
|
|
||||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
SUF 100 |
NATURAL/ |
250,000 |
|
73 |
95% |
100 U.S. Gals. |
GPH |
960 |
720 |
576 |
480 |
411 |
360 |
320 |
288 |
|
262 |
240 |
221 |
206 |
250NE |
PROPANE |
|
379 Litres |
LPH |
3632 |
2724 |
2179 |
1816 |
1557 |
1362 |
1211 |
1090 |
|
991 |
908 |
838 |
778 |
|||
|
|
|
|
|
||||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
SUF 130 |
NATURAL/ |
300,000 |
|
88 |
96% |
130 U.S. Gals. |
GPH |
1164 |
873 |
699 |
582 |
499 |
436 |
388 |
349 |
|
318 |
291 |
269 |
250 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|||||
300NEA |
PROPANE |
|
492 Litres |
LPH |
4406 |
3304 |
2644 |
2203 |
1888 |
1652 |
1469 |
1322 |
|
1201 |
1102 |
1017 |
945 |
|||
|
|
|
|
|
||||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
SUF 130 |
NATURAL/ |
399,900 |
|
117 |
96% |
130 U.S. Gals. |
GPH |
1552 |
1164 |
931 |
776 |
665 |
582 |
517 |
465 |
|
423 |
388 |
359 |
332 |
400 NEA |
PROPANE |
|
492 Litres |
LPH |
5875 |
4406 |
3525 |
2938 |
2518 |
2203 |
1958 |
1750 |
|
1602 |
1469 |
1356 |
1259 |
|||
|
|
|
|
|
||||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
SUF 130 |
NATURAL/ |
499,900 |
|
146 |
95% |
130 U.S. Gals. |
GPH |
1919 |
1439 |
1151 |
959 |
822 |
720 |
640 |
576 |
|
523 |
480 |
443 |
411 |
500 NEA |
PROPANE |
|
492 Litres |
LPH |
7263 |
5447 |
4358 |
3631 |
3113 |
2724 |
2421 |
2179 |
|
1981 |
1816 |
1676 |
1556 |
|||
|
|
|
|
|
||||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Recovery capacities are based on heater performance at 95% and 96% thermal efficiency.
Add “A” to model number when ordering ASME. Optional on SUF 60 120NE - SUF 100 250NE Models.Standardon SUF 130-300-500NEA Models.
Maximum gas supply pressure for 120 - 250: 10.5˝ w.c.natural gas 14˝ w.c propane. Maximum gas supply pressurefor 300 - 500 10˝ w.c.naturalgas 13˝ w.c. propane. Manifold pressure:4˝ w.c. natural gas 10˝ w.c. propane. Electrical requirements: 120/60Hz VAC,Blower2.2 Amps FL, Igniter4.0 Amps.
December 2009R