State PR6 75 XODS User Manual

0 (0)

Instruction Manual

RESIDENTIAL DIRECT VENT GAS WATER HEATERS

NOT FOR USE IN MANUFACTURED (MOBILE) HOMES

GAMA certification applies to all residential gas water heaters with capacities of 20 to 100 gallons with input rating of 75,000 BTU/Hr. or less.

For Your Safety

ANODORANTISADDEDTOTHEGASUSED

BYTHISWATERHEATER.

ALL TECHNICALAND WARRANTY QUESTIONS: SHOULD BE DIRECTED TO THE LOCAL DEALER FROM WHOM THE WATER HEATER WAS PURCHASED.IFYOUAREUNSUCCESSFUL,PLEASEWRITETOTHECOMPANYLISTEDONTHERATINGPLATEONTHEWATERHEATER.

 

KEEPTHIS MANUALIN THE POCKET ON HEATER FOR FUTURE REFERENCE

PRINTED 1005

WHENEVER MAINTENANCE ADJUSTMENT OR SERVICE IS REQUIRED.

183774-001

 

1

SAFE INSTALLATION, USE AND SERVICE

Your safety and the safety of others is extremely important in the installation, use and servicing of this water heater.

Many safety-related messages and instructions have been provided in this manual and on your own water heater to warn you and others of a potential injury hazard. Read and obey all safety messages and instructions throughout this manual. It is very important that the meaning of each safety message is understood by you and others who install, use or service this water heater.

All safety messages will generally tell you about the type of hazard, what can happen if you do not follow the safety message and how to avoid the risk of injury.

IMPORTANT DEFINITIONS

Qualified Installer: A qualified installer must have ability equivalent to a licensed tradesman in the fields of plumbing, air supply, venting and gas supply, including a thorough understanding of the requirements of the National Fuel Gas Code as it relates to the installation of gas fired water heaters. The qualified installer must also be familiar with the design features and use of flammable vapor ignition resistant water heaters, and have a thorough understanding of this instruction manual.

Service Agency: A service agency also must have ability equivalent to a licensed tradesman in the fields of plumbing, air supply, venting and gas supply, including a thorough understanding of the requirements of the National Fuel Gas Code as it relates to the installation of gas fired water heaters. The service agency must also have a thorough understanding of this instruction manual, and be able to perform repairs strictly in accordance with the service guidelines provided by the manufacturer.

Gas Supplier: The Natural Gas or Propane Utility or service who supplies gas for utilization by the gas burning appliances within this application. The gas supplier typically has responsibility for the inspection and code approval of gas piping up to and including the Natural Gas meter or Propane storage tank of a building. Many gas suppliers also offer service and inspection of appliances within the building.

Piezo-Electric Spark Gas Ignition System: A combination of a piezo-electric spark generator, high voltage lead(s) and a spark electrode(s) designed to ignite pilot burner gas at an appliance burner.

2

GENERAL SAFETY

3

TABLE OF CONTENTS

SAFE INSTALLATION, USE AND SERVICE

............................... 2

Start Up Conditions ........................................................

31

GENERAL SAFETY ..................................................................

3

Condensate ....................................................................

32

TABLE OF CONTENTS ..............................................................

4

Smoke/Odor ....................................................................

32

INTRODUCTION ........................................................................

4

Thermal Expansion .........................................................

32

Preparing for the New Installation ...................................

4

Strange Sounds

32

TYPICAL INSTALLATION

5 -6

OPERATIONALCONDITIONS

32

LOCATING THE NEW WATER HEATER

7

Smelly Water

32

Facts to Consider About Location

7 -8

“Air” in Hot Water Faucets

32

Venting Clearances

8

High Temperature Shut Off System

32

Optional Wire Grill

9

PERIODICMAINTENANCE

33

Flue Extensions

9

Venting System Inspection

33

Vertical Height (Extension Kit)

10

Burner Inspection

33

Horizontal (Extension Kit)

10

Burner Cleaning

33

Vent Installations

11 - 24

Housekeeping

34

INSTALLING THE NEW WATER HEATER

25

Anode Rod Inspection

34

Water Piping

25

Temperature-Pressure Relief Valve Operation

34

Temperature-Pressure Relief Valve ...............................

26

Filling the Water Heater ..................................................

27

Draining ..........................................................................

34

Gas Piping ................................................................

27 - 28

Drain Valve Washer Replacement .................................

35

Sediment Traps ..............................................................

28

LEAKAGE CHECKPOINTS ......................................................

35

Installation Checklist.......................................................

29

REPAIR PARTS .......................................................................

36

LIGHTING & OPERATING LABEL ............................................

30

TROUBLESHOOTING ..............................................................

40

TEMPERATUREREGULATION ................................................

31

NOTES ..............................................................................

41-43

FORYOUR INFORMATION .....................................................

31

WARRANTY .....................................................................

Insert

INTRODUCTION

Thank You for purchasing this water heater. Properly installed and maintained, it should give you years of trouble free service.

Abbreviations Found In This Instruction Manual:

CSACanadian StandardsAssociation

ANSI -American National Standards Institute

NFPANational Fire ProtectionAssociation

ASME - American Society of Mechanical Engineers

GAMA - GasAppliance Manufacturer’s Association

This gas-fired water heater is design certified by CSAINTERNATIONAL underAmerican National Standard/CSAStandard for Gas Water Heaters ANSI Z21.10.1 • CSA 4.1 (current edition).

This gas-fired water heater is equipped with a piezo-electric spark device used for pilot burner ignition, and complies with the Standard for Manually-Operated Piezo-Electric Spark Gas Ignition Systems and Components, ANSI Z21.77 • CGA 6.23.

PREPARING FOR THE INSTALLATION

1.Read the “General Safety” section, page 3 of this manual first and then the entire manual carefully. If you don’t follow the safety rules, the water heater will not operate properly. It could cause DEATH, SERIOUSBODILYINJURYAND/ORPROPERTYDAMAGE.

This manual contains instructions for the installation, operation, and maintenance of the gas-fired water heater. It also contains warnings throughout the manual that you must read and be aware of. All warnings and all instructions are essential to the proper operation of the water heater and your safety. Since we cannot put everything on the first few pages, READ THE ENTIRE MANUAL BEFORE

ATTEMPTING TO INSTALLOR OPERATE THE WATER HEATER.

2.The installation must conform with these instructions and the local code authority having jurisdiction. In the absence of local codes, installations shall comply with the National Fuel Gas Code ANSI Z223.1/NFPA 54. This publication is available from the Canadian Standards Association, 8501 East Pleasant Valley Rd., Cleveland Ohio 44131, or The National Fire Protection Association, 1 Batterymarch Park, Quincy, MA02269.

3.If after reading this manual you have any questions or do not understand any portion of the instructions, call the local gas utility or the manufacturer whose name appears on the rating plate.

4.Carefully plan the place where you are going to put the water heater. Correct combustion, vent action and vent pipe installation are very important in preventing death from possible carbon monoxide poisoning and fires, see Figures 1 and 2.

Examine the location to ensure the water heater complies with the “Locating the New Water Heater” section in this manual.

5.For California installation this water heater must be braced, anchored or strapped to avoid falling or moving during an earthquake. See instructions for correct installation procedures. Instructions may be obtained from California Office of the State Architect, 400 P Street, Sacramento, CA 95814.

6.Massachusetts Code requires this water heater to be installed in accordance with Massachusetts 248-CMR 2.00: State Plumbing Code and 248-CMR 5.00.

7.Complies with SCAQMD rule #1121 and districts having equivalent NOx requirements.

4

State PR6 75 XODS User Manual

TYPICAL INSTALLATION

GET TO KNOW YOUR WATER HEATER - GAS MODELS

A

Vent Assembly

I

Ground Joint Union

P

Inlet Dip Tube

B

Flue Outlet

J

Drip Leg (Sediment Trap)

Q

Temperature-Pressure Relief Valve

C

Anode

K

Inner Door

R

Rating Plate

D

Hot Water Outlet

L

Outer Doors with Gaskets

S

Flue Baffle

E

Outlet

M

Union

T

Thermostat

F

Insulation

N

Inlet Water Shut-off Valve

U

Drain Valve

G

Gas Supply

O

Cold Water Inlet

V

Pilot and Main Burner

H Manual Gas Shut-off Valve

 

 

W

Flue

 

 

 

 

X

Drain Pan

 

 

 

 

Y

Piezo Ignitor

 

 

 

 

 

Thermostat Shield (optional)

(V) PILOT & MAIN BURNER

(T) THERMOSTAT

*ALL PIPING MATERIALS TO BE SUPPLIED BY CUSTOMERS.

FIGURE1.

5

TYPICAL INSTALLATION

MIXING VALVE USAGE

FIGURE2.

This appliance has been design certifiedascomplyingwithAmericanNational Standard/CSA Standard for water heaters and is considered suitable for:

Water (Potable) Heating: All models are “considered suitable for water (potable) heating.”

Water (Potable) Heating and Space Heating: Certain models are “considered suitable for water (potable) heating and space heating.” Refer to the model and rating plate of the water heater.

HOT WATER CAN SCALD:

Water heaters are intended to produce hot water. Water heated to a temperature which will satisfy space heating, clothes washing, dish washing, and other sanitizing needs can scald and permanently injure you upon contact. Some people are more likely to be permanently injured by hot water than others. These include the elderly, children, the infirm or physically/ mentally handicapped. If anyone using hot water in your home fits into one of these groups or if there is a local code or state law requiring a certain temperature water at the hot water tap, then you must take special precautions. In addition to using the lowest possible temperature setting that satisfies your hot water needs, a means such as a *Mixing Valve shall be used at the hot water taps used by these people or at the water heater. Mixing valves are available at plumbing supply or hardware stores. Consult a Qualified Installer or Service Agency. Follow mixing valve manufacturer’s instructions for installation of the valves. Before changing the factory setting on the thermostat, read the “Temperature Regulation” section in this manual, see Figures 109 and 110.

6

LOCATING THE NEW WATER HEATER

FACTS TO CONSIDER ABOUT THE LOCATION

Carefully choose an indoor location for the new water heater, because the placement is a very important consideration for the safety of the occupants in the building and for the most economical use of the appliance. This water heater is not for use in manufactured

(mobile) homes or outdoor installation.

Whether replacing an old water heater or putting the water heater in a new location, the following critical points must be observed:

1.The location selected should be indoors, as close as practical to the outside wall through which the water heater vent is going to be installed, and as centralized with the water piping system as possible. The water heater, as all water heaters, will eventually leak. Do not install without adequate drainage provisions where water flow will cause damage.

2.Selected location must provide adequate clearances for servicing and proper operation of the water heater.

Installation of the water heater must be accomplished in such a manner that if the tank or any connections should leak, the flow will not cause damage to the structure. For this reason, it is not advisable to install the water heater in an attic or upper floor. When such locations cannot be avoided, a suitable drain pan should be installed under the water heater. Drain pans are available at your local hardware store. Such a drain pan must have a minimum length and width of at least 2 inches (5.1 cm) greater that the water heater dimensions and must be piped to an adequate drain. Drain pan depth must allow for access to the outer doors for servicing the pilot and burner.

Water heater life depends upon water quality, water pressure and the environment in which the water heater is installed. Water heaters are sometimes installed in locations where leakage may result in property damage, even with the use of a drain pan piped to a drain. However, unanticipated damage can be reduced or prevented by a leak detector or water shut-off device used in conjunction with a piped drain pan. These devices are available from some plumbing supply wholesalers and retailers, and detect and react to leakage in various ways:

Sensors mounted in the drain pan that trigger an alarm or turn off the incoming water to the water heater when leakage is detected.

Sensors mounted in the drain pan that turn off the water supply to the entire home when water is detected in the drain pan.

Water supply shut-off devices that activate based on the water pressure differential between the cold water and hot water pipes connected to the water heater.

Devices that will turn off the gas supply to a gas water heater while at the same time shutting off its water supply.

INSTALLATIONS INAREAS WHERE FLAMMABLE LIQUIDS (VAPORS) ARELIKELYTOBEPRESENTORSTORED(GARAGES,STORAGEAND UTILITYAREAS, ETC.): Flammable liquids (such as gasoline, solvents, propane [LP or butane, etc.] and other substances such as adhesives, etc.) emit flammable vapors which can be ignited by a gas water heater’s pilot light or main burner. The resulting flashback and fire can cause death or serious burns to anyone in the area, as well as property damage. If installation in such areas is your only option, then the installation must be accomplished in a way that the pilot flame and main burner flame are elevated from the floor at least 18 inches (45.7 cm). While this may reduce the chances of flammable vapors, from a floor spill being ignited, gasoline and other flammable substances should never be stored or used in the same room or area containing a gas water heater or other open flame or spark producing appliance. NOTE: Flammable vapors may be drawn by air currents from other areas of the structure to the appliance.

7

Also, the water heater must be located and/or protected so it is not subject to physical damage by a moving vehicle.

This water heater must not be installed directly on carpeting. Carpeting must be protected by metal or wood panel beneath the appliance extending beyond the full width and depth of the appliance by at least 3 inches (7.62 cm) in any direction, or if the appliance is installed in an alcove or closet, the entire floor must be covered by the panel. Failure to heed this warning may result in a fire hazard.

Minimum clearances between the water heater and combustible and noncombustible construction are 0 inch at the sides, 0 inches from back, 4(10.2 cm) from front of jacket to closet door and 3(7.6 cm) from top of jacket to combustible and noncombustible material. Minimum vent clearance: 0 inches.

FIGURE3.

NOTE: Provide 24 inches (61 cm) front clearance for servicing and a adequate clearance between the jacket top and ceiling for servicing the flue area.

Combustion Air and Ventilation

No vent damper, whether it is operated thermally or otherwise, is to be installed on this direct vent water heater. Alteration of any part of the factory-furnished vent assembly could result in improper operation due to restriction of flue gases and may cause carbon monoxide poisoning.

Venting Clearances

When determining the installation location for a direct vent water heater, snow accumulation and drifting should be considered in areas where applicable. See Figures 4 through 8 and items below.

18” minimum in all directions from any obstruction that may interfere.

18” minimum from the ground and 12 “ from ceiling overhangs.

The direct vent terminal shall terminate at least 3 feet above any forced air inlet located within 10 feet. See Figure 5.

9” minimum horizontally from or above any door, window or gravity air inlet into the building (50,000 BtuH input or less.)

12” minimum horizontally from or above any door, window or gravity air inlet into the building (over 50,000 BtuH input).

12” minimum below any door, window or gravity air inlet into the building (50,000 BtuH input or less).

18” minimum below any door, window or gravity air inlet into the building (over 50,000 BtuH input).

18” minimum from other gravity or natural appliance outlet vents when directly above or 135° to either side of center line. See Figure 6.

36” minimum from any outlet vents when directly below or 45° to either side of center line. See Figure 7.

36” minimum in all directions from any other forced air appliance outlet vent. See Figure 7.

The location selection must provide clearances for servicing and proper operation of the water heater. See Figure 8.

Vent termination must not be within 4 feet of any items such as gas meters, gas valves or other gas regulating equipment.

Unless specified at time of ordering, a standard extension kit (No. 9000687) is individually packaged and shipped with the water heater.

FIGURE 4.

8

Some local codes may require a vent cap cover. Figure 9 shows the optional wire vent cap protector available from the water heater manufacturer.

A wire mesh chain link fence (see Figure 9) may be used instead of the factory cover. Care should be taken to maintain adequate ventilation around the vent cap. If a chain link fence is installed, it must not be used as a storage area for items that may block proper ventilation.

FIGURE 5.

FIGURE 8.

Optional Wire Grill

When the water heater vent cap is low enough to be touched accidentally, or is accessible to small children, installation of a protective vent cover is recommended. See Figure 9.

FIGURE9.

Flue Extensions

There are three optional extension kits available. Any combination of the three kits can be chosen; however, only one kit can be used vertically and/or horizontally, see Figures 10 & 11.

Unless otherwise specified at the time of ordering, a standard extension kit (9000687) is individually packaged and shipped within the water heater carton.

FIGURE10.

9

Vertical Height (Extension Kit)

It is simple to determine which kit is needed for vertical height. Take the total height (to the top of the flue) required and comparing that to “F dimension” in the chart #1, it can be determined which kit needs to be used vertically.

FIGURE 11.

FIGURE 12.

CHART #1.

 

BTU’s

 

 

DIMENSION “F” (IN INCHES)

 

*Gal.

in 1000’s

9000687

 

9001246

 

9001247

9001248

Cap.

Nat/L.P

STD.

MIN.

MAX.

MIN.

MAX.

MIN.

MAX.

40

36/36

63 3/4

72

77

77

88

88

110

50

38/38

72

80 3/4

86

86

1/4

97 1/4

97 1/4

118 3/4

40

40/40

63 3/4

72

77

77

88

88

110

50

48/44

76

84

1/4

89 3/4

89 3/4

100 3/4

100 3/4

122 3/4

75

55 NAT.

76 1/4

84

1/2

89 1/2

89

1/2

100 1/2

100 1/2

122 1/2

 

BTU’s

 

DIMENSION “F” (IN CENTIMETERS)

 

*Gal.

in 1000’s

9000687

9001246

9001247

9001248

Cap.

Nat/L.P

STD.

MIN.

MAX.

MIN.

MAX.

MIN.

MAX.

40

36/36

162

183

196

196

224

224

279

50

38/38

183

205

218

219

247

247

302

40

40/40

162

183

196

196

224

224

279

50

48/44

193

214

228

228

256

256

312

75

55 NAT.

194

215

227

227

255

255

311

*Check the model and rating plate attached to the water heater for specific model number and other detailed information.

Horizontal (Extension Kit)

To determine the horizontal length and extension kit needed, simply plug the dimensions “D” and “G” into the equation below. The answer “E” should then be located in Chart #2. The size range in which “E” dimension falls indicates the kit that should be used horizontally to obtain the desired length.

“D” = The wall thickness

“G” = The distance wanted between the edge of the water heater and the inside edge of the wall

“E” = The distance the extension kit must be able to extend

The Equation: D + G = E

FIGURE13.

CHART #2.

DIMENSION “E” (IN INCHES)

 

 

 

 

 

 

40-50 GAL.

 

 

75 GAL.

VENT KITS

 

 

MIN

 

MAX

 

MIN

 

 

 

MAX

9000687-Std.

 

3 1/2

 

10

 

7/8

 

 

7 3/8

9001246

 

 

 

10

 

15 1/2

 

7 3/8

 

 

12 7/8

9001247

 

 

15 1/2

 

26 1/2

 

12 7/8

 

 

23 7/8

9001248

 

 

26 1/2

 

48

 

23 7/8

 

 

45 3/8

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

DIMENSION “E” (IN CENTIMETERS)

 

 

 

 

 

 

 

 

40-50 GAL.

 

 

75 GAL.

VENT KITS

 

MIN

 

MAX

 

MIN

 

 

 

MAX

9000687-Std.

 

8.9 cm

 

25.4 cm

 

2.2 cm

 

18.7 cm

9001246

 

 

25.4 cm

 

29.4 cm

 

18.7 cm

 

32.7 cm

9001247

 

 

39.4 cm

 

67.3 cm

 

32.7 cm

 

60.6 cm

9001248

 

 

67.3 cm

121.9 cm

 

60.6 cm

 

115.3 cm

 

 

 

 

 

 

 

 

 

 

 

BTU’s

 

 

DIMENSION “A, B, C” (INCHES/CENTIMETERS)

*Gal.

in 1000’s

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Cap.

Nat.

 

 

 

 

A

 

 

B

 

 

C

40

36/36

 

48 3/4”

 

124 cm

 

41 3/4”

 

106 cm

21”

 

53 cm

50

38/38

 

57 1/2”

 

146 cm

 

50 1/2”

 

128 cm

21”

 

53 cm

40

40/40

 

48 3/4”

 

124 cm

 

41 3/4”

 

106 cm

21”

 

53 cm

50

48/44

 

61”

 

155 cm

 

54”

 

137 cm

21”

 

53 cm

75

55 NAT.

 

63”

 

160 cm

 

54 3/4”

 

139 cm

26 1/4”

67 cm

10

ALL INSTALLATIONS

For ease of assembly the installation of the various kit combinations has been broken into individual sections. The two steps below are common to all installations. Once these have been performed, you need only to refer to the type installation that pertains to you.

Installation Using Vent Kits:

 

1. Standard Vent Kit 9000687 .............................................

Page 11

2. Optional Vertical Vent Kit .................................................

Page 14

with Standard Vent Kit

 

3. Optional Horizontal Vent Kit .............................................

Page 17

4. Optional Horizontal..........................................................

Page 19

and Vertical Vent Kits

 

Cutting The Opening Through The Outside Wall

After thoroughly reading the “Locating the New Water Heater” section of this manual and you have chosen a suitable water heater installation site, use Chart #1 to determine dimensions for the wall opening.

Cut a 6 1/4” (159 mm) diameter hole completely through the outside wall.

FIGURE14.

Water Heater Attitude

There is a certain amount of variance with regard to the direction the water heater faces.

Standing in front of the water heater (gas control facing you), set the 3” (76 mm) diameter elbow (slotted end) on the flue. This will give you a better understanding of the relation of the vent assembly to the opening in the wall and more importantly any possibility of interference of venting and water piping.

The direction of the water heater can now be made. Also consider the gas control valve to insure installation, lighting and maintenance accessibility are retained.

NOTE: Supplementary installation instructions are applicable only if this direct vent water heater is provided with the alternate brown porcelain-enameled vent cap and the 6” (152 mm) vent wall assembly show below, See pages 22 thru 24.

Standard Vent Kit - Installation #1

The opening through the wall should be cut at this time. If this has not been done, refer to “Cutting The Opening Through The Outside Wall ” section.

1.Lock the elbow to the straight 3” (76 mm) flue pipe. Set this assembly in place on the end of the water heater’s flue collar.

FIGURE15.

2.Mark the flue collar at the slots in the elbow. Using a #22 drill bit, drill holes into the flue collar at the two slots and secure the elbow to the flue collar using the screws provided.

NOTE: Make sure elbow is properly aligned to opening in the outside wall.

FIGURE16.

3.Using the tube of sealant supplied, run an ample amount around the oval flare of the jacket.

FIGURE 17.

11

4.First remove the 3” (76 mm) horizontal extension from the elbow. Starting with the long end (with four securing holes), place the 6” (152 mm) diameter vent elbow over the 3” (76 mm) diameter elbow. Bend the round end “oval” to fit the flared oval end of the jacket top.

FIGURE18.

5.Making sure the 6” (152 mm) diameter elbow is centered around the 3” (76 mm) diameter flue, secure the 6” (152 mm) diameter vent pipe using four sheet metal screws at the connection of the jacket top.

FIGURE19.

6.The standard vent kit includes a 6” (152 mm) diameter extension pipe which is used when “E” dimension is over 6 1/2” (165 mm).

FIGURE 20.

7. If “E” dimension is less than 6 1/2” (165 mm) move to next step.

If “E” dimension is over 6 1/2” (165 mm), assemble the 6” (152 mm) diameter extension pipe (crimped end) to the 6” (152 mm) diameter vent elbow and secure using two sheet metal screws.Apply an ample amount of sealant around the joint to ensure a good seal.

FIGURE21.

8.Slide the vent collar (to be installed later) over the 6” (152 mm) vent elbow.

FIGURE22.

9.Place the water heater at the opening in the wall, at the predetermined clearance.

FIGURE23.

10.Move outdoors with all the remaining vent parts. Using the tube of sealant supplied, run an ample amount on the inside surface of the collar assembly that will contact the exterior wall and also fill the bead on the end of the 6” ((152 mm) diameter vent collar.

FIGURE24.

12

11. Install the vent collar assembly through the wall, connecting it to the extension and/or elbow (depending on which one was used).

FIGURE25.

12.We have supplied four wood screws to temporarily attach the collar to the exterior wall of the building. However, other types of screws may have to be substituted depending on the material used in the construction of the exterior wall.

15. The vent cap has four holes around the outer edge. Remove the four screws used to temporarily attach the collar to the exterior wall. Then secure the vent cap assembly with the vent collar assembly to the exterior wall using the same four screws.

NOTE: Screws are supplied: However, substitution may be necessary depending on the exterior wall material.

FIGURE26.

13.Insert the 3” (76 mm) diameter flue extension pipe into the vent collar assembly (flared & notched end first) and lock (turn clockwise to lock studs to slots) the flue extension pipe to the flue elbow.

FIGURE28.

16.Go back indoors toattachinsidecollartotheinsidewall.Placethe collar against the wall. Secure to wall by using four long sheet metal screws.

NOTE: Screws are supplied: However, substitution may be necessary depending on the interior wall material.

FIGURE29.

14.Connect the vent cap by sliding its end over the 3” (76 mm) diameter extension pipe and O-ring.

NOTE: To facilitate ease of assembly of the vent cap to the 3”(76mm) pipe, a soap solution can be applied to the O-ring gasket.

17.Using the tube of sealant supplied, run an ample amount of sealant around the edge of the vent pipe where it is inserted through the inside collar to seal air drafts from wall.

FIGURE27.

FIGURE30.

13

Optional Vertical Vent Kit with Standard Horizontal Vent Kit - Installation #2

Any Optional Vent Kit

*Each part is stamped with a part number.

The opening through the wall should be cut at this time. If this has not been done, refer to “Cutting The Opening Through The Outside Wall,” onpage11.

1.First it must be determined how far the vertical 3” (76 mm) diameter telescoping flue sections are set and locked together using the two screws supplied.

FIGURE31.

Use chart #3, drawing and simple equation below, to find the length of expansion of the telescoping flue sections. Because of manufacturing tolerances, place the telescoping extension on the water heater and adjust the height (“X” Dimension) and mark the point. Once the length has been determined, lock the two sections together by drilling two holes (180° apart) in the pipe and securing with the screws supplied.

FIGURE32.

CHART #3

*GAL CAP.

*BTU’s in 1000’s - NAT./L.P.

 

A

40

36/36

48 3/4”

 

124 cm

 

50

38/38

57 1/2”

 

146 cm

40

40/40

48 3/4”

 

124 cm

50

48/44

61”

 

155 cm

75

55 NAT.

63”

 

160 cm

 

 

 

 

 

*Check the model and rating plate attached to the water heater for specific model number and other detailed information.

2.Set the vertical 3” (76 mm) diameter telescoping flue section in place on the flue collar. Using a # 22 drill bit, drill two holes (180° apart) and secure the vertical assembly to the flue collar.

FIGURE33.

3.Slide the 6” (152 mm) vent telescoping section apart to reveal the beads. Using the caulking supplied, fill the beads.

FIGURE34.

4.Apply an ample amount of sealant around the oval flare of the jacket.

FIGURE 35.

5.Place the 6” (152 mm) vent section over the 3” (76 mm) flue section. Subtract 3/4” (19 mm) from the predetermined “X” dimension. This determines the length of the 6” (152 mm) vent extension. Slide the 6” (152 mm) vent extension apart to this dimension and secure with the two screws supplied.

FIGURE36.

6.Form the round end of the 6” (152 mm) vent extension to the top of the jacket and secure with four sheet metal screws.

FIGURE 37.

14

Loading...
+ 30 hidden pages