HMSC pumps come equipped with pressure switch set to
operate within a 20-40 PSI range. HMSD, HMSE, and HMSF
pumps have 30-50 PSI pressure switches. When pump is
used with precharged tank in system, set tank pre-charge at
18 PSI with a 20-40 PSI switch; set tank pre-charge at 28
PSI with a 30-50 PSI switch. Check tank pre-charge annually
with an ordinary tire gauge. Pre-charge is set with no water
pressure on system.
Priming the Shallow Well Pump
Never run pump dry. Running pump without
water may cause pump to overheat, damaging seal and possibly causing burns to persons handling pump. Fill pump with
water before starting.
Never run pump against closed discharge.
To do so can boil water inside pump, causing hazardous
pressure in unit, risk of explosion and possibly scalding persons handling pump.
To prime the pump, completely open the priming valve located just below the suction opening on the tank body by turning
the valve stem counter-clockwise all the way until it stops.
This valve may be left open during operation as a shallow
well pump with no jet. See Figure 3 and “NOTICE” below.
Remove priming plug from top of elbow (see Figure 3), and
fill with clean water. Replace plug.
Start pump and between 45-60 seconds. If water is not being
pumped, turn off pump and repeat priming process.
NOTICE: If a bolt-on jet is being used, after pump is primed,
close the priming valve during operation as a shallow well
pump.
Service – Draining for Winter
Do not touch an operating motor. Modern
motors are designed to operate at high temperatures. To
avoid burns when servicing pump, allow it to cool for 20 minutes after shut-down before handling.
When the pump is to be disconnected from service, or is in
danger of freezing, it should be drained. The pump has a
drain plug which must be removed. Remove the priming plug
to vent the pump.
If pump and motor are damaged due to freezing, the
Warranty is void.
3
TABLE I
Recommended Fusing and Wiring Data – 60 Cycle Motors
DISTANCE IN FEET FROM MOTOR TO METER
BRANCH 0’ 101’ 201’ 301’ 401’
MAX. FUSE* to to to to to
MOTOR LOAD RATING 100’ 200’ 300’ 400’ 500’
HP VOLTS AMPERES AMPS
WIRE SIZE
3/4 115 14.8 20 12 8 6 6 4
3/4 230 7.4 15 14 14 14 12 10
1 115 19.2 25 10 8 6 4 4
1 230 9.6 15 14 14 12 10 10
1-1/2 115 24.0 30 10 6 6 4 3
1-1/2 230 12.0 15 14 14 12 10 10
*Fusetrons are recommended instead of fuses on all motor circuits.